A1 This is a product of National Development Engineers Ltd.(NDE). NDE


own the copyright to this drawing, which is strictly prohibited to be
copied, reproduced or disclosed to a third party without the written
permission.

930
Location Key Plan (Not to Scale)
PARAPET +4.50

7500 7430 5180 5055 6000


+3.03

6000 7090 6230

1720
5295

5565 7160 7160 N

7000 3125
+3.50

FLAT ROOF

4990
+3.50

FLAT ROOF

3730
+2.98

+3.73

5100 5220 7380 7380 BRITISH AMERICAN


TOBACCO

1150

5300
BANGLADESH
3065
PARAPET +4.50

1685
4425 5745 4705
5850 7350 7350

1500
10MM DIA 2M LONG AUCTUS
AIR TERMINAL

Property and infrastructure


ROOF CONDUCTOR CAPITA, 4th Floor, 75 Wells Street
London W1T 3QH
T 020 7580 5886
www.capita.co.uk/property
Registered office: 71 Victoria Street, Westminster, London, SW1H 0XA. Registered in
England and Wales No. 2018542 Part of the Capita Group Plc. www.capita.co.uk

5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000
2400 3850 70RM BYA CABLE &
FROM 30M BORING TO 3M STRUCTURAL DESIGN ASSOCIATES.
ROD BORING CONNECTION House # 28 ( 2nd Floor), Road # 8,
Nikunjo - 2, Khilkhet, Dhaka-1229.
Cell : +8801552375992, +8801733501944
:Em
l iam
oc@
9
0se.d
bta
-dsicosa
dsm
oc@
ay,.d
btn
-a
dsihca
Changing Room

2500
IT SERVER ROOM
Plant Room WC 02
Male
Toilet Tea Room
750 5600

SERVER ROOM
WC 01
5000

SECURITY
Search RM. 01
CLRS

Entrance Lobby
Search RM. 02

Off. Front Desk

2500
COPPER STRIP MESH WC 04

CONTROL ROOM Male Toilet


NATIONAL DEVELOPMENT ENGINEERS LTD.

5000
WC 05
House # 10, Road # 90, Gulshan-2
Lobby
Dhaka-1212, Bangladesh
Tel: +880-2-55051851, 55051852, 55051854-60

2500
Ent. Lobby
TURN STILE
Waiting Area
Corridor 02
CLR. 02 Fax: +880-2-55051853
5000

DESIGN & ENGINEERING BY:


5300

2500
Shower 02

700 WC 03 Sec. Manag. Office Office


Female WC 06
Meeting Room WC/Shower

5000
4600

70RM BYA CABLE

400
FROM 30M BORING TO 3M
ROD BORING CONNECTION
2700
REFERENCE CONTRACT DRAWINGS

BARE CONDUCTOR

LEGEND REVISION DETAILS

MAIN EARTHING LOOP BURIED 95mm² ABD 08.08.2018 GATEHOUSE BUILDING LIGHTNING PROTECTION SYSTEM LAYOUT

R1 18.07.2018
BARE COPPER CONDUCTOR. R0 06.08.2017
GATEHOUSE BUILDING LIGHTNING PROTECTION SYSTEM LAYOUT

GATEHOUSE BUILDING LIGHTNING PROTECTION SYSTEM LAYOUT

DEPTH OF EARTHING CABLE : MIN. 0.45M


PART
ROOF CONDUCTOR 75mm² (25mmx3mm) GATEHOUSE BUILDING LIGHTNING
PROTECTION SYSTEM LAYOUT 1/1

1 SET EARTH ROD.L=3m,d=20mm COMPLETE WITH INSPECTION PIT.

AIR TERMINAL UNIT (10mmØ, 254mm LONG)


NDE - BATB - MC - ENG - MEP - AB - 227
ABD
70 RM BYA CABLE

30 M BORING WITH INSPECTION PIT


(38 MM GI PIPE THROUGH 2 SWG COPPER WIRE)
08/08/2018
227

1 GATEHOUSE BUILDING LIGHTNING PROTECTION SYSTEM LAYOUT As Built