EHVH-E6V - E9W - EHVX-E3V - E6V - E9W - Data Books - EEDEN22 - English
EHVH-E6V - E9W - EHVX-E3V - E6V - E9W - Data Books - EEDEN22 - English
temperature split
Technical Data
EHVH-E6V /
EHVH-E9W /
EHVX-E3V /
EHVX-E6V /
EHVX-E9W
EEDEN22
TABLE OF CONTENTS
EHVH-E6V / EHVH-E9W /
EHVX-E3V / EHVX-E6V /
EHVX-E9W
1 Features 4
EHVX-E6V, EHVX-E9W, EHVH-E9W, EHVH-E6V, EHVX-E3V 4
2 Specifications 5
3 Electrical data 16
4 Combination table 17
5 Dimensional drawings 18
6 Centre of gravity 19
7 Piping diagrams 20
8 Wiring diagrams 21
Notes & Legend 21
Control Circuit 22
Power Supply, Back-up Heater 25
10 Installation 27
Installation Method 27
11 Operation range 28
12 Hydraulic performance 30
Static Pressure Drop Unit 30
3
Daikin Altherma low temperature split
1 Features
EHVX-E6V, EHVX-E9W, EHVH-E9W, EHVH-E6V, EHVX-E3V
Floor standing air to water heat pump for heating, cooling and hot water; ideal for low energy houses
1 ›› A combined stainless steel domestic hot water tank of 180 or 230L ›› Small installation footprint, similar to other household appliances
and heat pump for easy installation ›› Integrated back-up heater choice of 3, 6, 9 kW as well as back-up
›› W-LAN Adapter connection heater less models are available
›› PCB board and hydraulic components are located in the front for
easy access
2 Specifications
Technical specifications EHVH04S18E6V EHVH04S23E6V EHVH08S18E6V EHVH08S23E6V
Heater capacity Step 1 kW 2
Step 2 kW 2 or 4
Power input
Efficiency
Nom.
Domestic Net calorific value
kW
% 118 135
0.09
118 135
2
hot water
Casing Colour White + Black
Material Precoated sheet metal
Dimensions Unit Height mm 1,650 1,850 1,650 1,850
Width mm 595
Depth mm 625
Packed Height mm 1,820 2,020 1,820 2,020
unit Width mm 720
Depth mm 740
Weight Unit kg 119 128 119 128
Packed unit kg 135 144 135 144
Packing Material Wood / Carton / PE wrapping foil / Metal
Weight kg 16
PED Category Art4.3 / See note 9
Most Name Plate heat exchanger
critical Ps*V Bar*l 38
part
Refrigerant side Type Plate heat exchanger
heat exchanger Quantity 1
Plates Quantity 42
Pump Type Glandless circulator
Nr of speeds PWM
Power input W 52
Water side Heat Type Plate heat exchanger
exchanger Quantity 1
Plates Quantity 42
Water volume l 0.95
Water Min. l/min 12.0 (1)
flow rate
Expansion vessel Volume l 10
Max. water pressure bar 3
Pre pressure bar 1
Water filter Diameter perforations mm 0.8
Material Stainless steel / Plastic
Tank Name Stainless steel domestic Stainless steel domestic Stainless steel domestic Stainless steel domestic
hot water tank 180 l hot water tank 230 L hot water tank 180 l hot water tank 230 L
Tank Water volume l 180 230 180 230
Material Stainless steel (EN 1.4521)
Maximum water temperature °C 70
Maximum water pressure bar 10
Insula- Material Polyurethane foam
tion Heat loss kWh/24h 1.2 (2) 1.4 (2) 1.2 (2) 1.4 (2)
Standing S W 50 58 50 58
heat loss
Storage V l 181 220 181 220
volume
Corrosion protection Pickling
Energy efficiency class B
General Supplier/ Name or trademark Daikin Europe N.V.
