Download as pdf or txt
Download as pdf or txt
You are on page 1of 68

CLOSE CONTROL

AIR CONDITIONERS

TECHNICAL MANUAL

USE AND MAINTENANCE


SNMP GATEWAY
CLOSE CONTROL AIR CONDITIONERS

SYMBOLS

NOTE!
This symbol is used to indicate helpful hints for the operator.

The Manufacturer adopts a policy of continuous development and therefore, reserves the right to make changes and im-
provements to any product described in this document without prior notice. Technical data and dimensions are not binding.

2 TECHNICAL MANUAL
CLOSE CONTROL
AIR CONDITIONERS

TECHNICAL MANUAL

USE AND MAINTENANCE


SNMP GATEWAY

List of revisions
Revision Date Author Chapters Descriptions
A 01/2014 AF All First version
B 05/2015 AF All Insertion of SURVEYEVO (2.0)
C 10/2017 AF All Insertion of SURVEYEVO (2.1)
D 12/2017 AF All Errata corrige
E 10/2018 AF All Insertion of SURVEYEVO (2.2)

INSTALLATION AND MAINTENANCE 3


CLOSE CONTROL AIR CONDITIONERS

CONTENTS
WARRANTY CONDITIONS.............................................................................................................................................6
WARRANTY RESTRICTIONS..........................................................................................................................................7
1 INTRODUCTION.................................................................................................................................................8
2 SNMP PROTONODE RER GATEWAY...................................................................................................................9
2.1 TECHNICAL SPECIFICATIONS............................................................................................................................................................. 9
2.2 COMMUNICATION LEDS....................................................................................................................................................................10
2.3 SERIAL COMMUNICATION PROTOCOL CHARACTERISTICS...................................................................................................10
3 ELECTRICAL CONNECTIONS OF THE SNMP PROTONODE RER GATEWAY....................................................11
3.1 POWER SUPPLY OF THE SNMP PROTONODE RER GATEWAY................................................................................................12
3.2 MODBUS RTU MASTER RS485 SERIAL (HOST) COMMUNICATION BOARD.....................................................................13
3.3 ETHERNET RJ45 PORT CONNECTION............................................................................................................................................14
4 CONFIGURATION OF THE SNMP PROTONODE RER GATEWAY VIA PC..........................................................15
4.1 CONNECTION TO THE PC VIA THE ETHERNET PORT................................................................................................................15
4.2 CONFIGURING THE SNMP PROTONODE RER GATEWAY.........................................................................................................16
5 OBJECT IDENTIFIER (OID) OF THE VARIABLES, MIB FILE AND NOTIFICATIONS (TRAP) DOWNLOAD........21
5.1 DEFINITION OF THE OBJECT IDENTIFIER (OID) OF THE VARIABLES....................................................................................21
5.2 MIB FILE DOWNLOAD........................................................................................................................................................................21
5.3 ALARM NOTIFICATIONS (TRAP)......................................................................................................................................................21
6 LIST OF VARIABLES..........................................................................................................................................22
6.1 CLOSE CONTROL SURVEYEVO MICROPROCESSOR SUPERVISOR VARIABLES (SOFTWARE VERSION 2.2)................22
6.2 CLOSE CONTROL SURVEYEVO MICROPROCESSOR SUPERVISOR VARIABLES (SOFTWARE VERSION 2.1)................38
6.3 CLOSE CONTROL SURVEYEVO MICROPROCESSOR SUPERVISOR VARIABLES (SOFTWARE VERSION 2.0)................51
7 TROUBLESHOOTING AND FAULTS ELIMINATION..........................................................................................64
7.1 NO COMMUNICATION ON THE SERIAL BOARD RS485 RTU MODBUS..............................................................................64
7.2 NO COMMUNICATION ON THE ETHERNET PORT.....................................................................................................................64
8 NOTES...............................................................................................................................................................65

4 TECHNICAL MANUAL
INSTALLATION AND MAINTENANCE 5
CLOSE CONTROL AIR CONDITIONERS

WARRANTY CONDITIONS

All Products of the Manufacturer or bearing the trademark of the Manufacturer are built according to the state of the art
techniques, in compliance with the current reference standards, as stipulated in the certificate of conformity provided together with
the products.

All Products of the Manufacturer or bearing the trademark of the Manufacturer are designed to be installed within a plant
that controls them. The designer or installer of the Product assumes all liability and risk relating to its installation in the destination
plant.

The Manufacturer and its Branches/Affiliates do not guarantee that all aspects of the Product and any software included
will comply with the requirements of the destination plant. In this case, following specific agreements, the Manufacturer can act as a
consultant for the successful start-up of the Product, but will not be held liable, under any circumstances, for the smooth operation
of the destination plant.

All Products of the Manufacturer or bearing the trademark of the Manufacturer are subject to the following warranty which
is deemed as entirely accepted and signed while placing the order.

The warranty on the Products of the Manufacturer or bearing the trademark of the Manufacturer is valid for TWENTY-FOUR
MONTHS (2 years) from the shipment date of the material.

If start-up is not carried out by technicians authorised by the Manufacturer, the warranty is validated by submitting a com-
pleted copy of the Product’s technical start-up report.

During the warranty period, the Manufacturer, under its sole discretion and as quickly as possible, undertakes to repair or
provide as new any parts with acknowledged defects in their material, construction or workmanship, which make them unsuitable
for their intended use.

The claim must be submitted in writing, indicating the details of the reported fault, the serial number or code of the Product,
where the fault was identified and indication of the component that caused the fault, if this is easily identified. The Manufacturer will
accept no claim made over the phone.

For operational purposes, claims can only be accepted during office hours, Monday to Friday. If a request is submitted on a
public holiday, the Manufacturer will consider it as received at the beginning of the next working day after this has been sent.

Faulty components are replaced ex works (EXW). Transport costs are borne by the Customer, even if the warranty cover is
applied, unless specified otherwise by the Manufacturer.

The costs to replace faulty components (labour, materials, refrigerant, etc.) are borne by the Customer, even if the warranty
cover is applied, unless specified otherwise by the Manufacturer.

Materials replaced while under warranty are the property of the Customer, who must dispose of them according to current
regulations. Any disposal costs are borne by the Customer.

If parts should be returned while under warranty, they must be returned no later than three (3) months from the shipment
date of the replacement part, organised and the expenses borne by the Customer. Otherwise, all the parts will be charged at the
applicable list price at the time of their shipment.

The Manufacturer is not liable for compensation for direct or indirect damage, of any kind and for any reason. The Manufac-
turer is also not liable for any delay in the supply of parts under warranty or executing work under warranty.

6 TECHNICAL MANUAL
WARRANTY RESTRICTIONS

The above mentioned warranty conditions are valid as long as the Customer has fulfilled all obligations according to the contract and in
particular those relating to payment. A delayed payment or non-payment of the supply, even if partial, suspends any warranty. The warranty does not
give the Customer any right to suspend or delay payments, which must be paid in any case according to that stipulated in the order and specified in
the written order confirmation.

Without precluding proper compliance with other instructions provided in the technical documentation supplied with the Product, it must
be noted that the following instructions are to be complied with accordingly, for the warranty to b valid:

Transport and positioning

• Do not remove the Product from its original packaging until it has reached the installation site.
• Do not drop, knock or shake the Product, as the internal circuits and mechanisms may be irreparably damaged.
• Store the Product in an environment that complies with the temperature and humidity limits specified in the technical documentation.

Installation

1) The Product must be installed by skilled personnel who fulfil the adequate requisites for the task as defined by the regulations in the coun-
try where positioning and installation take place.
2) The plant which will control the Product must be implemented professionally, according to the instructions provided in the technical doc-
umentation and the regulations of the country where positioning and installation take place, with particular attention paid to the setting
up of:

• Water or cooling lines servicing the Product and the relevant components.
• Electrical power and connection lines of the Product and the relevant components.
• Aeraulic lines of the Product and the relevant components.

3) Do not install the Product outdoors or in environments that are subject to bad weather.
4) Do not install the Product in environments where oil is present, or where there are oil vapours or various kinds of aerosols, and where there
are flammable vapours.
5) Do not install the Product in an environment where there are corrosive gases, such as sulphur gases.
6) Do not install the Product in environments where there is equipment that generates electromagnetic waves, and where the line voltage is
subject to great fluctuations.
7) Do not install the device in an environment where the air is highly saline, such as near sea cliffs.
8) Do not install the device in vehicles or boats.
First start-up
1) The Product must be started up by skilled personnel who fulfil the adequate requisites for the task as defined by the regulations in the
country where positioning and installation take place.
2) The plant which will control the units must be started up professionally, according to the instructions provided in the technical documen-
tation and the regulations of the country where positioning and installation take place.
3) Copy of the technical start-up report of the Product must be delivered to the Manufacturer.
Use and maintenance
1) Do not use the Product for applications other than those specified in the technical documentation.
2) Do not use the Product in an environment that does not comply with the temperature and humidity limits specified in the technical doc-
umentation.
3) Perform maintenance cycles according to the schedules specified in the technical documentation.
4) Clean the Product with neutral detergent. Do not use corrosive chemicals and solvents or aggressive detergents.

Furthermore, the Manufacturer reserves the right to void the warranty of the products sold if:

A) The labels or plates bearing the trademark of the Manufacturer and the serial number or the registration number of the Product have been
deleted and/or removed.
B) The Product has been subjected to alterations or mechanical processes not specifically authorised by the Manufacturer.
C) The Product has been used inconsistently with the instructions provided in the technical documentation and regulations of the country
where positioning and installation take place, or for purposes other than those for which it was designed.
D) The defects are due to negligence, incompetence, poor maintenance, carelessness and inability of the End-user, damage caused by third
parties, fortuitous or force majeure or for any other reason not attributable to the defects in construction quality.

The following are considered as of now excluded from the warranty:

A) All parts with marginal defects that have a negligible effect on the value or functionality of the Product.
B) All parts typically subject to sliding or rolling friction (bearings, brushes, etc.);
C) All parts typically subject to consumption (filters, humidifier cylinders, etc.);
D) All parts typically subject to oxidation or corrosion if not properly used or serviced (manifolds, wires and copper contacts or metal alloys,
internal or external parts of the units, etc.);
E) All parts not supplied by the Manufacturer, even if these are an integral part of the plant which controls the product.

INSTALLATION AND MAINTENANCE 7


CLOSE CONTROL AIR CONDITIONERS
1 INTRODUCTION
The ProtoNode devices have been designed for all those who need to interface SURVEY microprocessors with a Modbus
RS485 card with other protocols.

The ProtoNode devices are the best solution for flexibility and versatility, they support virtual node mode that allows you to
connect multiple SURVEY controllers to a single ProtoNode, which will be seen as separate controllers.

The ProtoNode package includes all the hardware and software required to interface the actual product in the various net-
works with different protocols.

There are 2 types of ProtoNode devices:

• BACNET/SNMP/MODBUS TCP PROTONODE RER: integrates two RS-485 ports and one Ethernet port.
• LONWORKS PROTONODE LER: includes one LonWorks port, one RS-485 port and one Ethernet.

8 TECHNICAL MANUAL
2 SNMP PROTONODE RER GATEWAY
The Simple Network Management Protocol (SNMP) is a network protocol which belongs to the suite of Internet protocols
defined by IETF (Internet Engineering Task Force). The protocol operates at level 7 of the OSI model and allows for the configuration,
management and monitoring of devices connected in a network (regardless whether internal commutation nodes such as network
devices and user terminal nodes), with respect to all those aspects that require administrative action (Management).

SURVEY microprocessors can be fitted as part of a supervisory and/or remote assistance network that adopts the SNMP
standard and connects the actual Modbus RS485 serial card to a SNMP ProtoNode RER gateway.

2.1 TECHNICAL SPECIFICATIONS

SNMP ProtoNode RER Gateway


1 Connector with 6 poles for conductors of up to 1.5 mm2 (0.0028 in2)
Electrical connections 1 Connector with 3 poles for conductors of up to 1.5 mm2 (0.0028 in2)
1 Ethernet Port 10/100
CE (EN55022; EN55024; EN60950), UL916, FCC Class A Part 15, DNP3 Conform-
ance Tested, OPC Self-tested for Compliance, RoHS Compliant, CSA 205 Ap-
Certification
proved
BTL Marked
Electrical Power Supply 9 - 30 V DC or 12 - 24 V AC
Dimensions 11.5 cm L x 8.2 cm W x 4.0 cm H (4.5 x 3.2 x 1.6 in.)
Weight 0.2 kg (0.4 lbs.)
Operating temperature -40°C to 75°C (-40°F to167°F)
Operating humidity 5 - 90% RH (non condensing)
Electromagnetic compatibility EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT

INSTALLATION AND MAINTENANCE 9


CLOSE CONTROL AIR CONDITIONERS
2.2 COMMUNICATION LEDS

The SNMP ProtoNode RER gateway has LEDs that allow its operational state to be verified. The meaning of the individual
LEDs is explained in the table below:

Communication LED

LED Meaning
RTC – SPL Not used
RUN Flashing indicates correct operation
ERR If ON, it indicates a problem
RX Flashing indicates correct Modbus communication
TX Flashing indicates correct Modbus communication
PWR If ON, it indicates correct power supply

2.3 SERIAL COMMUNICATION PROTOCOL CHARACTERISTICS

Modbus RTU Master


Protocol Modbus Master, RTU mode
Communication Standard RS485 Opto-isolated in terms of the network (Host)
Baud Rate (default) 19200 Baud (9600/19200)
Word Length (default) 8 (7 - 8)
Parity (default) Even (None/Odd/Even)
Stop Bits (default) 1

SNMP
Protocol SNMP V2c
Communication Standard RJ45 Ethernet
IP Address (default) 192.168.1.24
Subnet Mask (default) 255.255.255.0
Default Gateway (default) 192.168.1.1
INTEGER
OCTET_STREAM
Data type
TIMER_TICKS
STRING
SNMP Get Request
Control SNMP GetNext Request / SNMP Walk
SNMP Set Request
Trap Send alarm Trap to the specified address

10 TECHNICAL MANUAL
3 ELECTRICAL CONNECTIONS OF THE SNMP PROTONODE RER GATEWAY

WARNING!

It is however necessary to always refer to the electrical diagram supplied with the unit.

The electrical wiring diagram suggests dimension values for the electricity line and the
corresponding protective devices.

WARNING FOR SIGNAL CABLES!


Connect one end only of shield-
Avoid splicing Do not install with power cables
ing to earth

The picture below identifies the connection points of the SNMP ProtoNode RER gateway. The connections are made by the
installer who is required to observe the contents of this manual.

