Professional Documents
Culture Documents
6965 Vortex 500 DIOM Rev B
6965 Vortex 500 DIOM Rev B
6965 Vortex 500 DIOM Rev B
500
Victaulic Vortex™ 500 Hybrid Fire Extinguishing System
For Protection of Information Technology Equipment and Motor Control Center Areas
WARNING
Failure to follow instructions and warnings can cause system failure, resulting in death or serious personal injury and property damage.
• Read and understand all instructions before attempting to install, remove, adjust, or maintain any Victaulic products.
• Wear safety glasses, hardhat, and foot protection.
• Save this design, installation, and maintenance manual for future reference.
If you need additional copies of any literature, or if you have any questions concerning the safe installation and operation of this product,
contact Victaulic.
REV_B I-VORTEX.500_1
TABLE OF CONTENTS
Section I – System Overview Section IV – Electrical
Hazard Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Electrical Wiring Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Definitions for "Should" and "Shall" References Used Power Supply/Charger Information . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Throughout This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 System Supervisory Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Safety Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Single-Zone System Diagram with Electrical Inputs
System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 (Active Release) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
System Operating Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Basic System Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 System Operation - Fluid Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
System Discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Section V – Installation
Nitrogen Supply Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Installation of the Victaulic Vortex™ 500 System Rack Model . . . . . . . 34
Nitrogen Gas Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Installation of the Victaulic Vortex™ 500 System Cabinet Model . . . . . . 39
Water Supply Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Section VI – Wiring
Agent-Releasing Fire Alarm Control Panel (FACP) . . . . . . . . . . . . . . . . . 5
Pressure Transducer Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Active Release Panel – Terminal Block Detail . . . . . . . . . . . . . . . . . . . 42
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Primary Solenoid Release Assembly Electrical Connections
Auxiliary Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 (With Manual Valve) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Auxiliary Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Section VII – System Acceptance
Tools and Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
System Acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Safety Signage/Placards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
System Discharge Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Overview of the Victaulic Vortex™ 500 System Rack Model . . . . . . . . . . 6
Overview of the Victaulic Vortex™ 500 System Cabinet Model . . . . . . . . 7 Section VIII – Operation and Maintenance
Manual Discharge Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Section II – Components
Returning the System to Service After Discharge . . . . . . . . . . . . . . . . . 49
™
Victaulic Vortex 500 System Active Release Manifold . . . . . . . . . . . . . 9
Maintenance and Inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Victaulic Vortex™ 500 System Rack Model Dimensions . . . . . . . . . . . . 10
Water Tank Filling Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Victaulic Vortex™ 500 System Cabinet Model Dimensions . . . . . . . . . . 11
Cylinders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Section IX – Troubleshooting
Primary Pilot Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Troubleshooting – Fluid Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Secondary Pilot Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Troubleshooting – General Equipment. . . . . . . . . . . . . . . . . . . . . . . . 53
Manifold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Manifold Isolation Valve Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Refill Adapter Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Victaulic Vortex™ 500 System Fluid Panel
(Multi-Zone) Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Water Flow Control Cartridge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Hybrid Emitter Water Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Hybrid Emitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Water Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Section III – Design
System Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Configurator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Calculate the Nitrogen Requirement . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Calculate the Number of Cylinders Required . . . . . . . . . . . . . . . . . . . . 22
Calculate the Number of Hybrid Emitters Required . . . . . . . . . . . . . . . 22
Calculate the Expected Oxygen Level . . . . . . . . . . . . . . . . . . . . . . . . . 22
Calculate the Water Quantity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
System Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Temperature Effects on Nitrogen Pressure - 49-liter Cylinder
with 2400-psi/165.5-Bar Nominal Fill . . . . . . . . . . . . . . . . . . . . . . . 24
Temperature Effects on Nitrogen Pressure - 80-liter Cylinder
with 2640-psi/182.0-Bar Nominal Fill . . . . . . . . . . . . . . . . . . . . . . . 24
Enclosure Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
System Refill . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
REV_B I-VORTEX.500_1
SECTION I
SYSTEM OVERVIEW
HAZARD IDENTIFICATION
Definitions for identifying the various hazard levels are p
rovided below. When you see this symbol, be alert to the possibility of
personal injury. Carefully read and fully understand the message that follows.
DANGER CAUTION
• T
he use of the word “DANGER” identifies an immediate • The use of the word “CAUTION” identifies possible hazards or
hazard with a likelihood of death or serious personal injury if unsafe practices that could result in personal injury and product
instructions are not followed. or property damage if instructions are not followed.
WARNING NOTICE
• T
he use of the word “WARNING” identifies the presence of
• The use of the word “NOTICE” identifies special instructions
hazards or unsafe practices that could result in death or serious
that are important but not related to hazards.
personal injury if instructions are not followed.
DEFINITIONS FOR "SHOULD" AND "SHALL" REFERENCES USED THROUGHOUT THIS MANUAL
References to "should" within this manual indicate areas of importance that are to be taken under consideration but are not a requirement.
References to "shall" within this manual indicate areas of critical importance that are a requirement.
I-VORTEX.500_2 REV_B
I-VORTEX.500 / Victaulic Vortex™ 500 System / General Design, Installation and Maintenance Manual
SAFETY REQUIREMENTS
WARNING
• Contractors shall be qualified, per local code requirements, and shall successfully complete all required
Victaulic training before attempting to install the Victaulic Vortex™ 500 System.
• The contractor shall install this product in accordance with all instructions. These instructions contain
important safety and operational information.
• Depressurize and drain the piping system before attempting to install, remove, adjust, or maintain any
Victaulic piping products.
• Compressed gas cylinders shall be handled only by personnel familiar with the hazards and proper handling
techniques. All nitrogen cylinder movement shall be done with appropriate material handling equipment.
Always secure nitrogen cylinders while in storage and during use.
• Use only Victaulic replacement parts when servicing the Victaulic Vortex™ 500 System.
• All installer-supplied piping shall be rated for the pressure and operating conditions to which it will be
subjected.
Failure to follow these instructions could result in death or serious personal injury.
SYSTEM OVERVIEW Fluid Panels contain an automatic regulating valve (ARV) that reduces
pressure from the nitrogen cylinders, using feedback from a pressure
NOTICE transducer located within the system piping.
The Victaulic Vortex™ 500 System Fluid Panel requires an installer-
• For proper system installation and operation of the Victaulic
supplied battery backup, 24VDC power supply. Victaulic Vortex™ 500
Vortex™ 500 System, qualified and trained individuals shall read
System is designed to operate from a installer-supplied agent releasing
and fully understand the contents of this manual and install the
FACP and utilize installer-supplied detection.
system in accordance with current NFPA and local codes and
standards. Several supervisory outputs are available from the Victaulic Vortex™ 500
System to monitor system readiness. The system is operated by sending
• Training and licensing of contractors is required in some
a 24V release signal from the customer-supplied, agent-releasing FACP.
jurisdictions.
The 24V release signal is connected to the Fluid Panel, where it is
• Performance criteria is based upon testing conducted and interlocked with the ARV and routes to the primary solenoid release
parameters derived by Victaulic. assembly.
• Components with equivalent function or purpose shall not be Hybrid emitters combine nitrogen at low pressure with a low volume of
used as a substitute for Victaulic Vortex™ System components. water to create hybrid media. Nominal operating pressure, supplied out
• THIS SYSTEM IS NOT TESTED OR APPROVED FOR EXPLOSIVE of the ARV to the hybrid emitters, is 25 – 50 psi/1.7 – 3.4 Bar, which is
ENVIRONMENT APPLICATIONS. programmed depending on the specific system design.
Cylinders supply high-pressure nitrogen and contain a primary solenoid
The Victaulic Vortex™ 500 Hybrid Fire Extinguishing System is a pre- release assembly and several secondary release assemblies that are
engineered, total flooding system that has been evaluated to protect used to charge the nitrogen supply manifold.
Class A and C applications and may be used as an alternative to clean
agent, CO2, and water mist systems for these applications. Victaulic SYSTEM DISCHARGE
Vortex™ 500 Systems have been deployed for the protection of hazards
within information technology equipment areas, motor control centers, WARNING
museums, control rooms, cable trays, cable spreading rooms, and
switch rooms. • Caution shall be taken to avoid by-products created from the
burning and extinguishment processes.
