Fxuq Pvju Series

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 44

EDUS391437-F15

FXUQ-PVJU
4-Way Blow
Ceiling-Suspended Type
EDUS391437-F15

FXUQ-PVJU
4-Way Blow Ceiling-Suspended Type

1. Features and Benefits .................................................................................2


2. Specifications ..............................................................................................3
3. Dimensions .................................................................................................5
4. Piping Diagrams..........................................................................................6
5. Wiring Diagrams..........................................................................................7
6. Electric Characteristics................................................................................8
7. Safety Devices Setting ................................................................................9
8. Capacity Tables ........................................................................................10
8.1 Cooling Capacity at Te: 43°F (6°C) ............................................................ 10
8.2 Heating Capacity ........................................................................................ 10
8.3 Correction Factor for Cooling Capacity at Te: 48°F (9°C) .......................... 10
9. Sound Levels (Reference Data)................................................................11
10.Center of Gravity .......................................................................................13
11.Installation Manual ....................................................................................14
12.Accessories...............................................................................................36
12.1 Optional Accessories (for Unit)................................................................... 36
12.2 Optional Accessories (for Controls)............................................................ 36
13.Detail of Optional Accessories ..................................................................37
13.1 BRE49B1F — Sensor Kit ........................................................................... 37

FXUQ-PVJU 1
Features and Benefits EDUS391437-F15

1. Features and Benefits


The unique 4-way ceiling-suspended cassette is an ideal solution for rooms without a false ceiling, or minimal space
above a false ceiling, where adaptive comfort control is preferred.

The optional Sensor Kit (occupancy and surface temperature) together with air temperature sensor and advanced
control functions enables the unit to provide an exceptional comfort level, energy efficiency, and flexibility.

„ Very low unit height of under 8" makes it an ideal solution for school, shops, restaurants and offices with no or low
false ceilings
„ Optional Sensor Kit enables input from three room sensors to provide optimized occupant comfort and efficiency
„ Stylish unit blends easily with any interior, as the air louvers close entirely when not in operation
„ Low energy consumption thanks to a specially developed small tube heat exchanger, DC fan motor and drain pump
„ Individual air louver control - one or more louver can be easily closed via the remote controller when required
„ Ideal for both new and existing buildings
„ Can also be mounted partially recessed in a false ceiling
„ Same appearance and size for all capacity models

2 FXUQ-PVJU
EDUS391437-F15 Specifications

2. Specifications
4-Way Blow Ceiling-Suspended Type
Model FXUQ18PVJU FXUQ24PVJU
Power supply 1 phase, 60Hz, 208/230V 1 phase, 60Hz, 208/230V
+1 +3 Cooling capacity Btu/h 18,000 (5.3) 24,000 (7.0)
(kW)
+2 +3 Heating capacity Btu/h 20,000 (5.9) 27,000 (7.9)
(kW)
Casing / Color Resin/Fresh White Resin/Fresh White
Dimensions: (H×W×D) in. 7-13/16×37-3/8×37-3/8 7-13/16×37-3/8×37-3/8
(mm) (198×950×950) (198×950×950)
Coil (Cross Rows×Stages×FPI 3×10×21 3×10×21
fin coil) Face area ft2 (m2) 3.55 (0.330) 3.55 (0.330)
Model QTS48D11M QTS48D11M
Type Turbo fan Turbo fan
Fan Motor output W 46 46
Airflow rate (H/M/L) cfm 795/689/565 (22.5/19.5/16.0) 795/689/565 (22.5/19.5/16.0)
3
(m /min)
Drive Direct drive Direct drive
Temperature control Microprocessor thermostat Microprocessor thermostat
for cooling and heating for cooling and heating
Sound absorbing thermal insulation material Polyethylene foam Polyethylene foam
Weight lbs (kg) 58 (26) 58 (26)
+4 Sound pressure level (H/M/L)
(Reference data) dB (A) 40/38/36 40/38/36
+4 Sound power level (H/M/L)
(Reference data) dB (A) 58/56/54 58/56/54

Liquid pipes in. φ1/4 (6.4) (Flare connection) φ3/8 (9.5) (Flare connection)
(mm)
Gas pipes in. φ1/2 (12.7) (Flare connection) φ5/8 (15.9) (Flare connection)
Piping (mm)
connections
VP20 VP20
Drain pipe in. External dia. 1 (26) External dia. 1 (26)
(mm) ( Internal dia. 13/16 (20) ) ( Internal dia. 13/16 (20) )
Safety devices Fuse Fuse
Refrigerant control Electronic expansion valve Electronic expansion valve
Connectable outdoor unit R410A VRV series R410A VRV series
Operation manual, Installation manual, Paper pattern for Operation manual, Installation manual, Paper pattern for
Standard accessories installation, Drain hose, Sealing pads, Clamps, Washers, installation, Drain hose, Sealing pads, Clamps, Washers,
Screws, Insulation for fitting, Clamp metal, Conduit mounting Screws, Insulation for fitting, Clamp metal, Conduit mounting
plate plate
Drawing No. C: 3D090219A C: 3D090219A
Notes:
+ 1. Nominal cooling capacities are based on the following conditions:
Return air temperature: 80.0°FDB (26.7°CDB), 67.0°FWB (19.4°CWB)
Outdoor temperature: 95.0°FDB (35.0°CDB)
Equivalent ref. piping length: 25ft (7.6m) (Horizontal)
+ 2. Nominal heating capacities are based on the following conditions:
Return air temperature: 70.0°FDB (21.1°CDB).
Outdoor temperature: 47.0°FDB (8.3°CDB), 43.0°FWB (6.1°CWB)
Equivalent ref. piping length: 25ft (7.6m) (Horizontal)
+ 3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
+ 4. Anechoic chamber conversion value, measured under JIS conditions. During actual operation,
these values may be higher as a result of installation conditions.
5. Refer to Electric Characteristics for the power input.

FXUQ-PVJU 3
Specifications EDUS391437-F15

4-Way Blow Ceiling-Suspended Type


Model FXUQ30PVJU FXUQ36PVJU
Power supply 1 phase, 60Hz, 208/230V 1 phase, 60Hz, 208/230V
+1 +3 Cooling capacity Btu/h 30,000 (8.8) 36,000 (10.6)
(kW)
+2 +3 Heating capacity Btu/h 34,000 (10.0) 40,000 (11.7)
(kW)
Casing / Color Resin/Fresh White Resin/Fresh White
Dimensions: (H×W×D) in. 7-13/16×37-3/8×37-3/8 7-13/16×37-3/8×37-3/8
(mm) (198×950×950) (198×950×950)
Coil (Cross Rows×Stages×FPI 3×10×21 3×10×21
fin coil) Face area ft2 (m2) 3.55 (0.330) 3.55 (0.330)
Model QTS48D11M QTS48D11M
Type Turbo fan Turbo fan
Fan Motor output W 106 106
Airflow rate (H/M/L) cfm 1,095/918/742 (31.0/26.0/21.0) 1,095/918/742 (31.0/26.0/21.0)
3
(m /min)
Drive Direct drive Direct drive
Temperature control Microprocessor thermostat Microprocessor thermostat
for cooling and heating for cooling and heating
Sound absorbing thermal insulation material Polyethylene foam Polyethylene foam
Weight lbs (kg) 60 (27) 60 (27)
+4 Sound pressure level (H/M/L)
(Reference data) dB (A) 47/44/40 47/44/40
+4 Sound power level (H/M/L)
(Reference data) dB (A) 65/62/58 65/62/58

Liquid pipes in. φ3/8 (9.5) (Flare connection) φ3/8 (9.5) (Flare connection)
(mm)
Gas pipes in. φ5/8 (15.9) (Flare connection) φ5/8 (15.9) (Flare connection)
Piping (mm)
connections
VP20 VP20
Drain pipe in. External dia. 1 (26) External dia. 1 (26)
(mm) ( Internal dia. 13/16 (20) ) ( Internal dia. 13/16 (20) )
Safety devices Fuse Fuse
Refrigerant control Electronic expansion valve Electronic expansion valve
Connectable outdoor unit R410A VRV series R410A VRV series
Operation manual, Installation manual, Paper pattern for Operation manual, Installation manual, Paper pattern for
Standard accessories installation, Drain hose, Sealing pads, Clamps, Washers, installation, Drain hose, Sealing pads, Clamps, Washers,
Screws, Insulation for fitting, Clamp metal, Conduit mounting Screws, Insulation for fitting, Clamp metal, Conduit mounting
plate plate
Drawing No. C: 3D090219A C: 3D090219A
Notes:
+ 1. Nominal cooling capacities are based on the following conditions:
Return air temperature: 80.0°FDB (26.7°CDB), 67.0°FWB (19.4°CWB)
Outdoor temperature: 95.0°FDB (35.0°CDB)
Equivalent ref. piping length: 25ft (7.6m) (Horizontal)
+ 2. Nominal heating capacities are based on the following conditions:
Return air temperature: 70.0°FDB (21.1°CDB).
Outdoor temperature: 47.0°FDB (8.3°CDB), 43.0°FWB (6.1°CWB)
Equivalent ref. piping length: 25ft (7.6m) (Horizontal)
+ 3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
+ 4. Anechoic chamber conversion value, measured under JIS conditions. During actual operation,
these values may be higher as a result of installation conditions.
5. Refer to Electric Characteristics for the power input.

4 FXUQ-PVJU
EDUS391437-F15 Dimensions

3. Dimensions
FXUQ18PVJU / FXUQ24PVJU / FXUQ30PVJU / FXUQ36PVJU

3D090217A

FXUQ-PVJU 5
Piping Diagrams EDUS391437-F15

4. Piping Diagrams
FXUQ18PVJU / FXUQ24PVJU / FXUQ30PVJU / FXUQ36PVJU

C: 4D034245K

Unit: in. (mm)


Model Gas Liquid

FXUQ18PVJU φ1/2 φ1/4


(12.7) (6.4)
φ5/8 φ3/8
FXUQ24PVJU / FXUQ30PVJU / FXUQ36PVJU
(15.9) (9.5)

6 FXUQ-PVJU
EDUS391437-F15 Wiring Diagrams

5. Wiring Diagrams
FXUQ18PVJU / FXUQ24PVJU / FXUQ30PVJU / FXUQ36PVJU

3D090218

FXUQ-PVJU 7
Electric Characteristics EDUS391437-F15

6. Electric Characteristics
FXUQ18PVJU / FXUQ24PVJU / FXUQ30PVJU / FXUQ36PVJU

4D090214A

8 FXUQ-PVJU
EDUS391437-F15 Safety Devices Setting

7. Safety Devices Setting


Model FXUQ18PVJU FXUQ24PVJU FXUQ30PVJU FXUQ36PVJU
Printed circuit board fuse 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A
Drain pump °F
thermal fuse (°C) – – – –

Fan motor thermal °F – – – –


protector (°C)
Fan motor thermal °F – – – –
fuse (°C)
C: 3D090213

FXUQ-PVJU 9
Capacity Tables EDUS391437-F15

8. Capacity Tables
8.1 Cooling Capacity at Te: 43°F (6°C)
Indoor air temp. °FWB (Te: 43°F (6°C))
Capacity 61 64 67 70 72 75
Model
indication TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH
FXUQ18PVJU 18 14.2 11.8 16.1 12.9 18.0 13.7 18.4 13.6 18.6 13.0 18.9 12.8
FXUQ24PVJU 24 19.0 15.4 21.5 16.9 24.0 18.0 24.5 17.8 24.8 17.0 25.3 16.6
FXUQ30PVJU 30 23.7 18.8 26.8 20.7 30.0 22.1 30.6 21.8 31.0 20.9 31.6 20.2
FXUQ36PVJU 36 28.4 22.1 32.2 24.2 36.0 26.0 36.7 25.7 37.2 24.7 37.9 23.6

TC: Total capacity: MBH


SHC: Sensible heat capacity: MBH

Notes: 1. These capacity tables can be used when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV
system satisfies the required heat load.
2. shows rated condition.

