Professional Documents
Culture Documents
Ss Garuf
Ss Garuf
Ss Garuf
Multi-Position,
Multi-speed Air Handler
with PSC Motor
1½ to 5 Tons
Contents
Nomenclature ........................................ 2
Product Specifications ........................... 3
Heater Kit Nomenclature....................... 3
Dimensions ............................................ 4
Airflow Data ........................................... 5
Heat Kit Data .......................................... 6
Wiring Diagrams .................................. 13
Accessories .......................................... 15
Product Features
• Check flowrator for cooling • Rigid SmartFrame™ cabinet
and heat pump applications • Horizontal or vertical
• Direct drive, multi-speed PSC blower motor configuration capabilities
• All-aluminum evaporator coil • 21" depth for easier attic access
• Coil mounting track for quick repositioning • DecaBDE-free thermoplastic drain
• Cabinet air leakage less than 2.0% at pan with secondary drain connections
1.0 inch H₂O when tested in accordance • Screw-less sides and back helps to reduce
with ASHRAE standard 193 condensation when installed in humid locations
• Cabinet air leakage less than 1.4% • Foil-faced insulation covers the internal
at 0.5 inch H₂O when tested in casing to reduce cabinet condensation
accordance with ASHRAE standard 193 • Galvanized, leather grain-embossed finish
• AHRI certified; ETL listed • Glue-less cabinet insulation retention
• Tool-less filter access
• Field Installed 3 kW – 25 kW electric heater
kits available
* Complete warranty details available from your local dealer or at www.goodmanmfg.com. To receive the 10-Year Parts Limited Warranty,
online registration must be completed within 60 days of installation. Online registration is not required in California or Québec.
A R U F 18 B 1 4 AA
1 2 3 4 5,6 7 8 10 11,12
Brand Engineering
*
A Single-‐piece Major/
Minor
Revisions
Air
Handler *
Not
used
for
inventory
management
HKS X 03 X A AA
1 2 3 4 5 6,7
2 www.goodmanmfg.com SS-GARUF
Product Specifications
ARUF ARUF ARUF ARUF ARUF ARUF ARUF ARUF ARUF ARUF ARUF
25B14* 29B14* 31B14* 37C14* 43C14* 49C14* 37D14* 43D14* 47D14* 49D14* 61D14*
Nominal Ratings
Cooling (Btu/h) 24,000 25,000 30,000 36,000 42,000 48,000 36,000 42,000 43,000 48,000 60,000
Piston Size 0.051 0.057 0.065 0.072 0.076 0.080 0.072 0.076 0.076 0.080 0.080
Blower
Diameter 9½" 9½" 9½" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝" 1115/16"
Width 6" 6" 6" 8" 8" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝"
Coil Connections
Liquid ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜"
Suction ¾" ¾" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞"
Coil Drain Connect (FPT) ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾"
Electrical Data
Voltage 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Min Circuit Ampacity 2.2/2.2 2.2/2.2 2.2/2.2 3.6/3.6 3.6/3.6 4/4 3.6/3.6 4/4 4/4 4/4 6/6
Max. Overcurrent Device (Amps) 15/15 15/15 15/15 15/15 15/15 15/15 15/15 15/15 15/15 15/15 15/15
Minimum VAC 197 197 197 197 197 197 197 197 197 197 197
Maximum VAC 253 253 253 253 253 253 253 253 253 253 253
Blower Motor
Full Load Amps (FLA) 1.75 1.75 1.75 2.85 2.85 3.1 2.85 3.5 3.5 3.5 4.6
Horsepower (HP) ⅓ ⅓ ⅓ ⅓ ⅓ ½ ⅓ ½ ½ ½ ¾
Ship Weight (Lbs.) 100 100 110 130 130 135 140 145 150 145 155
Note: For a properly matched system and piston sizing information, refer to Amana piston kit chart of the corresponding Amana® outdoor unit.
Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) for blower without supplemental heat installed.
Refer to unit nameplate and/or Heat Kit Data for specification with approved accessory heaters installed.
