Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 19

Subject : INSPECTION TANK Equiptment : OLYMPUS 38DL Sn.

130749310
TAG / Line No. : 35-T-101 Probe : D-790 SM s/n : 1050245
: TANK, CONDENSATE STORAGE Couplant : CMC
Location : GRISSIK GAS PLANT Velocity : 5900 m/s
P & ID. No. : ID-N-GL-PP0-PID-PL-42-0001 REV 4 PMO : 1100172642
Surface Temp. : Ambient Date of Insp. : 02 Agustus 2023
Date of Last Insp. : 25 April 2021

Report of wall thickness measurement


Dimension in mm

NOM. PREV. POINT OF MEASUREMENT SURFACE


PARTS IDENT. MINIMUM REMAKS
THK THK 1 2 3 4 COND
1st Course (Plate #1)
A 8.00 7.56 7.66 7.80 7.89 7.86 7.66 PNT
B 8.00 7.68 7.88 7.81 7.86 7.86 7.81 PNT
C 8.00 7.55 7.96 7.88 7.75 7.79 7.75 PNT
1st Course (Plate #2)
A 8.00 7.27 7.39 7.69 7.89 7.87 7.39 PNT
B 8.00 7.58 7.74 7.69 7.68 7.69 7.68 PNT
C 8.00 7.53 7.67 7.56 7.67 7.86 7.56 PNT
1st Course (Plate #3)
A 8.00 7.59 7.78 7.80 7.69 7.69 7.69 PNT
B 8.00 7.65 7.77 7.69 7.85 7.76 7.69 PNT
C 8.00 7.61 7.72 7.66 7.77 7.86 7.66 PNT
1st Course (Plate #4)
A 8.00 7.40 7.85 7.74 7.75 7.49 7.49 PNT
B 8.00 7.65 7.69 7.86 7.79 7.69 7.69 PNT
C 8.00 7.61 7.67 7.77 7.77 7.88 7.67 PNT
1st Course (Plate #5)
A 8.00 7.72 7.76 7.77 7.72 7.71 7.71 PNT
B 8.00 7.6 7.82 7.81 7.82 7.62 7.62 PNT
C 8.00 7.75 7.81 7.80 7.82 7.80 7.80 PNT
1st Course (Plate #6)
A 8.00 7.62 7.69 7.70 7.67 7.87 7.67 PNT
B 8.00 7.65 7.73 7.68 7.71 7.89 7.68 PNT
C 8.00 7.68 7.76 7.88 7.69 7.73 7.69 PNT

Inspected by, Reviewed by,


PT. GAMMA BUANA PERSADA MEDCO E&P (GRISSIK) Ltd
ASNT UT LEVEL II QA/QC

( DONNY CT /M ABDILLAH ) ( DARMA BALEN/ NOOR WAHAB )


Date : AUGUST 02, 2023 Date : AUGUST 02, 2023
Note:
Sm: Smooth Br: Buried RDM: Random
Ro: Rough Ug: Underground Ins: Insulated
Pnt: Painted
Subject : INSPECTION TANK Equiptment : OLYMPUS 38DL Sn. 130749310
TAG / Line No. : 35-T-101 Probe : D-790 SM s/n : 1050245
: TANK, CONDENSATE STORAGE Couplant : CMC
Location : GRISSIK GAS PLANT Velocity : 5900 m/s
P & ID. No. : ID-N-GL-PP0-PID-PL-42-0001 REV 4 PMO : 1100172642
Surface Temp. : Ambient Date of Insp. : 02 Agustus 2023
Date of Last Insp. : 25 April 2021

