Professional Documents
Culture Documents
Petronas Technical Standards: Offshore Temporary Refuges
Petronas Technical Standards: Offshore Temporary Refuges
Petronas Technical Standards: Offshore Temporary Refuges
PTS 11.20.01
August 2014
FOREWORD
PETRONAS Technical Standards (PTS) has been developed based on the accumulated knowledge,
experience and best practices of the PETRONAS group supplementing National and International
standards where appropriate. The key objective of PTS is to ensure standard technical practice across
the PETRONAS group.
Compliance to PTS is compulsory for PETRONAS-operated facilities and Joint Ventures (JVs) where
PETRONAS has more than fifty percent (50%) shareholding and/or operational control, and includes
all phases of work activities.
y
nl
Contractors/manufacturers/suppliers who use PTS are solely responsible in ensuring the quality of
O
work, goods and services meet the required design and engineering standards. In the case where
specific requirements are not covered in the PTS, it is the responsibility of the
se
Contractors/manufacturers/suppliers to propose other proven or internationally established
standards or practices of the same level of quality and integrity as reflected in the PTS.
lU
In issuing and making the PTS available, PETRONAS is not making any warranty on the accuracy or
na
completeness of the information contained in PTS. The Contractors/manufacturers/suppliers shall
ensure accuracy and completeness of the PTS used for the intended design and engineering
er
requirement and shall inform the Owner for any conflicting requirement with other international
nt
PETRONAS is the sole copyright holder of PTS. No part of this document may be reproduced, stored
in a retrieval system or transmitted in any form or by any means (electronic, mechanical, recording or
AS
otherwise) or be disclosed by users to any company or person whomsoever, without the prior written
consent of PETRONAS.
N
The PTS shall be used exclusively for the authorised purpose. The users shall arrange for PTS to be
O
kept in safe custody and shall ensure its secrecy is maintained and provide satisfactory information to
TR
ANNOUNCEMENT
Please be informed that the entire PTS inventory is currently undergoing transformation exercise from
2013 - 2015 which includes revision to numbering system, format and content. As part of this change,
the PTS numbering system has been revised to 6-digit numbers and drawings, forms and requisition
to 7-digit numbers. All newly revised PTS will adopt this new numbering system, and where required
make reference to other PTS in its revised numbering to ensure consistency. Users are requested to
refer to PTS 00.01.01 (Index to PTS) for mapping between old and revised PTS numbers for clarity. For
further inquiries, contact PTS administrator at ptshelpdesk@petronas.com.my
y
nl
O
se
lU
na
er
nt
-I
AS
N
O
TR
PE
PTS 11.20.01
OFFSHORE TEMPORARY REFUGES August 2014
Page 4 of 33
Table Of Contents
1.0 INTRODUCTION ..................................................................................................... 6
1.1 SCOPE ............................................................................................................................ 6
1.2 GLOSSARY OF TERMS..................................................................................................... 6
1.3 SUMMARY OF CHANGES ............................................................................................... 9
2.0 GENERAL REQUIREMENTS ................................................................................... 10
2.1 OBJECTIVES .................................................................................................................. 10
y
2.2 FUNCTIONAL REQUIREMENTS ..................................................................................... 10
nl
2.3 BASIS OF DESIGN ......................................................................................................... 10
O
3.0 TR CONFIGURATION ............................................................................................ 11
se
3.1 PRIMARY TR CONCEPTS ............................................................................................... 11
lU
3.2 SECONDARY TR CONCEPTS .......................................................................................... 11
3.3 CAPACITY ..................................................................................................................... 12
na
3.4 MUSTER SPACE ............................................................................................................ 12
er
y
nl
O
se
lU
na
er
nt
-I
AS
N
O
TR
PE
PTS 11.20.01
OFFSHORE TEMPORARY REFUGES August 2014
Page 6 of 33
1.0 INTRODUCTION
This PTS specifies requirements of the systems and subsystems which comprise the
Temporary Refuge (TR) and the associated means of escape and evacuation, their acceptance
criteria and provides the guidance and recommendations for the design and performance of
TR.
This PTS provides additional information over and above the available International standards
and guidance on TRs and the associated emergency response facilities; namely ISO 13702 and
ISO 15544.
y
1.1 SCOPE
nl
1.1.1 This PTS is intended for use in all new and existing manned/not normally manned offshore oil
O
and gas exploration and production facilities in Malaysian waters.
se
1.1.2 For international waters, standard used is as per local rules and regulations applies.
1.1.3
lU
This standard is applicable to both fixed and mobile offshore facilities.
na
1.2 GLOSSARY OF TERMS
1.2.1 General Definition of Terms & Abbreviations
er
Refer to PTS Requirements, General Definition of Terms, Abbreviations & Reading Guide PTS
nt
No Terms Definition
1 Acceptance criteria Measurement indicatiors to ensure any specific
N
No Terms Definition
10 Installation Fixed or mobile facility involved in offshore oil and
gas exploration or production activities.
