Fieldbus Monitor
User Manual
Relcom
www.mtl-fieldbus.com
© Copyright Relcom, Inc. 2006
Relcom, Inc.
2221 Yew St.
Forest Grove, OR 97116
USA
I. Table of Contents
II. Introduction
Summary of Features
III. Certifications
CE
The FBT-6 meets the European Union requirements for
electromagnetic radiation by complying with the EMC Directive
89/336/EEC.
FCC
The FBT-6 is a Class A digital device and complies with Part 15
of the FCC Rules. Operation is subject to the following two
conditions: (1) this device may not cause harmful interference,
and (2) this device must accept any interference received,
including interference that may cause undesired operation.
Before Starting
Select No, not this time and press the Next button to continue.
Now the previous dialog has the directory name filled in. Press
the Next button to continue.
This dialog shows that the driver has been installed. Press the
Finish button to exit.
Make sure that only Specify a location is marked, and press the
Next button to continue.
Now the previous dialog has the directory name filled in. Press
the OK button.
This dialog will show that the device driver has been found.
Press the Next button to continue.
This dialog shows that the driver has been installed. Press the
Finish button.
Now, from the Start menu, open the Control Panel by selecting
Start>Settings>Control Panel.
Open System.
V. Operation
RELCOM FBT-6
FW VER XX.XX
VOLTAGE
22.5V OK \ Twirling Icon
Underscore
Two buttons on the front of the Monitor control its operation. The
buttons are labeled FUNC (for FUNCTION) and SEL (for
SELECT). Press the FUNCTION button to cycle through the
available Monitor functions. Some functions have multiple sub-
screens of data available for display. Sub-screens available for
each function are cycled through by pressing the SELECT
button. Most functions are reset by holding down the SELECT
button for 2 seconds. After holding down the SELECT button for
2 seconds, the data collected for that function is erased giving
that function a “fresh start”. Short button presses (less than 2
seconds) are acted upon when the button is released, not when
depressed.
NETWORK CHECK
IN PROGRESS
In Network Check Mode, the Monitor collects the same data that
it continuously collects in Manual Mode. As the data is collected,
the Monitor evaluates the data to determine if it is out of
specification. When the Monitor has collected enough data to
determine that all of the measured parameters are in
specification, the display shows:
ALL MEASUREMENTS
OK
(+) TO SHIELD
SHORT
Manual Mode is entered when the Monitor detects the first out of
specification parameter or either button is pushed. The functions
available are described below in the order in which they will
appear.
1. Voltage
VOLTAGE
22.5V OK
VOLTAGE
8.5V BAD
2. Peak Noise
PK FF NOISE
64 mV OK
PK FF NOISE
99 mV BAD
PK LF NOISE
199 mV HIGH
3. Average Noise
AVG FF NOISE
68mV OK
AVG FF NOISE
1000mV BAD
AVG HF NOISE
200mV BAD
4. Shield Short
WIRING OK
(+) TO SHIELD
SHORT BAD
5. Retransmit
RETRANSMIT
NONE OK
Or
RETRANSMIT
DEVICE 19(13H)
RETRANSMITS=250+
DEVICE 19(13H)
6. Add-Drop
ADD or DROP
NONE
DROP 17 (11H)
690mV
ADD 19 (13H)
700mV
7. Device
DEVICE 16 (10H)
1000mV LAS OK
DEVICE 41 (29H)
1000mV + OK
DEVICE 41 (29H)
140mV BAD
8. Low
LOW= 580mV OK
ADDR= 41 (29H)
9. Device Count
DEVICE COUNT
12 OK
DEVICE COUNT
11 -
The Monitor can save the collected data in one of eight files
(memory blocks). The display shows the file that the Monitor will
store the data in.
SAVE DATA
File 1
Choose one of the eight files to store the current fieldbus data in
by pressing the SELECT button. Press the SELECT button to
increment the file number.
SAVE DATA
File 8
To save the data in the selected file, hold down the SELECT
button for 2 seconds. The display shows, SAVE DATA:SAVING
FILE #, while the data is being saved (# is the selected file
number).
SAVE DATA:SAVING
File 5
When the database has been saved, the display shows SAVE
DATA: SAVED.
Any file that has data saved in it will display SAVE DATA:
SAVED as shown above. When a file with saved data is chosen
and the SELECT button is held down for 2 seconds the originally
saved data is overwritten with new data.
Connect the FBT-6 to the USB port using the supplied USB
cable. Connect only one FBT-6 at a time. Open the FBT-6
Assistant program by double clicking on the FBT-6 Assistant
desktop icon or selecting Start – All Programs – FBT-6 Assistant
– FBT-6 Assistant. Pushbuttons to perform USB related
functions are displayed on the screen below.
Click the Transfer Data from FBT-6 button to transfer the data
saved in all eight FBT-6 files to a PC via the USB port.
