Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Ø168 Table.

1 Technical Parameters

Inner terminal for cable Top terminal fixing detail Rated voltage(50/60Hz): 245kV
Ø30 Top Terminal ,
Rated phase-to-earth voltage: 142kV
Brass Tin plated M10 3 One minute power frequency withstand

L4
Ø8 505kV
voltage(dry):
Anti-corona head,
Rated current: 800A
Aluminum alloy

35
Ø30 nut Partial discharge level at 245kV: ≤10pC
Ø30 2
Ø36 Tanδ of bushings: ≤0.4%
2240±10 (Arcing distance)

Lightning impulse withstand voltage(dry): 1050kV


Test tap voltage withstand level: 2kVrms

Test Tap Creepage distance: ≥7812mm


L3±20 (Draw lead length)

Rated thermal short-time current, 2sec(Ith): 20kA


Flange 1
M10 Rated dynamic current(Id): 50kA
Insulating layer Tube
Silicone rubber Ambient temperature: -10°C to+60°C
sheds
L±20

Cable Altitude above mean sea level: ≤1000m


Ø490
Installation angle: 0-90°
Grounding Cap Process: 1 -- 2 -- 3
Cantilever test load: 4000N
Type of conductor: Draw lead
A A Test tap A-A
25 30° Internal insulation: RIP
170

2-Lifting lugs 15°


2-M12 For Earthing External insulation/Colour: Silicone rubber / Gray
L2 (CT Length)

Comply with standard: IEC 60137


Flange,Aluminum alloy Test tap
Transformer **Please confirm the dimensions of the bushing.
Ø300(sealing area:min.diameter) air vent
Table.2 Main Dimensions
L1±5

Ø260
Main Dimensions(mm) Net
12-Ø22 Bushing Type weight
Ø400 kgs
L L1 L2 L3 L4
Ø450
B FBRGL-245/800-01 3690 1050 500 3450 125 410
View B
FBRGL-245/800-02 3885 1284 600 3725 80 450

FBRGL-245/800-03 3785 1184 500 3625 80 425


End shield,Aluminum alloy
R32.5 coated with insulating epoxy paint
FBRGL-245/800-04 3585 984 300 3425 80 400

ALL DIMENSIONS ARE IN MILLIMETERS


65

Drawing No.: 0CX.302.080.04-1 Rev.01: 30/11/2023


UNLESS OTHERWISE STATED

Designer
R32.5 Ø50
Nanjing Rainbow Electric Co.,Ltd
Ø245 Approver

You might also like