The Victaulic Vortex™ 500 System uses a combination of nitrogen and
atomized water to extinguish fire. Nitrogen is an inerting agent, which • Unprotected personnel shall not enter the space without
displaces oxygen and is used to atomize water into small (<10 micron self-contained breathing apparatus and personal protective
[0.00039 inch]) droplets. The high quantity of small water droplets has equipment, unless the space has been ventilated and the
a large available total surface area that provides rapid heat absorption fire department or their representative determines that the
and blocks radiant heat transfer. The combination of nitrogen and 10 atmosphere is safe for reentry.
micron water droplets distributes uniformly throughout the protected • Verify that there are no blockages between the Victaulic Vortex™
space and works together to create an atmosphere that does not Panel and hybrid emitters prior to any system testing.
support combustion. Failure to follow these instructions could result in death or serious
personal injury.
WARNING
• Changes to the hazard classification or to the hazard zone may The room may contain fire by-products created from the burning and
affect system performance. extinguishment processes. Typical by-products are carbon monoxide,
• All changes shall be reported to the authority having jurisdiction carbon dioxide, soot, and reduced oxygen content. In addition,
(AHJ) for review and approval. by-products of unburned fuel will be present. The Victaulic Vortex™ 500
System provides cooling properties; however, the potential for re-ignition
Failure to follow these instructions could cause improper system of fuel shall be evaluated.
operation, resulting in death or serious personal injury and Noise - Discharge of the Victaulic Vortex™ 500 System can cause noise
property damage. loud enough to be startling; however, the noise level is not high enough
to cause permanent or traumatic injury.
Turbulence - Discharge of the Victaulic Vortex™ 500 System can cause
SYSTEM OPERATING TEMPERATURE
enough general turbulence to move unsecured, light objects.
The Victaulic Vortex™ 500 System shall be maintained at an ambient Temperature - Discharge of the Victaulic Vortex™ 500 System can
temperature between 40° F / 4.4° C and 130° F / 54° C. The water supply cause reduction in temperature and visibility due to the condensation of
and water piping shall be protected from freezing temperatures. water vapor.
FLUID PANELS ARE NOT RATED FOR OUTDOOR USE.
Automatic door closings or other shutdown processes, if required, • In the event of system discharge, activation of the Victaulic
shall be controlled from the agent-releasing FACP in the event of an Vortex™ System will release nitrogen into the protected space.
activation. Refer to Section III for guidance on minimum and maximum • The protected space and any ventilation shall be designed to
required openings. prevent overpressurization.
The Victaulic Vortex™ 500 System includes Victaulic Vortex™ Hybrid Failure to follow these instructions could result in death or serious
Emitters, a Fluid Panel, nitrogen cylinders, and a water tank. personal injury.
I-VORTEX.500_8 REV_B
I-VORTEX.500 / Victaulic Vortex™ 500 System / General Design, Installation and Maintenance Manual
1 OR
2
OR
Secondary Gauge
Assembly
Tee Nipple
(¼-inch BSPP)
ER RID E -
Z00
095
004
0 OV
- MANUAL
P
U
LL
PIN
AND T
ev. A
0R
666
E
G
IS T AR
W
TO DISC H
Snubber
Assembly Pilot Hose
17.57 inches
2X 446.4 mm
A 12.73 inches
2X 323.3 mm
86.3 inches
2192.0 mm
78.82 inches/
2002 mm
16.72 inches/
425 mm
12.73 inches/
323 mm
82.94 inches/
2107 mm
55.99 inches/
1422 mm
62.99 inches/
1600 mm
87.49 inches/
2222 mm
94.49 inches/ 15.79 inches/
2400 mm 401 mm
Connection to
Nitrogen Cylinder
3.70 inches
3.40 inches 93 mm
86 mm
OVERR
ID UA L
AN
M
-
ARGE -
Z000
ev. A
95004
6660 R
ER RID E -
PULL P 0
Z00
095
004
0 OV
- MANUAL
P
CH
AN
IN
D
IS
D T W T TO
LL
IS
PIN
AND T
ev. A
0R
666
E
G
IS T AR
W
TO DISC H
The pilot hose is a ¼-inch ID reinforced rubber hose with a 90° elbow
and is used to connect the outlet of the releasing solenoid to the tee The discharge hose is used to transmit nitrogen gas from the cylinder
connection used on the cylinder valve. valves to the manifold.
To connect from front to rear cylinder rows, use the 27.5-inch/700-mm Restricting Valve (¾-inch NPT x ½-inch BSPT Connections)
pilot hose (ordered separately) to connect the cylinder valves.
To Manifold
NOTICE
• Verify that the threaded nut of the secondary gauge assembly is
tightened completely to the pilot connection port of the cylinder
valve during installation. Manifold Isolation Valve Kit
with 1½-inch/48.3-mm NPT Ball Valve
Secondary Pilot Hose
The secondary pilot hose is a ¼-inch The manifold isolation valve kit isolates the manifold assembly from the
ID reinforced rubber hose and is used Fluid Panel and includes a high-pressure ball valve with locking handle
to connect the tee connections on the kit and a universal ball valve switch. NOTE: Assembly of the universal
cylinder valves. The standard pilot hose ball valve switch shall be performed by the integrator.
is 11.8 inches/300 mm in length and is
provided to accommodate connection
REFILL ADAPTER ASSEMBLY
of cylinders. An optional pilot hose,
approximately 27.5 inches/700-mm long,
is used to interconnect rows (ordered
separately).
MANIFOLD
Wiring
Points
Nitrogen Nitrogen
Inlet Outlet
Automatic
Regulating
Valve (ARV)
J1 J2 J3 J4 J5 J6
J11 J10
J9
Auxiliary
Power
Connection
J8
LED 1
Alarm
LED 2
LED 3 Maintenance
Switch
LED 4
The printed circuit board (PCB) is located within Fluid Panels and provides user wiring connection points, LED diagnostics, and the logic to operate
components in the Fluid Panel. This PCB is designed for use with Victaulic-recommended 24-volt DC power supplies. A plastic cover protects
components against accidental contact during system installation.
Not all connectors are used in every installation. Refer to Section VI for specific wiring and connection details. Dedicated connectors for additional
end-of-line (EOL) resistors are provided to facilitate use with different agent-releasing FACPs. The PCB is protected by a 4A fuse. An unfused auxillary
power output connector is located in the upper-left-hand side of the PCB to allow daisy-chaining power from one panel to another.
In the normal system ready state, Fluid Panels should display three green LEDs (LED 2, LED 3, and LED 4). The top LED (LED 1) is red, which
indicates an alarm condition. The offset LED (LED 5) is yellow, which indicates a supervisory condition.
HYBRID EMITTERS
NOTICE
• Fluid supply pressure is dependent upon system piping
configurations.
• Typical systems require pressure settings 1 – 3 psi/
0.07 – 0.21 Bar higher than the hybrid emitter requirements
to accommodate for pressure drop between the pressure
The maintenance switch and yellow supervisory indicator light are transducer and hybrid emitter.
provided on each Fluid Panel. The maintenance switch is designed to • Verify that the proper size hybrid emitter and water flow control
prevent the ARV from operating during testing situations. Additionally, cartridge are specified in the system design.
the maintenance switch will reset or close the ARV when its end-of-
• Verify that the water flow control cartridge and strainer are
stroke is reached after a discharge.
installed in the proper orientation.
When the maintenance switch is in the ready position, the yellow
• Refer to Section III for typical applications.
supervisory indicator light will be off. When the maintenance switch is
in the maintenance position, the yellow supervisory indicator light will
be on. B
The yellow supervisory indicator light will operate whenever the ARV
is not in the normal, ready condition. Possible causes for the yellow
supervisory indicator light to be on are: pressure transducer or wiring
trouble, power loss, system discharge, or when the ARV is in motion. A
When either the maintenance switch or yellow supervisory indicator
light is on, a corresponding supervisory contact is closed so that proper
monitoring of system status can be performed. The normally-open
contact on the supervisory output is a dry-type contact and will be
open, unless any of the conditions described above are met. Victaulic Vortex™ Water Figure 2
Hybrid Emitter Orifice Nitrogen Water
WATER FLOW CONTROL CARTRIDGE Description Size Inlet Inlet "A" "B"
3/8-inch, Dome 0.063 inch 3/4 – 14 1/4 – 18 2.65 inches 1.81 inches
Foil 1.6 mm MNPT FNPT 67.3 mm 45.4 mm
5/8-inch, Dome 0.063 inch 3/4 – 14 1/4 – 18 2.86 inches 2.03 inches
Foil 1.6 mm MNPT FNPT 72.6 mm 51.6 mm
WATER TANK
The water tank, provided with the Victaulic Vortex® 500 System, is manufactured from Type 304 stainless steel and includes a pressure gauge,
restrictor, pressure relief valve, and a check valve. Water tanks are sized to contain the proper amount of water. Refer to the applicable Victaulic
submittal publication for water tank options.