8.2 Heating Capacity


Indoor air temp. °FDB
Capacity 62 65 68 70 72 75
Model indication TC TC TC TC TC TC
MBH MBH MBH MBH MBH MBH
FXUQ18PVJU 18 23.3 21.9 20.7 20.0 19.3 18.1
FXUQ24PVJU 24 31.5 29.5 28.0 27.0 26.0 24.5
FXUQ30PVJU 30 39.7 37.1 35.3 34.0 32.7 30.9
FXUQ36PVJU 36 46.7 43.7 41.5 40.0 38.5 36.3

TC: Total capacity: MBH

Notes: 1. These capacity tables can be used when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV
system satisfies the required heat load.
2. shows rated condition.

8.3 Correction Factor for Cooling Capacity at Te: 48°F (9°C)


Refer to the correction factor table below when a
residential indoor unit is connected to your VRV system.

Indoor air temp. °FWB (Te: 48°F (9°C))


Model Capacity 61 64 67 70 72 75
indication
TC SHF TC SHF TC SHF TC SHF TC SHF TC SHF
FXUQ18PVJU 18 0.706 1.162 0.765 1.108 0.786 1.090 0.806 1.073 0.841 1.045 0.865 1.028
FXUQ24PVJU 24 0.706 1.162 0.765 1.108 0.786 1.090 0.806 1.073 0.841 1.045 0.865 1.028
FXUQ30PVJU 30 0.707 1.161 0.773 1.103 0.795 1.087 0.811 1.077 0.842 1.053 0.865 1.035
FXUQ36PVJU 36 0.707 1.161 0.773 1.103 0.795 1.087 0.811 1.077 0.842 1.053 0.865 1.035

TC: Total capacity


SHF: Sensible heat factor

10 FXUQ-PVJU
EDUS391437-F15 Sound Levels (Reference Data)

9. Sound Levels (Reference Data)


FXUQ18PVJU / FXUQ24PVJU

4D090216A

FXUQ-PVJU 11
Sound Levels (Reference Data) EDUS391437-F15

FXUQ30PVJU / FXUQ36PVJU

4D090215A

12 FXUQ-PVJU
EDUS391437-F15 Center of Gravity

10. Center of Gravity


FXUQ18PVJU / FXUQ24PVJU / FXUQ30PVJU / FXUQ36PVJU

Unit: in. (mm)

4D090212

FXUQ-PVJU 13
Installation Manual EDUS391437-F15

11. Installation Manual


FXUQ18PVJU / FXUQ24PVJU / FXUQ30PVJU / FXUQ36PVJU

SAFETY CONSIDERATIONS WARNING


Read these SAFETY CONSIDERATIONS for Installation r 1PN[SWCNKƂGFRGTUQPPGNOWUVECTT[QWVVJGKPUVCNNC-
carefully before installing air conditioning equipment. After tion work. Installation must be done in accordance
completing the installation, make sure that the unit operates with this installation manual. Improper installation
properly during the startup operation. OC[TGUWNVKPYCVGTNGCMCIGGNGEVTKEUJQEMQTƂTG
Instruct the customer on how to operate and maintain the r When installing the unit in a small room, take mea-
unit. Inform customers that they should store this Installation sures to keep the refrigerant concentration from ex-
Manual with the Operation Manual for future reference. ceeding allowable safety limits. Excessive refrigerant
Always use a licensed installer or contractor to install this leaks, in the event of an accident in a closed ambient
product. Improper installation can result in water or refrigerant URCEGECPNGCFVQQZ[IGPFGƂEKGPE[
NGCMCIGGNGEVTKECNUJQEMƂTGQTGZRNQUKQP r 7UGQPN[URGEKƂGFCEEGUUQTKGUCPFRCTVUHQTKPUVCNNC-
Meanings of DANGER, WARNING, CAUTION, and NOTE VKQPYQTM(CKNWTGVQWUGURGEKƂGFRCTVUOC[TGUWNVKP
Symbols: YCVGTNGCMCIGGNGEVTKEUJQEMUƂTGQTVJGWPKVHCNNKPI
r Install the air conditioner or heat pump on a founda-
tion strong enough that it can withstand the weight
DANGER ................Indicates an imminently haz- QHVJGWPKV#HQWPFCVKQPQHKPUWHƂEKGPVUVTGPIVJOC[
ardous situation which, if not result in the unit falling and causing injuries.
avoided, will result in death or r Take into account strong winds, typhoons, or earth-
serious injury. quakes when installing. Improper installation may
WARNING ..............Indicates a potentially haz- result in the unit falling and causing accidents.
ardous situation which, if not r Make sure that a separate power supply circuit is pro-
avoided, could result in death vided for this unit and that all electrical work is carried
or serious injury. QWVD[SWCNKƂGFRGTUQPPGNCEEQTFKPIVQNQECNUVCVG
CPFPCVKQPCNTGIWNCVKQPU#PKPUWHƂEKGPVRQYGTUWRRN[
CAUTION ...............Indicates a potentially haz- capacity or improper electrical construction may lead
ardous situation which, if not VQGNGEVTKEUJQEMUQTƂTG
avoided, may result in minor r /CMGUWTGVJCVCNNYKTKPIKUUGEWTGFVJCVURGEKƂGF
or moderate injury. It may wires are used, and that no external forces act on the
also be used to alert against terminal connections or wires. Improper connections
unsafe practices. QTKPUVCNNCVKQPOC[TGUWNVKPƂTG
NOTE .......................Indicates situations that may r When wiring, position the wires so that the control box
result in equipment or proper- cover can be securely fastened. Improper positioning
ty-damage accidents only. of the control box cover may result in electric shocks,
ƂTGQTVJGVGTOKPCNUQXGTJGCVKPI
DANGER r Before touching electrical parts, turn off the unit.
r This equipment can be installed with a Ground-Fault
r Refrigerant gas is heavier than air and replaces oxy- Circuit Breaker (GFCI). Although this is a recognized
gen. measure for additional protection, with the earthing
A massive leak can lead to oxygen depletion, espe- system in North America, a dedicated GFCI is not
cially in basements, and an asphyxiation hazard could necessary.
occur leading to serious injury or death. r Securely fasten the outdoor unit terminal cover (pan-
r Do not ground units to water pipes, gas pipes, tele- el). If the terminal cover/panel is not installed properly,
phone wires, or lightning rods as incomplete ground- FWUVQTYCVGTOC[GPVGTVJGQWVFQQTWPKVECWUKPIƂTG
ing can cause a severe shock hazard resulting in or electric shock.
severe injury or death. Additionally, grounding to gas r When installing or relocating the system, keep the
pipes could cause a gas leak and potential explosion refrigerant circuit free from substances other than the
causing severe injury or death. URGEKƂGFTGHTKIGTCPV 4# UWEJCUCKT#P[RTGU-
r If refrigerant gas leaks during installation, ventilate ence of air or other foreign substance in the refriger-
the area immediately. Refrigerant gas may produce ant circuit can cause an abnormal pressure rise or
VQZKEICUKHKVEQOGUKPEQPVCEVYKVJƂTG'ZRQUWTGVQ rupture, resulting in injury.
this gas could cause severe injury or death. r Do not change the setting of the protection devices. If
r After completing the installation work, check that the the pressure switch, thermal switch, or other protec-
refrigerant gas does not leak throughout the system. tion device is shorted and operated forcibly, or parts
r &QPQVKPUVCNNWPKVKPCPCTGCYJGTGƃCOOCDNGOCVG- QVJGTVJCPVJQUGURGEKƂGFD[&CKMKPCTGWUGFƂTGQT
rials are present due to risk of explosions that can explosion may occur.
cause serious injury or death.
r Safely dispose all packing and transportation mate-
rials in accordance with federal/state/local laws or CAUTION
ordinances. Packing materials such as nails and other r &QPQVVQWEJVJGUYKVEJYKVJYGVƂPIGTU6QWEJKPIC
metal or wood parts, including plastic packing ma- UYKVEJYKVJYGVƂPIGTUECPECWUGGNGEVTKEUJQEM
terials used for transportation may cause injuries or r Do not allow children to play on or around the unit to
death by suffocation. prevent injury.

i 3P161684-8T English
3P161684-8T

14 FXUQ-PVJU
EDUS391437-F15 Installation Manual

r Do not touch the refrigerant pipes during and imme- F 9JGTGƃCOOCDNGICUOC[NGCMYJGTGVJGTGKU