11 Living quarters Permanently enclosed spaces e.g. cabins, dining
rooms, galleys, recreation rooms, sick-bay, offices,
change rooms, ablution areas and similar spaces
used for the accommodation and welfare of
personnel on board.
12 Manned/Not normally Manned – An installation on which people are
y
manned/Unmanned routinely accommodated.
nl
installation Not Normally Manned – An installation which are
O
connected by bridge to manned installation.
Unmanned – An installation where the people are
se
not accommodated.
lU
13 Muster area Gathering point where personnel gather in
response to a plant/facility safety alarm,
instructions or a change in the installation safety
na
status.
er
No Abbreviation Description
No Abbreviation Description
y
10 ESD Emergency shutdown
nl
O
11 HVAC Heating, ventilation and air conditioning
se
12 HEMP Hazard and effects management process
lU
13 ICRP International committee for radiation
protection
na
14 IDLH Immediately dangerous to life or health
er
No Abbreviation Description
29 TR Temporary refuge
y
nl
This PTS 11.20.01 replaces PTS 37.17.10.11 (December, 2011).
O
se
lU
na
er
nt
-I
AS
N
O
TR
PE
PTS 11.20.01
OFFSHORE TEMPORARY REFUGES August 2014
Page 10 of 33
2.1 OBJECTIVES
2.1.1 The main purpose of the TR is to serve as a temporary muster point with protection against
fire, heat and explosions for a short period, until the platform can be safely evacuated. This
can be provided by partially enclosing the TR or by locating the TR away from the
consequences of possible hazardous events.
2.1.2 All offshore installations shall have at least one place designated as the TR. The TR shall have
the sufficient capacity to protect the maximum persons on board (POB) the installation.
2.1.3 The TR may be an enclosure, multiple enclosures, or only an area on open deck. However, for
y
small platforms, a TR need not be integrated with the living quarters and need not be
nl
enclosed.
O
2.1.4 During the period required for the evacuation process to be completed, the TR is required to
maintain the safety of personnel. This period includes the following times and activities:
se
i. time required to complete the full muster at the TR;
ii.
lU
time required to account for personnel not reporting to their assigned muster
stations;
na
iii. time required to evaluate the situation and make decisions;
er
iv. time required to initiate responses to minimize the consequences and control the
emergency, if possible;
nt
v. time required to complete the evacuation (if required). This may be done in a phased
-I
The TR main function is to provide a location where the total POB can be mustered without
O
unnecessary risk. The location should have proper access to the communications, monitoring
TR
and control equipment required to ensure their personal safety and safe evacuation can be
conducted. The functions are to secure means of escape to the TR and to provide a complete
evacuation from the TR.
PE
3.0 TR CONFIGURATION
The TR configuration concepts depend on installation and potential incident hazard scenarios.
The TR system may need to be distributed across several locations, as a result of HEMP
analysis. The primary TR shall be identified as one location to provide all main command
support functions, while the other locations shall form secondary TRs.
The following principles should be integrated in the design of a TR for a large installation:
i. Single location providing protection from process events, helicopter accidents
and falling structures such as derricks and flare towers
y
ii. Minimal door openings to provide access for large numbers of personnel through
nl
air locks
O
iii. Secure communication, command and control facilities of which assessment of
the event is possible without exposing personnel or opening doors
se
iv. Adequate space for mustering, donning appropriate PPE and making way quickly
to the means of evacuation and treating casualties
v. Protected evacuation routes and systems
lU
na
3.1 PRIMARY TR CONCEPTS
er
quarters as TR
functions, all or part of the living quarters may provide the TR.
-I
planning phase.
TR
3.2.1 A secondary TR may be established, if it is demonstrated by HEMP that escape to the primary
TR may not be possible from a particular area. This is also referred to as a Protected Muster
Point (PMP). It should be subordinate to the main TR, with a reduced requirement for the
provision of communications, monitoring and control facilities. It shall have a secure means
of communication with the main TR and it should be possible to assess the ability to traverse
the evacuation route from the secondary TR. Secondary TRs shall have independent means of
evacuation and/or escape as determined by an EER assessment.
3.2.2 In order to avoid having to establish a secondary TR on an installation, all practical measures
e.g. steps to mitigate the effects of incidents and/or the provision of alternative escape and
evacuation routes should be taken. This would place an additional burden on TR facilities and
installation management.
PTS 11.20.01
OFFSHORE TEMPORARY REFUGES August 2014
Page 12 of 33
3.3 CAPACITY
Primary TR All personnel should go to the primary TR through the available access
Capacity routes. The primary TR shall have capacity for the maximum permitted POB.