WARNING
• An adequate supply of filtered or distilled water shall be available for proper system operation.
• DO NOT use unfiltered water to fill the water tank.
Failure to follow this instruction will void the Victaulic warranty and cause improper system operation, resulting in death or serious personal
injury and property damage.
I-VORTEX.500_20 REV_B
I-VORTEX.500 / Victaulic Vortex™ 500 System / General Design, Installation and Maintenance Manual
SYSTEM DESIGN
The Victaulic Vortex™ 500 System is pre-engineered for total flooding applications. The discharge quantities of hybrid media are based on a
volumetric calculation for the hazard and are set by the number and size of the nitrogen cylinders included in the system.
Generally, system design should start with a review of the type of application, which is based on the hazard. Consult with the AHJ to verify suitability
of the system according to the application. Refer to the following page for calculations.
WARNING
The Victaulic Vortex™ 500 System SHALL NOT be used in areas that contain the following materials, unless approved by the AHJ:
• Chemicals or mixtures of chemicals, such as cellulose nitrate and gun powder, that are capable of rapid oxidation in the absence of air
• Reactive metals, such as lithium, sodium, potassium, magnesium, titanium, zirconium, uranium, and plutonium
• Metal hydrides
• Chemicals, such as certain organic peroxides or hydrazine, that are capable of undergoing autothermal decomposition
Failure to follow these instructions could result in death or serious personal injury and property damage.
ACCEPTABLE APPLICATIONS
System Designs for Total Flooding Class A Surface Fire Applications – Limited to applications containing Class A materials where combustibility
is low, quantities of combustibles are low-to-moderate, and fires with low-to-moderate heat release rates are expected. These spaces are typically
able to be classified as Light Hazard or Ordinary Hazard 1. Examples include data centers, museums, cleanrooms, control rooms, cable trays, cable
spreading rooms, and switch gear rooms. Early detection systems should be considered for use in these applications. Hybrid flooding factors for
these designs were determined by evaluating extinguishment performance with wood, PMMA, polypropylene, and ABS materials. Generally, 5/8 -inch
hybrid emitters are preferred for Series 954 Total Flooding Class A Surfaces Fires. Smaller hybrid emitters are available for applications where a lower
discharge rate is required to meet the recommended discharge times in small enclosures.
Series 953 Emitter Design Specifications for Total Flooding Class A Surface Fire Applications
Total Flooding Applications with Energized Electrical Equipment – For applications where there is energized electrical equipment operating at
voltages lower than 480VAC, follow the recommendations for the de-energized fuels. Conditions for shutdown of energized equipment is at the
discretion of the AHJ and applicable codes and standards.
FM Approved Designs – If an FM Approved extinguishing system is required, the Victaulic Vortex™ 1000 or 2000 Systems should be specified. Refer
to the I-VORTEX.1000 or I-VORTEX.2000 System General Design, Installation, and Maintenance Manual for details regarding where these systems
may be specified.
CONFIGURATOR
Victaulic provides an online configuration tool for sizing and determing the model number for the Victaulic Vortex™ 500 System.
To
WN2_req = V x x ACF x Hhybrid x S.F.
T
Determine the total quantity of nitrogen required based on
Where:
the hazard volume, elevation above sea level, and the hybrid
WN2_req = Quantity of Nitrogen Gas (SCF)
correction factor. Impermeable, immovable objects do not need to
V = Volume of Hazard (ft³)
be included as part of the enclosure volume. NOTE: Where fuel
To = Standard Temperature (294.4K)
sources or hybrid emitter types are mixed, use the greatest hybrid
T = Enclosure Temperature in Kelvin
factor.
ACF = Atmospheric Correction Factor (From NFPA 2001 Table of Atmospheric
Correction Factors)
Hhybrid = Hybrid Factor (From Table on Page 21)
S.F. = Safety Factor
After choosing the hybrid emitter size, divide the minimum ncylinder x wcyl
tdischarge =
nitrogen flow required by the chosen hybrid emitter flow to find the
number of hybrid emitters required.
nhybrid emitters x Qhybrid emitter
One hybrid emitter is included with each 1- and 2-cylinder system, Where:
and two hybrid emitters are included with each 3- and 4-cylinder nhybrid emitters = Number of Hybrid Emitters Required
systems. QN2_min = Minimum Total Nitrogen Flow (SCFM)
qN2 = Hybrid Emitter Nitrogen Flow (SCFM)
02%actual = 20.95e
– (
ncylinder x wcyl
V x ACF
x
T
To (
Where:
02%actual = Oxygen Level for Cold Discharge
ncylinder = Number of Cylinders Required
Wcyl = Usable Nitrogen Capacity of Cylinder (SCF)
V = Volume of Hazard (ft3)
ACF = Atmospheric Correction Factor (From NFPA 2001 Table 5.5.3.3, Atmospheric Correction Factors)
T = Enclosure Temperature in Kelvin
NOTES: In the event of a fire, the oxygen level will be further reduced as a result of the combustion process.
The oxygen level will be lower at elevated enclosure temperatures. It may be necessary to verify oxygen levels at nominal and maximum
expected enclosure temperatures.
SYSTEM DIAGRAM
A single-zone system utilizes a Fluid Panel to regulate the flow of nitrogen and water to the hybrid emitters. In addition, a single-zone system requires
an integrator-supplied, approved releasing panel and detection that are installed in accordance with the manufacturers’ recommendations.
Victaulic Vortex™
Hybrid Emitters
Transducer
Pressure
Low-Pressure Piping
Water Piping
J2 Transducer Input
Discharge Active
J4 Supervisory -
J4 Supervisory-
System Fault
Victaulic Vortex™
Fluid Panel
ARV
24VDC
Pressure
Cartridge
Gauge
Strainer
J1
Flow
Solenoid Output
Release Input
Relief
Valve
Restrictor
Flow
J5
J6
Water
Pressure
Tank
Gauge
Nitrogen
High-Pressure Manifold
Discharge
Primary
Head
Nitrogen
Secondary
Discharge
Head
Nitrogen
Secondary
Discharge
Head
3000 psi
206.8 Bar
rfill
Ove
10%
2800 psi
193.1 Bar
sure
Pres
ina l Fill
2600 psi
179.3 Bar Nom
ss
re Lo
ressu
5% P
2400 psi
165.5 Bar
2200 psi
151.7 Bar
2000 psi
137.9 Bar
30˚F 40˚F 50˚F 60˚F 70˚F 80˚F 90˚F 100˚F 110˚F 120˚F 130˚F
-1˚C 4˚C 10˚C 16˚C 21˚C 27˚C 32˚C 38˚C 43˚C 49˚C 54˚C
3000 psi
206.8 Bar
ure
ress
al Fill P
N omin
2800 psi
193.1 Bar ss
re Lo
ressu
5% P
2600 psi
179.3 Bar
2400 psi
165.5 Bar
2200 psi
151.7 Bar
2000 psi
137.9 Bar
30˚F 40˚F 50˚F 60˚F 70˚F 80˚F 90˚F 100˚F 110˚F 120˚F 130˚F
-1˚C 4˚C 10˚C 16˚C 21˚C 27˚C 32˚C 38˚C 43˚C 49˚C 54˚C
PLACEMENT
The piping system is designed to minimize pressure differences
between hybrid emitters and to minimize pressure losses between the
Victaulic Vortex™ Panel and hybrid emitters.
• The Victaulic Vortex™ 500 System should be placed to allow even
distribution of hybrid media within the enclosure. Typically, the
system should be centered along a wall of the enclosure.