Manu- Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
facturer
details
3-way valve Coeffi- Space heating m³/h 8
cient of Domestic hot water tank m³/h 10
flow (kV)
Water circuit Piping connections diameter inch G 1" (female)
Piping material Cu
Internal piping diameter inch 1"
Piping inch 1"
Safety valve bar 3
Manometer Digital
Drain valve / fill valve No
Shut off valve Yes
Air purge valve Yes
Total water volume l 3.5 (3)
Minimum water volume in the system l 10 (4)
for cooling
Minimum water volume in the system l 0 (4)
for heating
2 Specifications
Technical specifications EHVH04S18E6V EHVH04S23E6V EHVH08S18E6V EHVH08S23E6V
Water circuit - Do- Piping material Stainless steel
mestic hot water Piping Cold water in / Hot water out inch G 3/4" FEMALE
2 side connec- Recirculation connection
tions
inch G 3/4" FEMALE
2 Specifications
Technical specifications EHVH08S18E9W EHVH08S23E9W
Heater capacity Step 1 kW 3
Step 2 kW max. 6 kW
Power input
Efficiency
Nom.
Domestic Net calorific value
kW
% 118
0.09
135
2
hot water
Casing Colour White + Black
Material Precoated sheet metal
Dimensions Unit Height mm 1,650 1,850
Width mm 595
Depth mm 625
Packed Height mm 1,820 2,020
unit Width mm 720
Depth mm 740
Weight Unit kg 119 128
Packed unit kg 135 144
Packing Material Wood / Carton / PE wrapping foil / Metal
Weight kg 16
PED Category Art4.3 / See note 9
Most Name Plate heat exchanger
critical Ps*V Bar*l 38
part
Refrigerant side Type Plate heat exchanger
heat exchanger Quantity 1
Plates Quantity 42
Pump Type Glandless circulator
Nr of speeds PWM
Power input W 52
Water side Heat Type Plate heat exchanger
exchanger Quantity 1
Plates Quantity 42
Water volume l 0.95
Water Min. l/min 12.0 (1)
flow rate
Expansion vessel Volume l 10
Max. water pressure bar 3
Pre pressure bar 1
Water filter Diameter perforations mm 0.8
Material Stainless steel / Plastic
Tank Name Stainless steel domestic hot water tank 180 l Stainless steel domestic hot water tank 230 L
Tank Water volume l 180 230
Material Stainless steel (EN 1.4521)
Maximum water temperature °C 70
Maximum water pressure bar 10
Insula- Material Polyurethane foam
tion Heat loss kWh/24h 1.2 (2) 1.4 (2)
Standing S W 50 58
heat loss
Storage V l 181 220
volume
Corrosion protection Pickling
Energy efficiency class B
General Supplier/ Name or trademark Daikin Europe N.V.
Manu- Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
facturer
details
3-way valve Coeffi- Space heating m³/h 8
cient of Domestic hot water tank m³/h 10
flow (kV)
Water circuit Piping connections diameter inch G 1" (female)
Piping material Cu
Internal piping diameter inch 1"
Piping inch 1"
Safety valve bar 3
Manometer Digital
Drain valve / fill valve No
Shut off valve Yes
Air purge valve Yes
Total water volume l 3.5 (3)
Minimum water volume in the system l 10 (4)
for cooling
Minimum water volume in the system l 0 (4)
for heating
2 Specifications
Technical specifications EHVH08S18E9W EHVH08S23E9W
Water circuit - Do- Piping material Stainless steel
mestic hot water Piping Cold water in / Hot water out inch G 3/4" FEMALE
2 side connec- Recirculation connection
tions
inch G 3/4" FEMALE
2 Specifications
2 Specifications
2 Specifications
2 Specifications
2 Specifications
2 Specifications
2 Specifications
(1)Operation area is extended to lower flow rates only in case the unit operates with heat pump only. (Not in startup, no BUH operation, no defrost operation). |
(2)Based on a dT of 45 K |
(3)ncluding piping + PHE + back-up heater; excluding expansion vessel |
(4)Excluding the water in the unit. This minimum water volume is sufficient for most applications. During critical processes extra water may be required. |
(5)DB/WB 7°C/6°C - LWC 35°C (DT=5°C) |
(6)Sound values are measured in a semi-anechoic room. Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level
2
drawings. |
(7)Refer to operation range of the unit. |
(8)4 pole 20 A curve 400V tripping class C (refer to wiring diagram) |
(9)PED unit category: Art3§3: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC |
(10)Above mentioned power supply of the hydrobox is for the backup heater only. The switch box and the pump of the hydrobox are supplied via the outdoor unit. The optional domestic hot water tank has a
separate power supply. |
(11)2 pole 20 A curve 400V tripping class C (refer to wiring diagram)
3 Electrical data
3-1 Electrical Data
EHV(H-X-Z)-E(3V_6V_9W)(G)
Electrical specifications
Not applicable for ·EHVH(04/08)D(A/J)V· models.