The secondary TRs should not be assigned prior to any incident. For joint
operations, personnel accommodated on the mobile unit should muster at
the TR of the mobile unit.
Secondary All potentially isolated individuals from the primary TR shall be
TR Capacity accommodated by the secondary TR. This shall be derived by the EER
assessment. With consideration of the margin of error in the anticipated
numbers, the contingency shall be individually determined for each case.
y
nl
3.4 MUSTER SPACE
O
3.4.1 As a guideline, an area of 1.25m2 should be provided if personnel are mustered in groups of
more than 20. This is based upon 50 percent seated and 50 percent standing, without baggage
se
and allowing for cross-flows.
lU
3.4.2 An area of 0.8 m² per person should be provided if personnel are mustered in groups of 20 or
less, such as in multiple muster stations. This is based upon 25 percent seated and 75 percent
na
standing, without significant cross-flows.
3.4.3 Heat stress, oxygen depletion and carbon dioxide build-up also affect the space requirement
er
for enclosed TRs. The minimum volume of an enclosed TR is 1.4 cubic metres of air per person
per hour of TR endurance.
nt
3.4.4 Additionally, consideration should also be given to providing adequate space for stretcher
-I
cases by checking the resultant volume to confirm that there are no unintended consequences
resulting from thermal stress under external thermal loads.
AS
3.5.1 There shall be an emergency control point (ECP) located in the primary TR, if the main
installation control point is not part of the primary TR. All the essential command support
O
3.5.2 Depending on whether they can be maintained from the main installation control point
following an incident, additional command support functions may be required in the ECP or
PE
the ERPt.
3.5.3 To facilitate effective management of incidents, the ECP and ERPt should be adjacent to each
other, or integrated with each other, and its command support functions should be secured
against unauthorised use.
3.5.4 To identify the major incidents by which the main installation control point may be threatened
and for which retreat to the TR may be necessary, the HEMP tools shall be used.
3.5.5 Consideration should be given to having a separate, but adjacent or nearby, space designated
as the emergency control point, if the main installation control point is part of the primary TR,
to provide the emergency response management team with a more suitable environment for
assimilating information and making complex decisions under stress than may be achievable
in the main control point.
PTS 11.20.01
OFFSHORE TEMPORARY REFUGES August 2014
Page 13 of 33
4.0 SYSTEMS
In order to meet primary objective of the TR, the main components of the system required
are life support, structural support, command support and escape and evacuation.
The acceptance criteria for the various systems are given in Section 5.
Function as a tool to maintain a non-hazardous environment for the personnel to ensure their
ability to take rational action.
y
nl
The life support system’s scope and extent will vary, from minimal or no specific provision
(with no environmental concern) to a purpose-designed enclosure incorporating specialist
O
environmental control facilities.
se
4.1.1 TR Leakage
It is essential to maintain the integrity of enclosed TRs by preventing smoke or gas ingress.
lU
Enclosed TR integrity is dependent on leak tightness if the HVAC system should shut down for
any reason.
na
The leakage rate for new TRs should be as low as reasonably practicable.
er
As for new designs, it should be possible to achieve a leakage rate of 0.1 air changes per hour
or lower whereby aximum acceptable air change rate should be stated as part of the TR
nt
performance standard.
-I
TR leakage rate can lead to a risk of rapid TR impairment if the seals around doors or
penetrations deteriorate or are damaged. In order to maintain the functionality of TR, regular
AS
testing and inspection should be conducted during its operating life to measure leakage rate.
If the tests show significant increase in the leakage rate above the design rate, the leak paths
shall be investigated in order to identify and repair the source of leakage.
N
O
4.2.1 Components of the topsides and substructure essential for maintaining the structural integrity
of the TR and other means of escape and evacuation.
i. TR structure, inclusive of bulkheads and decks;
PE
y
c) requests for, and communications with, outside assistance are
nl
possible.
O
Additional Loss or impairment would not necessarily compromise the integrity of the
command TR, escape or evacuation routes, or points of embarkation but are
se
support beneficial to the effective management of all incident scenarios.
functions
Secondary
TR's essential lU
a) Means of communication with the primary TR, for the relaying of
information regarding the whereabouts and numbers of personnel
na
command unable to reach the primary TR and to receive information regarding
support evacuation. This is intended to assist in accounting for personnel; and
er
functions
b) Means of monitoring conditions on the designated evacuation route,
nt
Based on HEMP and/or legal requirements, the following means of evacuation and escape to
O
If the EER analysis indicates personnel may be prevented from reaching the TR,
additional evacuation provision shall be made with consideration of
a) severe weather conditions in which the positions of certain craft may be
particularly vulnerable and further redundancy may be required;
b) reliability and availability of survival craft;
c) the evacuation of non-essential personnel first, and later evacuation of
remaining personnel if control measures fail; and
d) space for injured personnel (stretcher cases).