• Hybrid emitter piping may be rotated to avoid having the hybrid
SYSTEM REFILL
emitter impinge on objects. Victaulic recommends refilling any nitrogen cylinder that is more than
5% below the fill pressure for which the system is designed. Cylinder
• Centerline of hybrid emitter shall be at least 18 inches/457 mm
valves are tested to have a leakage rate of less than 0.15% per year.
below the ceiling
Part of the system design shall include plans for refilling the system
• Avoid direct impingement on electrical or other moisture-sensitive
in the event of system discharge or loss of nitrogen supply pressure
equipment where dripping after discharge could result in damage
due to normal maintenance and operations. In critical applications or
• Large, flat surfaces (such as equipment cabinets and furniture) remote locations, it may be desirable to have a nitrogen reserve that
directly in the path of hybrid emitter discharge may collect water. can be placed into service quickly. Identify and contact a compressed
A minimum clearance of 36 inches/914 mm is recommended. gas supplier that can provide nitrogen for system refill and to determine
The preferred method is to position hybrid emitters to use the full delivery times and any special equipment required.
width of the enclosure.
Cylinders may be removed from the rack and transported to a
• Avoid configurations where discharge of the hybrid emitter could compressed gas supplier to refill cylinders individually. A refill adapter
cause splashing of flammable materials. assembly, shown in Section II of this manual, is required. Refer to the
• Locate the tip of the hybrid emitter foil a minimum of 4 1/4 inches/ I-VORTEX.ADAPTER for detailed refilling instructions.
108 mm from the wall or ceiling onto which it is mounted.
• The Victaulic Vortex™ 500 System may be placed outside of a
protected space, and the hydrid emitters may be swiveled to
protrude backward through the wall and into the protected space
(refer to drawing in the following column).
I-VORTEX.500_26 REV_B
I-VORTEX.500 / Victaulic Vortex™ 500 System / General Design, Installation and Maintenance Manual
Discharge Active
Agent Release
(Optional)
Low Pressure
Fluid Panel Alarm
Supervisory Point
Fluid Panel Supervisory
J1
Releasing Fire 24VDC
Primary Solenoid Release Assembly
J5 ARV
Release Input
J4
J6 Supervisory -
Solenoid Output Discharge Active
J4
Supervisory-System
Fault/Water Valve
Location
Fluid Panel
Victaulic Vortex™
Head Head Head
Fluid Panel
Water Piping
Secondary Gauge Assembly on
SECTION IV - ELECTRICAL
Primary Solenoid Release Assembly on
Flow Flow
Restrictor Cartridge
Pressure
Gauge
Strainer
SINGLE-ZONE SYSTEM DIAGRAM WITH ELECTRICAL INPUTS (ACTIVE RELEASE)
I-VORTEX.500 / Victaulic Vortex™ 500 System / General Design, Installation and Maintenance Manual
Relief
Purpose
Water Valve
NOTE: Wiring for low nitrogen pressure supervisory switch, Hybrid Emitters
Indicates Low Pressure in
Indicates Low Pressure in
Primary Nitrogen Cylinder
I-VORTEX.500_29
I-VORTEX.500 / Victaulic Vortex™ 500 System / General Design, Installation and Maintenance Manual
ELECTRICAL CONNECTIONS
NOTICE
• J2 – J10 terminal block screws should be tightened to 3.1 – 3.5 in-lbs/0.35 – 0.40 N•m
• J1 and J11 terminal block screws should be tightened to 4.4 – 5.3 in-lbs/0.50 – 0.60 N•m
• J1 and J11 are rated for use with 10-20 AWG solid or stranded wire
• J2 – J8 are rated for use with 14-24 AWG wire
Power Input
The Victaulic Vortex™ Fluid Panel requires a constant non-resettable, 24-volt DC power source (Victaulic
24V Com EGND offers a 24-volt DC power source). Refer to the "Electrical Specifications" section on page 27 for the
current requirements. The power supply shall provide a means for reporting an AC failure, DC power loss,
and loss of battery connection in accordance with NFPA 72. Charging rates and battery capacities shall
be configured to meet NFPA 72 guidelines. Proper wire size calculations shall be performed to ensure
minimum voltage requirements are met. DO NOT make or break any connections with power applied to
the Fluid Panel. The power input is polarity sensitive; therefore, the Fluid Panel will not power up if the
J1 polarity is reversed.
J2
ARV+ ARV-
This terminal block is left unused on Victaulic Vortex™ 500 System Fluid Panels.
J3
Supervisory/Alarm Signals
Two ½-amp @ 30VDC normally-open dry contact outputs are provided to monitor system status. Terminal
Supervisory/Alarm block J10 is provided as a connection point for an EOL resistor on each of the two supervisory signals,
when the Victaulic Vortex™ 500 System is connected to agent-releasing FACPs that require a resistor. The
contacts will be open when the panel is in the normal, ready state. The contacts will be closed if the panel
is in an alarm or supervisory condition or if power is removed from the panel. The red alarm indicator light
(LED 1) is on when the alarm contacts are closed. The yellow supervisory indicator light (LED 5) is on
J4 when the supervisory connection is closed.
the needle valve is not fully seated or when the system is in maintenance.
When the maintenance switch is placed in the maintenance position, the
release input signal will be interrupted. The agent-releasing FACP should
be configured to supervise the release signal.
J6
J8
EOL Resistors When the agent-releasing FACP requires EOL resistors to supervise the
panel release input or supervisory contacts, terminal blocks J9 and J10
may be used as connection points for the EOL resistors.
Terminal block J9 is used for EOL resistors required on the panel release
input and is interlocked with the maintenance switch. Placing the
J9 J10 maintenance switch in the maintenance position will open the connection
to an EOL resistor installed in terminal block J9.
EOL Resistor EOL Resistor Terminal block J10 is used for EOL resistors installed on the supervisory
contacts.
Auxiliary Power Output
24V Com EGND
When multiple panels are required to power from the same power supply, the auxiliary power output connection
may be used to daisy-chain wiring to additional Victaulic Vortex™ Panels. Do not exceed 4A draw from the
auxiliary power connector. The auxiliary power connector is not protected by the fuse on the printed circuit
board (PCB).
J11
SYSTEM OPERATION - FLUID PANEL
Power On
Maintenance Light On
Seat ARV
ARV Seated
System Ready
Pressure
Transducer
Out of Range Pressure greater than 150 psi/10.3 Bar (active release) Key Switch
or Key Switch Needle valve release input on TB3 (dry contact) Off
Off
Regulates Output to
End Discharge
25 psi/1.7 Bar
ARV Full
Travel
N2 Output N2 Below
@ 15 psi/1.0 Bar 15 psi/1.0 Bar
Regulate N2
I-VORTEX.500_32 REV_B
I-VORTEX.500 / Victaulic Vortex™ 500 System / General Design, Installation and Maintenance Manual
Failure to follow this instruction could result in death or serious personal injury and product damage.
The Victaulic Vortex™ 500 System rack model is shipped as several separate components that require minimal assembly: an upper rack assembly, a
lower rack assembly, nitrogen cylinders, primary kit, and secondary pilot kits(s) if required.
1. Begin by placing the lower rack assembly in its intended locaton. The lower rack assembly may be bolted to the floor.
2. Place the upper rack assembly on top of the lower rack assembly. Secure the assemblies by using the strut channel connector. It is
recommended to place the strut channel connectors on the lower rack assembly and secure with two bolts on each side. This allows the upper
rack assembly to be lowered into the strut channel connectors.
3. Fasten the assembled rack assembly securely to the floor and wall with appropriate fasteners (and in accordance with all local codes and
standards).
SEE DETAIL A
DETAIL A
(8 PLACES)
4. Hybrid emitters ship in a separate box and are preassembled to a reducer and 1-inch pipe. Thread the emitter preassembly into the elbows
installed at the top of the hybrid emitter's upper rack assembly. The direction of the elbow and emitter piping may be adjusted to avoid
impingement on nearby objects and to meet the emitter placement guidelines in Section III. The 1-inch hybrid emitter piping may be replaced
with a longer piece, not to exceed 18 inches/457 mm. In certain cases, it is advantageous to locate the Victaulic Vortex™ 500 System outside
the protected space and along an adjacent wall, with the emitters pointing backward through the wall and into the protected space (refer to
Section III).
5. A flexible hose is provided to complete the water tubing connection between the emitter and the factory-installed water line. Install the ¼-inch
elbow in the jacket of the emitter assembly(ies) and connect the flexible hose to the elbow and the factory-installed water tubing.