3 Type
Capacity setting kW
3V
3 2-4 2-6 4-6
6V
·2-4· (in case of emergency: ·2-6·) 6 3-6 3-9
9W
·3-6· (in case of emergency: ·3-9·)
Capacity stage ·· 1 2 2 2 2 2 1 2 2 2 2
Capacity stage ·1· kW 3 2 2 2 2 2 6 3 3 3 3
Capacity stage ·2· kW - 4 6 4 4 6 - 6 9 6 9
Minimum time delay between stages Note ·4· Note ·5· Note ·5·
Backup heater
Power supply Phase 1~ 3~ 3~
(1) Frequency Hz 50 50
Voltage V 230 ±10% 400 ±10%
Nominal running current A 13 17,4 26,1 26,1 17,4 26,1 15 8,7 13 8,7 13
Ω 0,34 0,22 0,22 0,22 0,22 0,22 - -
Current Zmax (backup heater) (2)
Complex - -
Minimum Ssc value kVA - (3) (3) -
(1) The above-mentioned power supply of the hydrobox is for the backup heater only.
Booster heater power supply
(2) In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤
Zmax.
(3) The equipment complies with EN/IEC 61000-3-12.
Notes
EN/IEC 61000-3-11 European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated
current ≤ 75 A.
EN/IEC 61000-3-12 European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current > 16 A and ≤
75 A per phase.
Zsys System impedance
Note ·4· Backup heater ·(3V)· Minimum time delay between stages
Capacity [kW]
·1· min. ·10· min.
Note ·6· Booster heater Minimum time delay between stages
Time
Note ·5· Backup heater ·(6V/9W)· Minimum time delay between stages Stage ·1·
Capacity [kW]
·10· s ·1· min. ·2 (*)· min. ·1· min. ·0· s ·10· min. ·(*) : Unless manually activated Time
Stage ·2·
Stage ·1·
4 Combination table
4-1 Combination Table
EHVH-E6V / EHVH-E9W / EHVH-UE6V / EHVX-E3V / EHVX-E6V / EHVX-E9W / EHVZ-E6V / EHVZ-E9W
Heating only model ·EHVH*· 18 - 6V (9) 23 - 6V (9) Heating only model ·EHVH*· 18 - 6V (9) 18 - 9W (9) 23 - 6V (9) 23 - 9W (9)
Reversible model ·EHVX*· 18 - 3V 18 - 6V (9) 23 - 3V 23 - 6V (9) Reversible model ·EHVX*· 18 - 6V (9) 18 - 9W (9) 23 - 6V (9) 23 - 9W (9)
(Integrated Bizone) 18 - 6V (9) (Integrated Bizone) 18 - 6V (9) 18 - 9W (9) 23 - 6V (9) 23 - 9W (9)
Heating only indoor unit for the UK 18 - 6V (9) 23 - 6V (9) Heating only indoor unit for the UK 18 - 6V (9) 23 - 6V (9)
Backup heater ·3kW 1N~230 V· o - o - Backup heater ·3kW 1N~230 V· - - - -
Backup heater ·2-4-6kW 1N~230 V· - o - o Backup heater ·2-4-6kW 1N~230 V· o - o -
Backup heater ·2-4-6kW 3~230 V· - o - o Backup heater ·2-4-6kW 3~230 V· o - o -
Backup heater ·3-6-9kW 3N~400 V· - - - - Backup heater ·3-6-9kW 3N~400 V· - o - o
Domestic hot water tank ·180L· o o - - Domestic hot water tank ·180L· o o - -
Domestic hot water tank ·230L· - - o o Domestic hot water tank ·230L· - - o o
Kit availability
Reference Description
EHV*(04/08)S*E(A/J)* EHVH(04/08)SU*E(A/J)*
Reference Description
Notes
(1) PCB that provides additional output connections: · ·
(a) Control external heat source (bivalent operation).