Report of wall thickness measurement


Dimension in mm

NOM. PREV. POINT OF MEASUREMENT SURFACE


PARTS IDENT. MINIMUM REMAKS
THK THK 1 2 3 4 COND
2nd Course (Plate #1)
A 8.00 - 6.46 6.54 6.54 6.47 6.46 PNT
B 8.00 - 6.50 6.48 6.51 6.55 6.48 PNT
C 8.00 6.49 6.46 6.43 6.44 6.53 6.43 PNT
2nd Course (Plate #2)
A 8.00 - 6.65 6.57 6.65 6.68 6.57 PNT
B 8.00 - 6.72 6.74 6.69 6.70 6.69 PNT
C 8.00 6.42 6.68 6.75 6.73 6.74 6.68 PNT
2nd Course (Plate #3)
A 8.00 - 6.41 6.45 6.49 6.31 6.31 PNT
B 8.00 - 6.47 6.32 6.42 6.40 6.32 PNT
C 8.00 6.68 6.28 6.31 6.47 6.31 6.28 PNT
2nd Course (Plate #4)
A 8.00 - 6.51 6.55 6.46 6.43 6.43 PNT
B 8.00 - 6.42 6.40 6.47 6.32 6.32 PNT
C 8.00 6.60 6.45 6.49 6.41 6.45 6.41 PNT
2nd Course (Plate #5)
A 8.00 - 6.48 6.51 6.65 6.57 6.48 PNT
B 8.00 - 6.50 6.51 6.50 6.54 6.50 PNT
C 8.00 6.62 6.46 6.44 6.46 6.48 6.44 PNT
2nd Course (Plate #6)
A 8.00 - 6.65 6.46 6.54 6.48 6.46 PNT
B 8.00 - 6.69 6.48 6.47 6.32 6.32 PNT
C 8.00 6.58 6.73 6.43 6.43 6.44 6.43 PNT

Inspected by, Reviewed by,


PT. GAMMA BUANA PERSADA MEDCO E&P (GRISSIK) Ltd
ASNT UT LEVEL II QA/QC

( DONNY CT /M ABDILLAH ) ( DARMA BALEN/ NOOR WAHAB )


Date : AUGUST 02, 2023 Date : AUGUST 02, 2023
Note:
Sm: Smooth Br: Buried RDM: Random
Ro: Rough Ug: Underground Ins: Insulated
Pnt: Painted
Subject : INSPECTION TANK Equiptment : OLYMPUS 38DL Sn. 130749310
TAG / Line No. : 35-T-101 Probe : D-790 SM s/n : 1050245
: TANK, CONDENSATE STORAGE Couplant : CMC
Location : GRISSIK GAS PLANT Velocity : 5900 m/s
P & ID. No. : ID-N-GL-PP0-PID-PL-42-0001 REV 4 PMO : 1100172642
Surface Temp. : Ambient Date of Insp. : 02 Agustus 2023
Date of Last Insp. : 25 April 2021

Report of wall thickness measurement


Dimension in mm

NOM. PREV. POINT OF MEASUREMENT SURFACE


PARTS IDENT. MINIMUM REMAKS
THK THK 1 2 3 4 COND
3rd Course (Plate #1)
A 6.00 - 5.64 5.65 5.49 5.56 5.49 PNT
B 6.00 - 5.56 5.55 5.54 5.40 5.40 PNT
C 6.00 - 5.47 5.44 5.54 5.51 5.44 PNT
3rd Course (Plate #2)
A 6.00 - 5.45 5.42 5.42 5.45 5.42 PNT
B 6.00 - 5.42 5.50 5.42 5.49 5.42 PNT
C 6.00 - 5.46 5.45 5.42 5.56 5.42 PNT
3rd Course (Plate #3)
A 6.00 - 5.82 5.75 5.80 5.85 5.75 PNT
B 6.00 - 5.82 5.75 5.80 5.85 5.75 PNT
C 6.00 - 5.42 5.50 5.42 5.76 5.42 PNT
3rd Course (Plate #4)
A 6.00 - 5.72 5.76 5.76 5.75 5.72 PNT
B 6.00 - 5.42 5.75 5.42 5.82 5.42 PNT
C 6.00 - 5.74 5.82 5.80 5.85 5.74 PNT
3rd Course (Plate #5)
A 6.00 - 5.82 5.75 5.80 5.50 5.50 PNT
B 6.00 - 5.42 5.50 5.42 5.50 5.42 PNT
C 6.00 - 5.42 5.50 5.80 5.42 5.42 PNT
3rd Course (Plate #6)
A 6.00 5.34 5.75 5.75 5.76 5.82 5.75 PNT
B 6.00 5.32 5.82 5.75 5.80 5.82 5.75 PNT
C 6.00 5.21 5.85 5.50 5.80 5.42 5.42 PNT

Inspected by, Reviewed by,


PT. GAMMA BUANA PERSADA MEDCO E&P (GRISSIK) Ltd
ASNT UT LEVEL II QA/QC

( DONNY CT /M ABDILLAH ) ( DARMA BALEN/ NOOR WAHAB )


Date : AUGUST 02, 2023 Date : AUGUST 02, 2023
Note:
Sm: Smooth Br: Buried RDM: Random
Ro: Rough Ug: Underground Ins: Insulated
Pnt: Painted
Subject : INSPECTION TANK Equiptment : OLYMPUS 38DL Sn. 130749310
TAG / Line No. : 35-T-101 Probe : D-790 SM s/n : 1050245
: TANK, CONDENSATE STORAGE Couplant : CMC
Location : GRISSIK GAS PLANT Velocity : 5900 m/s
P & ID. No. : ID-N-GL-PP0-PID-PL-42-0001 REV 4 P & ID. No. : 1100172642
Surface Temp. : Ambient Date of Insp. : 02 Agustus 2023
Date of Last Insp. : 25 April 2021

