Rough Balance Busbar Protection and Breaker Failure Protection

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

The International Conference on Electrical Engineering 2012

No. PO4-4
Rough Balance Busbar Protection and Breaker Failure Protection
For the HK Electric’s Distribution Network
Mr. C.W. Chiu, Miss. Alfreda Ng
The Hongkong Electric Co. Ltd., Hong Kong

Abstract At present HK Electric has one power station


situated at the western tip of Lamma Island
Primary distribution substation busbar forms where electricity is generated and transmitted
an electrical node where incoming sources to Hong Kong Island and Apleichau Island at
and outgoing circuits come together, feeding 275kV. Electricity is stepped down either
in and sending out power directly to directly or via intermediate 132kV network to
customers. If a busbar fails or trips, it will 11kV or 22kV at primary zone substation
lead to the supply interruption to a large (Z/S) for feeding the distribution network.
number of customers fed by the outgoing
circuits connected to the busbar. The The HK Electric 11kV distribution system is
interruption time will be much longer because a pure cable network. Two or more 11kV
the supply restoration can only be done at feeders from Z/S’s are interconnected to form
downstream level through multiple switchings. a 'feeder group'. They are normally operated
Therefore, a reliable and discriminative as open ring circuits with 'normal-open' points
busbar protection is crucial to protect this at focal locations in the feeder group. 11kV
important piece of equipment in the cable fault in the ring will be cleared by the
distribution network and to achieve high respective feeder circuit breaker (CB) at Z/S
supply reliability. equipped with two-pole overcurrent and
single-pole earth fault (OCEF) protection.
Proper protection design of a distribution Supply will then be restored from backup
network should also cater for circuit breaker sources.
failure when an external fault occurs. When
this happens to a circuit breaker connected to In a typical Z/S, there are four zone
a busbar, tripping out of the busbar to clear transformers each feeding one 11kV busbar.
the fault is inevitable. For this reason, The four 11kV busbars are arranged to form a
breaker failure protection is normally ring with the use of bus-section (BS) or bus-
incorporated into the busbar protection interconnector (BI) breakers. A typical Z/S
scheme of a primary distribution substation as configuration with all BI breakers is shown in
a total solution. Figure 1.

This paper describes the HK Electric’s Z/Tx 1 Z/Tx 2 Z/Tx 3 Z/Tx 4


distribution protection system that employs a
simple yet effective rough balance differential
principle to achieve busbar protection and BI 1-2 BI 2-3 BI 3-4

breaker failure protection with proper fault


discrimination. The paper also compares the BI 4 -1
merits and drawbacks of different busbar and
breaker failure protection schemes adopted by Fig. 1 – Typical Z/S Configuration
us and some other utilities.
Normally, the busbar ring is split into two
1. INTRODUCTION sections with each section being fed by two
zone transformers running in parallel. For
The Hongkong Electric Co. Ltd. (HK Electric) Z/S constructed after 1989, a maximum of
was founded in the year 1890. It is one of the three zone transformers windings can operate
oldest electricity supply companies in Asia. in parallel such that when one of the four

© 2012 International Council on Electrical Engineering 390


July 8-12, 2012, KANAZAWA, JAPAN

transformers is taken out of service, the The CT and tripping arrangement of rough
remaining three transformers can operate in balance busbar protection for a typical
parallel to supply all four busbars. Tripping 132/11kV Z/S is shown in Figure 2.
of one of the two/three zone transformers
operating in parallel will therefore not result
in loss of supply to customers and the Z/TX
11kV OCEF
11kV Rough
Balance Busbar
OCEF
resilience of distribution network against any
transmission/zone transformer fault is very Busbar 1
Trip Trip Trip Trip
Busbar 2
high.