(b) Output remote ON/OFF signal space heating/cooling OR bottom plate heater ·*KBPHTH16* · control.
(c) Remote alarm output
(2) Additional relays to allow bivalent control in combination with an external room thermostat are field-supplied.
(3) PCB to receive up to 4 digital inputs for power limitation, only for ·EHV(H/X/Z)(04/08)E(A/J)*·.
(4) Data cable for connection with PC.
(5) Only 1 remote sensor can be connected: indoor OR outdoor sensor.
(6) This kit is mandatory for the UK models.
(7) The WLAN cartridge is supplied in the accessory bag of the unit and is meant to be plugged into the SD card slot on the MMI-2. In case of bad signal reception, the WLAN cartridge can be removed
and replaced by the WLAN module.
(8) Can only be used in combination with wireless room thermostat ·EKRTR1·.
(9) The backup heater capacity depends on a user interface setting.
Remark
Other combinations than mentioned in this combination table are prohibited.
3D130019A
5 Dimensional drawings
5-1 Dimensional Drawings
EHVX-E3V 1 Gas pipe connection ·Ø 15.90mm· flare
EHV(H-X)-E6V 2 Liquid pipe connection ·Ø 6.35mm· flare
5 EHVX-E6VG
258
98 80
80 4 Space heating water pressure sensor
5 Safety valve
8 11 10
6 Drain valve water circuit
58
8
111
3 4 5
7 Air purge
7
8 Shut-off valve
20
15 9 Magnetic filter / dirt separator
14
600
10 Water in connection ·1" F BSP·
634
24 18
22
11 Water out connection ·1" F BSP·
9
12 Domestic hot water: cold water in ·3/4" F BSP·
13 Domestic hot water: hot water out ·3/4" F BSP·
6 23
597 14 High voltage wiring intake ·Ø 24mm·
2 1 13 12
15 Low voltage wiring intake ·Ø 15mm·
21 16 Levelling feet
17 User interface
18 Recirculation connection ·G 3/4"· (female)
19 Drain outlet (unit + safety valve)
17
20 Expansion vessel
21 3-way valve
22 Pump
23 Backup heater
24 Flow sensor
19
1880
1855
1680
1655
19
180L 16 16
230L
16 Screws used in this unit:
T25 T25
The typical field installation has to be done
according to the applicable legislation.
