IN THE BOX

×1 ×1

CP-MWP ×1
Mute Wedge Condensate Pump

×1
×1

PRODUCT SAFETY

• CAUTION: The Mute Wedge Pump from the manufacturer or its

Thank you for buying our new condensate pump of MUTE WEDGE. has been evaluated for use with water only. service agent.
This manual gives instructions on the correct installation. Please record the
• WARNING: Risk of electric shock. This • Do not run this pump dry.
following information for your future reference.
pump has not been investigated for use in • Always ensure the metal magnet

swimming pool or marine areas. in the float is facing upwards.


TECHNICAL DATA • The means for isolation must be • Always ensure the reservoir is

incorporated in the fixed wiring in sitting flat and horizontal.


• Power supply :100-240V AC • Discharge tube:6mmID
accordance with wiring regulations. • The Pump is ideal for most
50/60Hz <4W • Class:II appliance

• Max.flow:38L/h @ 0 head • Rated:continuous • Ensure the pump is disconnected from the working and living environments.

• Sound level:<19dB(A) @ 1m • IP Protection:IPX5 mains supply before carrying out any It is not recommended where the

• Water storage: 230ml • Thermal protection: adjustments or servicing. environment is oily or particularly
• Max.recommended head:20m • Fully potted: • If the cord is damaged, it must be replaced dusty.
• Max.unit output: 46kw / 157000Btu/h • L×W×H:164mm×70mm×102mm
with a special cord or assembly available • Acceptable for indoor use only.
• Safety switch:3A Normally closed • CE marked
• Non-submersible pump.
• Max.water temperature:70ºC

TYPICAL PERFORMANCE INSTALLATION

11 1、 Filter

10

9
METRES HEAD

7
2、 3、
6

0
0 9 15 26 31 38 44 48
LITRES PER HOUR
4、 5、 6、 7、

35mm

30mm

8、

6 x 9mm

9、A high-level alarm switch should be wired into the cooling signal wire, to prevent the continued operation of the air conditioning unit in the event of the
pump failing.
IMPORTANT: This diagram is an example of how the pump could be installed and is therefore for reference only. All pump units must be installed by
qualified engineers, who have assessed the set-up of the individual a/c unit.

(1) Live connection is < 3 amps (2) Via a suitable contactor relay (normally (3) Where interruption of the live or neutral connections lead to comms problems
open) where the live connection is above 3
amps

① Indoor unit
② Outdoor unit
③ Pump unit
L:Brow C:Black N:Blue NC:Black
④ Contactor Relay (Normally Open)
100-240V 50/60Hz 100-240V 50/60Hz
100-240V 50/60Hz

10、 11、 12、 13、

28mm

SERVICING TROUBLE SHOOTING


• This Pump, like all mechanical equipment, requires maintenance. Fault: Pump runs all the time Please note:
• Every six months the reservoir should be removed, taking care to clean the filter, 1. Is float positioned with the magnet uppermost? • After installation and during operation,
float and reservoir thoroughly prior to reassembly. We recommend this is done in the 2. Is the reservoir lid (sensor) located firmly onto if you notice air in the pipe between the
Spring and the Autumn, using an anti-bacterial wash. the reservoir, with the float located inside the reservoir and the pump, you have a
• Take great care to replace the float with the magnet facing upwards.* reservoir, around the sensor column? siphoning problem. Follow advice in
3. Is there sludge inside the reservoir, preventing ‘Preventing Siphoning’ section).
float from resting on the bottom? (This may occur • The pump will only switch off when
if pump has been in operation for some time the float is at the bottom of the reservoir.
without cleaning. Clean using an anti-bacterial wash.)
Fault: Pump stops and starts and makes Fault: Pump isn’t operating at all.
a loud noise. 1. Is power reaching the pump?
1. The water is siphoning back through the pump. Is it correctly wired? Is the voltage
Follow advice in ‘Preventing Siphoning’ section. correct?
Fault: Pump runs but does not pump any water. 2. Is pump very hot? A thermal cut-out
1. Are there any air-leaks in the pipe running to may have been activated to protect pump.
the pump? This will automatically reset once pump
2. Check that reservoir and inlet tube are free of has cooled down.
sludge and debris.