SS-GARUF www.goodmanmfg.com 3
Dimensions
A
SUCTION TUBE
G LIQUID LINE 2 15/16" (7.46 cm)
INLET TUBE
SEE HORIZONTAL
DRAIN PORT DETAIL 3 3/4" (9.53 cm) 1 5/8" (4.13 cm)
10 3/16" (25.88 cm)
D
E VERTICAL DRAIN PORT DETAIL
SEE VERTICAL
DRAIN PORT DETAIL H
ARUF37C14* 53 /16
7
19⅞ 21 21 /16
13
18⅝ 17 /16
11
10 /16 13
613/16
ARUF43D14* 53 /16
7
23 /16
5
24½ 21½ 18 /16
5 21 /16
3
12⅝ 6⅞
4 www.goodmanmfg.com SS-GARUF
Airflow Data
SS-GARUF www.goodmanmfg.com 5
Heat Kit Data
SS-GARUF www.goodmanmfg.com 7
Heat Kit Data (cont.)
8 www.goodmanmfg.com SS-GARUF
Heat Kit Data (cont.)
SS-GARUF www.goodmanmfg.com 9
Heat Kit Data (cont.)
SS-GARUF www.goodmanmfg.com 11
Heat Kit Data (cont.)
12 www.goodmanmfg.com SS-GARUF
208/240
SEE NOTES 2 & 6 TERMINAL BLOCK SHOWN L1 L2 VOLTS
FOR 50HZ MODELS ONLY EQUIPMENT GROUND
USE COPPER WIRE
BL RD GR WH BR L1 L2
SS-GARUF
SR BK RD GRND
1 PLF PLF 2
PLF 1 2 3 4 5 6 7 8 9 1 PLM
3 PLM 2
PLM 1 2 3 4 5 6 7 8 9 RC EM
NC NO
BK RD PU BL BR WH M1
SEE HI
NOTE 4 EBTDR
M2 COM
BR LO
WH 1 2 3 SEE NOTE 1
TR
GR BK EBTDR R C EBTDR G
SEE NOTE 5 RD 4 24V 5
RD
PU SEE NOTE 1 6 5 4 PLM
G EBTDR RD
R NO C 1 2 3 240 RD WH BR BL GR
K1
BL XFMR-R RD
RD XFMR-C COM TR
K1 PU
5 24V 4 SEE NOTES 2 & 6
C
NC
BL SPEEDUP M1 M2 BL BL
RD COLOR CODE WIRING CODE
BK BLACK GR GREEN FACTORY WIRING
RD RED PU PURPLE HIGH VOLTAGE
BK YL YELLOW BR BROWN LOW VOLTAGE
COPPER POWER SUPPLY SEE
RD PU BL BLUE WH WHITE
(SEE RATING PLATE) NOTE 3 FIELD WIRING
USE MIN. 75°C FIELD WIRE COMPONENT CODE HIGH VOLTAGE
EVAPORATOR MOTOR LOW VOLTAGE
EM
THREE SPEED MOTOR WIRING RC RUN CAPACITOR TR TRANSFORMER
(SELECT MODELS ONLY) (COM) RD LOW BK
SR STRAIN RELIEF PLF FEMALE PLUG CONNECTOR
IF REPLACEMENT OF THE ORIGINAL WIRES SEE NOTE 3 (M2) BL MEDIUM R RELAY PLM MALE PLUG CONNECTOR
www.goodmanmfg.com
(M1) RC EBTDR FL FUSE LINK
SUPPLIED WITH THIS ASSEMBLY IS NECESSARY BK HIGH ELECTRONIC BLOWER
BR TIME DELAY RELAY TL THERMAL LIMIT
USE WIRE THAT CONFORMS TO THE (TR 1) PU EM EM GRND GROUND
NATIONAL ELECTRIC CODE. BR
3 SPEED BR
PU RC
NOTES:
1. RED WIRES TO BE ON TRANSFORMER TERMINAL "3" FOR 240 VOLTS
AND ON TERMINAL "2" FOR 208 VOLTS.
2. SEE COMPOSITE WIRING DIAGRAMS IN INSTALLATION INSTRUCTIONS
FOR PROPER LOW VOLTAGE WIRING CONNECTIONS.