For examples, refer to the
installer reference guide. 3D112072B
6 Centre of gravity
6-1 Centre of Gravity
EHVX-E3V
EHV(H-X-Z)-E6V
EHV(H-X-Z)-E9W
6
EHVX-E6VG
MODEL X Y Z
180L 297.5 299 718
230L 297.5 299 858
Z
X Y
3D113623A
7 Piping diagrams
7-1 Piping Diagrams
EHVH-E6V Water side Refrigerant side
EHVH-E9W 14
13
EHVX-E3V Field installed
9
18
7 EHVX-E6V(G) 15 R1T
EHVX-E9W 1
16
5
R2T 19
10 M 17
R8T 23
Evaporator
3 12 Condenser
R5T 22
4
8 R3T 20
9
21
Field installed 11
R4T
2
5
7
5
10
10
8 Wiring diagrams
8-1 Notes & Legend
EHVH-E6V / EHVH-E9W / EHVH-UE6V / EHVX-E6V / EHVX-E9W
X1M to go through before starting the unit
NOTES
X1M : Main terminal : Option
X2M 15 : Field wiring terminal for AC 8
X5M : Field wiring terminal for DC : Wiring depending on model
X6M : BUH Power supply terminal
X10M : Smartgrid terminal
: Not mounted in switch box
: Earth wiring
: Field supply
**/12.2 : PCB
1 : Several wiring possibilities
NOTES
1. Connection point of the power supply for the BUH should be foreseen outside the unit.
22
8
8-2
B1PR B1PW
EHVX-E6V
EHVH-E6V
EHVX-E9W
EHVH-E9W
X6Y X7Y
EHVH-UE6V
1 2 3 4 1 2 3
X60A R1T
1 1 1
CN1 1 2 3 4 -t°
1 3 2 2 2
SS1 3
3
ON X6A R2T
4
Control Circuit
OFF 4 1
1 F1U F2U 5 5 2 -t°
6 6
X7A R3T
CN2 X40A 1
1 2 -t°
KCR KFR KHR KHUR PHC1 2
X8A R4T
3
1
Wiring diagrams
X1 X2 X3 X4 YC Y1 Y2 Y3 Y4 4 -t°
230V AC 2
Control Device 5
6 X9A
L1 N1 L2 N2 R5T
7 1
SWB1 2 -t°
Alarm output 8
X2M Max. load
A1P/X21A X4A
9 0.3 A - 250 V AC X10M 1 2 3 4 X5M 10 9 6 5 X5M 14 13 4 3
X2M.13 SWB1 1 R8T
8 1
2
7 2 -t°
Ext. heat source 4 5 3
Max. load 0.3 A - 250 V AC 4 X8Y
S4S
L N Min. load 20 mA - 5 V DC
K1A A1 K2A A1
Options: ext. heat source output, alarm output
K1A
K2A
Smartgrid
3 A2 A2 Smartgrid PV power
A4P.Y2
X2M
A4P.YC
A1P/X21A contacts pulse meter
9
X2M.13 for HV smartgrid 1
8 for smartgrid X34A
7 2
3 1
3
X5M.9
X5M.6
X5M.5
X5M.10
Space C/H 2 B2L
ON/OFF output 1 2 3 4 5 6 4
3
Max. load 0.3 A - 250 V AC X85A 5
S10S
S11S
A8P
for LV smartgrid
Options: ON/OFF output X80A
3 3 4 5 1 2 3 4 5 6 7 8 9 10 11 12
X5M.9
X5M.6
X5M.5
X5M.4
X5M.3
X5M.10
X5M.14
X5M.13
DS1
ON
OFF
Q4L 1 2 3 4 1 2 3 4 5 X801M
S1S
S3S
S2S
Electric pulse Safety Electric pulse
meter input: thermostat meter input:
Preferential kWh 12 V DC pulse contact: 16 V DC 12 V DC pulse Power limitation digital
rate power supply detection detection detection inputs: 12 V DC / 12 mA
S6S
S7S
S8S
S9S
4D130329D
EHVX-E6V
EHVH-E6V
Only for preferential kWh rate power supply (outdoor) Only for normal power supply (standard) only for
EHVX-E9W
EHVH-E9W
SWB2
EHVH-UE6V
Use normal kWh rate power supply for indoor unit Indoor unit supplied from outdoor *6V & *9W