The required spare capacity shall be based on the results of the EER analysis,
y
which as a minimum shall consider the above issues.
nl
ii. Secondary means of evacuation:
O
Allows full control evacuation of the installation, exclusive of external assistance
se
and without personnel directly entering the sea. Usually, the optimum means of
secondary evacuation is survival craft such as TEMPSC in accordance with IMO
lU
and other acceptable standards.
na
iii. Tertiary means (for escape to sea):
Back-up systems chosen on the basis that they will ensure, so far as is reasonably
er
practicable, escape from the installation without the need to enter the water
nt
The general principles in the provision of tertiary methods (for escape to the sea)
are:
O
b) Weather conditions;
PE
The selection of tertiary method and its types, numbers and locations is based on
the likely demands derived from incident scenarios and the maximum personnel
distribution should be considere
PTS 11.20.01
OFFSHORE TEMPORARY REFUGES August 2014
Page 16 of 33
The dimension should be adequate for the number of people who may be required to use
them, taking account of the maximum level of occupancy, required transfer times and casualty
treatment handling.
In general, escape routes should be greater than 1m wide and have adequate vertical
clearance. For routes which are unlikely to be used frequently (and then only by a small
y
number of people), a reduction in width may be acceptable. External escape routes, escape
nl
routes used by personnel escaping from more than one area and evacuation routes should be
O
a minimum of 1.2m wide and have 2.2m vertical clearance.
4.4.2.1 Escape routes to the TR
se
To enable personnel to reach the TR following an incident on the installation a minimum of
lU
two routes, independent to the extent of being unlikely to be impaired by the same incident
scenario, shall be provided between each area of the installation and the TR.
na
Should the two alternative escape routes appears to be impractical, an area may have a single
exit leading from it with consideration for provision of escape equipment including respiratory
er
protective equipment in these areas and special access procedures should apply to such areas.
nt
Single exits may be acceptable from small access platforms, rooms and cabins with low
vulnerability.
-I
For bridge-linked installations,bridge connections should be accessible and passable under all
major incident scenarios, and/or the risk of loss of bridge integrity is acceptable, a single bridge
AS
may link platforms. Two routes should lead to such a bridge and, dependent on the likely
hazards, also lead from it.
N
Evacuation routes, to enable personnel to proceed from the TR to the points of embarkation
TR
for the purpose of platform abandonment, shall be provided by primary means and, if
applicable, secondary means.
PE
The evacuation routes should be sized for the maximum permitted POB with the condition of
a minimum of two evacuation routes, independent to the extent of being unlikely to be
impaired by the same incident scenario, shall be provided from the TR to each designated
point of embarkation.
require it. If an enclosed route is provided, the EER analysis should indicate the
standards of performance and endurance time the system will achieve.
y
nl
O
se
lU
na
er
nt
-I
AS
N
O
TR
PE
PTS 11.20.01
OFFSHORE TEMPORARY REFUGES August 2014
Page 18 of 33
Local regulations, mandatory guidance and industry standards acceptance criteria should be
used. The acceptance criteria that shall (PSR) be met by each of the four systems during the
y
endurance period are:
nl
5.1.1 Life support
O
Life support endurance is to be evaluated by analysing major incident scenarios.
se
The life support acceptance criteria relate to potentially hazardous conditions as per PTS
lU
16.50.01. Any such redefinition of acceptance criteria shall be clearly substantiated.
The calculation of TR impairment times will depend on the assumptions made for the integrity
na
and leakage of the TR following an incident. For TR design the anticipated wind-driven leakage
should be calculated using a model such as AIDA.
er
i. Generation of smoke
nt
The acceptance criteria for the endurance period of the TR is as per UK HSE -
-I
The acceptance criteria for those gases or vapours that may be released and are
flammable at concentrations below the level at which they become an asphyxiant
PE
Limits have been set in the IMO FTP (Fire Test Procedure) code for hazardous
vapour generation from firewalls exposed to radiant heat.
However, the physiological response to some of these hazards suggests that lower
levels in areas where personnel may be mustered should be used.
iv. Oxygen deficiency and carbon dioxide accumulation
For an enclosed TR, if the air is entrapped for longer time, muscular coordination
disturbance occurs at an oxygen level below 17%. The acceptance criterion is
therefore a minimum internal oxygen level of 17% for 60 minutes.