A RS485 Modbus RTU Master connection (Host)


B Electrical power supply connection
C RJ45 Ethernet connection
D Not used

A B

INSTALLATION AND MAINTENANCE 11


CLOSE CONTROL AIR CONDITIONERS
3.1 POWER SUPPLY OF THE SNMP PROTONODE RER GATEWAY

The table shows the meaning of the SNMP ProtoNode RER gateway pinout:

Electrical power supply connection

A + PWR
B - PWR
C FRAME GND

A B C

Terminal Specifications
+ PWR 9 – 30V DC/AC
- PWR 9 – 30V DC/AC
FRAME GND - FG Earth

MAIN FEATURES OF THE POWER SUPPLY CABLE


Type Fror 450/750 V cable
Shielding Not required
Section and number of conductors 2 x 1 mm2
Maximum length m 100
Example

12 TECHNICAL MANUAL
3.2 MODBUS RTU MASTER RS485 SERIAL (HOST) COMMUNICATION BOARD

To create a connection to the Modbus (SURVEY) system, simply connect the units from the terminals on it (see wiring dia-
gram for further information)

RS485 Modbus RTU Master connection

A Tx/+ - B+ (HOST)
B Rx/- - A-
C GND - SG

A B C
Terminal Specifications
Tx/+ - B+ (HOST) RS485 Modbus RTU Master +
Rx/- - A- (HOST) RS485 Modbus RTU Master -
GND - SG (HOST) RS485 Modbus RTU Master GND

A B C
A Unit 1
B Unit 2
C BMS / Supervision system/ Gate-
D D E
way
D Modbus network output termi-
nals
E Modbus network input terminals
F F F Modbus network connection
cable

Example of unit - gateway connection

The type of cable to be used for the connection must have the following features:

MAIN FEATURES OF SERIAL COMMUNICATION CABLE


Type Data transmission cable for RS485, Modbus or CANbus interfaces
Shielding Tinned copper braid - Cover at least 65%
Section and number of conductors 3 x 0.34 mm2 - AWG 22
Stranding Twisted pairs
Nominal loss (1 MHz) dB/100m 1.64
Maximum DC resistance for conductor at 20°C Ω/km 49
Insulation resistance at 20°C MΩ*km 5000
Mutual capacitance c-c / c-s nF/km 40 - 70
Inductance mH/km 0.7
Impedance Ohm 120 +/- 0.12
Maximum length m 100
Example

INSTALLATION AND MAINTENANCE 13


CLOSE CONTROL AIR CONDITIONERS
3.3 ETHERNET RJ45 PORT CONNECTION

To set up the connection to the Ethernet network simply connect the SNMP ProtoNode RER gateways via port RJ45 on the
board:

RJ45 connection (Configuration/SNMP)

A RJ45 Ethernet

Terminal Specifications
RJ45 Ethernet Ethernet connection

The type of cable to be used for the connection must have the following features:

SPECIFICATIONS OF ETHERNET COMMUNICATION CABLE


Cross-over cable EIA/TIA-568A/B (10Base-T, 100Base-TX)

14 TECHNICAL MANUAL
4 CONFIGURATION OF THE SNMP PROTONODE RER GATEWAY VIA PC

4.1 CONNECTION TO THE PC VIA THE ETHERNET PORT

The SNMP ProtoNode RER Gateway must be connected to a PC via the RJ45 Ethernet port to be configured.

SNMP ProtoNode RER Gateway is configured with IP address 192.168.1.24 and Subnet Mask 255.255.255.0. If the PC
should have different networks, proceed as follows:

1) Select: Start

2) Select: Control panel

3) Select: Network and Internet

4) Select: Network and Sharing Centre

5) Select: Local Area Connection (LAN)

6) Select: Propriety

7) Select: Internet Protocol version 4 (TCP/IPv4)

8) Select: Propriety

IP Address: 192.168.1.11
9) Configure:
Subnet mask: 255.255.255.0

10) Select:

INSTALLATION AND MAINTENANCE 15


CLOSE CONTROL AIR CONDITIONERS
4.2 CONFIGURING THE SNMP PROTONODE RER GATEWAY

The SNMP ProtoNode LER Gateway is configured via the specifically developed web interface. Access the configuration
page as follows:

1) Open the web browser (e.g. Internet Explorer).


2) Enter the IP address for the Gateway http://192.168.1.24/
3) The following will appear on the web browser page:

For the SNMP ProtoNode RER Gateway to run smoothly, at least one communication profile must be configured, i.e. at least
1 unit must be connected to it. The configuration page allows the following:

1) Configuring the network parameters for the gateway (IP address, etc.)
2) Configuring the parameters of the Modbus Master network.
3) Configure the parameters of the SNMP network.
4) Configuring the communication profiles of the connected units.
5) Override system restart.
6) Override system restart with profile deletion.
7) Accessing the system diagnostics page.

16 TECHNICAL MANUAL
4.2.1 CHANGING THE IP ADDRESS OF THE SNMP PROTONODE RER GATEWAY

If the IP address of the SNMP ProtoNode RER gateway is not compatible with the LAN or SNMP network in which it must be
connected, you can modify the default configuration settings as follows:

1) Open your web browser (ex. Internet explorer) and enter the IP address for the Gateway http://192.168.1.24/

2) On the configuration page press this button:

3) A new window will open

4) Proceed with the configuration of the parameters that are to be modified.

5) Confirm the changes with:

6) At the end of the configuration, reset the system by pressing the following button:

WARNING!

The SNMP ProtoNode RER gateway must be restarted for the settings to be implemented.

If the IP address of the SNMP ProtoNode RER gateway has been modified, the new IP ad-
dress in the Web browser must be used to re-access the configuration.

INSTALLATION AND MAINTENANCE 17


CLOSE CONTROL AIR CONDITIONERS
4.2.2 CONFIGURATION PARAMETERS OF THE MODBUS RTU MASTER NETWORK

On the configuration page it is possible to configure the parameters of the Modbus RTU Master network that the ProtoNode
RER gateway will be connected to:

Configuration parameters of the Modbus RTU Master network

Parameter Description Min Max Default


mod_baud Baud rate value of the Modbus RTU Master network 9600/19200 19200
mod_databits Data Bits value of the Modbus RTU Master network 7 8 8
mod_stopbits Stop Bits value of the Modbus RTU Master network 1 2 1
mod_parity Parity value of the Modbus RTU Master network None/Odd/Even Even
The default values are compatible with the default values of the units that can be associated to the BACnet ProtoNode
RER gateway

18 TECHNICAL MANUAL
4.2.3 CONFIGURATION PARAMETERS OF THE SNMP NETWORK

On the configuration page it is possible to configure the parameters of the SNMP V2c network that the SNMP ProtoNode
RER gateway will be connected to:

Configuration parameters of the SNMP network

Parameter Description Min Max Default


public_com Public Community SNMP value 9600/19200/38400/57600 9600
private_com Private Community SNMP value 7 8 8
trap_com Trap Community SNMP value 1 2 1
trap_ip Alarm Trap recipient IP address - 192.168.1.1

INSTALLATION AND MAINTENANCE 19


CLOSE CONTROL AIR CONDITIONERS
4.2.4 COMMUNICATION PROFILE CONFIGURATION

The SNMP ProtoNode RER gateway allows the communication profiles to be configured according to the type of system and
units connected to it:

Communication profile configuration

Parameter Description Min Max


Node ID Profile identification 1 99
Current profile Communication profile BACIP_SurveyEvo2.0 BACMSTP_SurveyEvo2.1
modbus_id Unit modbus identification (Master) 1 999

Proceed as follows to implement the configuration:

1) Open your web browser (ex. Internet explorer) and enter the IP address for the Gateway http://192.168.1.24/
2) The following section is found on the configuration page:

3) To add a configuration select:

4) Enter the Node ID of the new profile. We recommend entering an increasing number starting from 1.
5) Select the communication profile. You can choose between the following types of communication profiles:

• SNMP_SurveyEvo2.0: SNMP Profile for Close Control Survey evo software version 2.0 unit
• SNMP_SurveyEvo2.1: SNMP Profile for Close Control Survey evo software version 2.1 unit
• SNMP_SurveyEvo2.2: SNMP Profile for Close Control Survey evo software version 2.2 unit

You can configure different profiles within the same SNMP ProtoNode RER gateway.
6) Enter the reference unit Modbus ID.

7) Confirm profile entry by pressing:

8) Repeat the operations according to the number of units connected to the BACnet ProtoNode RER gateway.

9) To eliminate previously entered configurations, use:

10) At the end of the configuration, reset the system by pressing the following button:

11) To eliminate all previously entered configurations, use:

20 TECHNICAL MANUAL
5 OBJECT IDENTIFIER (OID) OF THE VARIABLES, MIB FILE AND NOTIFICATIONS (TRAP) DOWN-
LOAD

5.1 DEFINITION OF THE OBJECT IDENTIFIER (OID) OF THE VARIABLES

The variables are defined in the SNMP protocol by means of a unique Object Identifier (OID). The SNMP ProtoNode RER
gateway identifies the variables as follows:

.1.3.6.1.4.1.6347.1.1.0.0

The Object Identifier (OID) consists of the following:

.1.3.6.1.4.1.6347 .1 .1 .0 .0
Common to all OIDs Node ID Type of variable Variable ID This is a fixed number

5.2 MIB FILE DOWNLOAD

A management information base (also referred to as MIB) is a type of database for the management of devices in SNMP
communication networks.

When the gateway is configured it is possible to download the MIB file from the following address:

http://IPPROTONODE/fIPPROTONODE_smnpserver.mib

Where IPPROTONODE is the IP address for the gateway. For example, using the gateway with the default IP, you can down-
load from:

http://192.168.1.24/f192.168.1.24_snmpserver.mib

5.3 ALARM NOTIFICATIONS (TRAP)

The notifications are asynchronous messages sent by the Agent to report events that have occurred in the managed system
(e.g. alarms in case of faults). The SNMP notifications with no acknowledgement are generally called Traps.

SNMP ProtoNode RER gateway is configured to send Alarm traps to the IP address of the Receiver set within. The alarm Traps
are sent as soon as an active alarm state is noted. The alarms are active when the value of the relative variables is 1.

Below is an example of Traps sent to the Receiver:

INSTALLATION AND MAINTENANCE 21


CLOSE CONTROL AIR CONDITIONERS
6 LIST OF VARIABLES

WARNING!

The names of the variables are always followed by the value of the Node ID used for the
profile (ex. DamperStatusDI_1)

The table identifies the Object names relative to Node ID 1.

6.1 CLOSE CONTROL SURVEYEVO MICROPROCESSOR SUPERVISOR VARIABLES (SOFTWARE VERSION 2.2)

Unit of
OID Name Description Type
measure
Digital input status
.1.3.6.1.4.1.6347.1.1.1.0 DamperStatusDI_1 Motorised damper status
.1.3.6.1.4.1.6347.1.1.2.0 DirtyFilterDI_1 Dirty filter alarm
.1.3.6.1.4.1.6347.1.1.3.0 RemoteOffDI_1 Remote OFF status
.1.3.6.1.4.1.6347.1.1.4.0 ElecHeaterAlarmDI_1 Electric coil safety thermostat alarm
.1.3.6.1.4.1.6347.1.1.5.0 WaterAlarmDI_1 Water sensor/Condensate pump alarm
.1.3.6.1.4.1.6347.1.1.6.0 ConfigurableDI1_1 Configurable input 1
.1.3.6.1.4.1.6347.1.1.7.0 ConfigurableDI2_1 Configurable input 2
.1.3.6.1.4.1.6347.1.1.8.0 ConfigurableDI3_1 Configurable input 3 - R
.1.3.6.1.4.1.6347.1.1.9.0 ConfigurableDI4_1 Configurable input 4
.1.3.6.1.4.1.6347.1.1.10.0 Comp1ThermAlarmDI_1 Compressor 1 breaker alarm
.1.3.6.1.4.1.6347.1.1.11.0 Comp1HPAlarmDI_1 Compressor 1 high pressure alarm
.1.3.6.1.4.1.6347.1.1.12.0 Comp1LPAlarmDI_1 Compressor 1 low pressure alarm
.1.3.6.1.4.1.6347.1.1.13.0 Comp2ThermAlarmDI_1 Compressor 2 breaker alarm
.1.3.6.1.4.1.6347.1.1.14.0 Comp2HPAlarmDI_1 Compressor 2 high pressure alarm
.1.3.6.1.4.1.6347.1.1.15.0 Comp2LowPresAlarmDI_1 Compressor 2 low pressure alarm
Digital output status
.1.3.6.1.4.1.6347.1.1.16.0 FansDO_1 Fan control
.1.3.6.1.4.1.6347.1.1.17.0 DamperDO_1 Motorised dampers control
.1.3.6.1.4.1.6347.1.1.18.0 ElecHeaterStage1DO_1 Electric heating coil 1 stage
.1.3.6.1.4.1.6347.1.1.19.0 ElecHeaterStage2DO_1 Electric heating coil 2 stage
.1.3.6.1.4.1.6347.1.1.20.0 ConfigurableDO1_1 Configurable digital output 1
- R
.1.3.6.1.4.1.6347.1.1.21.0 ConfigurableDO2_1 Configurable digital output 2
.1.3.6.1.4.1.6347.1.1.22.0 ConfigurableDO3_1 Configurable digital output 3
.1.3.6.1.4.1.6347.1.1.23.0 ConfigurableDO4_1 Configurable digital output 4
.1.3.6.1.4.1.6347.1.1.24.0 Compressor1DO_1 Compressor 1 control
.1.3.6.1.4.1.6347.1.1.25.0 Compressor2DO_1 Compressor 2 control

22 TECHNICAL MANUAL
Unit of
OID Name Description Type
measure
Analogue inputs
.1.3.6.1.4.1.6347.1.2.1.0 ReturnHumidity_1 Return humidity %Rh
.1.3.6.1.4.1.6347.1.2.2.0 ReturnTemperature_1 Return temperature °C
.1.3.6.1.4.1.6347.1.2.3.0 SupplyHumidity_1 Supply humidity %Rh
.1.3.6.1.4.1.6347.1.2.4.0 SupplyTemperature_1 Supply temperature °C
.1.3.6.1.4.1.6347.1.2.5.0 AirPressure_1 Air pressure Pa
.1.3.6.1.4.1.6347.1.2.6.0 WaterINTemperature_1 Water inlet 1 temperature/Free cooling °C
.1.3.6.1.4.1.6347.1.2.7.0 WaterOUTTemperature_1 Water outlet temperature 1 °C
.1.3.6.1.4.1.6347.1.2.8.0 Comp1CondPress_1 Compressor 1 condensation pressure BarG
.1.3.6.1.4.1.6347.1.2.9.0 Compr2CondPress_1 Compressor 2 condensation pressure BarG
.1.3.6.1.4.1.6347.1.2.10.0 Compr1CondTemp_1 Compressor 1 condensation temperature °C
.1.3.6.1.4.1.6347.1.2.11.0 Comp2CondTemp_1 Compressor 2 condensation temperature °C
.1.3.6.1.4.1.6347.1.2.12.0 Comp1DischTemp_1 Compressor 1 discharge temperature °C
.1.3.6.1.4.1.6347.1.2.13.0 Comp2DischTemp_1 Compressor 2 discharge temperature °C
.1.3.6.1.4.1.6347.1.2.14.0 Comp1SuctionTemp_1 Compressor 1 suction temperature °C
.1.3.6.1.4.1.6347.1.2.15.0 Comp2SuctionTemp_1 Compressor 2 suction temperature °C
.1.3.6.1.4.1.6347.1.2.16.0 Comp1EvapPres_1 Compressor 1 evaporation pressure BarG
R
.1.3.6.1.4.1.6347.1.2.17.0 Comp2EvapPres_1 Compressor 2 evaporation pressure BarG
.1.3.6.1.4.1.6347.1.2.18.0 Comp1EvapTemp_1 Compressor 1 evaporation temperature °C
.1.3.6.1.4.1.6347.1.2.19.0 Comp2EvapTemp_1 Compressor 2 evaporation temperature °C
.1.3.6.1.4.1.6347.1.2.20.0 Comp1LiquidTemp_1 Compressor 1 liquid temperature °C
.1.3.6.1.4.1.6347.1.2.21.0 Compr2LiquidTemp_1 Compressor 2 liquid temperature °C
.1.3.6.1.4.1.6347.1.2.22.0 WaterFlow1_1 Water flow rate 1) l/h
.1.3.6.1.4.1.6347.1.2.23.0 WaterFlow2_1 Water flow rate 2 l/h
.1.3.6.1.4.1.6347.1.2.24.0 TotalWaterFlow_1 Total water flow rate l/h
.1.3.6.1.4.1.6347.1.2.25.0 ReturnHumidityAvg_1 Return humidity (local network average) %Rh
.1.3.6.1.4.1.6347.1.2.26.0 ReturnTempAvg_1 Return temperature (local network average) °C
.1.3.6.1.4.1.6347.1.2.27.0 SupplyHumidityAvg_1 Supply humidity (local network average) %Rh
.1.3.6.1.4.1.6347.1.2.28.0 SupplyTempAvg_1 Supply temperature (local network average) °C
.1.3.6.1.4.1.6347.1.2.29.0 AirPressureAvg_1 Air pressure (local network average) °C
.1.3.6.1.4.1.6347.1.2.30.0 WaterINTemperature2_1 Water inlet temperature 2 °C
.1.3.6.1.4.1.6347.1.2.31.0 WaterOUTemperature2_1 Water outlet temperature 2 °C
.1.3.6.1.4.1.6347.1.2.32.0 DiffFilterPressure_1
Dirty filter differential pressure Pa
Analogue outputs
.1.3.6.1.4.1.6347.1.2.33.0 UnitFansDryCoolerAO_1 Supply Fan / Dry cooler modulation %
.1.3.6.1.4.1.6347.1.2.34.0 CoolingAO_1 Cooling valve / Free cooling / External inverter %
.1.3.6.1.4.1.6347.1.2.35.0 HeatingAO_1 Heating valve / Modulating electrical coil %
R
.1.3.6.1.4.1.6347.1.2.36.0 TwoSourcesAO_1 Two sources water valve %
.1.3.6.1.4.1.6347.1.2.37.0 Condenser1AO_1 Condenser 1 %
.1.3.6.1.4.1.6347.1.2.38.0 Condenser2HumidifAO_1 Condenser 2 / External humidifier %

