Professional Documents
Culture Documents
300tr-Design-Water Cooled Chiller
300tr-Design-Water Cooled Chiller
Job Information
Job01
TIG
Unit Information
Refrigeration capacity 304.3 tons Cooling efficiency 0.7423 kW/ton
NPLV.IP 0.0000 kW/ton Refrigerant charge (HFC-134a) 283 kg
Shipping weight 7629 kg Operating weight 8264 kg
Full Load Sound Pressure-AHRI Condition 78 dBA
Pressure vessel code ASME pressure vessel code
Refrigeration isolation valves No refrigerant isolation valves
Oil cooler With oil cooler
Evaporator Information
Leaving fluid evap 42.00 F Flow evap 606.3 gpm
Entering fluid evap 54.01 F Fluid pressure drop evap 2.50 ft H2O
Minimum flow evap 604.2 gpm Fouling factor evap 0.000100 hr-sq ft-deg F/
Btu
Number of evaporator passes 2 Pass Fluid freeze point evap 0.00 C
Evap fluid type Water Fluid concentration evap
Condenser Information
Entering fluid cond 95.00 F Flow cond 55.04 L/s
Leaving fluid cond 105.00 F Fluid pressure drop cond 11.6 ft H2O
Number of cond passes 2 pass condenser Fouling factor cond 0.000250 hr-sq ft-deg F/
Btu
Cond fluid type Water Fluid concentration cond
Condenser tube type Enhanced fin - copper Maximum flow cond 107.3 L/s
Pressure drop at min flow cond 2.67 ft H2O Pressure drop at max flow cond 120 kPa
Minimum flow cond 385.2 gpm
Electrical Information
Unit voltage 415. Volt 3 phase Unit hertz 50. Hertz
Total power 225.9 kW Starter type Wye-delta closed transition starter
Minimum circuit ampacity 439.69 A Maximum overcurrent protection 791.45 A
Starter expected inrush 776.00 A Motor locked rotor amps 2515.00 A
Run load amps/chiller input amps 351.76 A AFD output amps
This unit complies with the efficiency requirements of ASHRAE Standard 90.1-1999
Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump
Water-Heating Packages Certification Program, which is based on AHRI Standard 550/590
(I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at
www.ahridirectory.org.