At a carbon dioxide level of 20,000 ppm (2%), respiration increases. This is not
y
harmful by itself, but will increase the effects of other toxins that may be present.
nl
The acceptance criterion for carbon dioxide accumulation is therefore a maximum
O
carbon dioxide level of 20,000 ppm (2%).
v. Mixed exposure
se
Personnel will be subjected to a mixture of hazards and the combined effect of
carbon monoxide, carbon dioxide and oxygen depletion.
lU
Mixed exposures of toxic gases and fumes may be additive and require careful
na
assessment for their health effects, as the majority of STELs are for single
compounds or for substances containing a common entity. Medical advice should
therefore be sought for mixed exposure.
er
As a screening criterion the maximum air temperature inside the TR should not
-I
exceed 70°C for 60 minutes. Norsok Z-013 provides an equation that may be used
to develop alternative times/temperatures. However at these elevated
AS
In certain circumstances (e.g. in open spaces and high H2S environments), the use
of RPE may be considered as a protection measure for personnel at the TR, and
PE
TR structural support should remain stable, usable and accessible condition during the
endurance period, hence, maintenance of the integrity of the supporting structure is required.
Mobile unit or floating vessel shall be able to remain on station and accessible during the
endurance period or for a sufficient time to enable all personnel to escape from the fixed
installation and muster in the TR.
PTS 11.20.01
OFFSHORE TEMPORARY REFUGES August 2014
Page 20 of 33
The acceptance criterion for command support is the availability and ability of the support
functions as described in the following table:
y
Request outside assistance; Communication with pipeline-
nl
Two-way voice communications with a connected installations;
Communication with gangway-
O
secondary TR, for the endurance period of
the secondary TR; connected installations;
se
Monitor fire, smoke and those toxic and Monitor fire in the major process areas,
flammable gases which may occur, and to e.g. Wellheads, gas compression, etc.;
monitor their propagation:
- in the TR; lU
Determine the physical condition of the
helideck and to detect fire, smoke and
na
- on evacuation routes; gas in its immediate vicinity;
- at embarkation areas; and Monitor and close TR boundary HVAC
er
- in modules and areas adjacent to the tr, fire dampers, where fitted;
Initiate process / emergency shutdown;
nt
- embarkation areas;
Monitor the running of the fire water
O
The conditions of integrity for escape and evacuation shall be maintained for their respective
endurance periods:
i. on at least one escape route to the TR(s);
ii. on at least one evacuation route from the TR(s) to the point of embarkation of the
primary and, as applicable, the secondary means of evacuation; and
iii. at sufficient embarkation areas, providing accessible survival craft (when
provided) with an aggregate capacity equal to or greater than the maximum
permitted POB.
y
nl
5.1.4.1 Fire
O
Escape and evacuation routes and points of embarkation shall be arranged so that
se
i. Personnel will not be affected by flame.
ii. Designed to remain passable by their position rather than by special protection.
iii.
lU
The structural integrity of escape and evacuation routes and points of
embarkation should not be considered in isolation which due regard should be
na
given to the structural elements that support them.
er
Fire protection should be considered to maintain the structural integrity of open walkways
and open decks which form escape and evacuation routes. Although these routes may not be
nt
passable whilst exposed to flames or radiation levels, fire protection may maintain their
-I
structural integrity for use after flames or radiation levels have subsided.
5.1.4.2 Thermal radiation (human exposure)
AS
There should be a recognised fire model to predict the level of thermal radiation in the fire
events. Acceptance criteria depend heavily on
N
i. time to exposure,
O
ii. clothing,
TR
For personnel with working PPE the following values are considered appropriate to the various
stages of the EER process.
i. Immediate fatality (unable to escape fire) : 35 kW/m2
ii. Escape route transit (1 minute) :6
iii. Emergency action e.g. closing valve, for 2 minutes :5
iv. Impairment of TEMPSC embarkation area :4
Where thermal radiation (and gas) can reasonably be predicted during an evacuation, the
default assumption should be that deluge protection on the TEMPSC and air purge to SOLAS
standards will enable evacuation from the area of immediate threat.
PTS 11.20.01
OFFSHORE TEMPORARY REFUGES August 2014
Page 22 of 33
y
nl
The routes for escape and evacuation should remain passable, and free of obstructive debris,
in the event of potential explosions. These routes and survival craft embarkation areas shall
O
be considered acceptable if this can be demonstrated on evaluation of such effects. It shall
also be demonstrated that any explosion shall not in any way adversely affect the operation
se
of the primary and, as applicable, secondary means to evacuate the POB.
lU
The acceptance criterion for personnel in explosions is subjected by the likelihood of injury
caused by missiles and impact with structure, rather than the static overpressure. A simple
screening criterion distilled from various guidance for personnel in blast waves is 3 bar.
na
5.1.4.4 Air quality
er
The life support conditions also apply to escape and evacuation routes and points of
embarkation.
nt
-I
The endurance period of the TR is the duration which relevant conditions of integrity shall be
AS
maintained. It shall (PSR) be based on the following two criteria, whichever is the shorter:
i. Duration of maximum major incident; or
N
From the time of "call to muster" (allowing for delays in calling), the endurance period shall
begin. The effect on the TR of an incident will not necessarily be present at the beginning of
the endurance period.