diately after operation as the refrigerant pipes may be ECTDQPƂDGTQTKIPKVCDNGFWUVUWURGPUKQPKPVJG
hot or cold, depending on the condition of the refriger- CKTQTYJGTGXQNCVKNGƃCOOCDNGUUWEJCUVJKPPGT
CPVƃQYKPIVJTQWIJVJGTGHTKIGTCPVRKRKPIEQORTGU- or gasoline are handled. Operating the unit in such
sor, and other refrigerant cycle parts. Your hands may EQPFKVKQPUECPECWUGCƂTG
suffer burns or frostbite if you touch the refrigerant r Take adequate measures to prevent the outdoor unit
pipes. To avoid injury, give the pipes time to return from being used as a shelter by small animals. Small
to normal temperature or, if you must touch them, be animals making contact with electrical parts can
sure to wear proper gloves. ECWUGOCNHWPEVKQPUUOQMGQTƂTG+PUVTWEVVJGEWU-
r *GCVGZEJCPIGTƂPUCTGUJCTRGPQWIJVQEWV tomer to keep the area around the unit clean.
6QCXQKFKPLWT[YGCTINQXGQTEQXGTVJGƂPUYJGP
working around them. NOTE
r Install drain piping to proper drainage. Improper drain
piping may result in water leakage and property dam- r Install the power supply and transmission wires for
age. the indoor and outdoor units at least 3.5 feet away
r Insulate piping to prevent condensation. from televisions or radios to prevent image interfer-
r Be careful when transporting the product. ence or noise. Depending on the radio waves, a dis-
r Do not turn off the power supply immediately after VCPEGQHHGGVOC[PQVDGUWHƂEKGPVVQGNKOKPCVGVJG
stopping operation. Always wait for at least 5 minutes noise.
before turning off the power supply. Otherwise, water r Dismantling the unit, treatment of the refrigerant, oil
leakage may occur. and additional parts must be done in accordance with
r Do not use a charging cylinder. Using a charging cylin- the relevant local, state, and national regulations.
der may cause the refrigerant to deteriorate. r Do not use the following tools that are used with con-
r 4GHTKIGTCPV4#KPVJGU[UVGOOWUVDGMGRVENGCP ventional refrigerants: gauge manifold, charge hose,
dry, and tight. ICUNGCMFGVGEVQTTGXGTUGƃQYEJGEMXCNXGTGHTKIGT-
(a) Clean and Dry - Foreign materials (including min- ant charge base, vacuum gauge, or refrigerant recov-
eral oils such as SUNISO oil or moisture) should be ery equipment.
prevented from getting into the system. r If the conventional refrigerant and refrigerator oil are
D 6KIJV4#FQGUPQVEQPVCKPCP[EJNQTKPGFQGU OKZGFKP4#VJGTGHTKIGTCPVOC[FGVGTKQTCVG
not destroy the ozone layer, and does not reduce r This air conditioner or heat pump is an appliance that
the earth’s protection again harmful ultraviolet should not be accessible to the general public.
TCFKCVKQP4#ECPEQPVTKDWVGVQVJGITGGPJQWUG r #UFGUKIPRTGUUWTGKURUKVJGYCNNVJKEMPGUUQH
effect if it is released. Therefore take proper mea- ƂGNFKPUVCNNGFRKRGUUJQWNFDGUGNGEVGFKPCEEQTFCPEG
sures to check for the tightness of the refrigerant with the relevant local, state, and national regulations.
piping installation. Read the chapter Refrigerant
Piping Work and follow the procedures.
r 5KPEG4#KUCDNGPFVJGTGSWKTGFCFFKVKQPCNTGHTKI-
erant must be charged in its liquid state. If the refriger-
ant is charged in a state of gas, its composition can
change and the system will not work properly.
r 6JGKPFQQTWPKVKUHQT4#5GGVJGECVCNQIHQTKP-
door models that can be connected. Normal operation
is not possible when connected to other units.
r Remote controller (wireless kit) transmitting distance
can be shorter than expected in rooms with electronic
ƃWQTGUEGPVNCORU KPXGTVGTQTTCRKFUVCTVV[RGU 
+PUVCNNVJGKPFQQTWPKVHCTCYC[HTQOƃWQTGUEGPVNCORU
as much as possible.
r Indoor units are for indoor installation only. Outdoor
units can be installed either outdoors or indoors.
r Do not install the air conditioner or heat pump in the
following locations:
(a) Where a mineral oil mist or oil spray or vapor is
produced, for example, in a kitchen.
Plastic parts may deteriorate and fall off or result in
water leakage.
(b) Where corrosive gas, such as sulfurous acid gas,
is produced.
Corroding copper pipes or soldered parts may
result in refrigerant leakage.
(c) Near machinery emitting electromagnetic waves.
Electromagnetic waves may disturb the operation
of the control system and cause the unit to mal-
function.

3P161684-8T English ii
3P161684-8T

FXUQ-PVJU 15
Installation Manual EDUS391437-F15

FXUQ18PVJU
FXUQ24PVJU
FXUQ30PVJU VRV SYSTEM Air Conditioners Installation manual
FXUQ36PVJU

CONTENTS  ACCESSORIES


Check if the following accessories are attached to the
SAFETY CONSIDERATIONS.................................[i] [ii] indoor unit.
1. BEFORE INSTALLATION ............................................ 1 (1) Drain (2) Metal (3) Washer for
Name (4) Clamp
2. SELECTION OF INSTALLATION LOCATION ............. 2 hose clamp hanger
3. PREPARATION BEFORE INSTALLATION .................. 3 Quantity 1 pc. 1 pc. 8 pcs. 10 pcs.
4. INSTALLATION OF THE INDOOR UNIT ..................... 7
5. REFRIGERANT PIPING WORK.................................. 8 Shape
6. DRAIN PIPING WORK .............................................. 10
7. ELECTRIC WIRING WORK....................................... 13
8. MOUNTING CORNER COVER · SUCTION (5) Washer Joint insulating Sealing
Name
GRILLE ...................................................................... 18 clamp material material
9. FIELD SETTING AND TEST OPERATION ............... 18 (8): 1 sheet
Quantity 4 sheets 2 pcs. 1 pc.
(9): 3 sheets
The original instructions are written in English. All other (8) Large
(6) For gas (7) For liquid
languages are translations of the original instructions.
piping piping
Shape
(9) Small
 BEFORE INSTALLATION
When unpacking the indoor unit or moving the unit after
WPRCEMGFJQNFVJGJCPIGTU RNCEGU CPFFQPQVCRRN[
(11) Installation (12) Blocking (13) L-bent
force to other parts (particularly refrigerant piping, drain Name (10) Elbow
pattern paper material piping
piping and resin parts).
r Make sure to check in advance that the refrigerant to be Quantity 1 pc. 1 sheet 1 pc. 1 pc.
used for installation work is R410A. Used in
The air conditioner will not properly operate if an unsuitable common with
refrigerant is used. packing
Shape
r For installation of the outdoor unit, refer to the installation
manual attached to the outdoor unit.
r Do not throw away the accessories until the installation
work is completed.
r After the indoor unit is carried into the room, to avoid the
indoor unit from getting damaged, take measures to protect Name (14) Screw (15) Non woven fabric (16) Insulation tube
the indoor unit with packing materials.
Quantity 5 pcs. 1 sheet 1 pc.
(1) Determine the route to carry the unit into the room.
(2) Do not unpack the unit until it is carried to the installa-
tion location. Shape
Where unpacking is unavoidable, use a sling of soft
material or protective plates together with a rope when /Z
lifting, to avoid damage or scratches to the indoor unit.
r Have the customer actually operate the air conditioner (17) Conduit (18) Mounting
Name
while looking at the operation manual. mounting plate screw
Instruct the customer how to operate the air conditioner Quantity 1 pc. 1 pc. (Miscellaneous)
RCTVKEWNCTN[ENGCPKPIQHVJGCKTƂNVGTUQRGTCVKQPRTQEGFWTGU
rOperation manual
and temperature adjustment).
rInstallation manual
r For selection of installation location, use the installation Shape
pattern paper (used in common with the packing case.) as
reference. /Z
r Do not use the air conditioner where in the salty atmo-
sphere such as coastal areas, vehicles, vessels or the
XQNVCIGƃWEVWCVKQPKUHTGSWGPVUWEJCUHCEVQTKGU
r Take off static electricity from the body when opening the
EQPVTQNDQZNKFCPFYJGPECTT[KPIQWVYKTKPI
The electric parts may be damaged.

1 3P161684-8T English
3P161684-8T

16 FXUQ-PVJU
EDUS391437-F15 Installation Manual

 OPTIONAL ACCESSORIES Check


Items to be checked
r For this indoor unit, the remote controller is separately column
required. *CXG[QWGZRNCKPGFVJGFGUETKRVKQPQHEQQNKPIJGCVKPI
Refer to the installation manual attached to the remote program dry and automatic (cooling/heating) given in the
controller for how to install. QRGTCVKQPOCPWCNVQVJGEWUVQOGT!
If you set the fan speed at thermostat OFF, did you
CARRY OUT THE WORK GIVING CAUTION TO THE GZRNCKPVJGUGVHCPURGGFVQVJGEWUVQOGT!
FOLLOWING ITEMS AND AFTER THE WORK IS Have you handed the operation manual and the installa-
COMPLETED CHECK THESE AGAIN. VKQPOCPWCNVQVJGEWUVQOGT!

 Items to be checked after the installation work is Points of the operation explanation
completed
In addition to the general usage, since the items in
Check
Items to be checked In case of defective the operation manual with the WARNING and
column
CAUTION marks are likely to result in human
Are the air conditioner rigidly Drop · vibration · bodily injuries and property damages, it is necessary
ƂZGF! noise not only to explain these items to the customer but
Are the installation work of the air Does not operate · also to have the customer read them.
EQPFKVKQPGTEQORNGVG! burnout It is also necessary to explain the items of “NOT
Have you carried out a leakage MALFUNCTION OF THE AIR CONDITIONER” to the
test with the test pressure speci- Does not cool / customer and have the customer read them carefully.
ƂGFKPVJGQWVFQQTWPKVKPUVCNNCVKQP Does not heat
OCPWCN!
Is the insulation of refrigerant
piping and drain piping completely Water leakage  SELECTION OF INSTALLATION LOCA-
ECTTKGFQWV! TION
&QGUVJGFTCKPƃQYQWVUOQQVJN[! Water leakage *QNFVJGJCPIGTUCVRNCEGUVQOQXGVJGKPFQQTWPKVYJGP
Is the power supply voltage identi- unpacking or after unpacked, and do not apply force to
Does not operate · the piping (refrigerant and drain) and resin parts.
cal to that stated in the manufac-
burnout
VWTGToUNCDGNQPVJGCKTEQPFKVKQPGT!
Are wiring and piping correctly Does not operate ·   Select the installation location that meets the follow-
EQPPGEVGFCPFPQVJKPIKUNQQUG! burnout ing conditions and get approval of the customer.
r Where the cool and warm air spreads evenly in the room.
Danger in case of
+UITQWPFKPIEQORNGVGF! r Where there are no obstacles in the air passage.
leakage
r Where drainage can be ensured.
Are the sizes of electric wiring ac- Does not operate ·
r Where the ceiling lower surface is not inclined.
EQTFKPIVQVJGURGEKƂECVKQP! burnout
r 9JGTGVJGTGKUUWHƂEKGPVUVTGPIVJVQYKVJUVCPFVJGOCUU
Are any of air outlets or inlets of QHVJGKPFQQTWPKV KHVJGUVTGPIVJKUKPUWHƂEKGPVVJGKPFQQT
the air conditioner blocked with unit may vibrate and get in contact with the ceiling and
QDUVCENGU! Does not cool / generate unpleasant chattering sound).
If so, it may lead to capacity drop Does not heat
r 9JGTGCURCEGUWHƂEKGPVHQTKPUVCNNCVKQPCPFUGTXKEGECP
due to fan speed drop or malfunc-
tion of equipment.
be ensured. 4GHGTVQ(KICPF(KI
r Where the piping length between the indoor and the out-
Have you recorded the refrigerant door units is ensured within the allowable length. (Refer
Refrigerant charge
piping length and the refrigerant
amount is not clear to the installation manual attached to the outdoor unit.)
EJCTIGCFFGF!
r 9JGTGVJGTGKUPQTKUMQHƃCOOCDNGICUNGCM
Make sure to recheck the items of “SAFETY
CONSIDERATIONS”. [Required installation space [in. (mm)]]
 Items to be checked at delivery When the air outlet is closed

Check
Items to be checked
column
40 (1000)

