Receptacle

NEC
Article 220

Type of Receptacle Load in VA

Single 180 VA

Doplex 180 VA

Triplex 180 VA

90 VA for 1
Double Doplex
so (4x90)=360 VA

90 VA for 1
Quad or 4 -plex
so (4x90)=360 VA

Load for power line(small - applicance branch circuits) =1500 VA


Load for 1 Single or Doplex Receptacle =180 VA

the max. no of Receptacle in a line =1500/180 = 8 socket


According to E.C
6 6 H ‫ﻣﻮاﺻﻔﺎت ﺑﻨﻮد اﻋﻤﺎل اﻟﺘﻮﺻ?ﻼت‬
7‫ﺎ‬9‫اﻟﻤ‬
5 =5 ‫ﺎﺋ?ﻪ‬AB‫ﻬ‬D‫ﺎت اﻟ‬9‫ﻛﻴ‬I‫واﻟ‬
NO. of soket >3 3X4mm C.b=20A
Recepticale
NO. of soket <=3 3X3mm C.b=16A
Prefere no of receptcal in a power line = 6 socket
Preference means that it is not mandatory or necessary