PE
TR shall (PSR) is designed to maintain its integrity until the immediate threat has been relieved
or has subsided. The integrity of the TR is no longer threatened when life support and
conditions external to the TR which are not harmful to personnel have been re-established.
The adoption of this method for calculating TR endurance does not eliminate the requirement
to provide a means of evacuation from the installation.
PTS 11.20.01
OFFSHORE TEMPORARY REFUGES August 2014
Page 23 of 33
The TR shall be designed to maintain its integrity for the time required to complete the
evacuation process. This includes the following elements:
y
nl
D1 - Response time Time required to inform all personnel on the installation that a
to an alarm major incident has occurred and the response that is necessary.
O
Personnel shall then act in accordance with the relevant
emergency procedures.
se
D2 - Travel time to Time required for all personnel to travel from their place of work
lU
the TR or rest to the TR. This time includes an allowance for personnel to
respond to instructions.
na
D3 - Time to muster Time required for all personnel on the installation to be accounted
and reach decision for. During this time the OIM shall be capable of assessing the
er
D4 - Evacuation The time required for evacuation of personnel from the installation
time by the most expeditious manner. This will include the donning of
-I
Response, escape, mustering and evacuation times may be affected by the result of different
incident scenarios and a factored time is required. The time estimates shall be developed in
consultation with competent Operations staff, and take account of specific practices and
N
procedures. On existing installations, the elements of the access and evacuation process shall
O
A minimum of ten minutes should be added to the total required time as a contingency to
reflect the level of qualitative assessment in above process. Experience from realistic drills on
PE
comparable existing installations shall be taken into account for new installations.
Calculation of evacuation times to be used for the determination of minimum and factored
endurance times is shown in the table given in the following page.
y
Account for personnel
D3 Muster A
nl
onboard
Assessment and Availability of, and
O
Evaluation B collation of information
se
Communications C Internal and external
Automatic systems - ESD,
lU
Executive action D
BOP
Quantity and quality of
Decision making E
na
information
Personnel don survival
er
equipment
D4 Evacuation Travel to point of
nt
evacuate
TOTAL
AS
Escape routes have different endurance period due to TR shall be required to maintain the
conditions of integrity (5.1) only for the time that they may be used as well as those evacuation
O
The endurance period required for escape routes to the TR shall enable to complete a full
muster in the TR from all installation locations. As a contingency plan, it should also consider
PE
i. the incident may occur at night or during a time when personnel are involved in
complex operations or activities;
ii. more than one route may have to be tried;
iii. the movement of personnel may be hampered by injury or the consequences of
the incident (e.g. smoke);
iv. the need to undertake a single search and rescue operation on the installation.
5.2.5 Evacuation routes from the TR
HSE Case shall be developed and maintained for all offshore installations and maintained
Major Accident Hazards and the barriers are required to prevent or manage these hazards
shall be identified and assessed. Barriers consist of one or more Safety Critical Elements
(SCEs).
Performance Standard shall be documented for each SCEs which describes the minimum
y
functional specification. It shall also be used as a basis for verification throughout the lifecycle
nl
of the facility.
O
6.1.1 Escape, evacuation and rescue (EER) assessment
se
Refer to ISO 15544.
lU
Any shortcomings are identified from the Assessment, modifications shall be proposed and
implemented in accordance with the ALARP principle.
na
6.2 HUMAN FACTORS
6.2.1 Behaviour under stress
er
nt
The design of the TR and its associated means of escape and evacuation shall limit physical
and psychological demands on personnel, whilst allowing for the inevitability of residual high
-I
levels of stress and based on what is normal and familiar in the daily routine.
6.2.2 Complex decision-making
AS
ii. Optimising the provision of information to assist in those decisions that are not
TR
automated.
PE
PTS 11.20.01
OFFSHORE TEMPORARY REFUGES August 2014
Page 26 of 33
7.0 FACILITIES
For enclosed TR systems where all or part of the living quarters is designated as the TR, general
materials and systems is according to PTS 11.22.04.
y
simple means of attachment to waist belt;
nl
ii. one pair of heat resistant gloves;
O
iii. one life jacket;
se
where applicable,
i.
ii. lU
respiratory protection sufficient to enable safe evacuation;
one immersion type survival suits similar to helicopter flying suit.
na
iii. in addition to communal stores of equipment held at key locations on the
installation (e.g. at survival craft stations).
er
nt
The correct arrangement involves the storage and donning of equipment in the protected
environment of a muster point in close proximity to evacuation systems and personal survival
-I
packs shall be located in accordance with the installation mustering philosophy and
procedures.