Report of wall thickness measurement


Dimension in mm

NOM. PREV. POINT OF MEASUREMENT SURFACE


PARTS IDENT. MINIMUM REMAKS
THK THK 1 2 3 4 COND
4th Course (Plate #1)
A 6.00 - 5.72 5.77 5.76 5.77 5.72 PNT
B 6.00 - 5.42 5.50 5.42 5.76 5.42 PNT
C 6.00 - 5.74 5.77 5.80 5.85 5.74 PNT
4th Course (Plate #2)
A 6.00 - 5.85 5.82 5.75 5.79 5.75 PNT
B 6.00 - 5.76 5.87 5.81 5.81 5.76 PNT
C 6.00 - 5.82 5.79 5.77 5.71 5.71 PNT
4th Course (Plate #3)
A 6.00 - 5.75 5.76 5.76 5.76 5.75 PNT
B 6.00 - 5.82 5.75 5.80 5.85 5.75 PNT
C 6.00 - 5.85 5.82 5.80 5.85 5.80 PNT
4th Course (Plate #4)
A 6.00 - 5.78 5.76 5.68 5.66 5.66 PNT
B 6.00 - 5.72 5.77 5.76 5.78 5.72 PNT
C 6.00 - 5.74 5.77 5.80 5.73 5.73 PNT
1st Course (Plate #5)
A 6.00 - 5.80 5.71 5.76 5.77 5.71 PNT
B 6.00 - 5.85 5.82 5.75 5.76 5.75 PNT
C 6.00 - 5.82 5.79 5.77 5.85 5.77 PNT
4th Course (Plate #6)
A 6.00 5.34 5.80 5.90 5.79 5.82 5.79 PNT
B 6.00 5.36 5.76 5.87 5.81 5.83 5.76 PNT
C 6.00 5.26 5.62 5.75 5.71 5.76 5.62 PNT

Inspected by, Reviewed by,


PT. GAMMA BUANA PERSADA MEDCO E&P (GRISSIK) Ltd
ASNT UT LEVEL II QA/QC

( DONNY CT /M ABDILLAH ) ( DARMA BALEN/ NOOR WAHAB )


Date : AUGUST 02, 2023 Date : AUGUST 02, 2023
Note:
Sm: Smooth Br: Buried RDM: Random
Ro: Rough Ug: Underground Ins: Insulated
Pnt: Painted
Subject : INSPECTION TANK Equiptment : OLYMPUS 38DL Sn. 1307
TAG / Line No. : 35-T-101 Probe : D-790 SM s/n : 1050245
: TANK, CONDENSATE STORAGE Couplant : CMC
Location : GRISSIK GAS PLANT Velocity : 5900 m/s
P & ID. No. : ID-N-GL-PP0-PID-PL-42-0001 REV 4 P & ID. No. : 1100172642
Surface Temp. : Ambient Date of Insp. : 02 Agustus 2023
Date of Last Insp. : 25 April 2021

Report of wall thickness measurement


Dimension in mm

NOM. PREV. POINT OF MEASUREMENT SURFACE


PARTS IDENT. MINIMUM REMAKS
THK THK 1 2 3 4 COND
5th Course (Plate #1)
A 6.00 - 5.80 5.95 5.90 5.81 5.80 PNT
B 6.00 - 5.87 5.86 5.82 5.84 5.82 PNT
C 6.00 - 5.89 5.91 5.91 5.89 5.89 PNT
5th Course (Plate #2)
A 6.00 - 5.96 5.95 5.94 5.63 5.63 PNT
B 6.00 - 5.97 5.98 5.95 5.93 5.93 PNT
C 6.00 - 5.87 5.99 5.94 5.99 5.87 PNT
5th Course (Plate #3)
A 6.00 - 5.83 5.78 5.81 5.80 5.78 PNT
B 6.00 - 5.84 5.82 5.86 5.85 5.82 PNT
C 6.00 - 5.86 5.88 5.76 5.77 5.76 PNT
5th Course (Plate #4)
A 6.00 - 5.92 5.94 5.91 5.90 5.90 PNT
B 6.00 - 5.95 5.92 5.95 5.95 5.92 PNT
C 6.00 - 5.96 5.92 5.95 5.89 5.89 PNT
5th Course (Plate #5)
A 6.00 5.96 5.92 5.90 5.81 5.94 5.81 PNT
B 6.00 5.81 5.95 5.91 5.80 5.94 5.81 PNT
C 6.00 - 5.63 5.87 5.99 5.94 5.63 PNT
5th Course (Plate #6)
A 6.00 5.91 5.83 5.78 5.89 5.89 5.78 PNT
B 6.00 5.95 5.87 5.82 5.95 5.80 5.80 PNT
C 6.00 5.9 5.84 5.91 5.94 5.85 5.84 PNT