INSTALLATION AND MAINTENANCE 23


CLOSE CONTROL AIR CONDITIONERS
Unit of
OID Name Description Type
measure
Unit status
.1.3.6.1.4.1.6347.1.2.39.0 UnitStatus_1 Unit status * - R
* 1 = Unit OFF - 2 = OFF Remote - 3 = OFF from supervisor - 4 = Off from alarm - 5 = Stand-by - 6 = Unit ON - 7 = Ultracap
Supply air flow
.1.3.6.1.4.1.6347.1.2.40.0 AirFlow_1 Air flow m3/h R
Working hours
.1.3.6.1.4.1.6347.1.2.41.0 UnitWorkingHours_1 Unit hours of operation h
.1.3.6.1.4.1.6347.1.2.42.0 Comp1WorkingHours_1 Compressor 1 hours of operation h
.1.3.6.1.4.1.6347.1.2.43.0 Compr2WorkingHours_1 Compressor 2 hours of operation h
.1.3.6.1.4.1.6347.1.2.44.0 HeatingWorkingHours_1 Hours of heating operation h
.1.3.6.1.4.1.6347.1.2.45.0 DryCoolerWorkHours_1 Hours of dry cooler operation h
R
.1.3.6.1.4.1.6347.1.2.46.0 HumidifWorkingHours_1 Hours of humidifier operation h
.1.3.6.1.4.1.6347.1.2.47.0 CoolValveWorkHours_1 Hours of cooling valve operation h
.1.3.6.1.4.1.6347.1.2.48.0 Cond1WorkingHours_1 Condenser 1 hours of operation h
.1.3.6.1.4.1.6347.1.2.49.0 Cond2WorkingHours_1 Condenser 2 hours of operation h
.1.3.6.1.4.1.6347.1.2.50.0 FreeCoolWorkHours_1 Free Cooling hours of operation h
Electronic expansion valves state
.1.3.6.1.4.1.6347.1.2.51.0 EEV1SuperheatSet_1 Current EEV1 superheating set-point K
.1.3.6.1.4.1.6347.1.2.52.0 EEV2SuperheatSet_1 Current EEV2 superheating set-point K
.1.3.6.1.4.1.6347.1.2.53.0 EEV1Superheat_1 Current EEV1 superheating K
.1.3.6.1.4.1.6347.1.2.54.0 EEV2Superheat_1 Current EEV2 superheating K
.1.3.6.1.4.1.6347.1.2.55.0 EEV1Position_1 Current EEV1 position %
.1.3.6.1.4.1.6347.1.2.56.0 EEV2Position_1 Current EEV2 position %
R
.1.3.6.1.4.1.6347.1.2.57.0 EEV1PDesuperheat_1 Current EEV1 desuperheating K
.1.3.6.1.4.1.6347.1.2.58.0 EEV2Desuperheat_1 Current EEV2 desuperheating K
.1.3.6.1.4.1.6347.1.2.59.0 EEV1PSubcooling_1 Current EEV1 sub-cooling K
.1.3.6.1.4.1.6347.1.2.60.0 EEV2Subcooling_1 Current EEV2 sub-cooling K
.1.3.6.1.4.1.6347.1.2.135.0 CompRatio1_1 Compression ratio 1 -
.1.3.6.1.4.1.6347.1.2.136.0 CompRatio2_1 Compression ratio 2 -
Internal humidifier status
.1.3.6.1.4.1.6347.1.2.61.0 HumidifSteamProd_1 Current humidifier production kg/h
.1.3.6.1.4.1.6347.1.2.62.0 HumidifWaterConduct_1 Supply water conductivity μS/cm
R
.1.3.6.1.4.1.6347.1.2.63.0 HumidifierCurrent_1 Absorbed humidifier current A
.1.3.6.1.4.1.6347.1.2.64.0 HumidifWorkingMode_1 Humidifier operating mode * -
* 1 = Not active; 2 = Soft-start; 3 = Start full production after reduced production; 4 = Full production; 5 = Reduced production; 6,
7, 8 = Soft-start
.1.3.6.1.4.1.6347.1.2.65.0 HumidifWorkStatus_1 Humidifier operating status * - R
* 1 = Not active (no demand or blocked or disabled); 2 = Start evaporation cycle; 3 = Water charging in progress; 4 = Evaporation
in progress; 5 = AFS discharge; 6 = Water discharge (through dilution or manual); 7 = End of water discharge; 8 = Full discharge for
long period of downtime; 9 = Full discharge from manual or network request; 10 = No water control; 11 = Pre-wash; 12 = Periodic
discharge
.1.3.6.1.4.1.6347.1.1.26.0 HumidifierPowerDO_1 Humidifier control
.1.3.6.1.4.1.6347.1.1.27.0 HumidifDrainValveDO_1 Discharge valve
- R
.1.3.6.1.4.1.6347.1.1.28.0 HumidifFillValveDO_1 Charging valve
.1.3.6.1.4.1.6347.1.1.29.0 HumidifWaterLevel_1 High water level

24 TECHNICAL MANUAL
Unit of
OID Name Description Type
measure
Fan status
.1.3.6.1.4.1.6347.1.2.66.0 Fan1SpeedRPM_1 Fan 1 speed RPM
.1.3.6.1.4.1.6347.1.2.67.0 Fan2SpeedRPM_1 Fan 2 speed RPM
.1.3.6.1.4.1.6347.1.2.68.0 Fan3SpeedRPM_1 Fan 3 speed RPM
.1.3.6.1.4.1.6347.1.2.69.0 Fan4SpeedRPM_1 Fan 4 speed RPM
.1.3.6.1.4.1.6347.1.2.70.0 Fan5SpeedRPM_1 Fan 5 speed RPM
.1.3.6.1.4.1.6347.1.2.71.0 Fan1Speed_1 Fan 1 speed %
.1.3.6.1.4.1.6347.1.2.72.0 Fan2Speed_1 Fan 2 speed %
.1.3.6.1.4.1.6347.1.2.73.0 Fan3Speed_1 Fan 3 speed %
.1.3.6.1.4.1.6347.1.2.74.0 Fan4Speed_1 Fan 4 speed %
.1.3.6.1.4.1.6347.1.2.75.0 Fan5Speed_1 Fan 5 speed %
R
.1.3.6.1.4.1.6347.1.2.76.0 Fan1Current_1 Fan 1 absorbed current A
.1.3.6.1.4.1.6347.1.2.77.0 Fan1Power_1 Fan 1 absorbed electrical power W
.1.3.6.1.4.1.6347.1.2.78.0 Fan2Current_1 Fan 2 absorbed current A
.1.3.6.1.4.1.6347.1.2.79.0 Fan2Power_1 Fan 2 absorbed electrical power W
.1.3.6.1.4.1.6347.1.2.80.0 Fan3Current_1 Fan 3 absorbed current A
.1.3.6.1.4.1.6347.1.2.81.0 Fan3Power_1 Fan 3 absorbed electrical power W
.1.3.6.1.4.1.6347.1.2.82.0 Fan4Current_1 Fan 4 absorbed current A
.1.3.6.1.4.1.6347.1.2.83.0 Fan4Power_1 Fan 4 absorbed electrical power W
.1.3.6.1.4.1.6347.1.2.84.0 Fan5Current_1 Fan 5 absorbed current A
.1.3.6.1.4.1.6347.1.2.85.0 Fan5Power_1 Fan 5 absorbed electrical power W
DC compressor inverter status
.1.3.6.1.4.1.6347.1.2.86.0 InverterCompSpeed_1 Current compressor speed Hz
.1.3.6.1.4.1.6347.1.2.87.0 InverterCompPower_1 Current compressor electrical power kW R
.1.3.6.1.4.1.6347.1.2.88.0 InverterCompCurrent_1 Current compressor absorbed current A
Water cooling power
.1.3.6.1.4.1.6347.1.2.89.0 WaterCoolingCap1_1 Chilled water cooling capacity 1 kW
.1.3.6.1.4.1.6347.1.2.90.0 EER1_1 EER 1 -
R
.1.3.6.1.4.1.6347.1.2.137.0 WaterCoolingCap2_1 Chilled water cooling capacity 2 kW
.1.3.6.1.4.1.6347.1.2.138.0 EER2_1 EER 2 -
Electric coil status
.1.3.6.1.4.1.6347.1.2.91.0 HeaterActiveStages_1 Number of active stages -
R
.1.3.6.1.4.1.6347.1.2.92.0 ElecHeaterPower_1 Electrical power requirement kW

INSTALLATION AND MAINTENANCE 25


CLOSE CONTROL AIR CONDITIONERS

Unit of
OID Name Description Type
measure
On/Off from supervision
.1.3.6.1.4.1.6347.1.1.30.0 SupervOFF_1 On/Off from supervisor - R/W
Set-point
.1.3.6.1.4.1.6347.1.2.93.0 TemperatureSetpoint_1 Temperature set-point °C
R/W
.1.3.6.1.4.1.6347.1.2.94.0 HumiditySetpoint_1 Humidity set-point %Rh
Ventilation set-point
.1.3.6.1.4.1.6347.1.2.95.0 AirFlowSetpoint_1 Supply air flow rate set-point m3/h
R/W
.1.3.6.1.4.1.6347.1.2.96.0 AirPressureSetpoint_1 Air pressure set-point Pa
Temperature Regulation
.1.3.6.1.4.1.6347.1.2.97.0 TempControlSel_1 Regulation sensor * - R/W
* 1 = Return; 2 = Supply
.1.3.6.1.4.1.6347.1.2.98.0 TempControlType_1 Regulation type * - R/W
* 1 = Proportional (P); 2 = Proportional + Integral (PI); 3 = Proportional + Integral + Derivative (PID)
.1.3.6.1.4.1.6347.1.2.99.0 ProportionalBand_1 Proportional Band °C
.1.3.6.1.4.1.6347.1.2.100.0 IntagrativeTime_1 Integration time s
.1.3.6.1.4.1.6347.1.2.101.0 DerivativeTime_1 Derivative time s R/W
.1.3.6.1.4.1.6347.1.2.102.0 HighTempAlarmOffset_1 High temperature alarm offset °C
.1.3.6.1.4.1.6347.1.2.103.0 LowTempAlarmOffset_1 Low temperature alarm offset °C
Limit temperature regulation
.1.3.6.1.4.1.6347.1.2.104.0 HighLimitTempThr_1 Upper temperature limit °C
R/W
.1.3.6.1.4.1.6347.1.2.105.0 HighLimitTempMng_1 High limit temperature management * -
* 1 = Alarm only; 2 = Stop component; 3 = Reduction; 4 = Cold activation
.1.3.6.1.4.1.6347.1.2.106.0 LowLimitTempThr_1 Lower temperature limit °C
R/W
.1.3.6.1.4.1.6347.1.2.107.0 LowLimitTempMng_1 Low limit temperature management * -
* 1 = Alarm only; 2 = Stop component; 3 = Reduction; 4 = Hot activation
Humidity regulation
.1.3.6.1.4.1.6347.1.2.108.0 DehumidifPropBand_1 Dehumidification proportional band %RH
.1.3.6.1.4.1.6347.1.2.109.0 HumidifPropBand_1 Humidification proportional band %RH
.1.3.6.1.4.1.6347.1.2.110.0 HighRetHumAlOffset_1 High return humidity alarm offset %RH
R/W
.1.3.6.1.4.1.6347.1.2.111.0 LowRetHumAlOffset_1 Low return humidity alarm offset %RH
.1.3.6.1.4.1.6347.1.2.112.0 HighSupHumThr_1 Upper supply humidity limit %RH
.1.3.6.1.4.1.6347.1.2.113.0 LowSupHumThr_1 Lower supply humidity limit %RH
Humidifier regulation
.1.3.6.1.4.1.6347.1.1.31.0 EnableHumidifier_1 Humidification enabling
.1.3.6.1.4.1.6347.1.1.32.0 HumidifManualDrain_1 Manual discharge - R/W
.1.3.6.1.4.1.6347.1.1.33.0 HumidifCylWashing_1 Cylinder pre-wash
Free cooling and two sources regulation
.1.3.6.1.4.1.6347.1.2.114.0 FreeCoolingDelta_1 Free cooling delta °C
.1.3.6.1.4.1.6347.1.2.115.0 TSWaterSetpoint_1 Two sources water set-point °C
R/W
.1.3.6.1.4.1.6347.1.2.116.0 TSWaterPropBand_1 Two sources water band °C
.1.3.6.1.4.1.6347.1.1.34.0 TSEchange_1 Two sources source exchange -
Condenser regulation
.1.3.6.1.4.1.6347.1.2.117.0 Cond1ActualSet_1 Current condenser 1 set-point °C
.1.3.6.1.4.1.6347.1.2.118.0 Cond2ActualSet_1 Current condenser 2 set-point °C
.1.3.6.1.4.1.6347.1.2.119.0 CondSetpoint_1 Condensation set-point °C
R/W
.1.3.6.1.4.1.6347.1.2.120.0 CondPropoBand_1 Condensation proportional band °C
.1.3.6.1.4.1.6347.1.2.121.0 CondSetIncrease_1 Condensation set-point increase °C
.1.3.6.1.4.1.6347.1.2.122.0 MaxCondSetpoint_1 Maximum condensation set-point °C

26 TECHNICAL MANUAL
Unit of
OID Name Description Type
measure
Dry cooler regulation
.1.3.6.1.4.1.6347.1.2.123.0 DryCoolerActualSet_1 Current dry cooler set-point °C
.1.3.6.1.4.1.6347.1.2.124.0 DryCoolerSetpoint_1 Dry cooler set-point °C
.1.3.6.1.4.1.6347.1.2.125.0 DryCoolerPropBand_1 Dry Cooler proportional band °C R/W
.1.3.6.1.4.1.6347.1.2.126.0 DryCoolerSetIncr_1 Dry Cooler set-point increase °C
.1.3.6.1.4.1.6347.1.2.127.0 MaxDryCoolerSet_1 Maximum dry Cooler set-point °C
Dirty filter regulation
.1.3.6.1.4.1.6347.1.2.128.0 DirtyFiltersSet_1 Dirty filter set-point Pa
R/W
.1.3.6.1.4.1.6347.1.2.129.0 DirtyFiltersDiff_1 Dirty filter differential Pa