6. Apply thread sealant to the restricting valves. Install the restricting valves into the manifold. Typically, a properly tightened restricting valve will
have three to four threads visible. If this is a double-row rack being used with an odd number of cylinders, a plug shall be installed in one of the
outside holes of the manifold. Use only plugs that are rated to the appropriate pressure.
WARNING
• All connections and bracing SHALL be installed and tightened before the manifold is pressurized and before
attempting to test or operate the system.
• Use only hoses, valves, and components provided with the Victaulic Vortex™ 500 System.
7. Install cylinders in rack. Typically, cylinders are oriented so that the discharge port is to the installer's left-hand side. It may be helpful to test fit a
discharge hose to verify that the cylinder is rotated correctly in the rack. DO NOT REMOVE PROTECTIVE CYLINDER CAPS UNTIL CYLINDERS
HAVE BEEN SECURED COMPLETELY WITH THE CYLINDER RETAINING STRAPS.
8. Install outer cylinder retaining straps to secure cylinders in rack.
9. Connect discharge hoses to cylinders and manifold. It may be necessary to rotate the manifold slightly to facilitate discharge hose installation.
NOTE: Hoses contain an o-ring seal. Verify that sealing surfaces are clean. Avoid rotating the hose when it is tightened against the sealing
surfaces. Start threads on each end of hose before tightening either end. Typically, properly tightened hoses have one to two threads visible.
10. Tighten the union at the end of the manifold.
11. Begin tightening the primary solenoid release and secondary gauge assemblies onto the cylinder valves. A single primary solenoid release
assembly can operate up to 24 cylinder valves. In multi-zone systems, or systems with large numbers of cylinders, multiple primary solenoid
release assemblies can be used. NOTE: To make hose routing easier, it is preferable to have the primary solenoid release assembly on the far
right cylinder in the group of cylinders.
12. Install the primary solenoid release assembly last, after all secondary assemblies are installed.
13. Attach the primary solenoid release assembly to the pilot release gauge port. NOTE: The primary solenoid release assembly contains wrench
flats on the inlet to prevent the assembly from rotating during tightening. DO NOT hold the assembly by the gauge or pressure switch during
tightening. The primary solenoid release assembly engages a Schrader* valve as it is tightened. When the Schrader* valve is engaged, it will take
more torque to tighten the assembly. Typically, the Schrader* valve engages with two to three threads visible and, when tigtened properly, the
assembly will have one or no threads visible.
14. Verify that all discharge hoses are tight at both ends.
15. Install the 1/4-inch BSPP pilot connection port on the rear of the cylinder valves. NOTE: To ease installation, leave this connection loose until all
pilot hoses are connected.
16. Determine pilot hose routing if multiple primary solenoid release assemblies are being used. NOTE: An 11.8-inch/300-mm length pilot hose
is provided with secondary pilot kits to connect adjacent cylinders. A 17.7-inch/450-mm length pilot hose is provided with primary pilot kits to
connect the primary solenoid release assembly to the tee on back of the cylinder valves. Longer pilot hoses are available when it is necessary
to run the primary pilot line between rows of cylinders or to adjacent cylinder racks. A 27 1/2-inch/ 700-mm length pilot hose can be used to
connect cylinders between two rows.
NOTE FOR TWO-CYLINDER ASSEMBLIES THAT CONTAIN ONE 80-LITER CYLINDER AND ONE 49-LITER CYLINDER: The 80-liter
cylinder MUST be the primary cylinder (containing the primary solenoid release assembly). In addition, the 80-liter cylinder MUST be used for
abbreviated discharge testing.
17. Rotate the maintenance switch to the “ON” position (red indicator light will be lit).
CAUTION
• During installation, nut torque will increase due to nitrogen pressure.
• Continue tightening the mounting nut until the primary pilot kit assembly is installed rigidly and does not rotate.
Failure to tighten the nut properly will cause of a loss of nitrogen, resulting in improper system operation.
18. Mount the primary pilot kit securely to the cylinder valve’s pilot release port. Tighten the mounting nut until the complete assembly is installed
rigidly and does not rotate. Inspect the entire assembly for nitrogen leaks. Connect the pilot line hose to the solenoid output, then mount the
primary solenoid coil.
* Schrader is a registered trademark of Schrader International, a Tomkins Company
RELOCATED ¼-INCH
BLEED VALVE
SEE DETAIL B
SEE DETAIL B
DETAIL B
(8 PLACES)
NOTICE
Push Key Hole/Button
to Release Handle
INSTALLATION OF THE VICTAULIC VORTEX™ 500 5. Install cylinders in rack. Typically, cylinders are oriented so that the
discharge port is to the installer's left-hand side. It may be helpful
SYSTEM CABINET MODEL to test fit a discharge hose to verify that the cylinder is rotated
correctly in the rack. DO NOT REMOVE PROTECTIVE CYLINDER
WARNING CAPS UNTIL CYLINDERS HAVE BEEN SECURED COMPLETELY
• The cabinet model of the Victaulic Vortex™ 500 System is top WITH THE CYLINDER RETAINING STRAPS.
heavy and shall be secured to the wall and floor. 6. Install the cylinder retaining straps to secure cylinders in rack.
Failure to follow this instruction could result in death or serious 7. Connect discharge hoses to cylinders and manifold. It may be
personal injury and product damage. necessary to rotate the manifold slightly to facilitate discharge hose
installation. NOTE: Hoses contain an o-ring seal. Verify that sealing
1. Position the Victaulic Vortex™ 500 System cabinet, as described in surfaces are clean. Avoid rotating the hose when it is tightened
Section III. Fasten the cabinet securely to the floor and wall with against the sealing surfaces. Start threads on each end of hose
appropriate fasteners (and in accordance with all local codes and before tightening either end. Typically, properly tightened hoses
standards). have one to two threads visible.
2. Hybrid emitters ship in a separate box and are preassembled to a 8. Tighten the union at the end of the manifold.
1-inch NPT connection installed into the 1-inch elbow port located 9. Attach the primary solenoid release assembly to the pilot release
on the upper rack assembly. NOTE: Only one port is available for gauge port. NOTE: The primary solenoid release assembly
single-cylinder units. contains wrench flats on the inlet to prevent the assembly from
3. A flexible hose is provided to complete the water connection rotating during tightening. DO NOT hold the assembly by the
between the emitter and factory-installed tubing. gauge or pressure switch during tightening. The primary solenoid
release assembly engages a Schrader* valve as it is tightened.
3a. Install the male 1/4-inch NPT into the water jacket of the emitter,
When the Schrader* valve is engaged, it will take more torque
then connect the female 1/4-inch NPT fitting to the supplied elbow
to tighten the assembly. Typically, the Schrader* valve engages
(NPT by inverted flare) located on the factory-installed tubing.
with two to three threads visible and, when tigtened properly, the
3b. Fill the water tank. NOTE: Do not fill the water tank if system assembly will have one or no threads visible.
testing without water is desired. In this case, fill the water tank
10. Attach the secondary gauge assembly to the pilot connection port.
after testing is complete.
NOTE: The secondary gauge assembly contains wrench flats on
4. Apply thread sealant to the restricting the inlet to prevent the assembly from rotating during tightening.
valves. Install the restricting valves DO NOT hold the assembly by the gauge or pressure switch during
into the manifold. Typically, a properly tightening.
tightened restricting valve will have
11. Install the tee fittings, included with the primary and secondary
three to four threads visible. If this is
kits, onto the back on each solenoid valve. DO NOT tighten the tee
a double-row rack being used with an
fittings until after the pilot hoses are installed.
odd number of cylinders, a plug shall
be installed in one of the outside holes 12. Install the snubber assembly and connect the primary pilot hose
of the manifold. Use only plugs that are between the snubber assembly and the tee on the primary cylinder
rated to the appropriate pressure. valve. Ensure that the copper washer is seated properly and
installed between the snubber assembly and the primary solenoid
WARNING assembly.
• All connections and bracing SHALL be 13. Install the secondary pilot hoses. The secondary pilot hoses
installed and tightened before the manifold connect the tees on the back of each cylinder.
is pressurized and before attempting to test 14. Install the bleed valve at the end of the pilot line. Ensure that the
or operate the system. copper washer is seated properly before installing the bleed valve.
