I. CURRENT METERING
Ratio CT Phase = 5000 : 1 A Source : SIDE 13,8 kV
Secondary Measured
Expected
Metering test Injected Accuracy (%) Remarks
Current (Amp)
Current(A) Current(A) Phase A Phase B Phase C
0.25 1250 1254 1245 1245 0.16% Ok
0.5 2500 2498 2498 2501 0.04% Ok
Phase Current
0.75 3750 3749 3739 3749 0.12% Ok
1 5000 5010 4988 5030 0.19% Ok
#REF!
#REF!
711556040.xlsx/PTOC Page 3 of 6
Jalan Arjuna Utara No.50 Jakarta Barat 11510
Jakarta Indonesia
Telp.(021) 5655010-5655020
Fax. (021) 5654630-5655030
Website : GAE.co.id
#REF!
#REF!
10
Trip time (second)
0.1
100% 1000%
I fault
Inject Current
Target (s) Actual (s) Error (%)
(A)
2 1 1.023 0.023
3 1 1.025 0.025
2. PHASE UV
Voltage
Target (s) Actual (s) Error (%)
(V)
40 1 1.102 0.1020
35 1 1.066 0.0660
711556040.xlsx/51P_27 Page 6 of 6