The document is an LSPS Susol design report that includes:
- A system summary listing the power source, generators, transformers, cables, motors, fuses, relays, loads, switches, LBS, ATLS, capacitors, and reactors for the system.
- Tables showing the short-circuit currents for 3-phase and phase-to-ground faults at each bus under 1/2 cycle, 3 cycle, 5 cycle, and steady state conditions.
- A single-line diagram configuration drawing of the system.
The document is an LSPS Susol design report that includes:
- A system summary listing the power source, generators, transformers, cables, motors, fuses, relays, loads, switches, LBS, ATLS, capacitors, and reactors for the system.
- Tables showing the short-circuit currents for 3-phase and phase-to-ground faults at each bus under 1/2 cycle, 3 cycle, 5 cycle, and steady state conditions.
- A single-line diagram configuration drawing of the system.
The document is an LSPS Susol design report that includes:
- A system summary listing the power source, generators, transformers, cables, motors, fuses, relays, loads, switches, LBS, ATLS, capacitors, and reactors for the system.
- Tables showing the short-circuit currents for 3-phase and phase-to-ground faults at each bus under 1/2 cycle, 3 cycle, 5 cycle, and steady state conditions.
- A single-line diagram configuration drawing of the system.
· Date : Diciembre de 2023 · Company : ISIE · Version : 1.0 3. System summary
System Information
Eq. Power Source
Total No. : 1 EA Min. SC current : 465 MVA Max. SC current : 465 MVA
Generator Total No. : 0 EA
Effective capacity : 0 kVA Total capacity: 0 kVA - Base kVA : 1000 kVA - Systemp Hz : 60 Hz Transformer Total No. : 3 EA - Fault impedance: 0 Ω Total capacity: 367 kVA
Cable 3ф cable length
: 507.00 m 1ф cable length : 0.00 m Total length : 507.00 m
Motor Total No. : 2 EA
Min. capacity: 12 kW Max. capacity: 16 kW Total capacity: 29 kW