Inspected by, Reviewed by,


PT. GAMMA BUANA PERSADA MEDCO E&P (GRISSIK) Ltd
ASNT UT LEVEL II QA/QC

( DONNY CT /M ABDILLAH ) ( DARMA BALEN/ NOOR WAHAB )


Date : AUGUST 02, 2023 Date : AUGUST 02, 2023
Note:
Sm: Smooth Br: Buried RDM: Random
Ro: Rough Ug: Underground Ins: Insulated
Pnt: Painted
Subject : INSPECTION TANK Equiptment : OLYMPUS 38DL Sn. 130749310
TAG / Line No. : 35-T-101 Probe : D-790 SM s/n : 1050245
: TANK, CONDENSATE STORAGE Couplant : CMC
Location : GRISSIK GAS PLANT Velocity : 5900 m/s
P & ID. No. : ID-N-GL-PP0-PID-PL-42-0001 REV 4 PMO : 1100172642
Surface Temp. : Ambient Date of Insp. : 02 Agustus 2023
Date of Last In : 25 April 2021

Report of wall thickness measurement


Dimension in mm

NOM. PREV. POINT OF MEASUREMENT SURFACE


PARTS IDENT. MINIMUM REMAKS
THK THK 1 2 3 4 COND
ROOF
R# 18.00 7.23 7.34 7.43 7.36 7.32 7.32 PNT
R# 2 8.00 7.23 7.43 7.45 7.52 7.52 7.43 PNT
R# 3 8.00 7.15 7.45 7.46 7.35 7.47 7.35 PNT
R# 4 8.00 7.33 7.44 7.34 7.45 7.41 7.34 PNT
R# 5 8.00 7.23 7.31 7.49 7.33 7.59 7.31 PNT
R# 6 8.00 7.17 7.37 7.36 7.39 7.38 7.36 PNT
R# 7 8.00 7.06 7.35 7.36 7.46 7.39 7.35 PNT
R# 8 8.00 7.09 7.39 7.36 7.32 7.48 7.32 PNT
R# 9 8.00 7.16 7.36 7.46 7.39 7.64 7.36 PNT
R# 10 8.00 7.15 7.49 7.55 7.56 7.35 7.35 PNT
R# 11 8.00 7.79 7.87 7.86 7.90 7.76 7.76 PNT
R# 12 8.00 7.14 7.40 7.24 7.31 7.48 7.24 PNT
R# 13 8.00 7.11 7.31 7.23 7.33 7.37 7.23 PNT
R# 14 8.00 7.16 7.26 7.57 7.61 7.65 7.26 PNT
R# 15 8.00 7.16 7.52 7.36 7.49 7.39 7.36 PNT
R# 16 8.00 7.13 7.60 7.33 7.35 7.74 7.33 PNT
R# 17 8.00 7.14 7.34 7.44 7.37 7.39 7.34 PNT
R# 18 8.00 7.36 7.46 7.49 7.39 7.44 7.39 PNT
R# 19 8.00 7.19 7.39 7.48 7.47 7.39 7.39 PNT
R# 20 8.00 7.36 7.49 7.49 7.39 7.49 7.39 PNT
R# 21 8.00 7.19 7.56 7.48 7.29 7.39 7.29 PNT
R# 22 8.00 7.71 7.85 7.81 7.65 7.75 7.65 PNT
Inspected by, Reviewed by,
PT. GAMMA BUANA PERSADA MEDCO E&P (GRISSIK) Ltd
ASNT UT LEVEL II QA/QC

( DONNY CT /M ABDILLAH ) ( DARMA BALEN/ NOOR WAHAB )