INSTALLATION AND MAINTENANCE 27


CLOSE CONTROL AIR CONDITIONERS

Unit of
OID Name Description Type
measure
Alarms
.1.3.6.1.4.1.6347.1.3.1.0 RetHumProbAl_1 Broken return humidity probe alarm
.1.3.6.1.4.1.6347.1.3.2.0 RetTempProbAl_1 Broken return temperature probe alarm
.1.3.6.1.4.1.6347.1.3.3.0 AirPrSensorAl_1 Broken air differential pressure sensor alarm
.1.3.6.1.4.1.6347.1.3.4.0 SupTempProbAl_1 Broken supply temperature probe alarm
Broken IN 1 water temperature probe alarm
.1.3.6.1.4.1.6347.1.3.5.0 WatIN1ProbAl_1
Broken free cooling temperature probe alarm
.1.3.6.1.4.1.6347.1.3.6.0 WatOUT1ProbAl_1 Broken OUT 1 water temperature probe alarm
Broken water flow 1 sensor alarm
.1.3.6.1.4.1.6347.1.3.7.0 WatFlw1ProbAl_1
Broken liquid 1 temperature probe alarm
.1.3.6.1.4.1.6347.1.3.8.0 SupHumProbAl_1 Broken supply humidity probe alarm
Broken water flow 2 sensor alarm
.1.3.6.1.4.1.6347.1.3.9.0 WatFlw2ProbAl_1
Broken liquid 2 temperature probe alarm
Water presence sensor alarm
.1.3.6.1.4.1.6347.1.3.10.0 WatPresAl_1
Condensate discharge pump alarm
.1.3.6.1.4.1.6347.1.3.11.0 ElHeatAl_1 Electric coil safety thermostat
.1.3.6.1.4.1.6347.1.3.12.0 DamperAl_1 Damper status alarm
.1.3.6.1.4.1.6347.1.3.13.0 FilterAl_1 Clogged air filter alarm
.1.3.6.1.4.1.6347.1.3.14.0 C1ThermAl_1 Compressor 1 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.3.15.0 C2ThermAl_1 Compressor 2 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.3.16.0 C1HighPresAl_1 Compressor 1 high pressure alarm
.1.3.6.1.4.1.6347.1.3.17.0 C2HighPresAl_1 Compressor 2 high pressure alarm
.1.3.6.1.4.1.6347.1.3.18.0 C1LowPresAl_1 Compressor 1 low pressure alarm
.1.3.6.1.4.1.6347.1.3.19.0 C2LowPresAl_1 Compressor 2 low pressure alarm
.1.3.6.1.4.1.6347.1.3.20.0 C1HighDischAl_1 Compressor 1 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.3.21.0 C2HighDischAl_1 Compressor 2 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.3.22.0 EEV1Al_1 EEV 1 alarm
.1.3.6.1.4.1.6347.1.3.23.0 EEV2Al_1 EEV 2 alarm - R
.1.3.6.1.4.1.6347.1.3.24.0 InverterCompAl_1 DC compressor inverter alarm
.1.3.6.1.4.1.6347.1.3.25.0 Fan1InverterAl_1 Fan 1 inverter alarm
.1.3.6.1.4.1.6347.1.3.26.0 Fan2InverterAl_1 Fan 2 inverter alarm
.1.3.6.1.4.1.6347.1.3.27.0 Fan3InverterAl_1 Fan 3 inverter alarm
.1.3.6.1.4.1.6347.1.3.28.0 Fan4InverterAl_1 Fan 4 inverter alarm
.1.3.6.1.4.1.6347.1.3.29.0 Fan5InverterAl_1 Fan 5 inverter alarm
.1.3.6.1.4.1.6347.1.3.30.0 InternalHumidifAl_1 Internal humidifier alarm
.1.3.6.1.4.1.6347.1.3.31.0 LocalNetworkAl_1 Local network communication alarm
.1.3.6.1.4.1.6347.1.3.32.0 RegHighTempAl_1 High temperature regulation alarm
.1.3.6.1.4.1.6347.1.3.33.0 RegLowTempAl_1 Low temperature regulation alarm
.1.3.6.1.4.1.6347.1.3.34.0 RetHighHumiAl_1 High return humidity alarm
.1.3.6.1.4.1.6347.1.3.35.0 RetLowHumiAl_1 Low return humidity alarm
.1.3.6.1.4.1.6347.1.3.36.0 SupHighHumiAl_1 High supply humidity alarm
.1.3.6.1.4.1.6347.1.3.37.0 SupLowHumiAl_1 Low supply humidity alarm
.1.3.6.1.4.1.6347.1.3.38.0 HighLimTempAl_1 High limit temperature alarm
.1.3.6.1.4.1.6347.1.3.39.0 LowLimTempAl_1 Low limit temperature alarm
.1.3.6.1.4.1.6347.1.3.40.0 DryCoolerAl_1 Dry cooler general alarm
.1.3.6.1.4.1.6347.1.3.41.0 ExternalHumidifAl_1 External humidifier general alarm
.1.3.6.1.4.1.6347.1.3.42.0 WaterPumpAl_1 General water pump alarm
.1.3.6.1.4.1.6347.1.3.43.0 Condenser1Al_1 Condenser 1 general alarm
.1.3.6.1.4.1.6347.1.3.44.0 Condenser2Al_1 Condenser 2 general alarm
.1.3.6.1.4.1.6347.1.3.45.0 GasLeakAl_1 Refrigerant gas leak detector alarm
.1.3.6.1.4.1.6347.1.3.46.0 FansGenAl_1 General supply fans alarm
.1.3.6.1.4.1.6347.1.3.47.0 FireSmokeAl_1 Fire/Smoke presence alarm
.1.3.6.1.4.1.6347.1.3.48.0 GenericSoftAl_1 Non-critical generic alarm

28 TECHNICAL MANUAL
Unit of
OID Name Description Type
measure
.1.3.6.1.4.1.6347.1.3.49.0 GenericSeriousAl_1 Critical generic alarm
.1.3.6.1.4.1.6347.1.3.50.0 CondUnitGeneralAl_1 Condensing unit generic alarm
.1.3.6.1.4.1.6347.1.3.51.0 PowerSupplyAl_1 No power supply alarm
.1.3.6.1.4.1.6347.1.3.52.0 C1LowComprRatioAl_1 Compressor 1 low compression alarm
.1.3.6.1.4.1.6347.1.3.53.0 C2LowComprRatioAl_1 Compressor 2 low compression alarm
.1.3.6.1.4.1.6347.1.3.54.0 WatIN2ProbAl_1 Broken IN 2 water temperature probe alarm
.1.3.6.1.4.1.6347.1.3.55.0 WatOUT2ProbAl_1 Broken OUT 2 water temperature probe alarm
.1.3.6.1.4.1.6347.1.3.56.0 DirtyFiltPresSensAl_1 Dirty filter pressure sensor alarm
.1.3.6.1.4.1.6347.1.3.57.0 EEV1CommAl_1 EEV1 communication down alarm
.1.3.6.1.4.1.6347.1.3.58.0 EEV1SuctProbAl_1 EEV1 suction temperature probe alarm
.1.3.6.1.4.1.6347.1.3.59.0 EEV1EvapProbAl_1 EEV1 evaporation pressure probe alarm
.1.3.6.1.4.1.6347.1.3.60.0 EEV1CondProbAl_1 EEV1 condensation pressure probe alarm
.1.3.6.1.4.1.6347.1.3.61.0 EEV1DischProbAl_1 EEV1 discharge temperature probe alarm
.1.3.6.1.4.1.6347.1.3.62.0 EEV2CommAl_1 EEV2 communication down alarm
.1.3.6.1.4.1.6347.1.3.63.0 EEV2SuctProbAl_1 EEV2 suction temperature probe alarm
.1.3.6.1.4.1.6347.1.3.64.0 EEV2EvapProbAl_1 EEV2 evaporation pressure probe alarm
.1.3.6.1.4.1.6347.1.3.65.0 EEV2CondProbAl_1 EEV2 condensation pressure probe alarm
.1.3.6.1.4.1.6347.1.3.66.0 EEV2DischProbAl_1 EEV2 discharge temperature probe alarm
.1.3.6.1.4.1.6347.1.3.67.0 CPYCommAl_1 CPY communication down alarm
.1.3.6.1.4.1.6347.1.3.68.0 CPYMemoryAl_1 Internal memory error
.1.3.6.1.4.1.6347.1.3.69.0 CPYParameterAl_1 Parameter error
.1.3.6.1.4.1.6347.1.3.70.0 CPYHighCurrentAl_1 High electrode current
.1.3.6.1.4.1.6347.1.3.71.0 CPYLowSteamAl_1 Low steam flow rate
.1.3.6.1.4.1.6347.1.3.72.0 CPYDrainAl_1 Failed discharge
.1.3.6.1.4.1.6347.1.3.73.0 CPYMaintAl_1 Maintenance time expired
.1.3.6.1.4.1.6347.1.3.74.0 CPYNoWaterAl_1 No water
- R
.1.3.6.1.4.1.6347.1.3.75.0 CPYCylMaintAl_1 Cylinder maintenance
.1.3.6.1.4.1.6347.1.3.76.0 CPYDirtyCylAl_1 Cylinder burnt out
.1.3.6.1.4.1.6347.1.3.77.0 CPYFoamAl_1 Foam presence
.1.3.6.1.4.1.6347.1.3.78.0 CPYLifeTimeAl_1 Life timer expired
.1.3.6.1.4.1.6347.1.3.79.0 CPYHighWatLevAl_1 High water level
.1.3.6.1.4.1.6347.1.3.80.0 CPYHighWatConductAl_1 High water conductivity
.1.3.6.1.4.1.6347.1.3.81.0 CPYConnectionAl_1 Connection error
.1.3.6.1.4.1.6347.1.3.82.0 Fan1PowerAl_1 Fan 1 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.3.83.0 Fan1CommAl_1 Fan 1 communication down alarm
.1.3.6.1.4.1.6347.1.3.84.0 Fan1HighTempAl_1 Fan 1 regulation module high temperature
.1.3.6.1.4.1.6347.1.3.85.0 Fan1NetComAl_1 Fan 1 no master-slave communication
.1.3.6.1.4.1.6347.1.3.86.0 Fan1InvRegAl_1 Fan 1 regulation module failure
.1.3.6.1.4.1.6347.1.3.87.0 Fan1HighMotTempAl_1 High fan 1 motor temperature
.1.3.6.1.4.1.6347.1.3.88.0 Fan1HallSensAl_1 Fan 1 Hall sensor error
.1.3.6.1.4.1.6347.1.3.89.0 Fan1OverloadAl_1 Fan 1 motor overload
.1.3.6.1.4.1.6347.1.3.94.0 Fan1LowDCAl_1 Low fan 1 DC power supply
.1.3.6.1.4.1.6347.1.3.95.0 Fan2PowerAl_1 Fan 2 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.3.96.0 Fan2CommAl_1 Fan 2 communication down alarm
.1.3.6.1.4.1.6347.1.3.97.0 Fan2HighTempAl_1 Fan 2 regulation module high temperature
.1.3.6.1.4.1.6347.1.3.98.0 Fan2NetComAl_1 Fan 2 no master-slave communication
.1.3.6.1.4.1.6347.1.3.99.0 Fan2InvRegAl_1 Fan 2 regulation module failure
.1.3.6.1.4.1.6347.1.3.100.0 Fan2HighMotTempAl_1 High fan 2 motor temperature
.1.3.6.1.4.1.6347.1.3.101.0 Fan2HallSensAl_1 Fan 2 Hall sensor error
.1.3.6.1.4.1.6347.1.3.102.0 Fan2OverloadAl_1 Fan 2 motor overload
.1.3.6.1.4.1.6347.1.3.107.0 Fan2LowDCAl_1 Low fan 2 DC power supply
.1.3.6.1.4.1.6347.1.3.108.0 Fan3PowerAl_1 Fan 3 no phase/power supply alarm

INSTALLATION AND MAINTENANCE 29


CLOSE CONTROL AIR CONDITIONERS

Unit of
OID Name Description Type
measure
.1.3.6.1.4.1.6347.1.3.109.0 Fan3CommAl_1 Fan 3 communication down alarm
.1.3.6.1.4.1.6347.1.3.110.0 Fan3HighTempAl_1 Fan 3 regulation module high temperature
.1.3.6.1.4.1.6347.1.3.111.0 Fan3NetComAl_1 Fan 3 no master-slave communication
.1.3.6.1.4.1.6347.1.3.112.0 Fan3InvRegAl_1 Fan 3 regulation module failure
.1.3.6.1.4.1.6347.1.3.113.0 Fan3HighMotTempAl_1 High fan 3 motor temperature
.1.3.6.1.4.1.6347.1.3.114.0 Fan3HallSensAl_1 Fan 3 Hall sensor error
.1.3.6.1.4.1.6347.1.3.115.0 Fan3OverloadAl_1 Fan 3 motor overload
.1.3.6.1.4.1.6347.1.3.120.0 Fan3LowDCAl_1 Low fan 3 DC power supply
.1.3.6.1.4.1.6347.1.3.121.0 Fan4PowerAl_1 Fan 4 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.3.122.0 Fan4CommAl_1 Fan 4 communication down alarm
.1.3.6.1.4.1.6347.1.3.123.0 Fan4HighTempAl_1 Fan 4 regulation module high temperature
.1.3.6.1.4.1.6347.1.3.124.0 Fan4NetComAl_1 Fan 4 no master-slave communication
.1.3.6.1.4.1.6347.1.3.125.0 Fan4InvRegAl_1 Fan 4 regulation module failure
.1.3.6.1.4.1.6347.1.3.126.0 Fan4HighMotTempAl_1 High fan 4 motor temperature
.1.3.6.1.4.1.6347.1.3.127.0 Fan4HallSensAl_1 Fan 4 Hall sensor error
.1.3.6.1.4.1.6347.1.3.128.0 Fan4OverloadAl_1 Fan 4 motor overload
.1.3.6.1.4.1.6347.1.3.133.0 Fan4LowDCAl_1 Low fan 4 DC power supply
.1.3.6.1.4.1.6347.1.3.134.0 Fan5PowerAl_1 Fan 5 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.3.135.0 Fan5CommAl_1 Fan 5 communication down alarm
.1.3.6.1.4.1.6347.1.3.136.0 Fan5HighTempAl_1 Fan 5 regulation module high temperature
- R
.1.3.6.1.4.1.6347.1.3.137.0 Fan5NetComAl_1 Fan 5 no master-slave communication
.1.3.6.1.4.1.6347.1.3.138.0 Fan5InvRegAl_1 Fan 5 regulation module failure
.1.3.6.1.4.1.6347.1.3.139.0 Fan5HighMotTempAl_1 High fan 5 motor temperature
.1.3.6.1.4.1.6347.1.3.140.0 Fan5HallSensAl_1 Fan 5 Hall sensor error
.1.3.6.1.4.1.6347.1.3.141.0 Fan5OverloadAl_1 Fan 5 motor overload
.1.3.6.1.4.1.6347.1.3.146.0 Fan5LowDCAl_1 Low fan 5 DC power supply
.1.3.6.1.4.1.6347.1.3.147.0 DFPSBrokenAl_1 Broken dirty filter pressure sensor alarm
.1.3.6.1.4.1.6347.1.3.148.0 DFPSCablingAl_1 Dirty filter pressure sensor cabling alarm
.1.3.6.1.4.1.6347.1.3.149.0 DFPSRangeAl_1 Dirty filter pressure sensor pressure range alarm
.1.3.6.1.4.1.6347.1.3.150.0 DFPSADCAl_1 Dirty filter pressure sensor overload ADC alarm
.1.3.6.1.4.1.6347.1.3.151.0 DFPSSettingAl_1 Dirty filter pressure sensor calibration alarm
.1.3.6.1.4.1.6347.1.3.152.0 DFPSDCOAl_1 Dirty filter pressure sensor DCO alarm
.1.3.6.1.4.1.6347.1.3.153.0 DFPSWatchdogAl_1 Dirty filter pressure sensor watchdog alarm
.1.3.6.1.4.1.6347.1.3.154.0 DFPSCommAl_1 Dirty filter pressure sensor communication alarm
.1.3.6.1.4.1.6347.1.3.155.0 InvCompCommAlarm_1 DC compressor inverter communication alarm
.1.3.6.1.4.1.6347.1.2.130.0 InvCompAlCode1_1 DC compressor inverter alarm code [0] *
.1.3.6.1.4.1.6347.1.2.131.0 InvCompAlCode2_1 DC compressor inverter alarm code [1] *
.1.3.6.1.4.1.6347.1.2.132.0 InvCompAlCode3_1 DC compressor inverter alarm code [2] *
.1.3.6.1.4.1.6347.1.2.133.0 InvCompAlCode4_1 DC compressor inverter alarm code [3] *
.1.3.6.1.4.1.6347.1.2.134.0 InvCompAlCode5_1 DC compressor inverter alarm code [4] *
* 48 = 0; 49 = 1; 50 = 2; 51 = 3; 52 = 4; 53 = 5; 54 = 6; 55 = 7; 56 = 8; 57 = 9; 70 = F