*CXG[QWECTTKGFQWVƂGNFUGVVKPI! KHPGEGUUCT[ Discharge


or more

(NOTE 2) 100 (2500) or more


60 (1500) 1-3/16 (30) from floor level
#TGVJGEQPVTQNDQZNKFVJGCKTƂNVGTCPFVJGUWEVKQPITKNNG or more Suction or more For high
CVVCEJGF! ∗ installation
Obstacles
Does the cool air discharge during the cooling operation
CPFVJGYCTOCKTFKUEJCTIGFWTKPIJGCVKPIQRGTCVKQP!
Floor level Fig. 1
*CXG[QWGZRNCKPGFJQYVQQRGTCVGVJGCKTEQPFKVKQPGT
YJKNGUJQYKPIVJGQRGTCVKQPOCPWCNVQVJGEWUVQOGT!
5WHƂEKGPVUGTXKEGURCEGKUTGSWKTGFHQTTGOQXKPIVJG
corner cover. (NOTE 2)

3P161684-8T English 2
3P161684-8T

FXUQ-PVJU 17
Installation Manual EDUS391437-F15

(NOTE 1) Exhaust (Discharge pattern) (Views from the ceiling)


Lighting fan
Indoor unit Indoor unit 4-way discharge 3-way discharge

Discharge 2 2 2
60 (1500) or more
60 (1500)
80 (2000) or more
or more
Distance between indoor units 160 (4000) or more 3 1 1 3 1
Fig. 2
[unit: in. (mm)]
4 4
CAUTION
2-way discharge (optional blocking material kit 2-way
r Install the indoor and outdoor units, power supply wiring, discharge is required)
remote controller wiring and transmission wiring at least 2 2
40 in. (1 m) away from televisions or radios to prevent im-
age interference or noise.
(Depending on the radio waves, a distance of 40 in. (1 m) 1
OC[PQVDGUWHƂEKGPVVQGNKOKPCVGVJGPQKUG
r +PUVCNNVJGKPFQQTWPKVCUHCTCURQUUKDNGHTQOƃWQTGUEGPV
lamps. (NOTE 1) 4

The indication “ . ” shows the refrigerant piping outlet


NOTE direction.
 4GUVTKEVKQPCRRNKGUVQVJGGZRQUGFV[RGNKIJVKPIDWVFQGU
: Backward outlet piping : Rightward outlet piping
not apply to the recessed type. (straight outlet) (piping needs to be bent)
 When the air outlet is closed, the space shown with “ ”
must have a distance of 1-3/16 in. (30 mm) or more. For upward outlet piping, any outlet pattern can be selected.
3. (QTUGVVKPIVJGCKTƃQYFKTGEVKQPQHJQTK\QPVCNDNCFGTGHGT
Fig. 3
to the operation manual attached to the indoor unit and
remote controller.
  Ceiling height : This indication shows the air discharge direction.
*
r This indoor unit can be hung from the ceiling of which
height is up to 11-1/2 ft. (3.5 m) (models 30, 36: up to 13 For cross-reference of air outlet No. to indication on indoor
unit
ft. (4.0 m)).
r *QYGXGTKHVJGEGKNKPIJGKIJVGZEGGFUHV O  Name of air outlet Indication on indoor unit
(models 30, 36: 10-1/2 ft. (3.2 m)), it is necessary to set Air outlet 1
on site from the remote controller. Refer to the section
Air outlet 2
“9. FIELD SETTING AND TEST OPERATION”.
Air outlet 3
(3) Air discharge direction Air outlet 4
Select the air discharge pattern according to the installa-
tion location. No. of air outlet
In case of 2-way and 3-way, it is required to set on site
from the remote controller. Indication on
For details, see the section “9. FIELD SETTING AND 4 indoor unit
TEST OPERATION”.
(Caution) Since there are some restriction on the piping
connection side, make sure to select the air
discharge pattern from the Fig. 3.
The names of air outlet are shown in inscription by the
Indoor unit
number of “ ” marks on the underside of the air outlet.
4GHGTVQVJG(KI
  Use hanging bolts for installation. Fig. 4
Investigate if the installation place can withstand the
mass of the indoor unit and, if necessary, hang the unit
with bolts after it is reinforced by beams etc.
(Refer to the installation pattern paper (11) for the mount-
3. PREPARATION BEFORE INSTALLATION
ing pitch.)   Check the locations of indoor unit hanging bolts, pip-
ing outlet holes, drain piping outlet hole and electric
wirings inlet hole. (The drawing shows the view from
the ceiling.) (Refer to Fig. 5 and Fig. 6)

3 3P161684-8T English
3P161684-8T

18 FXUQ-PVJU
EDUS391437-F15 Installation Manual

37-3/8 (950) [unit: in. (mm)]   Make holes for hanging bolts, piping outlet, drain
32-7/8 (835) (hanging bolt pitch) piping outlet and electric wiring inlet.
r Use the installation pattern paper (11) which shows the

32-7/8 (835) (hanging bolt pitch)


above hole locations.
r Determine the locations of hanging bolts, piping outlet,
drain piping outlet and electric wiring inlet. And make
the hole.

37-3/8 (950)
Ceiling slab

Foundation bolt

Long nut or turn-buckle

(50 - 100 mm)


2 - 4 in.
Gas piping

Liquid piping Hanging bolt


Ceiling surface

Fig. 7
Drain connection outlet (VP20)

Fig. 5 NOTE
[unit: in. (mm)] The above shown parts are all field supply. 4GHGTVQ(KI
r Use 3/8 in. (M8) or 7/16 in. (M10) bolts for hanging the
Locations of upward gas piping and drain connection indoor unit.
7UGJQNGKPCPEJQTUHQTVJGGZKUVKPIDQNVUCPFGODGF-
FGFKPUGTVUQTHQWPFCVKQPDQNVUHQTPGYDQNVUCPFƂZVJG
7/8 (23)
1-5/16 (34)

WPKVƂTON[VQVJGDWKNFKPIUQVJCVKVOC[YKVJUVCPFVJG
mass of the unit.
3-7/16 (88)
4-2/8 (108)

3-7/16 (88)
3-4/8 (89)

In addition, adjust the distance from the ceiling in


advance.

4-1/8 (105) (3) Remove the parts of the indoor unit.


5-9/16 (141) 4GOQXGVJGUWEVKQPITKNNG 4GHGTVQ(KI
7-1/16 (179) r 5NKFGVJGVYQUWEVKQPITKNNGƂZKPIMPQDUVQYCTFKPPGT
direction (as shown by an arrow) lifting upward. At the
same time, have another person lift the tape stuck to
Locations of backward gas piping and drain connection
the center of air outlet.
r 9JGPVJGUWEVKQPITKNNGKUQRGPGFVQCRRTQZKOCVGN[Œ
the grille can be removed from the unit.
4GOQXGVJGEQTPGTEQXGTU
6-6/8 (171)
1-9/16 (39)

2-2/8 (57)
3-7/16 (88)
4-6/8 (120)

4-1/8 (105)
5-3/16 (132)
5-4/8 (140)
Tape
Locations of rightward gas piping and drain connection
Tape
Suction grille

Corner cover at 4 places.


5-9/16 (141)

3-7/16 (88)
2-2/8 (57)
4-6/8 (120)
3-4/8 (89)
3-7/16 (88)

9/16 (14)
7-13/16 (198)

Fig. 6 Fig. 8

3P161684-8T English 4
3P161684-8T

FXUQ-PVJU 19
Installation Manual EDUS391437-F15

Hanger
1.

Hanger
Bend the horizontal
blade and pull it out.
Hanger
Fig. 9

r When carrying the indoor unit, hold it by the hanging metal


ƂVVKPIU (Refer to Fig. 9)
*QYVQDNQEMVJGCKTQWVNGVHQTYC[QTYC[CKT 2.
Claw parts
discharge
r For 2-way air discharge, in addition to the attached block- Turn the horizontal Bearing
blade backward.
ing material, the optional blocking material kit for 2-way
discharge is required.
The attached blocking material and the optional blocking Lift the claw on
the bearing
material for 2-way discharge can be used in common for
side.
any air outlet.
r For 2-way air discharge, take precautions with the inclina-
tion of the indoor unit when installing. For details, follow Remove the
horizontal
the instruction mentioned in the section “+056#..#- blade.
TION OF THE INDOOR UNIT”.
  Remove the horizontal blade of the air outlet to be
DNQEMGF 4GHGTVQ(KICPF(KI
 Without applying force to the bearings, lift the horizontal
blade with both hands and remove it from the bearing at
the side of the motor not mounted.
Claw (Lift upward.)
 After turning the horizontal blade backward, remove
the claw of the bearing on the motor side. Then, lift the
horizontal blade and remove it. Horizontal blade
*

Bearing

1. * When the horizontal blade is difficult to remove, slowly


push down the horizontal blade in the direction of this
arrow. The horizontal blade will become easier to remove.

Fig. 11

Horizontal blade   Fix the blocking material to the air outlet.


2.
Bend the horizontal Motor 4GHGTVQ(KICPF(KI 
blade and remove it.
 Insert the projected part (2 places) of the blocking mate-
Fig. 10 rial into the clearance between the upper decoration
panel and the insulation.
 Insert the bent part (2 places) at both ends of the block-
ing material into the clearance between the lower deco-
ration panel and the drain pan until you hear a clicking
sound.
When doing this work, lift the end of the lower decora-
tion panel slightly and insert the blocking material.
+HKVKUFKHƂEWNVVQKPUGTVKVƂTUVNQQUGPVJGUETGYUQPVJG
both sides of the lower decoration panel and then insert
it.
3. Insert the bent part (2 places) inside the blocking mate-
rial into the clearance between the lower decoration
panel and the drain pan until you hear a clicking sound,
CPFVJGPƂZVJGDNQEMKPIOCVGTKCN

5 3P161684-8T English
3P161684-8T

20 FXUQ-PVJU
EDUS391437-F15 Installation Manual

 Check that the sheet metal section of the blocking ma-
terial is not protruding from the end of the lower decora- 1.
tion panel.
Blocking material
Insert
Securely fix the blocking material and the indoor unit
so that no clearance remains. Insert
If clearance remains, it may cause air leakage and
condensation.
Projected part
Insulation
Drain pan Upper decoration
panel
Lower decoration panel

Insulation
2. Lift this part slightly.
(Other side also.)
2.

1.
Lower decoration
panel
Projected part
3.
Blocking material
2. Insert the bent part.
(Until you hear a cliking
Projected part 1.
Upper decoration panel sound.)

Fig. 12

Lower decoration
3. Bent part of panel
blocking material

Blocking material

Drain pan

Insert Clearance between


lower decoration
panel and drain pan

Insert so that the sheet metal


section does not protrude from the
end of the lower decoration panel.

