A. The design, installation and maintenance of standpipe systems shall be in accordance with NFPA 14,
Standard for the Installation of Standpipe, Private Hydrant and Hose Systems.
B. Wet Standpipes
Wet standpipe system extending from the cellar or basement into the topmost storey shall be required
in the following:
2. Educational, healthcare and detention and correctional, business and mercantile, industrial, and
hotels and apartments occupancies, four or more storeys in height, and
3. Hazardous storage and business and mercantile occupancies having a floor area
exceeding one thousand eight hundred sixty square meters (1,860 m²) per floor.
The following assembly occupancies with occupant load of one hundred fifty (150)
sprinkler system:
b. dance halls;
c. discotheques; and
Buildings containing assembly occupancies with occupant load of more than three hundred (300)
persons shall be protected by an approved, supervised automatic
sprinkler system:
b. throughout all storeys below the storey containing the assembly occupancy;
3. The provisions of paras 1 and 2 above shall not apply to assembly occupancy with all sides open and
places of worship at the level of exit discharge with sufficient means of egress.