L N 1N~, 50 Hz 11
Outdoor unit Outdoor unit 31 11
230 V AC 6,3 A
Q2DI Normal kWh 6 5 X2M Q1L
A11P/X1B.1
A11P/X1B.2
1 2 3 1 2 3 32 12
rate power X1M X1M A1
supply 1 2
X11YB TR1 K5M
1 2 3 X1M 1 2 3 X1M A2
X11YA 11
6 5 X2M 7 9 X2M
1
1 2 2 1 2
X2M.9
X11YB X11YA
X14Y.3
X14Y.2
X14Y.1
X14Y.4
A11P/X1A.4
A11P/X1A.1
X11Y 8 X11Y 8
Control Circuit
SWB1
A1P
X1A X19A X39A X48A X26A X31A X3A X21A
6 7 X17A
1 3 1 1 3 5 1 2 3 4 1 2 1 2 1 3 1 3 1 3
X2M.35
X2M.34
X2M.30
X2M.30
X2M.35a
X2M.34a
A2P A2P 3 FU1
H C COM H C COM
X2M 5
35 7
Wiring diagrams
R1T R1T 34
-t° -t° X24A
35a 1
3
34a
31 5
only for wired ON/OFF thermostat only for wired On/OFF thermostat
30 7
6 7 4 KPR
X14A K4R
X2M.35
X2M.34
X2M.30
X2M.31
X2M.30
X2M.31
X2M.35a
X2M.34a
3 1
3
A15P A15P
H C COM N L H C COM N L
1 3 5 E 1 3 5 1 2 1 3 1 2 1 2 1 2 3 4 5 6 5 3 1 3 1 3 1 3 1
A2P A2P X20A X28A X15A X18A X25A X11A X12A X13A
X2A X22A X16A
R1T R1H R1T R1H
%H20 %H20 SWB1
-t° -t°
SWB2
X1M X1M 1 3 5
X20A K1M A1 K2M A1
1 1
2 R2T 2 R2T A2 A2
GND
L
PWM
FB
N
PE
only for 3
only for 3 X20A
EKRTR1 14 -t° EKRTR1 14 -t° 1 3 5
X1M only for ext. X1M only for ext. MS only for *6V
1 1 3~ M1P and *9W SWB2
sensor sensor
only for 14 2 (floor or only for 14 2 (floor or
EKRTRB ambient) EKRTRB ambient) X2M 29 28 21 X2M 14a 14 13 12 8 7 X2M 2 1
SWB1
only for wireless ON/ only for wireless ON/
OFF thermostat OFF thermostat X5M 8 7 X5M 12 11
BLK
NC BLU 12
6 7 M
N
X2M.3
X2M.4
X2M.3
X2M.4
X2M.35
X2M.30
X2M.30
X2M.35a
A3P A3P M2S M3S M2P 1~
NO
3 wire type BRN 1 2
A11P/X1A.2
A11P/X1A.3
X2M.29
X2M.21
-t°
ext. ambient
9 NC valve sensor option
(indoor or Remote user
Shut-off valve interface
outdoor)
4D130329D
23
8
24
8
A9P
8-2
E1P E2P E3P E4P
EHVX-E6V
EHVH-E6V
EHVX-E9W
EHVH-E9W
EHVH-UE6V
1 2 3 4 5
X1
SWB1 A11P
X1A X8
13 PSU
A1P/X48A.1 4 1 2 3 4 5
Control Circuit
X5M.11 4 5
P1
X5M.12 3 P1P2
PSU +
A1P/X48A.2 2
PSU
PSU
A1P/X48A.1 1
X3
X4 1
USB
2
WLAN cartridge option CAN
3
4
10
WLAN SD CARD X10
Cartridge
10 A20P
J2 X9
1 1
2 2 X22
WLAN UART 30
3 3 P1M
Interface
4 4
5 5
X5
1
2
Debug UART
3
Interface
4
5
SW1 SW2
SW3 SW4 SW5
WLAN adapter module
option
4D130329D
8-3
1 1 1
F1T E3H
EHVX-E6V
EHVH-E6V
EHVX-E9W
EHVH-E9W
X1H
EHVH-UE6V
X1HA 1 2 3 SWB2 SWB1
SWB2 11 21 E2H E2H E2H E1H E1H E1H E2H E2H E2H
Q1L
12 22
1 2 4 1 1
E3H
F1T K1M F1T F1T F1T F1T F1T F1T F1T F1T F1T
SWB2 1 3
X1H X1H X1H
X1HA 1 2 3 X1HA 1 9 2 8 7 3 5 X1HA 1 2 3 7 8 9 5 SWB2 SWB1
SWB2 SWB2
SWB2 11 21
X6M E2H E2H E1H E1H E1H E2H E2H
1 3 5 E2H 1 3 5 1 3 5 E2H 1 3 5
Q1L K1M K2M K1M K2M
12 22 2 4 6 2 4 6 2 4 6 2 4 6
1 3
2 4
F1T F1T F1T F1T F1T F1T F1T F1T F1T