Fig.13

3P161684-8T English 6
3P161684-8T

FXUQ-PVJU 21
Installation Manual EDUS391437-F15

* If the blocking material is difficult to insert, loosen the left (3) Check the level of the unit from 2 directions (air outlet 1
and right screws of the lower decoration panel and insert it. and 2 ). 4GHGTVQ(KI
Make sure to tighten the loosened screws again after the
DNQEMKPIOCVGTKCNKUHKZGF 4GHGTVQ(KI Nut Hanging bolt
(Field supply)
Lower decoration panel

Hanger

Washer for hanger (3)


(accessory)
Tighten
Nut (Field supply)

Screw To fix hanger
Screw
Fig.15

< Screw location of piping >


Washer clamp (5) Upper nut
(accessory)
Lower decoration panel

Insert

Screw

Washer fixing method


Screw Fig.16

< Screw location other than piping part >


Piping part
Fig.14 4
3

 INSTALLATION OF THE INDOOR UNIT


<<It is easy to attach the optional parts before installing
the indoor unit. Refer to also the installation manual at- 1
tached to the optional parts.>>
2
For installation, use the attached installation parts and
specified parts.
  Attach the upper and lower nuts and the washers for the Fig.17
hanger (3) to the 4 hanging bolts. 4GHGTVQ(KI
If the attached washer clamp (5) are used, the washer for Piping part
the hanger (3) can be prevented from falling off.
4GHGTVQ(KI 4 3

  Installation of indoor unit. 4GHGTVQ(KI


r Insert the hangers on the air outlet 4 side and hang
them tentatively.
r Insert the remaining 2 hanging bolts into the hanger 2
CPFƂZVJGWPFGTUKFGYCUJGTUHQTVJGJCPIGT  CPF 1
the nuts. Level

Level must be ensured


Fig.18

7 3P161684-8T English
3P161684-8T

22 FXUQ-PVJU
EDUS391437-F15 Installation Manual

r Install the indoor unit leveled. Refrigerant piping can be connected from 3 directions.
If the unit is inclined and the drain piping side gets high, r In case of upward piping, remove the piping penetration
KVOC[ECWUGOCNHWPEVKQPQHCƃQCVUYKVEJCPFTGUWNVUKP cover, make holes for penetrating piping by cutting the
water leakage. cover with a cutter such as scissors.
However, for 2-way air discharge, install the unit in- After having the piping go through the cover, attach the
ENKPGFŒFQYPYCTFVQVJGFTCKPRKRKPI cover to the indoor unit. 4GHGTVQ(KI
r Attach nuts on the upper and lower side of hanger.
If there is no upper nut and the lower nut is over-tight- Electric wiring Piping penetration cover
ened, the hanging plate and the top plate will deform
and cause abnormal sound.
r &QPQVKPUGTVOCVGTKCNUQVJGTVJCPVJCVURGEKƂGFKPVQ
the clearance between the hanger and the washer for
hanger (3).
Drain Gas
Unless the washers are properly attached, the hanging
bolts may come off from the hanger. Liquid

WARNING Fig.19
The indoor unit must be securely installed on a
place that can withstand the mass. r The refrigerant is pre-charged in the outdoor unit.
+HVJGUVTGPIVJKUKPUWHƂEKGPVVJGWPKVOC[HCNNFQYPCPF r 7UGVJGƃCTGPWVCVVCEJGFVQVJGCKTEQPFKVKQPGT
cause injuries. r 9JGPOCMKPICƃCTGEQPPGEVKQPEQCVVJGƃCTGFKPPGT
surface only with either oil or ester oil. 4GHGTVQ(KI
6JGPVWTPVJGƃCTGPWVVQVKOGUYKVJ[QWTJCPFCPF
5. REFRIGERANT PIPING WORK screw in the nut.

r For the outdoor unit refrigerant piping, refer to the installa- Coat the flared inner surface only with
either oil or ester oil.
tion manual attached to the outdoor unit.
r Carry out insulation of both gas and liquid refrigerant piping
securely. If not insulated, it may cause water leakage. For
gas piping, use insulation material of which heat resistant
VGORGTCVWTGKUPQVNGUUVJCPŒ( Œ% 
For use under high humidity, strengthen the insulation ma- Fig. 20
terial for refrigerant piping. If not strengthened, the surface
of insulation material may sweat. CAUTION
r Before installation work, make sure that the refrigerant is &QPQVJCXGQKNCFJGTGVQVJGUETGYƂZKPIRCTVQHTGUKP
R410A. (Unless the refrigerant is R410A, the normal opera- parts
VKQPECPPQVDGGZRGEVGF If oil adheres, it may weaken the strength of screwed part.

CAUTION r When connecting the piping to the air conditioner, make


This air conditioner is a dedicated model for new re- sure to use a spanner and a torque wrench as shown in
HTKIGTCPV4#/CMGUWTGVQOGGVVJGTGSWKTGOGPVU (KI.
shown below and carry out installation work. (QTVJGFKOGPUKQPQHƃCTGFRCTVCPFVJGVKIJVGPKPI
r 7UGFGFKECVGFRKRKPIEWVVGTUCPFƃCTKPIVQQNUHQT torque, refer to the Table 1.
4#
r 9JGPOCMKPICƃCTGEQPPGEVKQPEQCVVJGƃCTGFKP- Torque wrench
ner surface only with either oil or ester oil.
r 7UGQPN[VJGƃCTGPWVUCVVCEJGFVQVJGCKTEQPFKVKQP-
Back up wrench
GT+HQVJGTƃCTGPWVUCTGWUGFKVOC[ECWUGTGHTKIGT-
ant leakage.
r To prevent contamination or moisture from getting
into the piping, take measures such as pinching or Flare nut
taping the piping.
&QPQVOKZUWDUVCPEGQVJGTVJCPVJGURGEKƂGFTGHTKI-
erant such as air into the refrigeration circuit.
Union joint Fig. 21
If the refrigerant leaks during the work, ventilate the
room.

<<Example of unfavorable consequences>>


When tools other than spanners are used, the thread ridge
of a flare nut will be damaged and cause gas leakage due
to defective tightening.

3P161684-8T English 8

3P161684-8T

FXUQ-PVJU 23
Installation Manual EDUS391437-F15

Table 1 r After leak test, referring to (KI, insulate both the


Piping Tightening Dimension for gas and liquid piping connection with the attached joint
size torque RTQEGUUKPIƃCTG Flare shape insulating material (6) and (7) to prevent the piping from
[in. (mm)] [lbf·ft. (N·m)] A [in. (mm)] IGVVKPIGZRQUGF
I 1/4 10.4 – 12.7 0.342 – 0.358 Then, tighten the both ends of insulating material with


(6.4) (15.7±1.5) (8.9±0.2) the clamp (4).

°±
45
I 3/8 24.1 – 29.4 0.504 – 0.520
(9.5) (36.3±3.6) (13.0±0.2) R0.016-0.031 Liquid side piping insulating method

90°±2°
I 1/2 36.5 – 44.5 0.638 – 0.654
Flare nut connection Joint insulating material (7) (accessory)
(12.7)

A
(54.9±5.4) (16.4±0.2)
I 5/8 45.6 – 55.6 0.760 – 0.776 Piping insulating material (unit side)
Bring the seam to
(15.9) (68.6±6.8) (19.5±0.2)
the top Do not leave clearance

CAUTION
&QPQVVKIJVGPƃCTGPWVUVQQVKIJV Piping insulating
Clamp (4) (accessory)
+HCƃCTGPWVETCEMUVJGTGHTKIGTCPVOC[NGCM material
(field supply) Tighten the section where
the piping insulating
r If there is no torque wrench, use Table 2 as a rule of For prevention of material and the joint
thumb. condensate, do not insulating material (7)
9JGPVKIJVGPKPICƃCTGPWVYKVJCURCPPGTJCTFGTCPF expose the piping overlap.
harder, there is a point where the tightening torque sud-
denly increases. Sealing material
From that position, tighten the nut additionally the angle Wrap the sealing (Small) (9)
material from the root (accessory)
shown in Table 2. of the unit to the part
#HVGTVJGYQTMKUƂPKUJGFEJGEMUGEWTGN[VJCVVJGTGKUPQ of flare nut connection
gas leak.
If the nut is not tightened as instructed, it may cause
slow refrigerant leak and result in malfunction (such as Liquid piping
does not cool or heat).
Table 2
Piping size Tightening Recommended arm length of
[in. (mm)] angle tool used
I 1/4 (6.4) ŒsŒ #RRTQZKP OO
I 3/8 (9.5) ŒsŒ #RRTQZKP OO
I 1/2 (12.7) ŒsŒ #RRTQZKP OO Gas piping
I 5/8 (15.9) ŒsŒ #RRTQZKP OO

CAUTION Gas side piping insulating method

+PUWNCVKQPQHƂGNFRKRKPIOWUVDGECTTKGFQWVWRVQVJG Flare nut connection Joint insulating material (6) (accessory)


connection inside the casing.
Piping insulating material (unit side)
+HVJGRKRKPIKUGZRQUGFVQVJGCVOQURJGTGKVOC[ECWUG Bring the seam to
sweating, burn due to touching the piping, electric shocks the top Do not leave clearance
QTCƂTGFWGVQVJGYKTKPIVQWEJKPIVJGRKRKPI

Piping insulating
Clamp (4) (accessory)
material
(field supply) Tighten the section where
the piping insulating
For prevention of material and the joint
condensate, do not insulating material (6)
expose the piping overlap.

Sealing material
Wrap the sealing (Small) (9)
material from the root (accessory)
of the unit to the part
of flare nut connection

Fig. 22
r Wrap the sealing material (Small) (9) around the joint
insulating material (6) (7).
r Make sure to bring the seam of joint insulating material
(6) and (7) to the top.

9 3P161684-8T English
3P161684-8T

24 FXUQ-PVJU
EDUS391437-F15 Installation Manual

r When carrying out upward and rightward piping, use the NOTE
attached L-shaped piping, and insulate the 2 places of  6JGRTQRGTRTGUUWTGHQTJCXKPIPKVTQIGPƃQYVJTQWIJVJG
connection. 4GHGTVQ(KI RKRKPIKUCRRTQZKOCVGN[RUK /2C CRTGUUWTG
+PCFFKVKQPDGPFVJGNKSWKFUKFGƂGNFRKRKPIWUKPIC that makes one feel like breeze and can be obtained
bender with radius is 1-9/16 in. (40 mm) or less. through a pressure reducing valve.
If the attached L-shaped piping is not used or the piping
 &QPQVWUGƃWZYJGPDTC\KPITGHTKIGTCPVRKRKPI
is bent with a bender with radius more than 1-9/16 in.
7UGRJQURJQTEQRRGTDTC\KPIƂNNGTOGVCN $%W2,+5<
|OO KVOC[KPVGTHGTGYKVJQVJGTRKRKPIQTFTCKPJQUG
3264/B-Cu93P-710/795: ISO 3677) that does not require
ƃWZ
+HEJNQTKPCVGFƃWZKUWUGFVJGRKRKPIYKNNDGEQTTQFGFCPF
KHƃWQTKPGKUEQPVCKPGFVJGTGHTKIGTCPVQKNYKNNDGFGVGTKQ-
rated and the refrigerant circuit damaged.
3. When carrying out leakage test of refrigerant piping
and the indoor unit after the installation of indoor unit is
ƂPKUJGFEQPƂTOVJGEQPPGEVKPIQWVFQQTWPKVKPUVCNNCVKQP
manual for test pressure.
Refer to also the outdoor unit installation manual or tech-
nical document for refrigerant piping.
Insulate the piping in the same manner as
shown in Fig. 22 using the attached joint  In case of refrigerant shortage due to forgetting addi-
insulating material (6). tional refrigerant charge, it will result in malfunction such
as not heating or cooling.
Refer to the outdoor unit installation manual or technical
For upward and rightward piping document for refrigerant piping.
L-shaped piping insulating method
CAUTION
Piping insulating material
(field supply) Do not use antioxidant when brazing piping.
To prevent sweating, do not
It may result in malfunction of components and clogging of
expose the piping to the piping due to residue.
atmosphere. Flare nut
connection
Joint insulating material (6) 6. DRAIN PIPING WORK
(accessory) L-shaped
piping (13)   Carry out drain piping.
Clamp (4) (accessory) Carry out drain piping so that drainage can ensured.
r Drain piping can be connected from 3 directions.
Tighten the section where the piping insulating material and the 4GHGTVQ(KICPF
joint insulating material (6) overlap.
Sealing material (Large) (8)
Fig. 23 (accessory)