The FBT-6 Assistant displays a screen like the one below for
each file it transfers from the FBT-6, allowing each file to be
saved separately.
When all files have been saved, the main menu is displayed.
The files are saved in a tab delimited text file format with an .xls
filename extension. Saved files can be opened with Excel or a
text editor (such as Notepad). The contents of the file and how it
will look when opened in Excel (following column width
adjustments) are shown in Table 2.
Date/Time Connected to Bus <Date and time the FBT-6 was connected to the bus, MM-DD-YY:HH:MM>
Date/Time Data Saved <Date and time the data set was saved by the user, MM-DD-YY:HH:MM>
Voltage (V) <Fieldbus DC Voltage to nearest 0.1V>
Lowest Device Signal (mV) <Lowest detected device signal level>
Lowest Device Signal Address <Address of the device with the lowest detected signal level, decimal (HexH)>
Date/Time of Lowest Device Signal <Date and time the lowest device signal was detected, MM-DD-YY:HH:MM>
Avg Fieldbus Frequency Noise (mV) <Average Fieldbus Frequency Band Noise>
Peak Fieldbus Frequency Noise (mV) <Peak Fieldbus Frequency Band Noise>
Peak Fieldbus Frequency Noise Date/Time <Date and time that Peak Fieldbus Frequency Band Noise was detected, MM-DD-YY:HH:MM>
Avg Low Frequency Noise (mV) <Average Low Frequency Band Noise>
Peak Low Frequency Noise (mV) <Peak Low Frequency Band Noise>
Peak Low Frequency Noise Date/Time <Date and time that Peak Low Frequency Band Noise was detected, MM-DD-YY:HH:MM>
Avg High Frequency Noise (mV) <Average High Frequency Band Noise>
Peak High Frequency Noise (mV) <Peak High Frequency Band Noise>
Peak High Frequency Noise Date/Time <Date and time that Peak High Frequency Band Noise was detected, MM-DD-YY:HH:MM>
Shield Short <Shield short to +, Shield short to -, or None>
LAS Address <Address of the LAS, decimal (HexH)>
Most Recent Add/Drop Address <Address of the most recently added or dropped device, decimal (HexH)>
Device Add or Drop <Indicates whether the device above was added or dropped (Add, Drop, or NA)>
Date/Time of Device Add/Drop <Date and time the last device add or drop was detected, MM-DD-YY:HH:MM>
No. of Active Devices <0-32>
… …
Limitations
Initial Discovery
EXCESS NOISE, NO
FIELDBUS MEAS.
To exit the Excess Noise Mode, remove the source of the noise
from the bus then disconnect and reconnect the FBT-6. If the
high noise level is still present, the FBT-6 will again enter Excess
Noise Mode.
Unavailable Data
The data for some or all displays will be unavailable during Initial
Discovery, Excess Noise Mode, after a function is reset, or
because the network is silent. When the FBT-6 is collecting and
processing network data, information may not be ready for
display. In this case, only the selected FBT-6 function name is
displayed. The FUNCTION and SELECT buttons still navigate
through the menus as they normally would.
VII. Specifications
Dimensions: 146 x 88 x 28 mm
(5.7 x 3.5 x 1.1in.)
Weight: 378g (0.83lb.)
Case material: ABS
Case Specifications: Provides IP54 Protection
VIII. Service
The FBT-6 does not contain any user serviceable parts. All
adjustments and/or repairs have to be performed at the factory.
If the FBT-6 needs to be serviced, return it to Relcom, Inc. If the
FBT-6 is covered by the limited warranty, the repairs or
replacement will be made free of charge. For service outside the
warranty, please call or write to determine the charges for the
service before sending the FBT-6.
IX. Warranty
Relcom, Inc. has made every effort to assure the accuracy of the
information contained in this manual. Relcom is not, however,
responsible for any errors or omissions. Please contact us with
any questions or suggestions.
Relcom, Inc.
2221 Yew St.
Forest Grove, OR 97116
USA
Electrostatic
Pass EN61000-4-2 Enclosure B
Discharge Immunity
RF Electromagnetic
Pass EN61000-4-3 Enclosure A
Field Immunity
Electrical Fast
Pass EN61000-4-4 Transient/Burst AC Mains B
Immunity
RF Conducted
Pass EN61000-4-6 AC Mains A
Immunity
Magnetic Field
N/A EN61000-4-8 N/A N/A
Immunity
Voltage Dips/Short
EN61000-4-
N/A Interruptions N/A N/A
11
Immunity
I, Cyrus Kelly , representative for Relcom, Inc., verify that the product tested
is representative of production products to be sold. Based on the results
presented in this report the FBT-6 product family can be marked with the FCC
mark (as a Class A digital device) and the CE mark.
(signature)