30 TECHNICAL MANUAL
Unit of
OID Name Description Type
measure
Alarms reset
Water presence sensor alarm reset
.1.3.6.1.4.1.6347.1.1.35.0 WatPresAlRes_1
Condensate discharge pump alarm reset
.1.3.6.1.4.1.6347.1.1.36.0 ElHeatAlRes_1 Electr. coil safety thermostat alarm reset
.1.3.6.1.4.1.6347.1.1.37.0 DamperAlRes_1 Damper status alarm reset
.1.3.6.1.4.1.6347.1.1.38.0 FilterAlRes_1 Clogged air filter alarm reset
Compressor 1 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.1.39.0 C1ThermAlRes_1
reset
Compressor 2 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.1.40.0 C2ThermAlRes_1
reset
.1.3.6.1.4.1.6347.1.1.41.0 C1HighPresAlRes_1 Compressor 1 high pressure alarm reset
.1.3.6.1.4.1.6347.1.1.42.0 C2HighPresAlRes_1 Compressor 2 high pressure alarm reset
Compressor 1 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.1.43.0 C1HighDischAlRes_1
reset
Compressor 2 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.1.44.0 C2HighDischAlRes_1
reset
.1.3.6.1.4.1.6347.1.1.45.0 EEV1AlRes_1 Compressor 1 EEV alarm reset
.1.3.6.1.4.1.6347.1.1.46.0 EEV2AlRes_1 Compressor 2 EEV alarm reset
.1.3.6.1.4.1.6347.1.1.47.0 InverterCompAlRes_1 Compressor 1 inverter alarm reset
.1.3.6.1.4.1.6347.1.1.48.0 C1LoComprRatioAlRes_1 Comp. 1 low compression alarm reset
.1.3.6.1.4.1.6347.1.1.49.0 C2LoComprRatioAlRes_1 Comp. 2 low compression alarm reset
.1.3.6.1.4.1.6347.1.1.50.0 Fan1InverterAlRes_1 Fan 1 inverter alarm reset - RW
.1.3.6.1.4.1.6347.1.1.51.0 Fan2InverterAlRes_1 Fan 2 inverter alarm reset
.1.3.6.1.4.1.6347.1.1.52.0 Fan3InverterAlRes_1 Fan 3 inverter alarm reset
.1.3.6.1.4.1.6347.1.1.53.0 Fan4InverterAlRes_1 Fan 4 inverter alarm reset
.1.3.6.1.4.1.6347.1.1.54.0 Fan5InverterAlRes_1 Fan 5 inverter alarm reset
.1.3.6.1.4.1.6347.1.1.55.0 IntHumidifAlRes_1 Internal humidifier alarm reset
.1.3.6.1.4.1.6347.1.1.56.0 DryCoolerAlRes_1 Dry cooler general alarm reset
.1.3.6.1.4.1.6347.1.1.57.0 ExtHumidifAlRes_1 External humidifier general alarm reset
.1.3.6.1.4.1.6347.1.1.58.0 WaterPumpAlRes_1 General water pump alarm reset
.1.3.6.1.4.1.6347.1.1.59.0 Condenser1AlRes_1 Condenser 1 general alarm reset
.1.3.6.1.4.1.6347.1.1.60.0 Condenser2AlRes_1 Condenser 2 general alarm reset
.1.3.6.1.4.1.6347.1.1.61.0 GasLeakAlRes_1 Refrigerant gas leak detector alarm reset
.1.3.6.1.4.1.6347.1.1.62.0 FansGenAlRes_1 General supply fans alarm reset
.1.3.6.1.4.1.6347.1.1.63.0 FireSmokeAlRes_1 Fire/Smoke presence alarm reset
.1.3.6.1.4.1.6347.1.1.64.0 GenericSoftAlRes_1 Non-critical generic alarm reset
.1.3.6.1.4.1.6347.1.1.65.0 GenericSeriousAlRes_1 Critical generic alarm reset
.1.3.6.1.4.1.6347.1.1.66.0 CondUnitGenAlRes_1 Condensing unit generic alarm reset
.1.3.6.1.4.1.6347.1.1.67.0 PowerSupplyAlRes_1 No power supply alarm reset
.1.3.6.1.4.1.6347.1.1.68.0 C1LowPresAlRes_1 Compressor 1 low pressure alarm reset
.1.3.6.1.4.1.6347.1.1.69.0 C2LowPresAlRes_1 Compressor 2 low pressure alarm reset

INSTALLATION AND MAINTENANCE 31


CLOSE CONTROL AIR CONDITIONERS

Unit of
OID Name Description Type
measure
Remote module probes
.1.3.6.1.4.1.6347.1.2.139.0 Probe1Module1Value_1 Probe 1 module 1 value
.1.3.6.1.4.1.6347.1.2.140.0 Probe2Module1Value_1 Probe 2 module 1 value
.1.3.6.1.4.1.6347.1.2.141.0 Probe3Module1Value_1 Probe 3 module 1 value
.1.3.6.1.4.1.6347.1.2.142.0 Probe4Module1Value_1 Probe 4 module 1 value
.1.3.6.1.4.1.6347.1.2.143.0 Probe5Module1Value_1 Probe 5 module 1 value
.1.3.6.1.4.1.6347.1.2.144.0 Probe6Module1Value_1 Probe 6 module 1 value
.1.3.6.1.4.1.6347.1.2.145.0 Probe1Module2Value_1 Probe 1 module 2 value
.1.3.6.1.4.1.6347.1.2.146.0 Probe2Module2Value_1 Probe 2 module 2 value
.1.3.6.1.4.1.6347.1.2.147.0 Probe3Module2Value_1 Probe 3 module 2 value
-
.1.3.6.1.4.1.6347.1.2.148.0 Probe4Module2Value_1 Probe 4 module 2 value
.1.3.6.1.4.1.6347.1.2.149.0 Probe5Module2Value_1 Probe 5 module 2 value R
.1.3.6.1.4.1.6347.1.2.150.0 Probe6Module2Value_1 Probe 6 module 2 value
.1.3.6.1.4.1.6347.1.2.151.0 Probe1Module3Value_1 Probe 1 module 3 value
.1.3.6.1.4.1.6347.1.2.152.0 Probe2Module3Value_1 Probe 2 module 3 value
.1.3.6.1.4.1.6347.1.2.153.0 Probe3Module3Value_1 Probe 3 module 3 value
.1.3.6.1.4.1.6347.1.2.154.0 Probe4Module3Value_1 Probe 4 module 3 value
.1.3.6.1.4.1.6347.1.2.155.0 Probe5Module3Value_1 Probe 5 module 3 value
.1.3.6.1.4.1.6347.1.2.156.0 Probe6Module3Value_1 Probe 6 module 3 value
.1.3.6.1.4.1.6347.1.2.157.0 AvgTempProbeValue_1 Modules temperature probes average °C
.1.3.6.1.4.1.6347.1.2.158.0 AvgHumiProbeValue_1 Modules humidity probes average %Rh
.1.3.6.1.4.1.6347.1.2.159.0 AvgPressProbeValue_1 Modules pressure probes average Pa
Remote module probes status
.1.3.6.1.4.1.6347.1.2.160.0 Probe1Module1Status_1 Probe 1 module 1 status *
.1.3.6.1.4.1.6347.1.2.161.0 Probe2Module1Status_1 Probe 2 module 1 status *
.1.3.6.1.4.1.6347.1.2.162.0 Probe3Module1Status_1 Probe 3 module 1 status *
.1.3.6.1.4.1.6347.1.2.163.0 Probe4Module1Status_1 Probe 4 module 1 status *
.1.3.6.1.4.1.6347.1.2.164.0 Probe5Module1Status_1 Probe 5 module 1 status *
.1.3.6.1.4.1.6347.1.2.165.0 Probe6Module1Status_1 Probe 6 module 1 status *
.1.3.6.1.4.1.6347.1.2.166.0 Probe1Module2Status_1 Probe 1 module 2 status *
.1.3.6.1.4.1.6347.1.2.167.0 Probe2Module2Status_1 Probe 2 module 2 status *
.1.3.6.1.4.1.6347.1.2.168.0 Probe3Module2Status_1 Probe 3 module 2 status *
- R
.1.3.6.1.4.1.6347.1.2.169.0 Probe4Module2Status_1 Probe 4 module 2 status *
.1.3.6.1.4.1.6347.1.2.170.0 Probe5Module2Status_1 Probe 5 module 2 status *
.1.3.6.1.4.1.6347.1.2.171.0 Probe6Module2Status_1 Probe 6 module 2 status *
.1.3.6.1.4.1.6347.1.2.172.0 Probe1Module3Status_1 Probe 1 module 3 status *
.1.3.6.1.4.1.6347.1.2.173.0 Probe2Module3Status_1 Probe 2 module 3 status *
.1.3.6.1.4.1.6347.1.2.174.0 Probe3Module3Status_1 Probe 3 module 3 status *
.1.3.6.1.4.1.6347.1.2.175.0 Probe4Module3Status_1 Probe 4 module 3 status *
.1.3.6.1.4.1.6347.1.2.176.0 Probe5Module3Status_1 Probe 5 module 3 status *
.1.3.6.1.4.1.6347.1.2.177.0 Probe6Module3Status_1 Probe 6 module 3 status *
* 0 = Disabled; 1 = Temperature; 2 = Humidity; 3 = Pressure; 4 = Alarm

32 TECHNICAL MANUAL
Remote module probes alarms
.1.3.6.1.4.1.6347.1.3.156.0 ComMod1Alr_1 Module 1 communication alarm
.1.3.6.1.4.1.6347.1.3.157.0 Mod1Probe1Alr_1 Probe 1 module 1 alarm
.1.3.6.1.4.1.6347.1.3.158.0 Mod1Probe2Alr_1 Probe 2 module 1 alarm
.1.3.6.1.4.1.6347.1.3.159.0 Mod1Probe3Alr_1 Probe 3 module 1 alarm
.1.3.6.1.4.1.6347.1.3.160.0 Mod1Probe4Alr_1 Probe 4 module 1 alarm
.1.3.6.1.4.1.6347.1.3.161.0 Mod1Probe5Alr_1 Probe 5 module 1 alarm
.1.3.6.1.4.1.6347.1.3.162.0 Mod1Probe6Alr_1 Probe 6 module 1 alarm
.1.3.6.1.4.1.6347.1.3.163.0 ComMod2Alr_1 Module 2 communication alarm
.1.3.6.1.4.1.6347.1.3.164.0 Mod2Probe1Alr_1 Probe 1 module 2 alarm
.1.3.6.1.4.1.6347.1.3.165.0 Mod2Probe2Alr_1 Probe 2 module 2 alarm
.1.3.6.1.4.1.6347.1.3.166.0 Mod2Probe3Alr_1 Probe 3 module 2 alarm - R
.1.3.6.1.4.1.6347.1.3.167.0 Mod2Probe4Alr_1 Probe 4 module 2 alarm
.1.3.6.1.4.1.6347.1.3.168.0 Mod2Probe5Alr_1 Probe 5 module 2 alarm
.1.3.6.1.4.1.6347.1.3.169.0 Mod2Probe6Alr_1 Probe 6 module 2 alarm
.1.3.6.1.4.1.6347.1.3.170.0 ComMod3Alr_1 Module 3 communication alarm
.1.3.6.1.4.1.6347.1.3.171.0 Mod3Probe1Alr_1 Probe 1 module 3 alarm
.1.3.6.1.4.1.6347.1.3.172.0 Mod3Probe2Alr_1 Probe 2 module 3 alarm
.1.3.6.1.4.1.6347.1.3.173.0 Mod3Probe3Alr_1 Probe 3 module 3 alarm
.1.3.6.1.4.1.6347.1.3.174.0 Mod3Probe4Alr_1 Probe 4 module 3 alarm
.1.3.6.1.4.1.6347.1.3.175.0 Mod3Probe5Alr_1 Probe 5 module 3 alarm
.1.3.6.1.4.1.6347.1.3.176.0 Mod3Probe6Alr_1 Probe 6 module 3 alarm