(e.g. Insulate the piping in the same manner for


upward and rightward piping.) Elbow (10) (accessory)

To prevent small animals and insects getting into the


KPFQQTWPKVOCMGUWTGVQVKIJVN[ƂVVJGRKRKPIRGPGVTCV- Metal clamp (2)
ing cover to the casing and seal the clearance between (accessory)
the piping and the hole with putty and insulating material
ƂGNFUWRRN[ 
r $GHQTGDTC\KPITGHTKIGTCPVRKRKPIJCXGPKVTQIGPƃQY
through the refrigerant piping and substitute air with
nitrogen (NOTE 1). 4GHGTVQ(KI Then, carry out Fig. 25
brazing (NOTE 2). (Upward piping) Shorter side
#HVGTCNNVJGDTC\KPIYQTMUCTGƂPKUJGFECTT[QWVƃCTG
connection with the indoor unit. 4GHGTVQ(KI

Pressure reducing valve


Brazing
place Taping

Nitrogen
Nitrogen
Refrigerant piping Stop valve
Fig. 24

3P161684-8T English 10
3P161684-8T

FXUQ-PVJU 25
Installation Manual EDUS391437-F15

If drain stagnates in the drain piping, the piping may be


clogged.
Metal clamp (2) r Install supports at a distance of 3 to 5 feet (1 to 1.5 m) so
(accessory) that the piping does not get clogged. 4GHGTVQ(KI
Drain hose (1)
(for connection to VP20)
Elbow (10) (accessory)
(accessory) Drain piping Support
Longer side (field supply) Ceiling slab
Distance 3-5 ft. (1-1.5 m)
Sealing material (Large) (8)

(600 mm)
Fig. 26

23-5/8 in.
(Backward piping) (accessory) Riser
VP20
VP20

Elbow (10) (accessory)

Metal clamp (2) Metal clamp (2) (accessory)


(accessory) OK

Drain piping
Drain hose (1)
(accessory) Riser

Sealing material (Large) (8)


(accessory)
Elbow
Fig. 27
(Rightward piping) Not acceptable

r 5GNGEVVJGRKRKPIFKCOGVGTGSWCNVQQTNCTIGTVJCP GZ-
Fig. 29
cept for riser) that of the connection piping (polyvinyl (Caution for upward drain piping)
chloride piping, nominal diameter 13/16 in. (20mm),
outside diameter 1 in. (26mm). Make sure to use the attached drain hose (1) (for right-
r Install the drain piping as short as possible with down- ward piping), the elbow (10) (for upward and backward
ward inclination of 1/100 or more and without where air piping) and metal clamp (2).
may stagnate. 4GHGTVQ(KI
(It may cause an abnormal bubbling sound.) If an old drain hose or an elbow or a clamp is used, it
may cause water leakage.
Downward inclination of 1/100 or more
r Insulate the piping that goes through indoors.
CAUTION
r To avoid damaging the attached drain hose (1), do not
bend nor twist it.
OK r Do not connect the drain piping directly to sewage emit-
ting an ammonia odor.
The ammonia in the sewage may go through the drain
RKRKPICPFEQTTQFGVJGJGCVGZEJCPIGTQHVJGKPFQQTWPKV
Not acceptable
< Caution to be taken when carrying out upward drain
piping >
Fig. 28
r 6JGOCZKOWOJGKIJVQHVJGFTCKPTKUGTKUKP
|OO 
r Install the drain riser vertically. 4GHGTVQ(KI

11 3P161684-8T English
3P161684-8T

26 FXUQ-PVJU
EDUS391437-F15 Installation Manual

If the drain riser is installed inclined, the float switch < In case of bending the tip >
may malfunction and cause water leakage.
Tightened part
r Make sure to use the drain hose (1), the elbow (10) and
the sealing material (Large) (8) attached to the indoor
unit as accessories.

approx.
90°
 To prevent the elbow from getting damaged by the
metal clamp (2) for upward and backward piping,
wrap the vinyl tape around the elbow 2 to 3 times so
that the tape covers more than the width of metal
clamp (2) leaving 3/8 - 5/8 in. (10 - 15 mm) from the Bend the tip without tearing
tip of the elbow (10) without wrapping as shown in the sealing material (Large) (8).
(KI.
Fig. 32-1
For upward piping : shorter side (Section A - A of Fig. 31)
For backward piping : longer side
< In case of sticking vinyl tape >
3/8-5/8 in.
(10-15 mm) Tightened part

Elbow (10) (accessory)

approx.
90°
Vinyl
tape

Vinyl tape Stick vinyl tape without


Wrap with the width (approx. 13/16 in. tearing the sealing material
(20mm)) larger than metal clamp (2). (Large) (8).
Fig. 30

 Insert the drain hose (1) and the elbow (10) to the Fig. 32-2
root of the drain socket. Tighten the metal clamp (2) (Section A - A of Fig. 31)
within the taped range of hose inserted tip with the
torque 1.00±0.11 lbf·ft. (1.35±0.15 N·m).  Insulate the metal clamp (2), the drain hose (1), the
4GHGTVQ(KICPF elbow (10) with the attached sealing material (Large)
(8). 4GHGTVQ(KICPF
Insert without leaving any clearance The metal clamp (2) causes condensation.
Indoor unit (Drain socket) Drain hose (1) Metal clamp (2)
Taped part (accessory) (accessory)

Drain hose (1) (accessory) Sealing material (8)


(accessory)

Wrap the sealing


Start wrapping from
material so that the
Metal clamp (2) (accessory) where the clamp is
clamp end side may be
tightened.
doubled.
Fix the metal clamp (2) so that the screw
head faces downward. Fig. 31 Fig. 33

r Do not tighten the metal clamp (2) with the torque more
VJCPVJGURGEKƂGFXCNWG
The socket, the drain hose (1), the elbow (10) or the
metal clamp (2) may be damaged.
(KZVJGOGVCNENCOR  UQVJCVVJGVKIJVGPGFRCTVOC[DG
in the range shown by (KI.
3. Wrap the vinyl tape around the end of the metal
clamp (2) so that the sealing material (large) (8) to
DGWUGFCVVJGPGZVRTQEGUUOC[PQVDGFCOCIGF
with the clamp end or bend the tip of the metal
clamp (2) inward as shown. 4GHGTVQ(KI

3P161684-8T English 12
3P161684-8T

FXUQ-PVJU 27
Installation Manual EDUS391437-F15

  #HVGTRKRKPIKUƂPKUJGFEJGEMKHVJGFTCKPƃQYU 3. )TCFWCNN[RQWTICN |. QHYCVGTHTQOVJGCKT


smoothly. outlet (3) into the drain pan (KI giving caution
=9JGPVJGGNGEVTKEYKTKPIYQTMKUƂPKUJGF? to avoid splashing water on the electric components
r )TCFWCNN[RQWTICN |. QHYCVGTHTQOVJGCKTQWVNGV such as drain pump.
(3) into the drain pan (KI giving caution to avoid If the air outlet (3) is closed, pour water from the air
splashing water on the electric components such as outlet (2).
FTCKPRWORCPFEQPƂTOFTCKPCIGD[QRGTCVKPIVJG  When the power supply is turned on, the drain pump
indoor unit under cooling mode according to “9. FIELD will operate. Check drainage.
SETTING AND TEST OPERATION”. (The drain pump will automatically stop after 10
If the air outlet (3) is closed, pour water from the air minutes.)
outlet (2). 5. Turn off the power supply after checking drainage,
Drain outlet for service (with rubber plug) and remove the power supply wiring.
(Use it when draining water in the drain pan) 6. #VVCEJVJGEQPVTQNDQZNKFCUDGHQTG

(3)
(4)  ELECTRIC WIRING WORK

 GENERAL INSTRUCTIONS


r Make certain that all electric wiring work is carried out by
SWCNKƂGFRGTUQPPGNCEEQTFKPIVQVJGCRRNKECDNGNGIKUNCVKQP
(1)
(2) Location of drain pump
and this installation manual, using a separate dedicated
and float switch circuit.
+PUWHƂEKGPVECRCEKV[QHVJGRQYGTUWRRN[EKTEWKVQTKORTQRGT
GNGEVTKECNEQPUVTWEVKQPOC[NGCFVQGNGEVTKEUJQEMUQTCƂTG
Plastic container for pouring water
(Tube length of 4 in. (100 mm) is necessary) r Make sure to install a ground leakage breaker.
(CKNWTGVQFQUQOC[ECWUGGNGEVTKECNUJQEMUCPFCƂTG
(How to pour water) r Do not turn on the power supply (branch switch, branch
Fig. 34 QXGTEWTTGPVDTGCMGT WPVKNCNNVJGYQTMUCTGƂPKUJGF
r Multiple number of indoor unit are connected to one out-
=9JGPVJGGNGEVTKEYKTKPIYQTMKUPQVƂPKUJGF? door unit. Name each indoor unit as A-unit, B-unit ….. and
r The electric wiring works (including grounding) must the like. When these indoor units are wired to the outdoor
DGECTTKGFQWVD[CSWCNKƂGFGNGEVTKEKCP unit and the Branch Selector unit, always wiring the indoor
r +HCSWCNKƂGFRGTUQPKUPQVRTGUGPVCHVGTVJGGNGEVTKE unit to the terminal indicated with the same symbol on the
YKTKPIYQTMKUƂPKUJGFEJGEMVJGFTCKPCIGCEEQTFKPI terminal block. If the wiring and the piping are connected
VQVJGOGVJQFURGEKƂGFKP[When the electric wiring to the different indoor units and operated, it will result in
YQTMKUƂPKUJGF?. malfunction.
 1RGPVJGEQPVTQNDQZNKFCPFEQPPGEVVJGUKPING r Make sure to ground the air conditioner. Grounding resis-
phase power supply to the terminal (L1, L 2) on the tance should be according to applicable legislation.
terminal block (X2M). r Do not connect the ground wiring to gas or water piping,
Connect the ground wiring to the ground terminal. lightning conductor or telephone ground wiring.
(Refer to Fig. 35) r Gas piping .................+IPKVKQPQTGZRNQUKQPOC[QEEWTKH
Power supply terminal block the gas leaks.
(X2M) r Water piping ..............Hard vinyl tubes are not effective
grounds.
Power supply terminal block r Lightning conductor or telephone ground wiring .............
(X2M)
.................................Electric potential may rise abnor-
mally if struck by a lightning bolt.
r For electric wiring work, refer to also the “WIRING DIA-
)4#/qCVVCEJGFVQVJGEQPVTQNDQZNKF
r Carry out wiring between the outdoor units, indoor units
L1 L 2 and the remote controllers according to the wiring diagram.
r Carry out installation and wiring of the remote controller ac-
cording to the “installation manual” attached to the remote
Ground terminal
controller.
Power supply
single phase r Do not touch the Printed Circuit Board assembly. It may
208/230 V cause malfunction.
60 Hz Fig. 35

 /CMGUWTGVJGEQPVTQNDQZNKFKUENQUGFDGHQTGVWTP-
ing on the power supply.