2. ROUGH BALANCE BUSBAR


PROTECTION
Fig. 2 – CT And Tripping Arrangement Of 11kV
Consistent with the open ring network, HK Rough Balance Busbar OCEF Protection
Electric adopts non-unit protection design in
the 11kV distribution system based on the In addition to providing the main protection
short time fault ratings of the primary to the busbar, the rough balance protection
apparatus and grading between successive can serve as the first backup protection for the
stages of protective devices, which are 11kV feeder protection as well as circuit
typically 'Inverse Definite Minimum Time breaker failure protection (CBF) for the
Lag' (IDMTL) OCEF protection. outgoing feeder circuits. It is a simple and
economical protection scheme since no
The rough balance busbar protection is the busbar protection CT’s are required on 11kV
main protection for the 11kV busbars at HK feeder circuits. It does not impose stringent
Electric Z/S’s. The busbar protection requirement on the CT’s and does not require
measures the currents at all in-feed points to sophisticated busbar CT selection schemes.
the busbar, which are roughly balanced to
give the total busbar load/fault current, but The main disadvantage of rough balance
will cancel out any current flows to scheme is that the busbar fault clearance time
load/faults outside the protected zone. The is moderate, typically around 0.9 second.
rough balance CT’s are only installed on the However, it should be noted that the
transformer incomer, BI and BS circuits. frequency of distribution feeder faults and
The secondary outputs of these CT’s are associated breaker failure scenarios are much
connected in parallel to the rough balance higher than switchgear busbar faults. The
busbar protection which senses the busbar benefit of serving the backup protection and
load current during normal condition and breaker failure protection for feeder faults in
remains stable. the same rough balance scheme should
outweigh its relatively slower busbar fault
When there is a fault on the busbar or its clearance time as compared with other busbar
outgoing feeders, the busbar protection will protection schemes elaborated below.
sense the full fault current, irrespective of the
location and number of the feeding 3. OTHER TYPES OF BUSBAR
transformer(s), being in-zone or out-zone. PROTECTION
The rough balance busbar protection will then
initiate the tripping of fault in-feed sources 3.1. Exact Balance Busbar Protection
into the busbar simultaneously, including the
transformer 11kV incomer, BS and BI CB’s The exact balance busbar protection is a unit
(and the capacitor bank feeder if it is type protection with CT’s installed on all
connected to the busbar) according to IDMTL associated circuits connected to the protected
current setting. busbar. Currents entering and leaving the
protected zone are added up to give zero
output under normal condition or full fault
current under in-zone fault condition. This

391 © 2012 International Council on Electrical Engineering


The International Conference on Electrical Engineering 2012

can provide fast operation at a low fault and type tested for breaking fault current with
setting on internal faults and retain stability a large DC component. To avoid damaging
on external faults. the CB, the tripping is deliberately delayed by
adding external timer relays and this will
The CT arrangement of the exact balance again complicate the protection scheme.
scheme is shown in Figure 3. This type of
busbar protection scheme usually employs a Finally, this scheme cannot provide feeder
high impedance relay to achieve stability backup protection and detect feeder CBF
under through fault condition. A proper condition. Separate backup and CBF schemes
voltage setting which is greater than the are required, usually by sequential tripping of
voltage likely to develop across the relay the BI’s followed by in-feed transformer and
during maximum through fault condition shall overall tripping time over 1.5 seconds is
be selected to ensure protection stability. expected.

3.2. Frame Earth Leakage Protection

Busbar
High
This scheme involves the measurement of
Impedance
Diff..
Busbar 1 Busbar 2
fault current flowing from switchgear frame
to earth. All the metal parts of the switchgear
must be insulated from the earth to avoid
spurious currents being circulated. A CT is
installed at the earthing cable connecting
Fig. 3 – CT Arrangement Of Exact Balance Busbar between the frame and the earthing point.
High Impedance Differential Protection The CT energizes an instantaneous ground
fault relay to trip the switchgear, typically all
The main disadvantage of such scheme is the the CB’s connected to the busbar.
requirement for dedicated CT with high
performance (Class PX) for all associated HK Electric has adopted this type of busbar
circuits connecting to the busbar. This will protection for the 525V DC switchgear at
impose a significant cost and may create traction substations. Based on past
space problem to accommodate such CT in experience, some issues that affect the
modern standardized distribution switchgear. reliability of the protection scheme are
summarized below:-
Furthermore to avoid relay mal-operation due
to earth loop current when a feeder cable is a. Low insulation between the switchgear
earthed at both ends during cable maintenance, frame and earth will form a shunt path
repeat relays that mimic the actual status of for the earth fault current which
the switchgear’s earthing switch by its normally flows through the CT, thus
auxiliary contacts are required to short and reducing the sensitivity of the protection.
disconnect the associated CT from the busbar b. Mal-operation of the relay may also
protection scheme. The repeat relay contacts happen when external electrical energy is
in the CT path may compromise the discharged through the panel to the earth
dependability, jeopardize security and inadvertently.
complicate the protection scheme with extra c. It is difficult to locate and repair the low
costs. insulation fault between the metal frame
and substation earth.
The fast operation of the exact balance d. Separate protection schemes are required
scheme in a pure distribution cable network to cater for feeder backup and CBF
will also create its own problem [1] to be condition with significant fault clearance
solved. Due to the high X/R ratio of the zone time.
transformer impedance, there will be a large
DC component in the 3-phase fault current.
Distribution CB’s are not normally designed

