Professional Documents
Culture Documents
CVDDC
CVDDC
CVDDC
3. Before starting the following work, verify calibration of room temperature sensors,
operation of reheat and radiation valves, and operation of c.v. box volume control dampers.
h. Check unit mixing plenums and dampers by measuring air temperatures in a grid
pattern to determine if temperature stratification exists. Do this during cold weather
for the maximum permitted out door air quantity, (not greater than 50%) and
minimum out door air positions. Where units have air blenders do these checks after
the air blenders. Be careful not to freeze coils.
i. When testing is complete return all controls and equipment status to normal operating
conditions.
j. Calculate air system component capacities and compare to specified capacities.
Calculate coil capacities at test conditions. Use Manufacturer's published data and the
calculated capacity at test conditions to compute actual capacities at design
conditions.