13 3P161684-8T English
3P161684-8T

28 FXUQ-PVJU
EDUS391437-F15 Installation Manual

 ELECTRICAL CHARACTERISTICS Connection of 2 Connection of 2 Connection of


wirings of same wirings on one side wiring of different
Indoor units Power supply Fan motor size must be is prohibited. sizes is prohibited.
Voltage carried out on both
Model Hz Volts MCA MOP kW FLA
range sides.
FXUQ18PVJU
0.6 15 0.046 0.5
FXUQ24PVJU /CZ
60 208/230
FXUQ30PVJU Min. 187
1.4 15 0.106 1.1
FXUQ36PVJU
MCA: Min. Circuit Amps (A) ; MOP: /CZ1XGTEWTTGPV2TQVGEVKXG&GXKEG #
kW: Fan Motor Rated Output (kW) ; FLA: Full Load Amps (A)
Fig. 37

 SPECIFICATION FOR FIELD SUPPLY FUSES r 7UGVJGTGSWKTGFYKTKPIEQPPGEVVJGOUGEWTGN[CPFƂZ


AND WIRING VJGUGYKTKPIUQVJCVGZVGTPCNHQTEGOC[PQVCRRN[VQVJG
terminals.
Remote controller wiring r Use a proper screw driver for tightening the terminal
Power supply wiring screws.
Transmission wiring
If an improper screw driver is used, it may damage the
MOP screw head and a proper tightening cannot be carried
Size Wiring Size
out.
2-conductor, r If a terminal is over tightened, it may be damaged.
Wiring size and length stranded non- AWG Refer to the table shown below for tightening torque of
15A must comply with local shielded copper 18-16 terminals.
codes. cable PVC/vinyl (0.75-1.25mm2) Tightening torque
jacket (NOTE 2) [lbf·ft. (N·m)]
The lengths of remote controller wiring and transmission wiring Terminal block for remote control- 0.65 ± 0.07
are as follows: ler and transmission wirings (0.88 ± 0.08)
(1) Remote controller wiring (indoor unit - remote controller) Terminal for power supply 0.965 ± 0.095
............................................................../CZHV O Ground terminal (1.31 ± 0.13)
(2) Transmission wirings ... Total wiring length 6,560 ft. (2,000 m) r &QPQVECTT[QWVUQNFGTKPIƂPKUJYJGPUVTCPFGFYKTKPIU
r Outdoor unit - Indoor unit........ /CZHV O are used.
r Outdoor unit - Branch Selector unit ... /CZHV O
r Branch Selector unit - Indoor unit ..... /CZHV O r Power supply wiring, ground wiring
r Indoor unit - Indoor unit .......... /CZHV O 4GOQXGVJGEQPVTQNDQZNKFOCVEJVJGU[ODQNVQVJCV
of the power supply terminal block (X2M) and connect
NOTE the wiring. Connect the ground wiring also to the power
 Shows only in case of protected piping. Use H07RN-F in supply terminal block (X2M). Then, lead the wiring into
case of no protection. the indoor unit through the hole bored on the cover for
 Vinyl cord with sheath or cable (Insulated thickness : penetrating piping according to the section “5. REFRIG-
1/16 in. (1 mm) or more) ERANT PIPING WORK” and bind the wiring with the
clamp (4).
 WIRING CONNECTION METHOD r Remote controller wiring, transmission wiring.
4GHGTVQ(KI Connect the remote controller wiring to [P1 · P2] and
the transmission wiring to [F1 · F2] of the terminal block
CAUTION FOR WIRING (X1M) for remote controller and transmission wiring.
r The indoor units in the same system can be connected Bind the remote controller wiring and the transmission
to the power supply from one branch switch. wiring with the clamp (4).
However, selection of branch switch, branch over cur- r Sticking non woven fabric (15).
rent breaker and wiring size must be according to appli- 6QRTGXGPVYKTKPIHTQOƃQCVKPIUVKEMPQPYQXGPHCDTKE
cable legislation. (15).
r For connection to the terminal block, use ring type crimp
CAUTION
style terminals with insulation sleeve or treat the wiring
with insulation. (Refer to Fig. 36) r Never connect the power supply wiring to the terminal
block for remote controller/transmission wiring (X1M).
Insulation sleeve It may damage the total system.
Wiring
Ring type crimp style terminal r Do not connect the remote controller/transmission wir-
ing to the wrong terminal block.

Fig. 36
r If the above is not available, make sure to observe the
following items.
(Abnormal heating may occur if the wiring are not tight-
ened securely.)

3P161684-8T English 14
3P161684-8T

FXUQ-PVJU 29
Installation Manual EDUS391437-F15

Conduit mounting %QPFWKV ƂGNFUWRRN[


RNCVG  %QPFWKVOQWPVKPIRNCVG 

Tab

Mounting r Make sure to install the conduit


X2M screw (18) OQWPVKPIRNCVGƂTUVDGHQTG
wiring.

Tab of conduit
Conduit mounting mounting plate
RNCVG 
Slot
Insert the tab of conduit
mounting plate to slot.

Power supply wiring · Ground wiring


X1M Transmission wiring
Remote controller wiring
Fig. 38
Bind the power supply wiring and the
ground wiring, and the remote
Non woven fabric (15)
controller and the transmission wiring.

Non woven fabric (15) Insulation tube (16)


sticking reference

Clamp (4) (accessory)


Start sticking from the #HVGTVJGYKTKPICTGƂZGFEWVVJG
radius ending line. GZVTCRCTV

Power supply terminal block (X2M)


0QPYQXGPHCDTKE  UVKEMKPIOGVJQF 
Terminal block for remote
controller/transmission wiring (X1M)
2-1/8 - 3-1/8 in. (60-80 mm)

Ground (Sheath peeling allowance) < Power supply wiring · Ground wiring · Remote
terminal controller wiring · Transmission wiring >

Ground
L1 L2 wiring Ground wiring
Sheathed part of the remote
The part of the wiring controller wiring or the
Power supply shown with “ ” must transmission wiring
wiring Sheathed part be orderly formed so
that they may not be #RRTQZKP OO
tensioned.
After the cover is
< Power supply wiring · Ground wiring > peeled, twist the
wiring.
3/8 - 1-9/16 in.
(10-40 mm)
1-3/16 - 1-3/8 in.
Clamp (4) (accessory)
(30-35 mm)
#HVGTVJGYKTKPICTGƂZGF
EWVVJGGZVTCRCTV (Sheath peeling allowance)
Prohibited
r Do not connect power supply
< Remote controller wiring ·
wiring (high voltage).
Transmission wiring >

15 3P161684-8T English
3P161684-8T

30 FXUQ-PVJU
EDUS391437-F15 Installation Manual

CAUTION FOR MENDING THE COVER 0QU[UVGO9JGPECTT[KPIQWVITQWREQPVTQNQT


remote controllers control >
r In case the cover for penetrating piping is cut off and used
Note: It is not necessary to designate indoor
as wiring penetrating hole, after the wiring connection is
unit address when using group
ƂPKUJGFOGPFVJGEQXGT control. The address is automatically
r Cut the sealing material (Small) (9) into two pieces and set when power is activated.
wrap each wiring with each piece.
r Seal the clearance around the wiring with putty and insulat- Power supply Power supply Power supply Power supply
single phase Outdoor unit single phase single phase single phase
KPIOCVGTKCN ƂGNFUWRRN[  208/230 V Control box 208/230 V 208/230 V 208/230 V
IN/D OUT/D
(If insects and small animals get into the indoor unit, short 60 Hz L1 L2 F1 F2 F1 F2
L1 L2 60 Hz L1 L2 60 Hz L1 L2 60 Hz
EKTEWKVKPIOC[QEEWTKPUKFGVJGEQPVTQNDQZ No. 2
System
r If the low voltage wiring (remote controller wiring, transmis- Most
sion wiring) and the high voltage wiring (power supply wir- downstream
Indoor indoor unit
ing, ground wiring) are brought into the indoor unit from the
unit A
same place, they may be affected by electric noise (outside L2 L1 P1 P2 F1 F2 T1 T2 L2 L1 P1 P2 F1 F2 T1 T2 L2 L1 P1 P2 F1 F2 T1 T2 L2 L1 P1 P2 F1 F2 T1 T2

noise) and cause malfunction or failure. Indoor Indoor


r -GGRVJGFKUVCPEGQHKP |OO DGVYGGPVJG unit B unit C
P1 P2 P1 P2

low voltage wiring (remote controller wiring, transmission P1 P2 For use with 2
remote controllers
wiring) and the high voltage wiring (power supply wiring,
ground wiring) at anywhere outside the indoor unit. (KI
If both the wiring are laid down together, they may be af-
fected by electric noise (outside noise) and cause malfunc- < No.3 system: When Branch Selector unit is used >
tion or failure. Power supply Outdoor unit Power supply
single phase Control box single phase
208/230 V IN/D OUT/D
F1 F2 F1 F2 Branch L1 208/230 V Branch
L2
Seal with putty and insulating 60 Hz L1 L2
Selector unit 60 Hz Selector unit
material. No. 3
Control box Control box
System OUT/D IN/D OUT/D IN/D
F1 F2 F1 F2 F1 F2 F1 F2

Sealing material (Small) (9)

Remote controller/ Indoor unit A Most


L2 L1 P1 P2 F1 F2 T1 T2 L2 L1 P1 P2 F1 F2 T1 T2
downstream
transmission wiring indoor unit

Power supply wiring/


ground wiring P1 P2 P1 P2

Fig. 39 (KI

NOTE
r Remote controller wiring and transmission wiring do not
WARNING have polarity.
r 9JGPYKTKPIHQTOVJGYKTKPIQTFGTN[UQVJCVVJGEQPVTQNDQZ
lid can be securely fastened. WARNING
+HVJGEQPVTQNDQZNKFKUPQVKPRNCEGVJGYKTKPIOC[ƃQCVWR Be sure to install a ground leakage circuit breaker.
QTDGUCPFYKEJGFD[VJGDQZCPFVJGNKFCPFECWUGGNGEVTKE (CKNWTGVQFQUQOC[ECWUGGNGEVTKEUJQEMUCPFCƂTG
UJQEMUQTCƂTG

