The original scope is addition of 125A MCCB in the Emergency Switchboard (C002-SB-PSS02E01).
Electrical and mechanical interlock is also required between the existing Q01 MCCB and the newly added
125A MCCB.
The existing MCCB part number is 3VA1163-5EF32-0AA0. For electrical and mechanical interlock to be
provided, the 2 nos. 125A MCCB Incomer have to be fixed next to each other. Internal view of the cubicle
is shown below.
It is not possible to install 2 nos. 125A MCCB Incomers with electro-mechanical interlock in the space
available in the compartment since spare is not available for additional 125A MCCB. A possible solution
would be to keep the 2 nos. incomers in this section and move the other 2 nos. MCCB in the section above
if space is available.
However, this solution is not possible and the scope of adding a new 125A MCCB is cancelled.
In Busbar A1, panel number NE01+N02 (2nd cubicle) there are 4 circuit breakers 4 pole. Part number of
breakers F16A, F17A & F18A is 3VA1112-5EF32-0AA0.
The original scope is to replace 3 of them (F16A, F17A & F18A) by 2 pole, and adding new 1 circuit
breaker 2 pole in same cubicle.
The revised scope is to remove all the 4 nos. 4P MCCB and install new 1 no. 3P MCCB and 5 nos. 2P
MCCB. The part number proposed are as below:
- 1 no. 3P MCCB is 3VA1112-5EF32-0AA0 circuit breaker 3VA1 IEC frame 160 breaking capacity
class M Icu=55kA @ 415V 3-pole, line protection TM240, ATAM, In=125A overload protection
Ir=88A...125A short-circuit protection Ii=5... 10 x In nut keeper kit + door drive mechanism is
3VA9157-0FK21 door mounted rotary operator standard IEC IP65 with door interlock accessory for:
3VA1 100/160
- 5 nos. 2P MCCB is 3VA1112-5ED22-0AA0 circuit breaker 3VA1 IEC frame 160 breaking capacity
class M Icu=55kA @ 415V 2-pole, line protection TM210, FTFM, In=125A overload protection
Ir=125A fixed short-circuit protection Ii=10 x In nut keeper kit. A door drive mechanism is not
possible for 2P MCCB.
The front door should be replaced with door drive mechanism for the 3 pole MCCB. There is no door drive
mechanism for the 2 pole MCCB.
In Busbar A1, panel number NE01+N02 (3rd cubicle) there are 2 circuit breakers 4 pole (F19A, F20A), and
free space for future circuit breakers. Part number of existing circuit breakers are 3VA1112-5EF32-0AA0.
The original scope is to add new 3 circuit breakers 2 pole in the available space.
The front door should be replaced with door drive mechanism for the newly added 4 pole MCCB.
In Busbar B1 NE01+N02 (2nd cubicle) there are 4 circuit breakers 4 pole. Part number of breakers F14B &
F15B is 3VA1125-5GI42-0AA0.
The original scope is to replace F14B & F15B with 2 pole MCCB.
- 2 no. 2P MCCB type 3VA1125-5ED22-0AA0 circuit breaker 3VA1 IEC frame 160 breaking capacity
class M Icu=55kA @ 415V 2-pole, line protection TM210, FTFM, In=25A overload protection Ir=25A
fixed short-circuit protection Ii=12.8 x In nut keeper kit
The front door should be replaced since there is no door drive mechanism for the 2 pole MCCB.
The original scope is to replace 1 of them (F16B) by 2 pole and adding new 1 spare circuit breaker 2 pole
in the available space.
The revised scope is to replace 1 no. 4P MCCB (F16B) by 1 no. 2P MCCB and add 2 nos. 2P MCCB.
- 3 nos. 2P MCCB type 3VA1125-5ED22-0AA0 circuit breaker 3VA1 IEC frame 160 breaking capacity
class M Icu=55kA @ 415V 2-pole, line protection TM210, FTFM, In=25A overload protection Ir=25A
fixed short-circuit protection Ii=12.8 x In nut keeper kit
The front door should be replaced since there is no door drive mechanism for the 2 pole MCCB.
The original scope in Busbar A and B, is to replace 2 circuit breakers F07A and F07B by RCD type with
considering the replacement of the cubical door.
- 2 nos. MCCB - 3VA1163-5EF32-0AA0 circuit breaker 3VA1 IEC frame 160 breaking capacity class
M Icu=55kA @ 415V 3-pole, line protection TM240, ATAM, In=63A overload protection
Ir=44A...63A short-circuit protection Ii=5...10 x In nut keeper kit +
- 2 nos. RCD unit - 3VA9113-0RS20 residual current device RCD510 Basic RCD type A side mounted
rated resid. current 0.03...5A at 50/60Hz adjustable tv 0...3000ms 3-pole In=160A Ue=127-480V
accessory for: 3VA1 with terminal connection +
- 4 sets box terminals - 3VA9153-0JA11 Box terminal TS1.1 3 units 1.5…70 mm² accessories for:
3VA1 100/160 +
- 2 nos. door drive mechanism - 3VA9157-0FK21 door mounted rotary operator standard IEC IP65
with door interlock accessory for: 3VA1 100/160.