Date : AUGUST 02, 2023 Date : AUGUST 02, 2023
Note:
Sm: Smooth Br: Buried RDM: Random
Ro: Rough Ug: Underground Ins: Insulated
Pnt: Painted
Subject : INSPECTION TANK Equiptment : OLYMPUS 38DL Sn. 130749310
TAG / Line No. : 35-T-101 Probe : D-790 SM s/n : 1050245
: TANK, CONDENSATE STORAGE Couplant : CMC
Location : GRISSIK GAS PLANT Velocity : 5900 m/s
P & ID. No. : ID-N-GL-PP0-PID-PL-42-0001 REV 4 PMO : 1100172642
Surface Temp. : Ambient Date of Insp. : 02 Agustus 2023
Date of Last I : 25 April 2021

Report of wall thickness measurement


Dimension in mm

NOM. PREV. POINT OF MEASUREMENT SURFACE


PARTS IDENT. MINIMUM REMAKS
THK THK 1 2 3 4 COND
NOZZLE
Dia 24" MH1 12.70 9.2600003 9.54 9.57 9.41 9.40 9.40 PNT
Dia 20" MH2 12.70 9.34 9.79 9.75 9.79 9.84 9.75 PNT
Dia 4" N1 8.56 7.3499996 7.56 7.79 7.78 7.72 7.56 PNT
Dia 2" N2a - - 5.46 5.20 5.35 5.50 5.20 PNT
Dia 2" N2b - - 5.40 5.28 5.30 5.25 5.25 PNT
Dia 3" N3a 7.62 7.07 7.40 7.22 6.99 6.87 6.87 PNT
Dia 3" N3b 8.07 8.18 8.07 8.12 8.07 PNT
Dia 4" N4 8.56 7.3499996 8.19 8.27 8.43 8.12 8.12 PNT
Dia 3" N5 7.62 - 7.96 7.51 7.72 7.93 7.51 PNT
Dia 6" N6 10.97 10.02 10.56 10.89 11.03 10.41 10.41 PNT
Dia 20" N7 12.70 9.4500004 9.67 9.63 9.61 9.49 9.49 PNT
Dia 20" N8 12.70 9.53 9.75 9.76 9.77 9.72 9.72 PNT
Dia 8" N9 12.70 10.36 10.39 10.65 10.87 10.45 10.39 PNT

Inspected by, Reviewed by,


PT. GAMMA BUANA PERSADA MEDCO E&P (GRISSIK) Ltd
ASNT UT LEVEL II QA/QC

( DONNY CT /M ABDILLAH ) ( DARMA BALEN/ NOOR WAHAB )


Date : AUGUST 02, 2023 Date : AUGUST 02, 2023
Note:
Sm: Smooth Br: Buried RDM: Random
Ro: Rough Ug: Underground Ins: Insulated
Pnt: Painted
PLATE SHELL

Plate #1
5TH COURSE
N4
4''

Plate #1
4TH COURSE

Plate #1
3RD COURSE

Plate #1
2ND COURSE
N2B
2''

1 2 3 4 Plate #3
Plate #1 A
1ST COURSE B
Plate #2 NP Plate #3 Plate #5 Plate #6

N1 N2A N3A N3B MH


4'' 2'' 3'' 3'' 24''

Subject INSPECTION TANK Drawing By : DONNY CT / M.ABDILLAH

35-T-101
Line no.
3
Location GRISSIK GAS PLANT
PRODUCED WATER TANK
Date August 2, 2023 P & ID ID-N-GL-PP0-PID-PL-42-0001 REV 4
PLATE ROOF 35-T-101

#22
#15
#21
N8
#17
#20
N9

#19 #10
#14 #12
#18
#16 N5
N6
#11 #9 #7
#5
#13 MH2
La
dd
er

#4
N7
#6 #3
#8
#2
#1

Subject INSPECTION TANK Drawing By : DONNY CT / M.ABDILLAH


3

35-T-101
Line no. Location GRISSIK GAS PLANT
PRODUCED WATER TANK
Date August 2, 2023 P & ID ID-N-GL-PP0-PID-PL-42-0001 REV 4
Subject INSPECTION TANK Drawing By : DONNY CT / M.ABDILLAH

35-T-101
Line no.
3
Location GRISSIK GAS PLANT
PRODUCED WATER TANK
Date August 2, 2023 P & ID ID-N-GL-PP0-PID-PL-42-0001 REV 4
PHOTOGRAPH ROOF

PHOTOGRAPH SHELL

Subject INSPECTION TANK Drawing By : DONNY CT / M.ABDILLAH

35-T-101
Line no.
3
Location GRISSIK GAS PLANT
PRODUCED WATER TANK
Date August 2, 2023 P & ID ID-N-GL-PP0-PID-PL-42-0001 REV 4
#REF! #REF!