Wiring diagrams
K1M
F1B
SWB2 1 3
I I X1H 2 4 6 14 X1H 2 4 6 14
2 4 X1HA 1 9 2 8 7 3 5 X1HA 1 2 3 7 8 9 5
K5M K5M
1 3 5 13 1 3 5 13
Power Supply, Back-up Heater
2 2
3~, 50 Hz L1 L2 L3 1N~, 50 Hz L N 3N~, 50 Hz L1 L2 L3 N
230 V AC 230 V AC 400 V AC
Q1DI Q1DI Q1DI
for *6T1 (3~, 230 V, 6 kW) for *6V3 (1N~, 230 V, 6 kW) for *6WN (3N~, 400 V, 6 kW)
and *9WN (3N~, 400 V, 9 kW)
only for *6V only for *9W
L1 L2 L3 L N L1 L2 L3 N
4D130329D
25
Daikin Europe N.V. SWB2 - BUH power supply Altherma BML FS - E-series 4D130329 -
Daikin Altherma low temperature split
STANDARD PART
Power supply OUTDOOR UNIT
1 Only for normal power supply installation
unit power supply: 230 V + earth 3 core
X1M: L-N-earth
normal kWh rate power supply for indoor unit: 230 V 2 core X1M: 1-2-3
FIELD SUPPLY
2 Preferential kWh rate 3 core
power supply contact INDOOR UNIT FIELD SUPPLY
2 Only for LV smartgrid
Only for *KRP1HB*
Smartgrid contact S10S X1M: 1-2-3
A4P: Y1-YC 2 core
X2M: 5-6 X2M: 7-9 Alarm indication
2 core Alarm output 230 V
Optional part 2x0.75
2 Only for HV smartgrid X5M: 9-10
signal 2 core
A4P: X1-X2
Smartgrid contact K1A Ext. heat source (eg boiler)
Changeover to
ext. heat source output signal
2 core
2x0.75
Smartgrid relais K1A X10M: 1-2 A4P: Y2-YC
2 core X2M: 7-9 2 core Cooling/heating
2x0.75 Cooling/heating 230 V ON/OFF output
Smartgrid relais K2A X10M: 3-4 ON/OFF output
HV smartgrid control supply: 230 V 4 core
2 core
X2M: 1-2 Circulation pump for DHW
230 V
3 X5M: 13
FIELD SUPPLY X5M: 14 2WAY VALVE
NO valve: X2M: 21-28 2 core
3 2 core M2S for cooling mode
2x0.75 NC valve: X2M: 21-29 230 V
Safety thermostat Q4L X5M: 13-14
2 core 5
X5M: 5-6 Electricity meter pulse input 1
signal
Only for HV smartgrid 5
Smartgrid contact K2A
Only for LV smartgrid 5
Smartgrid contact S11S
5 or 4 or 3
backup heater power supply (3/6/9 kW): 400 V or 230 V + earth core X6M: L1-L2-L3 + earth 2 core 6
or L-N + earth X5M: 3-4 Electricity meter pulse input 2
(F1B) or L1-L2-L3-N + earth signal
6
Smartgrid pulse meter
OPTIONAL PART
2 core Only for KRCS01-1 or EKRSCA1
X5M: 7-8 External thermistor (indoor or outdoor)
OPTIONAL PART signal
NOTE
• In case of signal cable: keep minimum distance to power cables > 5 cm
4D130331D
10 Installation
10 - 1 Installation Method
EHVH-E6V
EHVH-E9W
EHVX-E3V
EHVX-E6V(G) 10
EHVX-E9W
MIN. 600
MIN. 300
MIN. 500
3D112073A
11 Operation range
11 - 1 Operation Range
EHVX-E3V
EHV(H-X-Z)-E6V
EHV(H-X-Z)-E9W
EHVX-E6VG
11 Heat-up times
120,00
EHV*S*23(D/E)(A/J)* EHV*S*18(D/E)(A/J)*
110,00
Heat-up time (min)
100,00
90,00
80,00
70,00
60,00
35 40 45 50 55 60
Notes
1.