INSTALLATION AND MAINTENANCE 33


CLOSE CONTROL AIR CONDITIONERS
6.1.1 ALARM TRAPS

Type Name Description

Alarm traps
.1.3.6.1.4.1.6347.1.0.1 retHumProbAlTrap_1 Broken return humidity probe alarm
.1.3.6.1.4.1.6347.1.0.2 retTempProbAlTrap_1 Broken return temperature probe alarm
.1.3.6.1.4.1.6347.1.0.3 airPrSensorALTrap_1 Broken air differential pressure sensor alarm
.1.3.6.1.4.1.6347.1.0.4 supTempProbAlTrap_1 Broken supply temperature probe alarm
Broken IN 1 water temperature probe alarm
.1.3.6.1.4.1.6347.1.0.5 watIN1ProbAlTrap_1
Broken free cooling temperature probe alarm
.1.3.6.1.4.1.6347.1.0.6 watOUT1ProbAlTrap_1 Broken OUT 1 water temperature probe alarm
Broken water flow 1 sensor alarm
.1.3.6.1.4.1.6347.1.0.7 watFlw1ProbAlTrap_1
Broken liquid 1 temperature probe alarm
.1.3.6.1.4.1.6347.1.0.8 supHumProbAlTrap_1 Broken supply humidity probe alarm
Broken water flow 2 sensor alarm
.1.3.6.1.4.1.6347.1.0.9 watFlw2ProbAlTrap_1
Broken liquid 2 temperature probe alarm
Water presence sensor alarm
.1.3.6.1.4.1.6347.1.0.10 watPresAlTrap_1
Condensate discharge pump alarm
.1.3.6.1.4.1.6347.1.0.11 elHeatAlTrap_1 Electric coil safety thermostat
.1.3.6.1.4.1.6347.1.0.12 damperAlTrap_1 Damper status alarm
.1.3.6.1.4.1.6347.1.0.13 filterAlTrap_1 Clogged air filter alarm
.1.3.6.1.4.1.6347.1.0.14 c1ThermAlTrap_1 Compressor 1 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.0.15 c2ThermAlTrap_1 Compressor 2 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.0.16 c1HighPresAlTrap_1 Compressor 1 high pressure alarm
.1.3.6.1.4.1.6347.1.0.17 c2HighPresAlTrap_1 Compressor 2 high pressure alarm
.1.3.6.1.4.1.6347.1.0.18 c1LowPresAlTrap_1 Compressor 1 low pressure alarm
.1.3.6.1.4.1.6347.1.0.19 c2LowPresAlTrap_1 Compressor 2 low pressure alarm
.1.3.6.1.4.1.6347.1.0.20 c1HighDischAlTrap_1 Compressor 1 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.0.21 c2HighDischAlTrap_1 Compressor 2 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.0.22 eEV1AlTrap_1 EEV 1 alarm
.1.3.6.1.4.1.6347.1.0.23 eEV2AlTrap_1 EEV 2 alarm
.1.3.6.1.4.1.6347.1.0.24 inverterCompAlTrap_1 DC compressor inverter alarm
.1.3.6.1.4.1.6347.1.0.25 fan1InverterAlTrap_1 Fan 1 inverter alarm
.1.3.6.1.4.1.6347.1.0.26 fan2InverterAlTrap_1 Fan 2 inverter alarm
.1.3.6.1.4.1.6347.1.0.27 fan3InverterAlTrap_1 Fan 3 inverter alarm
.1.3.6.1.4.1.6347.1.0.28 fan4InverterAlTrap_1 Fan 4 inverter alarm
.1.3.6.1.4.1.6347.1.0.29 fan5InverterAlTrap_1 Fan 5 inverter alarm
.1.3.6.1.4.1.6347.1.0.30 internalHumidifAlTrap_1 Internal humidifier alarm
.1.3.6.1.4.1.6347.1.0.31 localNetworkAlTrap_1 Local network communication alarm
.1.3.6.1.4.1.6347.1.0.32 regHighTempAlTrap_1 High temperature regulation alarm
.1.3.6.1.4.1.6347.1.0.33 regLowTempAlTrap_1 Low temperature regulation alarm
.1.3.6.1.4.1.6347.1.0.34 retHighHumiAlTrap_1 High return humidity alarm
.1.3.6.1.4.1.6347.1.0.35 retLowHumiAlTrap_1 Low return humidity alarm
.1.3.6.1.4.1.6347.1.0.36 supHighHumiAlTrap_1 High supply humidity alarm
.1.3.6.1.4.1.6347.1.0.37 supLowHumiAlTrap_1 Low supply humidity alarm
.1.3.6.1.4.1.6347.1.0.38 highLimTempAlTrap_1 High limit temperature alarm
.1.3.6.1.4.1.6347.1.0.39 lowLimTempAlTrap_1 Low limit temperature alarm
.1.3.6.1.4.1.6347.1.0.40 dryCoolerAlTrap_1 Dry cooler general alarm
.1.3.6.1.4.1.6347.1.0.41 externalHumidifAlTrap_1 External humidifier general alarm
.1.3.6.1.4.1.6347.1.0.42 waterPumpAlTrap_1 General water pump alarm
.1.3.6.1.4.1.6347.1.0.43 condenser1AlTrap_1 Condenser 1 general alarm
.1.3.6.1.4.1.6347.1.0.44 condenser2AlTrap_1 Condenser 2 general alarm
.1.3.6.1.4.1.6347.1.0.45 gasLeakAlTrap_1 Refrigerant gas leak detector alarm
.1.3.6.1.4.1.6347.1.0.46 fansGenAlTrap_1 General supply fans alarm

34 TECHNICAL MANUAL
Type Name Description

.1.3.6.1.4.1.6347.1.0.47 fireSmokeAlTrap_1 Fire/Smoke presence alarm


.1.3.6.1.4.1.6347.1.0.48 genericSoftAlTrap_1 Non-critical generic alarm
.1.3.6.1.4.1.6347.1.0.49 genericSeriousAlTrap_1 Critical generic alarm
.1.3.6.1.4.1.6347.1.0.50 condUnitGeneralAlTrap_1 Condensing unit generic alarm
.1.3.6.1.4.1.6347.1.0.51 powerSupplyAlTrap_1 No power supply alarm
.1.3.6.1.4.1.6347.1.0.52 c1LowComprRatioAlTrap_1 Compressor 1 low compression alarm
.1.3.6.1.4.1.6347.1.0.53 c2LowComprRatioAlTrap_1 Compressor 2 low compression alarm
.1.3.6.1.4.1.6347.1.0.54 watIN2ProbAlTrap_1 Broken IN 2 water temperature probe alarm
.1.3.6.1.4.1.6347.1.0.55 watOUT2ProbAlTrap_1 Broken OUT 2 water temperature probe alarm
.1.3.6.1.4.1.6347.1.0.56 dirtyFiltPresSensAlTrap_1 Dirty filter pressure sensor alarm
.1.3.6.1.4.1.6347.1.0.57 eEV1CommAlTrap_1 EEV1 communication down alarm
.1.3.6.1.4.1.6347.1.0.58 eEV1SuctProbAlTrap_1 EEV1 suction temperature probe alarm
.1.3.6.1.4.1.6347.1.0.59 eEV1EvapProbAlTrap_1 EEV1 evaporation pressure probe alarm
.1.3.6.1.4.1.6347.1.0.60 eEV1CondProbAlTrap_1 EEV1 condensation pressure probe alarm
.1.3.6.1.4.1.6347.1.0.61 eEV1DischProbAlTrap_1 EEV1 discharge temperature probe alarm
.1.3.6.1.4.1.6347.1.0.62 eEV2CommAlTrap_1 EEV2 communication down alarm
.1.3.6.1.4.1.6347.1.0.63 eEV2SuctProbAlTrap_1 EEV2 suction temperature probe alarm
.1.3.6.1.4.1.6347.1.0.64 eEV2EvapProbAlTrap_1 EEV2 evaporation pressure probe alarm
.1.3.6.1.4.1.6347.1.0.65 eEV2CondProbAlTrap_1 EEV2 condensation pressure probe alarm
.1.3.6.1.4.1.6347.1.0.66 eEV2DischProbAlTrap_1 EEV2 discharge temperature probe alarm
.1.3.6.1.4.1.6347.1.0.67 cPYCommAlTrap_1 CPY communication down alarm
.1.3.6.1.4.1.6347.1.0.68 cPYMemoryAlTrap_1 Internal memory error
.1.3.6.1.4.1.6347.1.0.69 cPYParameterAlTrap_1 Parameter error
.1.3.6.1.4.1.6347.1.0.70 cPYHighCurrentAlTrap_1 High electrode current
.1.3.6.1.4.1.6347.1.0.71 cPYLowSteamAlTrap_1 Low steam flow rate
.1.3.6.1.4.1.6347.1.0.72 cPYDrainAlTrap_1 Failed discharge
.1.3.6.1.4.1.6347.1.0.73 cPYMaintAlTrap_1 Maintenance time expired
.1.3.6.1.4.1.6347.1.0.74 cPYNoWaterAlTrap_1 No water
.1.3.6.1.4.1.6347.1.0.75 cPYCylMaintAlTrap_1 Cylinder maintenance
.1.3.6.1.4.1.6347.1.0.76 cPYDirtyCylAlTrap_1 Cylinder burnt out
.1.3.6.1.4.1.6347.1.0.77 cPYFoamAlTrap_1 Foam presence
.1.3.6.1.4.1.6347.1.0.78 cPYLifeTimeAlTrap_1 Life timer expired
.1.3.6.1.4.1.6347.1.0.79 cPYHighWatLevAlTrap_1 High water level
.1.3.6.1.4.1.6347.1.0.80 cPYHighWatConductAlTrap_1 High water conductivity
.1.3.6.1.4.1.6347.1.0.81 cPYConnectionAlTrap_1 Connection error
.1.3.6.1.4.1.6347.1.0.82 fan1PowerAlTrap_1 Fan 1 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.0.83 fan1CommAlTrap_1 Fan 1 communication down alarm
.1.3.6.1.4.1.6347.1.0.84 fan1HighTempAlTrap_1 Fan 1 regulation module high temperature
.1.3.6.1.4.1.6347.1.0.85 fan1NetComAlTrap_1 Fan 1 no master-slave communication
.1.3.6.1.4.1.6347.1.0.86 fan1InvRegAlTrap_1 Fan 1 regulation module failure
.1.3.6.1.4.1.6347.1.0.87 fan1HighMotTempAlTrap_1 High fan 1 motor temperature
.1.3.6.1.4.1.6347.1.0.88 fan1HallSensAlTrap_1 Fan 1 Hall sensor error
.1.3.6.1.4.1.6347.1.0.89 fan1OverloadAlTrap_1 Fan 1 motor overload
.1.3.6.1.4.1.6347.1.0.94 fan1LowDCAlTrap_1 Low fan 1 DC power supply
.1.3.6.1.4.1.6347.1.0.95 fan2PowerAlTrap_1 Fan 2 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.0.96 fan2CommAlTrap_1 Fan 2 communication down alarm
.1.3.6.1.4.1.6347.1.0.97 fan2HighTempAlTrap_1 Fan 2 regulation module high temperature
.1.3.6.1.4.1.6347.1.0.98 fan2NetComAlTrap_1 Fan 2 no master-slave communication
.1.3.6.1.4.1.6347.1.0.99 fan2InvRegAlTrap_1 Fan 2 regulation module failure
.1.3.6.1.4.1.6347.1.0.100 fan2HighMotTempAlTrap_1 High fan 2 motor temperature
.1.3.6.1.4.1.6347.1.0.101 fan2HallSensAlTrap_1 Fan 2 Hall sensor error
.1.3.6.1.4.1.6347.1.0.102 fan2OverloadAlTrap_1 Fan 2 motor overload

INSTALLATION AND MAINTENANCE 35


CLOSE CONTROL AIR CONDITIONERS

Type Name Description

.1.3.6.1.4.1.6347.1.0.107 fan2LowDCAlTrap_1 Low fan 2 DC power supply


.1.3.6.1.4.1.6347.1.0.108 fan3PowerAlTrap_1 Fan 3 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.0.109 fan3CommAlTrap_1 Fan 3 communication down alarm
.1.3.6.1.4.1.6347.1.0.110 fan3HighTempAlTrap_1 Fan 3 regulation module high temperature
.1.3.6.1.4.1.6347.1.0.111 fan3NetComAlTrap_1 Fan 3 no master-slave communication
.1.3.6.1.4.1.6347.1.0.112 fan3InvRegAlTrap_1 Fan 3 regulation module failure
.1.3.6.1.4.1.6347.1.0.113 fan3HighMotTempAlTrap_1 High fan 3 motor temperature
.1.3.6.1.4.1.6347.1.0.114 fan3HallSensAlTrap_1 Fan 3 Hall sensor error
.1.3.6.1.4.1.6347.1.0.115 fan3OverloadAlTrap_1 Fan 3 motor overload
.1.3.6.1.4.1.6347.1.0.120 fan3LowDCAlTrap_1 Low fan 3 DC power supply
.1.3.6.1.4.1.6347.1.0.121 fan4PowerAlTrap_1 Fan 4 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.0.122 fan4CommAlTrap_1 Fan 4 communication down alarm
.1.3.6.1.4.1.6347.1.0.123 fan4HighTempAlTrap_1 Fan 4 regulation module high temperature
.1.3.6.1.4.1.6347.1.0.124 fan4NetComAlTrap_1 Fan 4 no master-slave communication
.1.3.6.1.4.1.6347.1.0.125 fan4InvRegAlTrap_1 Fan 4 regulation module failure
.1.3.6.1.4.1.6347.1.0.126 fan4HighMotTempAlTrap_1 High fan 4 motor temperature
.1.3.6.1.4.1.6347.1.0.127 fan4HallSensAlTrap_1 Fan 4 Hall sensor error
.1.3.6.1.4.1.6347.1.0.128 fan4OverloadAlTrap_1 Fan 4 motor overload
.1.3.6.1.4.1.6347.1.0.133 fan4LowDCAlTrap_1 Low fan 4 DC power supply
.1.3.6.1.4.1.6347.1.0.134 fan5PowerAlTrap_1 Fan 5 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.0.135 fan5CommAlTrap_1 Fan 5 communication down alarm
.1.3.6.1.4.1.6347.1.0.136 fan5HighTempAlTrap_1 Fan 5 regulation module high temperature
.1.3.6.1.4.1.6347.1.0.137 fan5NetComAlTrap_1 Fan 5 no master-slave communication
.1.3.6.1.4.1.6347.1.0.138 fan5InvRegAlTrap_1 Fan 5 regulation module failure
.1.3.6.1.4.1.6347.1.0.139 fan5HighMotTempAlTrap_1 High fan 5 motor temperature
.1.3.6.1.4.1.6347.1.0.140 fan5HallSensAlTrap_1 Fan 5 Hall sensor error
.1.3.6.1.4.1.6347.1.0.141 fan5OverloadAlTrap_1 Fan 5 motor overload
.1.3.6.1.4.1.6347.1.0.146 fan5LowDCAlTrap_1 Low fan 5 DC power supply
.1.3.6.1.4.1.6347.1.0.147 dFPSBrokenAlTrap_1 Broken dirty filter pressure sensor alarm
.1.3.6.1.4.1.6347.1.0.148 dFPSCablingAlTrap_1 Dirty filter pressure sensor cabling alarm
.1.3.6.1.4.1.6347.1.0.149 dFPSRangeAlTrap_1 Dirty filter pressure sensor pressure range alarm
.1.3.6.1.4.1.6347.1.0.150 dFPSADCAlTrap_1 Dirty filter pressure sensor overload ADC alarm
.1.3.6.1.4.1.6347.1.0.151 dFPSSettingAlTrap_1 Dirty filter pressure sensor calibration alarm
.1.3.6.1.4.1.6347.1.0.152 dFPSDCOAlTrap_1 Dirty filter pressure sensor DCO alarm
.1.3.6.1.4.1.6347.1.0.153 dFPSWatchdogAlTrap_1 Dirty filter pressure sensor watchdog alarm
.1.3.6.1.4.1.6347.1.0.154 dFPSCommAlTrap_1 Dirty filter pressure sensor communication alarm
.1.3.6.1.4.1.6347.1.0.155 invCompCommAlarmTrap_1 DC compressor inverter communication alarm
.1.3.6.1.4.1.6347.1.0.156 ComMod1AlrTrap_1 Module 1 communication alarm
.1.3.6.1.4.1.6347.1.0.157 Mod1Probe1AlrTrap_1 Probe 1 module 1 alarm
.1.3.6.1.4.1.6347.1.0.158 Mod1Probe2AlrTrap_1 Probe 2 module 1 alarm
.1.3.6.1.4.1.6347.1.0.159 Mod1Probe3AlrTrap_1 Probe 3 module 1 alarm
.1.3.6.1.4.1.6347.1.0.160 Mod1Probe4AlrTrap_1 Probe 4 module 1 alarm
.1.3.6.1.4.1.6347.1.0.161 Mod1Probe5AlrTrap_1 Probe 5 module 1 alarm
.1.3.6.1.4.1.6347.1.0.162 Mod1Probe6AlrTrap_1 Probe 6 module 1 alarm
.1.3.6.1.4.1.6347.1.0.163 ComMod2AlrTrap_1 Module 2 communication alarm
.1.3.6.1.4.1.6347.1.0.164 Mod2Probe1AlrTrap_1 Probe 1 module 2 alarm
.1.3.6.1.4.1.6347.1.0.165 Mod2Probe2AlrTrap_1 Probe 2 module 2 alarm
.1.3.6.1.4.1.6347.1.0.166 Mod2Probe3AlrTrap_1 Probe 3 module 2 alarm
.1.3.6.1.4.1.6347.1.0.167 Mod2Probe4AlrTrap_1 Probe 4 module 2 alarm
.1.3.6.1.4.1.6347.1.0.168 Mod2Probe5AlrTrap_1 Probe 5 module 2 alarm
.1.3.6.1.4.1.6347.1.0.169 Mod2Probe6AlrTrap_1 Probe 6 module 2 alarm
.1.3.6.1.4.1.6347.1.0.170 ComMod3AlrTrap_1 Module 3 communication alarm

