Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

REMARKS

PROCESS : 12,000m3/day
UNIT PROCESS REQUIREMENTS TOTAL UNIT PERFORMANCE SPECIFICATION

Capacity : 1.85m3/min
- Transfer Pump 12 nos Total Head : 8.0m 6 duty, 6 standby
Anaerobic Tank Power : 6kW
Peak Flow : 36,417.43 m3/day
- Process Instrumentation : Level/Pressure 12 nos
Float switch
Brand : Bi-Act SDO
Model : 25.48.60
Total Media plates: 165 ca
- Bi-Act SDO (Based on Capacity & tank) 30 nos Total Surface area: 36.0 m2/packs
SECONDARY TREATMENT

Air supply : 2.75 m3/min


DO/Pack : 346.5 kgs.O2/day
Aeration Tank
Capacity : 1.5m3/min
12 nos Total Head : 8m For access sludge (12 duty)
- MLSS Pump (Based on capacity & tank) Power : 2.9kW

- Process Instrumentation : 1 set each tank DO,pH,Turbidity,Temperature


1 set each tank (total 6 set)
DO,pH,Turbidity,Temp (total 6 set) Power : 0.1kW

Capacity : 2.5 m3/min


- RAS/WAS Pump 6 nos Total Head :12m 4 duty, 2 standby
Power : 9kW
Clarifier
Diameter : 22m
- Scrapper 2nos Depth : 6m
Power : 0.75kW
Capacity : 1.5m3/min
Sludge Storage Tank - Sludge Pump 3nos Total Head : 8m 2 duty, 1 standby
Power : 2.9kW
Air required : 40.0 m3/min
Blower House -Blower (For Aeration tank only) 5 nos Pressure Head : 0.8kgf/cm2 For Aeration Tank only (3 duty 2 standby)
Power : 90kW