 WIRING EXAMPLES


0QU[UVGO9JGPTGOQVGEQPVTQNNGTKUWUGFHQT
indoor unit >

Power supply Outdoor unit Power supply Power supply Power supply
single phase Control box single phase single phase single phase
IN/D OUT/D
208/230 VL1 L2 F1 F2 F1 F2
L1 L2 208/230 VL1 L2 208/230 VL1 L2 208/230 V
60 Hz No. 1 60 Hz 60 Hz 60 Hz
System

L2 L1 P1 P2 F1 F2 T1 T2 L2 L1 P1 P2 F1 F2 T1 T2 L2 L1 P1 P2 F1 F2 T1 T2 L2 L1 P1 P2 F1 F2 T1 T2

Indoor Indoor Indoor Most


unit A unit B unit C downstream
P1 P2 P1 P2 P1 P2 indoor unit P1 P2

(KI

3P161684-8T English 16
3P161684-8T

FXUQ-PVJU 31
Installation Manual EDUS391437-F15

 (14%10641.9+6*4'/16'%10641.-  FOR REMOTE CONTROL (FORCED OFF OR


.'45 61%10641.+0&11470+69+6* ON/OFF OPERATION)
REMOTE CONTROLLERS)   9KTKPIOGVJQFCPFURGEKƂECVKQP
r For control with 2 remote controllers, set one remote con- r 4GOQVGEQPVTQNKUCXCKNCDNGD[EQPPGEVKPIVJGGZVGTPCN
troller as main and the other remote controller as sub. input to the terminals T1 and T2 on the terminal block
< Changeover method from main to sub and vice versa > for remote controller and transmission wiring.
Refer to the installation manual attached to the remote
controller.
F2 T1 T2
< Wiring method >
  4GOQXGVJGEQPVTQNDQZNKFCEEQTFKPIVQVJGp9+4-
FORCED
ING CONNECTION METHOD”.
OFF
  Carry out additional wiring from the remote controller
2 (Sub) to the terminals (P1·P2) for remote controller Input A
YKTKPIQPVJGVGTOKPCNDNQEM :/ KPVJGEQPVTQNDQZ
Terminal block (X1M) for 9KTKPIURGEKƂECVKQP Sheathed vinyl cord or 2 core cable
remote controller wiring (P1, P2)
Gauge AWG18-16 (0.75-1.25 mm2)
No polarity Wiring length /CZHV O
'ZVGTPCNEQPVCEV Contact that can make and break the
URGEKƂECVKQP min. load DC15 V, 1 mA

  Actuation
r Input A of FORCED OFF and ON/OFF OPERATION
will be as the table shown below.

In case of FORCED OFF by input Remote controller


FORCED A of “ON” (Remote permitted by input A
OFF controller prohibited) of “OFF”
Remote controller 1 Remote controller 2 In case of
Operation by input A of Stop by input A of
(Main) (Sub) ON/OFF
“OFF” o “ON” “ON” o “OFF”
OPERATION
Fig. 43
< Caution >
(3) How to choose FORCED OFF or ON/OFF OPERA-
When using the group control and the 2 remote controllers
TION
control at the same time, connect the remote controller 2
(Sub) to the indoor unit at the end of the crossover wiring r For choosing FORCED OFF or ON/OFF OPERATION,
(the largest No.). 4GHGTVQ(KI setting by remote controller is required.
(Refer to “9. FIELD SETTING AND TEST OPERATION”)
Indoor unit 1 Indoor unit 2 Indoor unit Largest No.

Remote Crossover wiring Remote


controller 1 (Remote controller) controller 2
(Main) (Sub)
Fig. 44

 FOR CENTRALIZED CONTROL


r When centralized equipment (such as centralized control-
ler) is used for control, it is required to set the group No. on
the remote controller.
For details, refer to the manual attached to the centralized
equipment.
r Connect the centralized equipment to the indoor unit con-
nected to the remote controller.

17 3P161684-8T English
3P161684-8T

32 FXUQ-PVJU
EDUS391437-F15 Installation Manual

 MOUNTING CORNER COVER · SUC- r After attaching the suction grille in opposite order men-
tioned in the clause “3. PREPARATION BEFORE INSTAL-
TION GRILLE LATION - (3)” 4GHGTVQ(KI(1)), hook the strap (a)
(QTVGUVQRGTCVKQPYKVJQWVVJGEQTPGTEQXGTƂTUVTGHGTVQ for preventing the suction grille from falling. (Refer to Fig.
“9. FIELD SETTING AND TEST OPERATION”>> (2))
r For backward and rightward piping outlet, cut the corner r Hook the strap (b) for preventing the suction grille from fall-
cover as shown in (KI and remove it. ing. 4GHGTVQ(KI(3))
(When cutting, give caution and mount on the indoor unit so
that the parts for the corner cover may not fall off.)
Hook the strap on the nearer one
For backward piping outlet
Give caution so
Piping penetrating place that it may not fall
Cut with saw blade. off.
(1 place)
Corner cover
(Piping section)
Corner cover

For rightward piping outlet (2)


(1)
(2)
Piping penetrating place
Strap (a) for
Cut with a saw blade. preventing
Give caution so
the suction grille
that it may not fall
from falling
off.
Hook the strap
Corner cover
(3)

Fig. 45
(3)
r Attach the corner cover to the indoor unit.
6JGPƂZVJGEQTPGTEQXGTYKVJVJGCVVCEJGFUETGYU  
while pressing the corner cover so that the end of the
corner cover and the end of the indoor unit contact together. Strap (b) for
(3 places) preventing
4GHGTVQ(KI
the suction grille
Screw (14) (accessory) Screw (14) (accessory) from falling
Fig. 47

Corner cover Corner cover


9. FIELD SETTING AND TEST OPERATION
Screw (14) <<Refer to also the installation manual attached to the
(accessory) outdoor unit.>>
Indoor unit
CAUTION
$GHQTGECTT[KPIQWVƂGNFUGVVKPIEJGEMVJGKVGOUOGPVKQPGFKP
Have the end of the clause 2 p+VGOUVQDGEJGEMGFCHVGTVJGKPUVCNNCVKQP
the corner cover Corner cover
and the end of work is completed” on page 2.
the indoor unit r Check if all the installation and piping works for the air con-
contact together. Screw (14) (accessory) ditioner are completed.
(all 4 corners) r %JGEMKHVJGEQPVTQNDQZNKFUQHVJGCKTEQPFKVKQPGTCTG
Have the end of the corner cover closed.
and the end of the indoor unit
Corner cover contact together. (all 4 corners)

Fig. 46

3P161684-8T English 18
3P161684-8T

FXUQ-PVJU 33
Installation Manual EDUS391437-F15

C: 3P161684-8T

34 FXUQ-PVJU
EDUS391437-F15 Installation Manual

< TEST OPERATION >


r After cleaning the indoor unit inside and the suction grille,
carry out a test run according to installation manual at-
tached to the outdoor unit.
r 9JGPVJGTGOQVGEQPVTQNNGTQRGTCVKQPNCORƃCUJGUKV
shows that something is abnormal.
Check the malfunction codes on the remote controller.
The relation between the malfunction codes and malfunc-
tion details is described in the operation manual attached to
the outdoor unit.
Particularly, if the indication is one of those shown in the
Table 7, it may be an error in the electrical wiring or the
power supply is disconnected. Therefore, recheck wiring.
Table 7
Remote controller
Details
indication
Though the central-
ized control is not
r The terminals (T1 · T2) for FORCED OFF
on the indoor unit transmission terminal
carried out, the lamp
block is short circuited.
“ ” turns on.
r The power supply to the outdoor unit is not
made.
r The power supply work to the outdoor unit
“U4” turns on is not carried out.
“UH” turns on r The transmission wiring and the remote
controller wiring and FORCED OFF wiring
are incorrectly connected.
r The transmission wiring is disconnected.
r The power supply to the indoor unit is not
made.
r The power supply work to the indoor unit is
not carried out.
No indication r The remote controller wiring and the
transmission wiring and FORCED OFF
wiring are incorrectly connected.
r The remote controller wiring is
disconnected.

CAUTION
After test operation is completed, check the items men-
tioned in the clause 2 “+VGOUVQDGEJGEMGFCVFGNKX-
ery” on page 2.
+HVJGKPVGTKQTƂPKUJYQTMKUPQVEQORNGVGFYJGPVJGVGUV
QRGTCVKQPKUƂPKUJGFHQTRTQVGEVKQPQHVJGCKTEQPFKVKQPGT
ask the customer not operate the air conditioner until the
KPVGTKQTƂPKUJYQTMKUEQORNGVGF
If the air conditioner is operated, the inside of the indoor
units may be polluted by substances generated from the
EQCVKPICPFCFJGUKXGUWUGFHQTVJGKPVGTKQTƂPKUJYQTM
and cause water splash and leakage.

To the operator carrying out test operation


After test operation is completed, before delivering the
CKTEQPFKVKQPGTVQVJGEWUVQOGTEQPƂTOVJCVVJGEQPVTQN
DQZNKFKUENQUGF
+PCFFKVKQPGZRNCKPVJGRQYGTUWRRN[UVCVWU RQYGTUWR-
ply ON/OFF) to the customer.

3P161684-8T English 20
3P161684-8T

FXUQ-PVJU 35
Accessories EDUS391437-F15

12. Accessories
12.1 Optional Accessories (for Unit)
Option Note FXUQ18PVJU FXUQ24PVJU FXUQ30PVJU FXUQ36PVJU
Blocking material kit for 2-way discharge KDBHP49B140
Air outlet blocking decoration panel KDBTP49B140
Replacement long life filter KAFP551K160
3D090253A

12.2 Optional Accessories (for Controls)


Option Note FXUQ18PVJU FXUQ24PVJU FXUQ30PVJU FXUQ36PVJU
Remote controller Wired type BRC1E73
Sensor unit (Sensor kit) 2 BRE49B1F
Central remote controller DCS302C71
Electrical box KJB311AA
Unified ON/OFF controller DCS301C71
Electrical box KJB212AA
Schedule timer DST301BA61
intelligent Touch controller DCS601C71
Group control adaptor printed circuit board 1 KRP4A74
Adaptor mounting box KRP1BA97
Remote sensor 2 KRCS01-4B
DIII-NET expander adaptor DTA109A51
C: 3D090253A

Notes: 1. Adaptor mounting box (KRP1BA97) is necessary.


2. The remote sensor cannot be installed when applying the Sensor unit (Sensor kit).

36 FXUQ-PVJU
EDUS391437-F15 Detail of Optional Accessories

13. Detail of Optional Accessories


13.1 BRE49B1F — Sensor Kit

C: 3D090211

FXUQ-PVJU 37
Detail of Optional Accessories EDUS391437-F15

1P383776-1

38 FXUQ-PVJU
EDUS391437-F15 Detail of Optional Accessories

1P383776-1

FXUQ-PVJU 39
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

Specifications, designs and other content appearing in this brochure are current as of May 2015 but subject to change without notice.

© All rights reserved 05/15 FS

You might also like