AS
Additional personal survival packs should be located at secondary TR locations, areas such as
control rooms or other normally manned locations remote from the TR, and personal descent
N
The provision, number and location of general survival and emergency response, medical and
welfare equipment should be separately determined taking account of TR configuration and
PE
endurance, likely hazards and the equipment provided to fulfil dual operational functions.
The following key equipment should be made available to personnel at the TR and any
secondary TR.
Survival equipment Medical equipment
1) Safety lamps and self-contained 1) First-aid medical kits (refer to
charging units; HSE Report 94023) plus additional
2) Portable gas detectors; capable of dressings and burns packs;
detecting, testing and measuring 2) Stretcher(s);
quantitative concentrations in air of 3) Portable automatic oxygen resuscitator(s);
hydrocarbons, carbon monoxide,
4) Packs of eye wash; and
hydrogen sulphide, and oxygen.
5) Bottles of drinking water.
PTS 11.20.01
OFFSHORE TEMPORARY REFUGES August 2014
Page 27 of 33
7.3 SIGNS
7.3.1 Signs
i. Should be provided as necessary to allow personnel to identify escape routes,
including indication of the direction to muster areas, embarkation areas and
means of escape to the sea.
ii. Shall be different from those leading from the TR to embarkation areas to direct
personnel to the TR. The differences shall be readily and instantly distinguishable.
iii. Signs inside the living quarters shall be provided in accordance with PTS 11.22.04.
7.3.2 Safety information
y
i. Diagrams showing the basic room/module layouts, evacuation routes, emergency
nl
escape equipment and locations/details of fire control arrangements shall be
O
located in strategic areas around the installation.
ii. They shall be clearly visible and, if necessary, illuminated.
se
7.4 ENTRANCES AND EXITS
lU
The protection, location and type of enclosed TR entrances and exits are critical factors in the
na
fulfilment of certain TR objectives and can enhance safety by:
7.4.1 Flow and movement of personnel
er
The location of entrances and exits should allows single directional flow of personnel during
nt
an incident, if possible avoiding crossflow and counterflow. This is also applicable for:
-I
who may use them at any one time where minimum of two entrances and two exits which are
O
7.4.2 Protection
i. The number of entrances and exits should be restricted to only those needed to
PE
comply with the foregoing requirements concerning the flow and movement of
personnel.
ii. Where a TR has another operational function (e.g. accommodation) there will
probably be a number of additional external doors for operational reasons or for
escape from internal fire or other similar incidents however limited to the number of
external doors to the minimum practicable.
iii. Entrances and exits to the TR shall be protected against the ingress of smoke and gas
and against blast and radiant heat. Positioning of the entrances and exits in locations
naturally protected shall provide primary protection
iv. Entrances and exits should be located where they are least likely to be affected by
blast and impingement of smoke, gas, heat and flame. Only where it is unavoidable
should shielding be used to protect entrances and exits from blast and radiant heat.
PTS 11.20.01
OFFSHORE TEMPORARY REFUGES August 2014
Page 28 of 33
7.4.3 Doors
i. All TR external doors should resist smoke and gas penetration based on the
performance requirements.
ii. All TR doors and doorframes shall be capable of maintaining the fire and dynamic
overpressure integrity of the bulkhead in which they are placed.
iii. TR doors which serve escape and evacuation routes shall be designed to be usable
for the endurance period. The design shall account for the effect of potential
explosions and fire on the operation of the door.
iv. All doors should be clearly marked to indicate the circumstances under which they
y
are to be used.
nl
v. All TR external doors exposed to potential explosion overpressures should be
O
categorised according to the table below and designed to ensure the specified
function following an explosion.
se
Category Door Condition Door Function
lU
after Blast
I Operable The door shall remain operable after the blast event
na
and maintain its specified integrity against smoke and
gas ingress and fire loading.
er
The design shall account for the effect of potential explosions and fire on the operation of the
O
door. The doors should be clearly marked to indicate the circumstances under which they are
TR
Where there is a likelihood of smoke and gas ingress, there should be at least one, but
PE
preferably a number of, airlocks or intervening spaces between the external environment and
TR muster and control points.
The design of entrances, exits and airlocks shall take account of the requirements of stretcher
access. In particular, airlocks should be sized to ensure that only one door needs to be open
at any one time.