36 TECHNICAL MANUAL
Type Name Description

.1.3.6.1.4.1.6347.1.0.171 Mod3Probe1AlrTrap_1 Probe 1 module 3 alarm


.1.3.6.1.4.1.6347.1.0.172 Mod3Probe2AlrTrap_1 Probe 2 module 3 alarm
.1.3.6.1.4.1.6347.1.0.173 Mod3Probe3AlrTrap_1 Probe 3 module 3 alarm
.1.3.6.1.4.1.6347.1.0.174 Mod3Probe4AlrTrap_1 Probe 4 module 3 alarm
.1.3.6.1.4.1.6347.1.0.175 Mod3Probe5AlrTrap_1 Probe 5 module 3 alarm
.1.3.6.1.4.1.6347.1.0.176 Mod3Probe6AlrTrap_1 Probe 6 module 3 alarm

INSTALLATION AND MAINTENANCE 37


CLOSE CONTROL AIR CONDITIONERS
6.2 CLOSE CONTROL SURVEYEVO MICROPROCESSOR SUPERVISOR VARIABLES (SOFTWARE VERSION 2.1)

Unit of
OID Name Description Type
measure
Digital input status
.1.3.6.1.4.1.6347.1.1.1.0 DamperStatusDI_1 Motorised damper status
.1.3.6.1.4.1.6347.1.1.2.0 DirtyFilterDI_1 Dirty filter alarm
.1.3.6.1.4.1.6347.1.1.3.0 RemoteOffDI_1 Remote OFF status
.1.3.6.1.4.1.6347.1.1.4.0 ElecHeaterAlarmDI_1 Electric coil safety thermostat alarm
.1.3.6.1.4.1.6347.1.1.5.0 WaterAlarmDI_1 Water sensor/Condensate pump alarm
.1.3.6.1.4.1.6347.1.1.6.0 ConfigurableDI1_1 Configurable input 1
.1.3.6.1.4.1.6347.1.1.7.0 ConfigurableDI2_1 Configurable input 2
.1.3.6.1.4.1.6347.1.1.8.0 ConfigurableDI3_1 Configurable input 3 - R
.1.3.6.1.4.1.6347.1.1.9.0 ConfigurableDI4_1 Configurable input 4
.1.3.6.1.4.1.6347.1.1.10.0 Comp1ThermAlarmDI_1 Compressor 1 breaker alarm
.1.3.6.1.4.1.6347.1.1.11.0 Comp1HPAlarmDI_1 Compressor 1 high pressure alarm
.1.3.6.1.4.1.6347.1.1.12.0 Comp1LPAlarmDI_1 Compressor 1 low pressure alarm
.1.3.6.1.4.1.6347.1.1.13.0 Comp2ThermAlarmDI_1 Compressor 2 breaker alarm
.1.3.6.1.4.1.6347.1.1.14.0 Comp2HPAlarmDI_1 Compressor 2 high pressure alarm
.1.3.6.1.4.1.6347.1.1.15.0 Comp2LowPresAlarmDI_1 Compressor 2 low pressure alarm
Digital output status
.1.3.6.1.4.1.6347.1.1.16.0 FansDO_1 Fan control
.1.3.6.1.4.1.6347.1.1.17.0 DamperDO_1 Motorised dampers control
.1.3.6.1.4.1.6347.1.1.18.0 ElecHeaterStage1DO_1 Electric heating coil 1 stage
.1.3.6.1.4.1.6347.1.1.19.0 ElecHeaterStage2DO_1 Electric heating coil 2 stage
.1.3.6.1.4.1.6347.1.1.20.0 ConfigurableDO1_1 Configurable digital output 1
- R
.1.3.6.1.4.1.6347.1.1.21.0 ConfigurableDO2_1 Configurable digital output 2
.1.3.6.1.4.1.6347.1.1.22.0 ConfigurableDO3_1 Configurable digital output 3
.1.3.6.1.4.1.6347.1.1.23.0 ConfigurableDO4_1 Configurable digital output 4
.1.3.6.1.4.1.6347.1.1.24.0 Compressor1DO_1 Compressor 1 control
.1.3.6.1.4.1.6347.1.1.25.0 Compressor2DO_1 Compressor 2 control

38 TECHNICAL MANUAL
Unit of
OID Name Description Type
measure
Analogue inputs
.1.3.6.1.4.1.6347.1.2.1.0 ReturnHumidity_1 Return humidity %Rh
.1.3.6.1.4.1.6347.1.2.2.0 ReturnTemperature_1 Return temperature °C
.1.3.6.1.4.1.6347.1.2.3.0 SupplyHumidity_1 Supply humidity %Rh
.1.3.6.1.4.1.6347.1.2.4.0 SupplyTemperature_1 Supply temperature °C
.1.3.6.1.4.1.6347.1.2.5.0 AirPressure_1 Air pressure Pa
.1.3.6.1.4.1.6347.1.2.6.0 WaterINTemperature_1 Water inlet 1 temperature/Free cooling °C
.1.3.6.1.4.1.6347.1.2.7.0 WaterOUTTemperature_1 Water outlet temperature 1 °C
.1.3.6.1.4.1.6347.1.2.8.0 Comp1CondPress_1 Compressor 1 condensation pressure BarG
.1.3.6.1.4.1.6347.1.2.9.0 Compr2CondPress_1 Compressor 2 condensation pressure BarG
.1.3.6.1.4.1.6347.1.2.10.0 Compr1CondTemp_1 Compressor 1 condensation temperature °C
.1.3.6.1.4.1.6347.1.2.11.0 Comp2CondTemp_1 Compressor 2 condensation temperature °C
.1.3.6.1.4.1.6347.1.2.12.0 Comp1DischTemp_1 Compressor 1 discharge temperature °C
.1.3.6.1.4.1.6347.1.2.13.0 Comp2DischTemp_1 Compressor 2 discharge temperature °C
.1.3.6.1.4.1.6347.1.2.14.0 Comp1SuctionTemp_1 Compressor 1 suction temperature °C
.1.3.6.1.4.1.6347.1.2.15.0 Comp2SuctionTemp_1 Compressor 2 suction temperature °C
.1.3.6.1.4.1.6347.1.2.16.0 Comp1EvapPres_1 Compressor 1 evaporation pressure BarG
R
.1.3.6.1.4.1.6347.1.2.17.0 Comp2EvapPres_1 Compressor 2 evaporation pressure BarG
.1.3.6.1.4.1.6347.1.2.18.0 Comp1EvapTemp_1 Compressor 1 evaporation temperature °C
.1.3.6.1.4.1.6347.1.2.19.0 Comp2EvapTemp_1 Compressor 2 evaporation temperature °C
.1.3.6.1.4.1.6347.1.2.20.0 Comp1LiquidTemp_1 Compressor 1 liquid temperature °C
.1.3.6.1.4.1.6347.1.2.21.0 Compr2LiquidTemp_1 Compressor 2 liquid temperature °C
.1.3.6.1.4.1.6347.1.2.22.0 WaterFlow1_1 Water flow rate 1) l/h
.1.3.6.1.4.1.6347.1.2.23.0 WaterFlow2_1 Water flow rate 2 l/h
.1.3.6.1.4.1.6347.1.2.24.0 TotalWaterFlow_1 Total water flow rate l/h
.1.3.6.1.4.1.6347.1.2.25.0 ReturnHumidityAvg_1 Return humidity (local network average) %Rh
.1.3.6.1.4.1.6347.1.2.26.0 ReturnTempAvg_1 Return temperature (local network average) °C
.1.3.6.1.4.1.6347.1.2.27.0 SupplyHumidityAvg_1 Supply humidity (local network average) %Rh
.1.3.6.1.4.1.6347.1.2.28.0 SupplyTempAvg_1 Supply temperature (local network average) °C
.1.3.6.1.4.1.6347.1.2.29.0 AirPressureAvg_1 Air pressure (local network average) °C
.1.3.6.1.4.1.6347.1.2.30.0 WaterINTemperature2_1 Water inlet temperature 2 °C
.1.3.6.1.4.1.6347.1.2.31.0 WaterOUTemperature2_1 Water outlet temperature 2 °C
.1.3.6.1.4.1.6347.1.2.32.0 DiffFilterPressure_1
Dirty filter differential pressure Pa
Analogue outputs
.1.3.6.1.4.1.6347.1.2.33.0 UnitFansDryCoolerAO_1 Supply Fan / Dry cooler modulation %
.1.3.6.1.4.1.6347.1.2.34.0 CoolingAO_1 Cooling valve / Free cooling / External inverter %
.1.3.6.1.4.1.6347.1.2.35.0 HeatingAO_1 Heating valve / Modulating electrical coil %
R
.1.3.6.1.4.1.6347.1.2.36.0 TwoSourcesAO_1 Two sources water valve %
.1.3.6.1.4.1.6347.1.2.37.0 Condenser1AO_1 Condenser 1 %
.1.3.6.1.4.1.6347.1.2.38.0 Condenser2HumidifAO_1 Condenser 2 / External humidifier %

INSTALLATION AND MAINTENANCE 39


CLOSE CONTROL AIR CONDITIONERS
Unit of
OID Name Description Type
measure
Unit status
.1.3.6.1.4.1.6347.1.2.39.0 UnitStatus_1 Unit status * - R
* 1 = Unit OFF - 2 = OFF Remote - 3 = OFF from supervisor - 4 = Off from alarm - 5 = Stand-by - 6 = Unit ON - 7 = Ultracap
Supply air flow
.1.3.6.1.4.1.6347.1.2.40.0 AirFlow_1 Air flow m3/h R
Working hours
.1.3.6.1.4.1.6347.1.2.41.0 UnitWorkingHours_1 Unit hours of operation h
.1.3.6.1.4.1.6347.1.2.42.0 Comp1WorkingHours_1 Compressor 1 hours of operation h
.1.3.6.1.4.1.6347.1.2.43.0 Compr2WorkingHours_1 Compressor 2 hours of operation h
.1.3.6.1.4.1.6347.1.2.44.0 HeatingWorkingHours_1 Hours of heating operation h
.1.3.6.1.4.1.6347.1.2.45.0 DryCoolerWorkHours_1 Hours of dry cooler operation h
R
.1.3.6.1.4.1.6347.1.2.46.0 HumidifWorkingHours_1 Hours of humidifier operation h
.1.3.6.1.4.1.6347.1.2.47.0 CoolValveWorkHours_1 Hours of cooling valve operation h
.1.3.6.1.4.1.6347.1.2.48.0 Cond1WorkingHours_1 Condenser 1 hours of operation h
.1.3.6.1.4.1.6347.1.2.49.0 Cond2WorkingHours_1 Condenser 2 hours of operation h
.1.3.6.1.4.1.6347.1.2.50.0 FreeCoolWorkHours_1 Free Cooling hours of operation h
Electronic expansion valves state
.1.3.6.1.4.1.6347.1.2.51.0 EEV1SuperheatSet_1 Current EEV1 superheating set-point K
.1.3.6.1.4.1.6347.1.2.52.0 EEV2SuperheatSet_1 Current EEV2 superheating set-point K
.1.3.6.1.4.1.6347.1.2.53.0 EEV1Superheat_1 Current EEV1 superheating K
.1.3.6.1.4.1.6347.1.2.54.0 EEV2Superheat_1 Current EEV2 superheating K
.1.3.6.1.4.1.6347.1.2.55.0 EEV1Position_1 Current EEV1 position %
.1.3.6.1.4.1.6347.1.2.56.0 EEV2Position_1 Current EEV2 position %
R
.1.3.6.1.4.1.6347.1.2.57.0 EEV1PDesuperheat_1 Current EEV1 desuperheating K
.1.3.6.1.4.1.6347.1.2.58.0 EEV2Desuperheat_1 Current EEV2 desuperheating K
.1.3.6.1.4.1.6347.1.2.59.0 EEV1PSubcooling_1 Current EEV1 sub-cooling K
.1.3.6.1.4.1.6347.1.2.60.0 EEV2Subcooling_1 Current EEV2 sub-cooling K
.1.3.6.1.4.1.6347.1.2.135.0 CompRatio1_1 Compression ratio 1 -
.1.3.6.1.4.1.6347.1.2.136.0 CompRatio2_1 Compression ratio 2 -
Internal humidifier status
.1.3.6.1.4.1.6347.1.2.61.0 HumidifSteamProd_1 Current humidifier production kg/h
.1.3.6.1.4.1.6347.1.2.62.0 HumidifWaterConduct_1 Supply water conductivity μS/cm
R
.1.3.6.1.4.1.6347.1.2.63.0 HumidifierCurrent_1 Absorbed humidifier current A
.1.3.6.1.4.1.6347.1.2.64.0 HumidifWorkingMode_1 Humidifier operating mode * -
* 1 = Not active; 2 = Soft-start; 3 = Start full production after reduced production; 4 = Full production; 5 = Reduced production; 6,
7, 8 = Soft-start
.1.3.6.1.4.1.6347.1.2.65.0 HumidifWorkStatus_1 Humidifier operating status * - R
* 1 = Not active (no demand or blocked or disabled); 2 = Start evaporation cycle; 3 = Water charging in progress; 4 = Evaporation
in progress; 5 = AFS discharge; 6 = Water discharge (through dilution or manual); 7 = End of water discharge; 8 = Full discharge for
long period of downtime; 9 = Full discharge from manual or network request; 10 = No water control; 11 = Pre-wash; 12 = Periodic
discharge
.1.3.6.1.4.1.6347.1.1.26.0 HumidifierPowerDO_1 Humidifier control
.1.3.6.1.4.1.6347.1.1.27.0 HumidifDrainValveDO_1 Discharge valve
- R
.1.3.6.1.4.1.6347.1.1.28.0 HumidifFillValveDO_1 Charging valve
.1.3.6.1.4.1.6347.1.1.29.0 HumidifWaterLevel_1 High water level

40 TECHNICAL MANUAL
Unit of
OID Name Description Type
measure
Fan status
.1.3.6.1.4.1.6347.1.2.66.0 Fan1SpeedRPM_1 Fan 1 speed RPM
.1.3.6.1.4.1.6347.1.2.67.0 Fan2SpeedRPM_1 Fan 2 speed RPM
.1.3.6.1.4.1.6347.1.2.68.0 Fan3SpeedRPM_1 Fan 3 speed RPM
.1.3.6.1.4.1.6347.1.2.69.0 Fan4SpeedRPM_1 Fan 4 speed RPM
.1.3.6.1.4.1.6347.1.2.70.0 Fan5SpeedRPM_1 Fan 5 speed RPM
.1.3.6.1.4.1.6347.1.2.71.0 Fan1Speed_1 Fan 1 speed %
.1.3.6.1.4.1.6347.1.2.72.0 Fan2Speed_1 Fan 2 speed %
.1.3.6.1.4.1.6347.1.2.73.0 Fan3Speed_1 Fan 3 speed %
.1.3.6.1.4.1.6347.1.2.74.0 Fan4Speed_1 Fan 4 speed %
.1.3.6.1.4.1.6347.1.2.75.0 Fan5Speed_1 Fan 5 speed %
R
.1.3.6.1.4.1.6347.1.2.76.0 Fan1Current_1 Fan 1 absorbed current A
.1.3.6.1.4.1.6347.1.2.77.0 Fan1Power_1 Fan 1 absorbed electrical power W
.1.3.6.1.4.1.6347.1.2.78.0 Fan2Current_1 Fan 2 absorbed current A
.1.3.6.1.4.1.6347.1.2.79.0 Fan2Power_1 Fan 2 absorbed electrical power W
.1.3.6.1.4.1.6347.1.2.80.0 Fan3Current_1 Fan 3 absorbed current A
.1.3.6.1.4.1.6347.1.2.81.0 Fan3Power_1 Fan 3 absorbed electrical power W
.1.3.6.1.4.1.6347.1.2.82.0 Fan4Current_1 Fan 4 absorbed current A
.1.3.6.1.4.1.6347.1.2.83.0 Fan4Power_1 Fan 4 absorbed electrical power W
.1.3.6.1.4.1.6347.1.2.84.0 Fan5Current_1 Fan 5 absorbed current A
.1.3.6.1.4.1.6347.1.2.85.0 Fan5Power_1 Fan 5 absorbed electrical power W
DC compressor inverter status
.1.3.6.1.4.1.6347.1.2.86.0 InverterCompSpeed_1 Current compressor speed Hz
.1.3.6.1.4.1.6347.1.2.87.0 InverterCompPower_1 Current compressor electrical power kW R
.1.3.6.1.4.1.6347.1.2.88.0 InverterCompCurrent_1 Current compressor absorbed current A
Water cooling power
.1.3.6.1.4.1.6347.1.2.89.0 WaterCoolingCap1_1 Chilled water cooling capacity 1 kW
.1.3.6.1.4.1.6347.1.2.90.0 EER1_1 EER 1 -
R
.1.3.6.1.4.1.6347.1.2.137.0 WaterCoolingCap2_1 Chilled water cooling capacity 2 kW
.1.3.6.1.4.1.6347.1.2.138.0 EER2_1 EER 2 -
Electric coil status
.1.3.6.1.4.1.6347.1.2.91.0 HeaterActiveStages_1 Number of active stages -
R
.1.3.6.1.4.1.6347.1.2.92.0 ElecHeaterPower_1 Electrical power requirement kW