© 2012 International Council on Electrical Engineering 392


July 8-12, 2012, KANAZAWA, JAPAN

Besides, when applied to a.c. busbars, this configuration like ours with a maximum of
scheme can only detect unbalance faults, i.e. three transformers operating in parallel, the
it may not be effective for 3-phase-to-earth voltage selection scheme will be very
fault, which is the typical fault nature for complicated.
three phase common tank distribution
switchgear. For a double-busbar configuration with
multiple in-feed transformers, bus-couplers
3.3. Interlock Overcurrent Busbar and BS, repeat relays are required to mimic
Protection (ILOC) the transformer, bus-coupler and BS CB’s as
well as isolator switch statuses such that the
The Interlock Overcurrent (ILOC) busbar directional relays installed on the bus-
protection scheme [2] [3] relies on the use of couplers and BS can receive the correct
numerical relays with multiple built-in polarising voltage from the associated
characteristics. Numerical overcurrent (OC) transformer VT.
relays are installed on all 11kV outgoing
feeder circuits, and numerical directional The CBF protection offered by ILOC scheme
overcurrent (DOC) relays at 11kV incomer depends heavily on the communication
and BI / BS circuits. The feeder OC’s are set between the OC and DOC relays. If the
to sense the fault currents on the feeders. The communication is achieved by hard wires
DOC on the incomer circuit is set to trip the between these relays, the number of control
busbar unless blocked by any of the feeder wirings could be numerous. In addition,
OC relays. Time coordination is required to single wiring defect in the VT circuit can
avoid racing conditions for this scheme which blow the VT’s fuses and render the scheme
is commonly in the form of definite time useless. If the OC relay fails to send a
delay in operation. blocking signal to the DOC relay, the DOC
relay will trip unnecessarily for a non-busbar
Nowadays numerical relays can incorporate fault. The voltage selection scheme will also
more than one protection function in the same require the use of repeat relays and auxiliary
relay and the CBF protection function can contacts which further complicates the
easily be enabled on the numerical OC relay. scheme and lowers the reliability of the
If the feeder OC fails to operate or when CBF blocking scheme.
condition is detected by the OC relay, the
blocking will not be provided or will be Furthermore, directional relays usually come
removed to allow fast tripping of busbar with VT failure (VTF) self-monitor alarm
protection scheme to clear the fault. which will block the relay from operation if
an unhealthy voltage is detected. If one of the
This protection scheme has a number of voltage selection repeat relay contacts fails to
merits over the exact balance and frame earth switch over to the associated polarising
leakage busbar protection. It does not require voltage, relay operation will be blocked by
high performance and dedicated CT’s; it VTF alarm and therefore, the relay will be
provides backup and CBF protection and is inhibited from operation.
not restricted to earth fault.
To avoid such situation, extra supervision
The DOC relay installed on the incomer and features have to be implemented to avoid mal-
BI circuits requires the busbar voltage signal operation or non-operation condition. This
to determine the fault current direction. As will further complicate the scheme and
11kV voltage transformer (VT) are not impose extra cost.
normally available on the 11kV BI or BS
circuits, additional busbar VTs or VT buswire With the maturity of the IEC61850
from the transformer incomers are required to technology and GOOSE communication,
provide this voltage signal to the DOC relay. these relays can be linked by optical fibres via
For the more complex substation IEC61850 [4] and thereby eliminating the

393 © 2012 International Council on Electrical Engineering


The International Conference on Electrical Engineering 2012

extra control wirings as well as overcoming Typical time-current curves of the 3-second
many of the short-comings of ILOC in the IDMTL relay are shown in Figure 4.
future.
4.2. Grading Margin
4. ROUGH BALANCE BUSBAR
PROTECTION SETTING In order that the minimum amount of the
PHILOSOPHY plant is disconnected to isolate the fault, fault
discrimination has to be provided between the
As pointed out at the beginning of this paper, upstream and downstream relays so that a
rough balance protection as a non-unit feeder fault should be cleared by feeder
protection has the advantages of being able to OCEF relay while upstream protection, i.e.
provide protection to a larger section of rough balance busbar protection, should
network and cater for backup protection and remain stable. When the feeder CB fails to
CBF condition. An uncleared feeder 3-phase clear the fault, the busbar protection will be
fault due to either relay failure or a stuck required to operate.
11kV feeder breaker will be cleared by the
rough balance busbar protection in about 0.9 The grading margin between the two
second. If rough balance busbar protection is successive stages of OCEF relays needs to
not provided, the fault clearance time is much cover the following:-
longer as fault clearance has to be achieved
by 2-stage trippings of the BS / BI and the a. Feeder CB interrupting time
transformer incomer CB’s with separate 11kV b. Rough busbar OCEF relay overshoot time
backup protection. To achieve discriminative c. Relay and CT errors for both relays under
fault clearance, IDMTL OCEF protection grading
with proper time grading between the d. Safety margin
upstream and downstream protection is
adopted on the network. This is a It can be seen that items 'a' and 'b' are more or
complicated process and requires careful less constant while items 'c' and 'd' are
judgment. variable depending on the relay operating
times. In the grading of OCEF relays in HK
4.1. IDMTL OCEF Relay Electric system, a typical grading margin of
0.4 second is used for feeder faults.
The IDMTL OCEF relay possesses the
characteristic of decreasing relay operating 4.3. Special Consideration To Cater For
time with increasing relay current, that is, the Sequential Earth Faults On Two
higher the fault current, the faster the relay Feeders
operation.
Since the 11kV system in HK Electric is
resistive-earthed, voltage on sound phases
will rise from 6.5kV up to 11kV during
single-phase-to-earth fault condition. The
temporary voltage stress may precipitate
failure of weak points in the system, say a
defective cable joint. A second earth fault
may then occur before the first one is cleared.
Having responded to the first fault, the
induction disc of the busbar protection relay
will continue to move in the presence of the
second fault and thus proper grading between
Fig. 4 – Typical Time/Current Characteristic of 3- the busbar protection and the feeder
Second Standard IDMTL Overcurrent Relay protection (second fault) cannot be
maintained. Similar behaviour can also be