PTS 11.20.01
OFFSHORE TEMPORARY REFUGES August 2014
Page 29 of 33
i. Minimal usage
ii. Shutterless type, certified to the fire and blast ratings of the bulkheads in which
they are placed and capable of maintaining the fire, acoustic, dynamic
overpressure and thermal insulation integrity of the bulkhead.
iii. The external face should form a weather, smoke and gas tight barrier whereby
the internal face should form a sealed barrier to maintain internal air pressure,
y
but be removable for cleaning and maintenance.
nl
O
7.6 EMERGENCY POWER AND LIGHTING
7.6.1 General
se
This section applies primarily to manned installations. The provision of emergency power and
7.6.2
lighting should be in accordance with PTS 13.00.01.
Emergency power requirement lU
na
Emergency power is required to supply the following personnel during an incident:
er
i. communications;
nt
In each instant, the duration of emergency power shall be determine where the minimum
duration shall be greater than the required TR endurance.
N
The duration of the emergency power system is inclusive of sufficient contingency to ensure
O
To indicate the design duration of all emergency power sources required for the TR functions,
a notice should be provided at the TR
PE
Emergency lighting systems shall be provided in the following areas, for the
endurance period:
a) at the TR;
b) on escape routes to the TR;
c) on evacuation routes from the TR;
d) at survival craft embarkation areas;
e) at personal descent systems if provided;
PTS 11.20.01
OFFSHORE TEMPORARY REFUGES August 2014
Page 30 of 33
y
nl
iii. Lighting of escape routes to the TR
O
All escape routes on the installation should be provided with emergency lighting
of the battery backed fluorescent type. If smoke may obstruct vision when the
se
escape route is to be used, some form of illuminated low level route indication
should be provided.
iv.
lU
Lighting of evacuation routes from the TR
na
Lighting of the evacuation routes from the TR shall be available when the platform
is evacuated. If smoke may obstruct vision when the evacuation route is to be
er
used, some form of illuminated low level route indication should be provided.
High intensity LED based lighting is particularly effective in highlighting handrails
nt
The power supply to the evacuation route lighting should be provided from within
the TR so that it can be manually switched on when it is actually required.
AS
Luminaires should be of the internal battery backed type as this will allow light to
N
Cabling for the evacuation route lighting circuits should be well protected and
TR
able to resist fire damage to the same standard required for the protection of the
evacuation route.
PE
7.8 HVAC
The HVAC system, if provided, is according to ISO 15138.
During the operation of the HVAC system, it should be able to maintain life support conditions
and provide protection through the:
i. maintenance of a supply of breathable air;
ii. prevention of heat build-up;
iii. prevention of smoke and gas ingress through positive pressurisation of the TR;
y
iv. provision of sufficient airflow dilution and displacement of any leakage or other
nl
ingress (e.g. through the use of doors); and
O
v. maintenance of visibility (in smoke).
se
The design should maximise the duration of HVAC operation during an incident. A detailed
assessment should be made to establish the suitable number and location of air inlets.
lU
In the event of smoke or gas detection at the air inlets, HVAC system shall shut down
na
automatically and the TR shall be isolated.
Evaluation of the size of intake, air flow patterns, voting philosophy, should be conducted
er
when deciding on the number of detectors. Also, it shall consider the speed of response of
inlet-gas detection and the time needed to stop the HVAC.
nt
In the event of a fire on the platform and the TR is close to the process area, it should be
-I
considered whether the integrity of the TR is better preserved by automatically closing the
HVAC dampers to the TR .
AS
It is required for the system to be design thus that it can be shut down and restart the HVAC
system from the TR.
N
lost, for example due to smoke or gas being present at the air intakes;
ii. prevention / minimization of smoke spread within the TR;
PE
8.0 BIBLIOGRAPHY
In this PTS, reference is made to the following other Standards/Publication. Unless specifically
designated by date, the latest edition of each publication shall be used, together with any
supplements/revisions thereto:
y
nl
Fire, gas and smoke detection systems PTS 14.12.07
O
Telecommunications for offshore platforms PTS 14.40.03
se
Electrical engineering design PTS 13.00.01
13702:1999)
-I
15544:2000)
N
Medical Emergency Guidelines for Health Case Professionals and HSE Report 94023
TR
BRITISH STANDARDS
PE
HSE Guidance Note: Workplace exposure limits: Containing the list HSE EH40
of workplace exposure limits for use with the control of substances
hazardous to health regulations
Issued by:
Health and Safety Executive
Ferguson House, 15 Marylebone Road
London, NW1 5JD,
UK
PTS 11.20.01
OFFSHORE TEMPORARY REFUGES August 2014
Page 33 of 33
INTERNATIONAL STANDARDS
Petroleum and natural gas industries — Control and mitigation of ISO 13702
fires and explosions on offshore production installations —
Requirements and guidelines
y
installations — Heating, ventilation and air-conditioning
nl
O
se
lU
na
er
nt
-I
AS
N
O
TR
PE