1 Technical Parameters
Test Tap
Rated voltage(50/60Hz): 245kV
Ø40 Top Terminal ,
Flange Rated phase-to-earth voltage: 142kV
Brass Tin plated
125
Insulating layer One minute power frequency withstand
505kV
voltage(dry):
Anti-corona head,
Rated current: 1600A
Aluminum alloy
Partial discharge level at 245kV: ≤10pC
Grounding Cap
Tanδ of bushings: ≤0.4%
2240±10 (Arcing distance)
sheds
Altitude above mean sea level: ≤1000m
Ø490 12-Ø22 Installation angle: 0-90°
Ø400
Ø450 Cantilever test load: 4000N
Type of conductor: Bottom connection
A A Test tap
25 Internal insulation: RIP
170
Ø300(sealing area:min.diameter)
1215±5
90
40
185
150
22.5
δ25