© 2012 International Council on Electrical Engineering 394


July 8-12, 2012, KANAZAWA, JAPAN

found in numerical relays and it is a very Another note-worthy point is that according
relay-specific characteristic. to our experience, the same type of relays
having the same operating characteristic,
To cater for sequential earth faults on two especially the overshoot / reset characteristics,
separate feeders fed from the same busbar, a should be used at all points wherever possible,
special grading margin between feeder E/F although this is not an absolute rule. If this
and busbar E/F relay has been adopted. The practice cannot be followed, extra care is
special grading margin covers the following:- necessary to ensure that discrimination is
maintained at all points.
a. Operating time of feeder E/F relay
b. Two times CB interrupting time 5. CONCLUSION
c. Two times relay overshoot time
d. Relay and CT errors for two feeder E/F Based on field experience of other utilities
relays and one busbar E/F relay under and ours, it can be concluded that the rough
grading balance busbar protection has a number of
e. Safety margin advantages over the other types of busbar
protection in our application. It is simple,
Items (b) to (e) are similar to those in Section cost effective and reliable that can serve our
4.2 except that items (b) and (c) are double radial-feed distribution system well with
and item (d) includes errors of two feeder E/F single busbar configuration. However, for a
relays. Item (a) is added to the grading more complex busbar configuration, it is not
margin to cater for the additional feeder earth always possible to achieve the required
fault. grading margin using this scheme. For this
reason, one should always consider its own
Similarly, the above special grading margin is unique network and operation characteristics
also required for grading between BS (or BI) in choosing the appropriate total protection
E/F relay and feeder E/F relay. The bigger solution for the distribution primary
grading margin will lead to longer fault substation busbar protection which has direct
clearance time for 11kV earth fault. However, impact to a large number of customers for any
it is considered a good compromise in view of in-correct or mis-operation of busbar
the small earth fault current of less than 2kA protection.
and LV voltage dip less than 10%. Apart
from the above cases, normal grading margin 6. ACKNOWLEDGEMENT
is applied to other E/F relays and to all O/C
relays. The authors are grateful to the senior
management of The Hongkong Electric Co.
Figure 5 shows typical grading curves for Ltd. for permission to publish this paper.
IDMTL relays.
7. REFERENCE

[1] C.W. Chiu, K.W. Yeung – “Protection


Scheme for the HK Electric’s New
132kV and 22kV Busbar configurations”,
ICEE 2010

[2] Wong, Wai Kay, Lai King Tong, Poon


Kin Yan – “Replacement of Existing
11kV Leakage-to-frame Busbar
Protection with Interlock Overcurrent
Fig. 5 – Grading Curves For Upstream And Busbar Protection”, ICEE 2007
Downstream Relays

395 © 2012 International Council on Electrical Engineering


The International Conference on Electrical Engineering 2012

[3] K. Brewis, K. Hearfield, and K.


Chapman (VATECH Reyrolle ACP Ltd.,
UK) – “Theory and practical
performance of interlocked overcurrent
busbar zone protection in distribution
substations”, 7th International
Conference on Developments in Power
Systems Protection (DPSP 2001)

[4] Antti HAKALA-RANTA, Olli


RINTAMAKI and Janne STARCK
(ABB) – “Utilizing possibilities of
IEC61850 and GOOSE”, CIRED 2009,
Paper 0741

© 2012 International Council on Electrical Engineering 396

You might also like