• Use only hoses, valves, and components 15. Tighten the tee fittings on the back of each cylinder. Verify that all
provided with the Victaulic Vortex™ 500
pilot hose connections have been tightened.
System.
16. Verify that the discharge hoses are tight at both ends.
• DO NOT attempt to tighten or loosen any pressurized
connections. 17. Refer to Section VI for instructions on how to complete the wiring
• During inspection and maintenance, any damaged components of the Victaulic Vortex™ 500 System.
shall be replaced.
• Transportation and installation of compressed gas cylinders
shall be performed only by individuals that have been trained on
proper handling techniques. Compressed gas cylinders contain
stored energy that can discharge explosively.
• NEVER TRANSPORT COMPRESSED GAS CYLINDERS WITHOUT
THE CYLINDER CAP INSTALLED.
• For additional safety and handling information, always reference
the applicable I-VORTEX Design, Installation, and Maintenance
Manual; the local AHJ requirements; and thefollowing codes/
standards:
- Code of Federal Regulation (49 CFR 171-179 and 14 CFR 103)
- OSHA 1910.101
- Compressed Gas Association (C-6-1968, C-8-1962, and P-1)
- NFPA 55
Failure to follow these instructions can cause unexpected, violent
movement of compressed gas cylinders, resulting in death or
serious personal injury and property damage.
I-VORTEX.500_40 REV_B
I-VORTEX.500 / Victaulic Vortex™ 500 System / General Design, Installation and Maintenance Manual
NC
~ ~ ~
24V Sig EGND
J2
• The pressure transducer is factory installed and wired.
• Shielded, twisted pair, 18 American Wire Gauge (AWG) electrical wiring is required to prevent signal noise degradation. The distance shall not
exceed a maximum of 1000 feet/305 meters (Belden* 5300FE meets these specifications).
• Wiring shall be protected and installed per National Electrical Code and local guidelines.
• Pressure transducer wiring can be run in the same conduit as supervisory and primary release signals and 24-volt DC power for the panel, as
allowed by applicable electrical codes.
• Do not run pressure transducer wiring in the same conduit as AC power wiring.
Prior to Servicing the System
CAUTION
• The nitrogen isolation valve and water supply valves shall remain closed to prevent accidental discharge of the system.
Failure to follow this instruction could result in property damage.
1. Remove all solenoids from the primary solenoid release assemblies before any connections take place. As a final step, and after all circuits are
tested for functionality, the solenoids can be placed onto the release heads.
2. Place the maintenance switch in the maintenance position to prevent the valve from opening in case of accidental discharge. Reset the
maintenance switch as a final step when the system is ready to become active.
3. Close all isolation valves until the system is ready to become active.
I-VORTEX.500_42
Pin 2 = Pressure Transducer Signal (Sig)
Low-Pressure
Supervisory
18 AWG Twisted Shielded Pair Switch
24V Release Signal from FACP
N/C (Nitrogen Cylinder Group 1)
CONNECTOR IS
PRE-WIRED AT FACTORY
Power in from
24VDC Supply
Solenoid Output (Nitrogen Cylinder Group 1)
24V Com EGND 24V Sig EGND ARV+ ARV- Supervisory/Alarm R1+ R1- R2+ R2- S1+ S1- S2+ S2-
J1 J2 J3 J4 J5 J6 Pins 1 & 2 = Release Signal
Power Input Transducer ARV Release Signal Nitrogen Release Solenoid Output Not Polarity Sensitive
Supervisory | Alarm Input 1 & 2 1&2
LED 1
AUX Power NITROGEN CYLINDER GROUP 1
SECTION VI - WIRING
Out LED 2 J9 J10 Nitrogen Release Input PRIMARY SOLENOID RELEASE ASSEMBLY
Auxiliary power output provided for EOL Resistor EOL Resistor 3&4 LOCATED ON NITROGEN CYLINDER
additional Victaulic Vortex™ Panels. LED 5
J11 J7
J8
REV_B
I-VORTEX.500 / Victaulic Vortex™ 500 System / General Design, Installation and Maintenance Manual
2
with Manual Valve
Normally-Open ½-inch
3 FNPT
(Closed Above
Set Point)
1
Low-Pressure
Supervisory
Switch
Normally-Closed
(Closed Below
Set Point)
½-inch
FNPT 3
1
DIN 43650
Not Used Connector Bottom
I-VORTEX.500_44 REV_B
I-VORTEX.500 / Victaulic Vortex™ 500 System / General Design, Installation and Maintenance Manual
SYSTEM ACCEPTANCE 6. Hybrid emitters shall be installed in such a manner that piping
cannot become detached during discharge.
DANGER 7. Hybrid emitters, piping, and mounting brackets shall be installed
in such a manner that they do not cause injury to personnel.
• Before performing maintenance on any Victaulic Vortex™ 500
System components, verify that nitrogen and water valves are 8. All water and gas storage containers shall be located in
fully closed and locked out. accordance with an approved set of system drawings.
• Prior to disconnecting any hoses from the manifold or cylinder 9. All containers and mounting brackets shall be fastened in
valve, verify that the manifold is depressurized to prevent a accordance with the manufacturer's requirements.
release of high-pressure nitrogen. 10. All filters and strainers shall be inspected for proper location.
• All lines shall be depressurized and drained, and all electrical 11. Hybrid emitters shall be inspected for minimum clearances to
circuits shall be locked and tagged to prevent accidental obstructions, per the manufacturer’s requirements.
activation.
12. Hybrid emitters shall be inspected to verify that they are not
• Inform personnel of any testing or of the potential for a system clogged.
discharge. Safety items such as personnel training, warning
Review of Electrical Components
signs, discharge alarms, self-contained breathing apparatus,
evacuation plans, and fire drills shall be considered. 1. All wiring systems shall be checked for proper installation in
• To avoid pressurization, verify that there are no blockages conduit and in compliance with approved drawings.
between the panel and hybrid emitters prior to any system 2. Confirm that AC and DC wiring are not combined in a common
testing. conduit or raceway, unless shielded and grounded properly.
Failure to follow these instructions could result in death or serious 3. All wiring systems shall be checked for grounding and shielding, in
personal injury. accordance with the design and installation working plans.
4. All field circuits shall be confirmed to be free from ground faults
NOTICE and short circuits.
• Inspection, testing, and maintenance shall be implemented 5. Hybrid system branch piping shall be verified that it is not being
in accordance with procedures that meet or exceed those used as an electrical ground.
established in this document and in accordance with applicable 6. Detection devices shall be checked for proper type and location,
requirements of NFPA and the local AHJ. as specified on system drawings.
• Installation, acceptance, testing, and maintenance procedures 7. Manual pull stations, if installed, shall be confirmed as accessible,
shall be conducted only by a qualified contractor or by a accurately identified, and properly protected to prevent damage.
qualified representative of the building owner.
Functional Tests
• Always follow all Victaulic and local safety guidelines when
installing, inspecting, maintaining, or testing any Victaulic If the system is connected to an alarm-receiving office, the alarm-
Vortex™ 500 System. receiving office shall be notified that the fire system test is being
conducted and that an emergency response by the fire department is
• Any impairments to the system shall be corrected in a timely
not desired.
manner.
Supervisory Output Verification
Victaulic recommends that system acceptance review and testing be 1. Victaulic Vortex™ Panel Supervisory – located in the Victaulic
conducted prior to placing a Victaulic Vortex™ 500 System into service. Vortex™ Panels and indicates power good, maintenance switch,
Acceptance testing should follow the recommendations of applicable pressure transducer signal good (if applicable)
standards, and a complete acceptance test procedure should be
2. Nitrogen Cylinder Low Pressure – located on the primary discharge
developed prior to performing acceptance testing. Acceptance testing
assembly and indicates nitrogen pressure is below the set point
shall be documented in a test report.
indicated in Section II
Victaulic does not require a system discharge as part of the acceptance
3. Optional Secondary Nitrogen Cylinder Low-Pressure Switch –
testing. Where the Victaulic Vortex™ 500 System operates in conjunction
located on the secondary gauge assembly and indicates nitrogen
with other building systems, functions, or components, the final testing
pressure is below the set point indicated in Section II
shall be conducted with those systems, as appropriate.