3. CONFIRM SPEED TAP SELECTED IS APPROPRIATE FOR APPLICATION.
IF SPEED TAP NEEDS TO BE CHANGED, CONNECT APPROPRIATE
MOTOR WIRE (RED FOR LOW, BLUE FOR MEDIUM, AND BLACK FOR
HIGH SPEED) ON "COM" CONNECTION OF THE EBTDR.
INACTIVE MOTOR WIRES MUST BE CONNECTED TO "M1 OR M2"
ON EBTDR.
4. BROWN AND WHITE WIRES ARE USED WITH HEAT KITS ONLY.
5. EBTDR HAS A 7 SECOND ON DELAY WHEN "G" IS ENERGIZED
AND A 65 SECOND OFF DELAY WHEN "G" IS DE-ENERGIZED.
6. LOW VOLTAGE FIELD WIRING TO BE N.E.C CLASS 2 WIRES.
0140A00242-A
13
unit for the most up-to-date wiring.
⚠ Warning ⚡
Wiring Diagram – Air Handler
14
NOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP MUST EXCEED OR EQUAL THE MINIMUM BLOWER TB
CIRCUIT 1
SPEED (MBS) SPECIFIED FOR THE AIRHANDLER/HEATER KIT COMBINATION ON THIS UNIT'S SERIAL PLATE. 1 PH 208-240V
L1 L2
AFTER INSTALLING OPTIONAL HEAT KIT, MARK AN "X" IN THE PROVIDED BELOW.
NO MARK INDICATES NO HEAT KIT INSTALLED. BK RD
PC
L1 TR
1 BK
1 4
BK
HTR3 TL
FL L2
RD 2 2
BK RD
3 5
BK HTR2 PU 3 PU RD
FL TL BL BL
L3 L2 L1 BK BL 4 RD
BK HTR1
FL TL RD PU
EBTDR
BK GR PU
BK 5
RD K1
NO
GND BK XFMR-R
BK 6 WH XFMR-C COM
BK K1
C BK
BL
BK BK BK 7
NC
BL BL
BK WH BR SPEEDUP M1 L1
CC RS
L1 T1 BK BK WH GR
M1 M3 8 RD
Wiring Diagram – Three-Phase Heater Kit
BK BK WH PK
L2 R T2 BK PU
M2 M4 BL
BK 9
L3 T3 BK
PU BR WH BR
WH WH RC EM
SR
CIRCUIT 2 BR
3 PH. 208-240V
www.goodmanmfg.com
(CIRCUIT 1) L1
L1 L2 L3
L2
PC
208/240 VOLTS COMPONENT CODE COLOR CODE
1 T1 T2 T3
FL HTR3 TL FL HTR2 TL HTR HEAT ELEMENT
EM EVAPORATOR MOTOR BK BLACK
2
EBTDR ELEC. BLOWER TIME DELAY RELAY BL BLUE
RC EM
RS RELAY/SEQUENCER BR BROWN
3
LOW NC NO FL HTR1 TL RC RUN CAPACITOR
M1 GR GREEN
EBTDR 4 TL THERMAL LIMIT
OR ORANGE
TR TRANSFORMER
NOTE:- HIGH COM PK PINK
5 TB TERMINAL BLOCK
PU PURPLE
THIS LABEL MUST BE CC CONTACTOR
M2 M1 RD RED
6 PC 9-PIN CONNECTOR
ATTACHED ON THE 1 2 3 WH WHITE
SR STRAIN RELIEF
7 YL YELLOW
AIRHANDLER IN A PROMINENT TR FL FUSE LINK
CC
LOCATION 8 M4 M3 CB CIRCUIT BREAKER
4 24 VOLT 5
SS-GARUF
⚠ Warning
Accessories
Expansion Valve Kits for Air Conditioning and Heat Pump Applications
Kit Tonnage:
Description Application Refrigerant
Number Outdoor Unit
TX2N4A Non-bleed Valve AC or HP R-410A 1½ - 2 Ton
ARUF49D14**
ARUF61D14**
Filters
SS-GARUF www.goodmanmfg.com 15
Notes
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without
notice or without incurring obligations. © 2018 Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA.
16 www.goodmanmfg.com SS-GARUF