Time the indoor unit (heat pump only operation) requires to heat up the domestic hot water tank from 10°C to the indicated temperature.
See the operation range for maximum domestic hot water tank temperature during heat pump only operation.
4D113329C
EHVX-E3V
EHV(H-X-Z)-E6V
EHV(H-X-Z)-E9W
EHVX-E6VG
580
480 EHV*S*23(D/E)(A/J)*
280
230
180
130
40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55
If a higher daily Veq 40°C is required, then additional heat-up cycles are required within 24 hours.
See the operation manual for more information.
Notes
(1) According to EN16147.
4D113329C
11 Operation range
11 - 1 Operation Range
EHBH-E6V / EHBH-E9W / EHBX-E6V / EHBX-E9W
EHSH-E / EHSHB-E / EHSX-E / EHSXB-E
Outdoor temperature [°C DB]
EHVH-E6V / EHVH-E9W / EHVH-UE6V / EHVX-E3V
EHVX-E6V / EHVX-E9W / EHVZ-E6V / EHVZ-E9W 25 11
Outdoor temperature [°C DB]
Heating mode
43 10
·4~8· kW class
Cooling mode
·1·-phase ·D/E· series
0
·4~8· kW class
-5
-15
18 -20
-25
10 -30
5 13 22 50 5 15 18 25 30 35 45 50 55 60 65
Leaving water evaporator temperature [°C] Leaving water condensor temperature [°C]
Legend
Backup heater only operation
No outdoor unit operation
Pull-down area
Outdoor unit operation if setpoint >·55·°C and ΔT = ·10·°C (ΔT = outlet temperature – inlet temperature)
Remark
In restricted power supply mode, the outdoor unit, booster heater and backup heater can only operate separately.
Warning
In areas with low ambient temperatures and high humidity, or in areas with heavy snowfall, remove the suction grille to ensure proper operation.
Non-exhaustive list of areas: Austria, Czech Republic, Denmark, Estonia, Finland, Germany, Hungary, Latvia, Lithuania, Norway, Poland, Romania, Serbia, Slovakia, Sweden, …
3D111563D
12 Hydraulic performance
12 - 1 Static Pressure Drop Unit
EHVH-E6V
EHVH-E9W
EHVX-E3V
12 EHVX-E6V(G)
EHVX-E9W
EHV(H/X)(04/08)*(D/E)(A/J)*
Operation area
70
60
External static pressure [kPa]
50
40
30
20
10
0
0 5 10 15 20 25 30 35 40
-10
Opera�on area is extended to lower flow rates only in case the unit operates with heat pump only.
(Not in startup, no BUH operation, no defrost operation.)
Notes
1
Selecting a flow outside the operating area can damage the unit or cause the unit to malfunction.
See also the minimum and maximum allowed water flow range in the technical specifications.
4D112012B
The present leaflet is drawn up by way of information only and does not constitute an
offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of
this leaflet to the best of its knowledge. No express or implied warranty is given for the
completeness, accuracy, reliability or fitness for particular purpose of its content and the
products and services presented therein. Specifications are subject to change without prior
notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in
EEDEN22 09/2022
the broadest sense, arising from or related to the use and/or interpretation of this leaflet.
All content is copyrighted by Daikin Europe N.V.