4. The optional coil position monitor located on the primary solenoid
Review of Mechanical Components
release assembly indicates that the coil has been removed from
1. For a total flooding system, the protected enclosure should be the primary solenoid release assembly
reviewed to determine that it is in general conformance with 5. Proper operation of auxiliary devices shall be verified
construction documents and that the number and size of openings
are in accordance with working plans. 6. Proper operation of the agent-releasing FACP and all connected
devices, such as detectors, manual stations, time delays, alarms,
2. The piping system shall be inspected to determine that it is in remote annunciators, and releasing devices, shall be verified.
compliance with design and installation documents.
3. Hybrid emitters and pipe size shall be in accordance with
approved working plans.
4. The means of pipe size reduction and pipe fitting size and
arrangement shall be checked for conformance to design and
installation documents.
5. Piping joints, hybrid emitters, and piping supports shall be
restrained to prevent unacceptable vertical or lateral movement
during discharge.
Operational Testing Full Discharge Test – may be used to verify high-pressure piping to
the Victaulic Vortex™ Panel, pneumatic operation of cylinder valves,
1. ™
Confirm basic operation of the Victaulic Vortex Panel(s) by cycling
discharge active output of the Victaulic Vortex™ Panel, discharge
the maintenance switch from the maintenance position to the
solenoid operation, ARV operation, water valve operation, drain valve
ready position. The ARV will attempt to seat the needle valve, and
operation, hybrid emitter operating pressure, and approximate final
the yellow supervisory indicator light will go out.
oxygen level
2. Confirm operation of the supervisory contacts in Fluid Panels.
When a discharge test is required, a minimum of one cylinder is
3. For Fluid Panels, needle valve operation may be tested using the required for each 1/2-inch and 5/8-inch hybrid emitter. Nitrogen flow
test button on the PCB. Verify that the nitrogen isolation valve is requirements that exceed 250 SCFM/425 m3/hr per cylinder may
closed and that there is no pressure in the nitrogen inlet piping. prevent the Victaulic Vortex™ Panel and hybrid emitters from reaching
Push and hold the yellow test button, and the needle valve will the set system pressure before the nitrogen supply is exhausted.
open. When the yellow test button is released, the needle valve will
Testing may be conducted using solenoid operation through the agent-
begin closing. After testing, cycle the maintenance switch to the
releasing FACP. Active release panels may be tested manually by using
maintenance position and then back to the ready position to seat
the handwheel on the primary solenoid release assembly.
the needle valve and bring the panel back to the ready state.
Pre-Test (All Discharge Tests)
Leak Testing
1. Review applicable sections of this manual for relevant warnings
The water and nitrogen piping systems should be verified to be
and cautions related to system design, installation, and use.
connected completely and properly. A visual inspection may be
conducted to verify that all piping is connected and terminated correctly. 2. Contact all required personnel and agencies prior to performing
If required by the AHJ, a pressure test may be conducted as part of the supervisory switch tests.
nitrogen and water piping system verification. 3. Prepare the area being protected before any system testing
occurs. Vacate all personnel from the area or verify that approved
SYSTEM DISCHARGE TESTS self-contained breathing apparatus and personal protective
equipment is provided, as required.
NOTICE
4. Personnel involved in testing shall be qualified to perform testing.
• The building owner or occupant shall contact all required 5. Means of monitoring oxygen level may be required.
personnel (contractors, emergency response, facility manager)
6. Inspect piping completely, especially high-pressure piping and
prior to performing system discharge tests and shall advise as to
cylinder hose connections, to verify all connections are secure.
the sequence and operation of the testing procedure.
7. In some applications, it may be helpful to slowly pressurize the
• Prepare the area being protected before any system testing
high-pressure piping by manually opening the handwheel of one
occurs. To prevent unnecessary exposure to system discharge,
nitrogen cylinder. The nitrogen released into the manifold can
vacate all personnel from the area being protected. Inform all
then be used for an abbreviated discharge, or it can be released
personnel that a discharge test will be conducted. Everyone shall
through the bleed valve in the Victaulic Vortex™ Panel.
be aware that various equipment will shut off or turn on.
Pressurization Test Without Discharge
• All required personnel shall be advised upon completion of
testing and when the system is returned to service. 1. Open the water tank fill port to avoid pressurizing the water tank.
2. Place the maintenance switch in the Fluid Panel in the
Victaulic does not require a discharge test as part of system maintenance position. Confirm that the yellow supervisory indicator
acceptance testing. Discharge testing may be used as part of the final light is on.
system check; however, discharge testing may not reveal all possible
3. Release nitrogen at the primary solenoid release assembly.
deficiencies in the system design or installation. Where practical, a
a. For solenoid release, actuate the solenoid via the agent-
pressure test without discharge is recommended. Alternatively, when
releasing FACP
there are concerns about loss of nitrogen, pressurization testing of
b. For manual release, rotate the handwheel on the primary
the high-pressure piping may be conducted with an external nitrogen
solenoid release assembly in the indicated open direction
source, as described earlier in this section.
4. Verify release of nitrogen from the primary solenoid release
When required by the AHJ, the Victaulic Vortex™ 500 System may
assembly has:
be tested in one of three ways: pressurization test without discharge,
a. Pressurized the manifold
abbreviated discharge, or full discharge. Abbreviated discharge and full
b. Actuated all cylinder valves (raised cylinder valve plungers)
discharge tests may be conducted. Potential damage to items in the
protected space shall be evaluated as part of the decision to conduct a 5. Close all primary solenoid release assemblies by removing the
discharge test using water. solenoid release signal from the agent-releasing FACP or by
rotating the handwheel on the primary solenoid release assembly
Verify correct system application, design, installation, and use as
in the indicated closed direction.
described in this manual.
a. The pilot line will remain pressurized, and the cylinder
Pressurization Test Without Discharge – may be used to verify high- valve plungers will remain raised
pressure piping to the Victaulic Vortex™ Panel, pneumatic operation of
cylinder valves, discharge active output of the Victaulic Vortex™ Panel,
and discharge solenoid operation
Abbreviated Discharge Test – may be used to verify high-pressure
piping to the Victaulic Vortex™ Panel, pneumatic operation of cylinder
valves, discharge active output of the Victaulic Vortex™ Panel, discharge
solenoid operation, ARV operation, water valve operation, and drain
valve operation
6. Relieve pressure from the pilot line by depressing the pin on the
CAUTION pilot line bleed valve with the appropriate tool.
• Care shall be taken when depressing the pin on the pilot line a. Relieving pilot line pressure will cause all of the cylinder
valve plungers to lower - the manifold will remain pressurized
bleed valve. A sharp noise and release of pressure will occur
when the pin on the pilot line bleed valve is depressed. 7. Return the maintenance switch to the ready position to start
discharge. Verify that the yellow supervisory indicator light remains
• DO NOT use your finger to manually depress the pin on the pilot
off.
line bleed valve.
a. Pressure at the input of an active release panel will cause the
• Wear personal protective equipment (hearing protection, safety ARV needle valve to begin opening, sending nitrogen to the
glasses, etc.) when working around the pilot line bleed valve. hybrid emitters
Failure to follow these instructions could result in personal injury. b. Pressure at the input of the Victaulic Vortex™ Panel will
cause a discharge active supervisory output from the Panel
6. Relieve pressure from the pilot line by depressing the pin on the 8. Return the system to service.
pilot line bleed valve with the appropriate tool. a. Cycle maintenance switch to maintenance position and then
a. Relieving pilot line pressure will cause all of the cylinder back to ready position - the ARV will re-seat, and the yellow
valve plungers to lower - the manifold will remain pressurized supervisory indicator light will remain off
b. In multi-zone systems, or where multiple groups of cylinders b. Refill the water tank
are used, relieve pressure from every pilot line c. Verify that there are no supervisory outputs at the agent-
7. Return the system to service. releasing FACP
a. Bleed trapped pressure from the manifold and high pressure d. Verify that the remaining nitrogen cylinder pressure is
piping by opening the bleed valve. adequate for protection of the space
b. Close bleed valve e. Verify that the water level in the water tank is adequate for
c. Return the maintenance switch to the ready position. Verify protection of the space
that the yellow supervisory indicator light remains off. Full Nitrogen Discharge
d. Verify that there are no supervisory outputs at the agent-
1. This test may be conducted with or without water discharge. If the
releasing FACP
test is to be conducted without water discharge, open the fill port
Abbreviated Nitrogen Discharge on the water tank to avoid pressurizing the water tank.
