20 · GEA BOCK HG SEMI-HERMETIC COMPRESSORS

OPERATING LIMITS

R134a Operating limits

tC (°C) HGX12P, HGX34e/ -4 tC (°C) HGX22e, HGX34e/-4 S, HGX44e, HGX56e

80 80
70 70
∆t0h<20K ∆t0h<20K
60
60
50
50
40
40 30
t0h+20 °C t0h+20 °C
30 20
20 10

–30 –20 –10 0 10 20 30 t0 (°C) –30 –20 –10 0 10 20 30 t0 (°C)

tC (°C) HGX66e, HGX88e

t0 Evaporating temperature (°C)


80 tC Condensing temperature (°C)
∆t0h Suction gas superheat (K)
70
0K

t0h Suction gas temperature (°C)


<2

60
0 h
∆t

50 Max. permissible operating pressure (LP/HP) 1): 19/28 bar


40 LP = low pressure, HP = high pressure
1)

30 Unlimited application range


t0h+20 °C
20 Motor version -S- (more powerful motor)
Supplementary cooling or reduced suction gas temperature
–30 –20 –10 0 10 20 30 t0 (°C) Supplementary cooling and reduced suction gas temperature

NOTES
R134a Notes

Operating limits Conversion factor for 60 Hz = 1.2


Compressor operation is possible within the limits shown on the Performance data for other operating points, see GEA VAP software
application diagrams. Please note the colored areas. Compressor (vap.gea.com).
application limits should not be chosen for design purposes or
continuous operation. ASERCOM certified performance data

Restrictions to operating limits may occur when using a frequency


converter.
For further explanations consult www.gea.com

Performance data For compressors with this label, the performance data are certified
The performance data for R134a are based on European Standard according to the strict requirements of ASERCOM.
EN 12900 50 Hz power supply frequency.
This signifies: 20 °C suction gas temperature without liquid subcooling. ASERCOM is the Association of European Refrigeration Compressors
This results in significant differences compared to specifications with and Controls Manufacturers.
liquid undercooling and/or suction-gas temperatures. Information about the Association and the constantly updated
overview of certified GEA compressors can be found at
A comprehensive modification to 20 °C suction gas temperature will www.asercom.org and www.gea.com.
follow at a later date.