1. This test may be conducted with or without water discharge. If the 2. Release nitrogen at the primary solenoid release assembly.
test is to be conducted without water discharge, open the water a. For solenoid release, actuate the solenoid via the agent-
tank fill port to avoid pressurizing the water tank. releasing FACP
a. Closing the water supply valve will generate a supervisory b. For manual release, rotate the handwheel on the primary
output signal from the Victaulic Vortex™ Panel, indicating a solenoid release assembly in the indicated open direction
closed water valve 3. Verify release of nitrogen from the primary solenoid release
2. Place the maintenance switch in the Fluid Panel in the assembly has:
maintenance position. Confirm that the yellow supervisory indicator a. Pressurized the manifold
light is on. b. Actuated all cylinder valves (raised cylinder valve plungers)
3. Release nitrogen at the primary solenoid release assembly. 4. Place the maintenance switch in the Fluid Panel in the ready
a. For solenoid release, actuate the solenoid via the agent- position to start discharge. Verify that the yellow supervisory
releasing FACP indicator light remains off.
b. For manual release, rotate the handwheel on the primary a. Pressure at the input of an active release panel will cause the
solenoid release assembly in the indicated open direction ARV needle valve to begin opening, sending nitrogen to the
4. Verify release of nitrogen from the primary solenoid release hybrid emitters
assembly has: b. Pressure at the input of the Victaulic Vortex™ Panel will
a. Pressurized the manifold cause a discharge active supervisory output from the Panel
b. Actuated all cylinder valves (raised cylinder valve plungers) c. Water discharge will occur within 30 seconds from the
start of the discharge
5. Close the primary solenoid release assembly by removing the d. Nitrogen pressure at the hybrid emitters will reach 85% of
solenoid release signal from the agent-releasing FACP or by the operating pressure within 30 seconds
rotating the handwheel on the primary solenoid release assembly
in the indicated closed direction. 5. Return the system to service.
a. The pilot line will remain pressurized, and the cylinder valve a. Cycle maintenance switch to maintenance position and then
plungers will remain raised back to ready position - the ARV will re-seat, and the yellow
supervisory indicator light will remain off
b. Verify that there are no supervisory outputs at the agent-
CAUTION releasing FACP
• Care shall be taken when depressing the pin on the pilot line c. Refill the nitrogen cylinders
bleed valve. A sharp noise and release of pressure will occur d. Refill the water tank
when the pin on the pilot line bleed valve is depressed.
• DO NOT use your finger to manually depress the pin on the pilot
line bleed valve.
• Wear personal protective equipment (hearing protection, safety
glasses, etc.) when working around the pilot line bleed valve.
Failure to follow these instructions could result in personal injury.
I-VORTEX.500_48 REV_B
I-VORTEX.500 / Victaulic Vortex™ 500 System / General Design, Installation and Maintenance Manual
1. Complete all steps outlined in the “Weekly Visual Inspection” and 3h. A hose that passes a hydrostatic test shall be marked as
“Semi-Annual Inspection” sections on this page. “passed” and shall contain the date of the test.
2. Cycle the nitrogen valve and verify proper operation (discharge test 3i. A hose that fails a hydrostatic test shall be marked as “failed”
is not required). and destroyed. A new assembly shall be installed in its place.
3. Replace water in storage containers. Drain and inspect interior Most jurisdictions will require inspection or testing of cylinders prior to
of water tanks. Clean (flush) water tanks to remove debris. Refill refilling. For DOT rated cylinders requiring refilling, refer to the Code of
water tanks. Federal Regulations (CFR). Title 49, parts 100-199 allows for a 12-year
requalification of cylinders used as a fire extinguisher (part 180). For
4. Inspect all system hoses. If visual examination shows any damage additional guidance on marking, testing, recharge, requalification,
or deterioration, the affected hoses shall be replaced immediately. and shipment, refer to the Fire Suppression Systems Association's
5. Verify that all warning placards are installed in their proper (FSSA's) Test Guide for Use with Special Hazard Fire Suppression
locations and that they are not obstructed from view. Systems Containers. It is the responsibility of the building owner or their
6. Check the water tank and nitrogen cylinders for signs of damage. representative to maintain the system in accordance with all applicable
local codes and requirements, including those of the AHJ.
7. Verify operation of primary discharge solenoid coil.
Records
Records of inspections, tests, and system maintenance shall be made
available to the AHJ, upon request.
Records shall indicate the procedures performed, the organization that
performed the work, the results, and the date.
Records shall be maintained in accordance with requirements of the
local AHJ.
Water Tank
Fill Port
Lift Handle
to Open
I-VORTEX.500_52 REV_B
I-VORTEX.500 / Victaulic Vortex™ 500 System / General Design, Installation and Maintenance Manual
Supervisory contact from Victaulic Vortex™ Panel is closed. Pressure transducer wiring is faulty Verify and repair pressure transducer wiring
Yellow fault indicator lamp is on.
Maintenance switch is in maintenance position Place maintenance switch in ready position
Internal wiring to the ARV, or the ARV itself, is damaged Check internal panel wiring for unplugged components
Supervisory contact from Victaulic Vortex™ Panel is on. A component is unplugged or internal Victaulic Vortex™ Panel wiring Check internal Victaulic Vortex™ Panel wiring for unplugged compo-
Yellow fault indicator lamp is on. LED 3 is off. is damaged nents
LED 4 is off Needle valve is not seated Cycle maintenance switch to maintenance position and then back to
ready position to seat needle valve
Intermittent supervisory indication from Victaulic Vortex™ Interference on pressure transducer wiring Verify Victaulic Vortex™ Panel is grounded properly
Panel Verify pressure transducer wiring is proper type and is grounded
properly
Verify pressure transducer on DC power wiring is not located in conduit
with power signals
ARV does not open when test button is pressed Victaulic Vortex™ Panel is in supervisory state Cycle maintenance switch and troubleshoot supervisory contact/fault
indicator lamp
Maintenance switch is in maintenance position Return maintenance switch to ready position
ARV does not operate when 24V is applied to release input Victaulic Vortex™ Panel is in supervisory state Cycle maintenance switch and troubleshoot supervisory contact/fault
(dry contact panels only) indicator lamp
Victaulic Vortex™ Panel is not a dry contact panel Verify system design and bill of materials against installed equipment
ARV does not operate when pressure is applied to the inlet of Victaulic Vortex™ Panel is in supervisory state Cycle maintenance switch and troubleshoot supervisory contact/fault
the Victaulic Vortex™ Panel (active release panels only) indicator lamp
Victaulic Vortex™ Panel is not an active release panel Configure system with appropriate ARV release signal from agent-
releasing FACP
Alarm contact is closed. Red fault indicator lamp is on. Nitrogen pressure greater than 150 psi/10.3 Bar is applied to the inlet Close the nitrogen supply - relieve pressure by using nitrogen bleed
of the Victaulic Vortex™ Panel valve in Victaulic Vortex™ Panel
Agent-releasing FACP indicates open circuit on needle valve Agent-releasing FACP requires lower impedence to clear supervisory Add a properly-sized resistor to J9 on PCB
release signal (dry contact panels only)
Agent-releasing FACP indicates open circuit on nitrogen Needle valve is not seated Cycle maintenance switch to maintenance position and then back to
solenoid release signal ready position to seat needle valve
Maintenance switch is in maintenance position Return maintenance switch to ready position
Primary discharge solenoid does not activate when nitrogen Needle valve is not seated Cycle maintenance switch to maintenance position and then back to
release signal is applied ready position to seat needle valve
Maintenance switch is in maintenance position Return maintenance switch to ready position
Low-pressure supervisory from primary or secondary gauge Nitrogen cylinder pressure is not sufficient to reset low-pressure Verify nitrogen cylinder pressure is higher than setpoint of pressure
assembly switch switch (generally greater than 2400 psi/165.5 Bar)
CAUTION
• DO NOT make or break any connections with power applied to the Victaulic Vortex™ Panel.
Failure to follow this instruction could cause damage to the ARV, resulting in improper system operation.
If you have any questions concerning the safe installation and operation of this product, contact Victaulic (scan QR code on front cover for
contact information for your region).