INSTALLATION AND MAINTENANCE 41


CLOSE CONTROL AIR CONDITIONERS

Unit of
OID Name Description Type
measure
On/Off from supervision
.1.3.6.1.4.1.6347.1.1.30.0 SupervOFF_1 On/Off from supervisor - R/W
Set-point
.1.3.6.1.4.1.6347.1.2.93.0 TemperatureSetpoint_1 Temperature set-point °C
R/W
.1.3.6.1.4.1.6347.1.2.94.0 HumiditySetpoint_1 Humidity set-point %Rh
Ventilation set-point
.1.3.6.1.4.1.6347.1.2.95.0 AirFlowSetpoint_1 Supply air flow rate set-point m3/h
R/W
.1.3.6.1.4.1.6347.1.2.96.0 AirPressureSetpoint_1 Air pressure set-point Pa
Temperature Regulation
.1.3.6.1.4.1.6347.1.2.97.0 TempControlSel_1 Regulation sensor * - R/W
* 1 = Return; 2 = Supply
.1.3.6.1.4.1.6347.1.2.98.0 TempControlType_1 Regulation type * - R/W
* 1 = Proportional (P); 2 = Proportional + Integral (PI); 3 = Proportional + Integral + Derivative (PID)
.1.3.6.1.4.1.6347.1.2.99.0 ProportionalBand_1 Proportional Band °C
.1.3.6.1.4.1.6347.1.2.100.0 IntagrativeTime_1 Integration time s
.1.3.6.1.4.1.6347.1.2.101.0 DerivativeTime_1 Derivative time s R/W
.1.3.6.1.4.1.6347.1.2.102.0 HighTempAlarmOffset_1 High temperature alarm offset °C
.1.3.6.1.4.1.6347.1.2.103.0 LowTempAlarmOffset_1 Low temperature alarm offset °C
Limit temperature regulation
.1.3.6.1.4.1.6347.1.2.104.0 HighLimitTempThr_1 Upper temperature limit °C
R/W
.1.3.6.1.4.1.6347.1.2.105.0 HighLimitTempMng_1 High limit temperature management * -
* 1 = Alarm only; 2 = Stop component; 3 = Reduction; 4 = Cold activation
.1.3.6.1.4.1.6347.1.2.106.0 LowLimitTempThr_1 Lower temperature limit °C
R/W
.1.3.6.1.4.1.6347.1.2.107.0 LowLimitTempMng_1 Low limit temperature management * -
* 1 = Alarm only; 2 = Stop component; 3 = Reduction; 4 = Hot activation
Humidity regulation
.1.3.6.1.4.1.6347.1.2.108.0 DehumidifPropBand_1 Dehumidification proportional band %RH
.1.3.6.1.4.1.6347.1.2.109.0 HumidifPropBand_1 Humidification proportional band %RH
.1.3.6.1.4.1.6347.1.2.110.0 HighRetHumAlOffset_1 High return humidity alarm offset %RH
R/W
.1.3.6.1.4.1.6347.1.2.111.0 LowRetHumAlOffset_1 Low return humidity alarm offset %RH
.1.3.6.1.4.1.6347.1.2.112.0 HighSupHumThr_1 Upper supply humidity limit %RH
.1.3.6.1.4.1.6347.1.2.113.0 LowSupHumThr_1 Lower supply humidity limit %RH
Humidifier regulation
.1.3.6.1.4.1.6347.1.1.31.0 EnableHumidifier_1 Humidification enabling
.1.3.6.1.4.1.6347.1.1.32.0 HumidifManualDrain_1 Manual discharge - R/W
.1.3.6.1.4.1.6347.1.1.33.0 HumidifCylWashing_1 Cylinder pre-wash
Free cooling and two sources regulation
.1.3.6.1.4.1.6347.1.2.114.0 FreeCoolingDelta_1 Free cooling delta °C
.1.3.6.1.4.1.6347.1.2.115.0 TSWaterSetpoint_1 Two sources water set-point °C
R/W
.1.3.6.1.4.1.6347.1.2.116.0 TSWaterPropBand_1 Two sources water band °C
.1.3.6.1.4.1.6347.1.1.34.0 TSEchange_1 Two sources source exchange -
Condenser regulation
.1.3.6.1.4.1.6347.1.2.117.0 Cond1ActualSet_1 Current condenser 1 set-point °C
.1.3.6.1.4.1.6347.1.2.118.0 Cond2ActualSet_1 Current condenser 2 set-point °C
.1.3.6.1.4.1.6347.1.2.119.0 CondSetpoint_1 Condensation set-point °C
R/W
.1.3.6.1.4.1.6347.1.2.120.0 CondPropoBand_1 Condensation proportional band °C
.1.3.6.1.4.1.6347.1.2.121.0 CondSetIncrease_1 Condensation set-point increase °C
.1.3.6.1.4.1.6347.1.2.122.0 MaxCondSetpoint_1 Maximum condensation set-point °C

42 TECHNICAL MANUAL
Unit of
OID Name Description Type
measure
Dry cooler regulation
.1.3.6.1.4.1.6347.1.2.123.0 DryCoolerActualSet_1 Current dry cooler set-point °C
.1.3.6.1.4.1.6347.1.2.124.0 DryCoolerSetpoint_1 Dry cooler set-point °C
.1.3.6.1.4.1.6347.1.2.125.0 DryCoolerPropBand_1 Dry Cooler proportional band °C R/W
.1.3.6.1.4.1.6347.1.2.126.0 DryCoolerSetIncr_1 Dry Cooler set-point increase °C
.1.3.6.1.4.1.6347.1.2.127.0 MaxDryCoolerSet_1 Maximum dry Cooler set-point °C
Dirty filter regulation
.1.3.6.1.4.1.6347.1.2.128.0 DirtyFiltersSet_1 Dirty filter set-point Pa
R/W
.1.3.6.1.4.1.6347.1.2.129.0 DirtyFiltersDiff_1 Dirty filter differential Pa

INSTALLATION AND MAINTENANCE 43


CLOSE CONTROL AIR CONDITIONERS

Unit of
OID Name Description Type
measure
Alarms
.1.3.6.1.4.1.6347.1.3.1.0 RetHumProbAl_1 Broken return humidity probe alarm
.1.3.6.1.4.1.6347.1.3.2.0 RetTempProbAl_1 Broken return temperature probe alarm
.1.3.6.1.4.1.6347.1.3.3.0 AirPrSensorAl_1 Broken air differential pressure sensor alarm
.1.3.6.1.4.1.6347.1.3.4.0 SupTempProbAl_1 Broken supply temperature probe alarm
Broken IN 1 water temperature probe alarm
.1.3.6.1.4.1.6347.1.3.5.0 WatIN1ProbAl_1
Broken free cooling temperature probe alarm
.1.3.6.1.4.1.6347.1.3.6.0 WatOUT1ProbAl_1 Broken OUT 1 water temperature probe alarm
Broken water flow 1 sensor alarm
.1.3.6.1.4.1.6347.1.3.7.0 WatFlw1ProbAl_1
Broken liquid 1 temperature probe alarm
.1.3.6.1.4.1.6347.1.3.8.0 SupHumProbAl_1 Broken supply humidity probe alarm
Broken water flow 2 sensor alarm
.1.3.6.1.4.1.6347.1.3.9.0 WatFlw2ProbAl_1
Broken liquid 2 temperature probe alarm
Water presence sensor alarm
.1.3.6.1.4.1.6347.1.3.10.0 WatPresAl_1
Condensate discharge pump alarm
.1.3.6.1.4.1.6347.1.3.11.0 ElHeatAl_1 Electric coil safety thermostat
.1.3.6.1.4.1.6347.1.3.12.0 DamperAl_1 Damper status alarm
.1.3.6.1.4.1.6347.1.3.13.0 FilterAl_1 Clogged air filter alarm
.1.3.6.1.4.1.6347.1.3.14.0 C1ThermAl_1 Compressor 1 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.3.15.0 C2ThermAl_1 Compressor 2 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.3.16.0 C1HighPresAl_1 Compressor 1 high pressure alarm
.1.3.6.1.4.1.6347.1.3.17.0 C2HighPresAl_1 Compressor 2 high pressure alarm
.1.3.6.1.4.1.6347.1.3.18.0 C1LowPresAl_1 Compressor 1 low pressure alarm
.1.3.6.1.4.1.6347.1.3.19.0 C2LowPresAl_1 Compressor 2 low pressure alarm
.1.3.6.1.4.1.6347.1.3.20.0 C1HighDischAl_1 Compressor 1 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.3.21.0 C2HighDischAl_1 Compressor 2 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.3.22.0 EEV1Al_1 EEV 1 alarm
.1.3.6.1.4.1.6347.1.3.23.0 EEV2Al_1 EEV 2 alarm - R
.1.3.6.1.4.1.6347.1.3.24.0 InverterCompAl_1 DC compressor inverter alarm
.1.3.6.1.4.1.6347.1.3.25.0 Fan1InverterAl_1 Fan 1 inverter alarm
.1.3.6.1.4.1.6347.1.3.26.0 Fan2InverterAl_1 Fan 2 inverter alarm
.1.3.6.1.4.1.6347.1.3.27.0 Fan3InverterAl_1 Fan 3 inverter alarm
.1.3.6.1.4.1.6347.1.3.28.0 Fan4InverterAl_1 Fan 4 inverter alarm
.1.3.6.1.4.1.6347.1.3.29.0 Fan5InverterAl_1 Fan 5 inverter alarm
.1.3.6.1.4.1.6347.1.3.30.0 InternalHumidifAl_1 Internal humidifier alarm
.1.3.6.1.4.1.6347.1.3.31.0 LocalNetworkAl_1 Local network communication alarm
.1.3.6.1.4.1.6347.1.3.32.0 RegHighTempAl_1 High temperature regulation alarm
.1.3.6.1.4.1.6347.1.3.33.0 RegLowTempAl_1 Low temperature regulation alarm
.1.3.6.1.4.1.6347.1.3.34.0 RetHighHumiAl_1 High return humidity alarm
.1.3.6.1.4.1.6347.1.3.35.0 RetLowHumiAl_1 Low return humidity alarm
.1.3.6.1.4.1.6347.1.3.36.0 SupHighHumiAl_1 High supply humidity alarm
.1.3.6.1.4.1.6347.1.3.37.0 SupLowHumiAl_1 Low supply humidity alarm
.1.3.6.1.4.1.6347.1.3.38.0 HighLimTempAl_1 High limit temperature alarm
.1.3.6.1.4.1.6347.1.3.39.0 LowLimTempAl_1 Low limit temperature alarm
.1.3.6.1.4.1.6347.1.3.40.0 DryCoolerAl_1 Dry cooler general alarm
.1.3.6.1.4.1.6347.1.3.41.0 ExternalHumidifAl_1 External humidifier general alarm
.1.3.6.1.4.1.6347.1.3.42.0 WaterPumpAl_1 General water pump alarm
.1.3.6.1.4.1.6347.1.3.43.0 Condenser1Al_1 Condenser 1 general alarm
.1.3.6.1.4.1.6347.1.3.44.0 Condenser2Al_1 Condenser 2 general alarm
.1.3.6.1.4.1.6347.1.3.45.0 GasLeakAl_1 Refrigerant gas leak detector alarm
.1.3.6.1.4.1.6347.1.3.46.0 FansGenAl_1 General supply fans alarm
.1.3.6.1.4.1.6347.1.3.47.0 FireSmokeAl_1 Fire/Smoke presence alarm
.1.3.6.1.4.1.6347.1.3.48.0 GenericSoftAl_1 Non-critical generic alarm

44 TECHNICAL MANUAL
Unit of
OID Name Description Type
measure
.1.3.6.1.4.1.6347.1.3.49.0 GenericSeriousAl_1 Critical generic alarm
.1.3.6.1.4.1.6347.1.3.50.0 CondUnitGeneralAl_1 Condensing unit generic alarm
.1.3.6.1.4.1.6347.1.3.51.0 PowerSupplyAl_1 No power supply alarm
.1.3.6.1.4.1.6347.1.3.52.0 C1LowComprRatioAl_1 Compressor 1 low compression alarm
.1.3.6.1.4.1.6347.1.3.53.0 C2LowComprRatioAl_1 Compressor 2 low compression alarm
.1.3.6.1.4.1.6347.1.3.54.0 WatIN2ProbAl_1 Broken IN 2 water temperature probe alarm
.1.3.6.1.4.1.6347.1.3.55.0 WatOUT2ProbAl_1 Broken OUT 2 water temperature probe alarm
.1.3.6.1.4.1.6347.1.3.56.0 DirtyFiltPresSensAl_1 Dirty filter pressure sensor alarm
.1.3.6.1.4.1.6347.1.3.57.0 EEV1CommAl_1 EEV1 communication down alarm
.1.3.6.1.4.1.6347.1.3.58.0 EEV1SuctProbAl_1 EEV1 suction temperature probe alarm
.1.3.6.1.4.1.6347.1.3.59.0 EEV1EvapProbAl_1 EEV1 evaporation pressure probe alarm
.1.3.6.1.4.1.6347.1.3.60.0 EEV1CondProbAl_1 EEV1 condensation pressure probe alarm
.1.3.6.1.4.1.6347.1.3.61.0 EEV1DischProbAl_1 EEV1 discharge temperature probe alarm
.1.3.6.1.4.1.6347.1.3.62.0 EEV2CommAl_1 EEV2 communication down alarm
.1.3.6.1.4.1.6347.1.3.63.0 EEV2SuctProbAl_1 EEV2 suction temperature probe alarm
.1.3.6.1.4.1.6347.1.3.64.0 EEV2EvapProbAl_1 EEV2 evaporation pressure probe alarm
.1.3.6.1.4.1.6347.1.3.65.0 EEV2CondProbAl_1 EEV2 condensation pressure probe alarm
.1.3.6.1.4.1.6347.1.3.66.0 EEV2DischProbAl_1 EEV2 discharge temperature probe alarm
.1.3.6.1.4.1.6347.1.3.67.0 CPYCommAl_1 CPY communication down alarm
.1.3.6.1.4.1.6347.1.3.68.0 CPYMemoryAl_1 Internal memory error
.1.3.6.1.4.1.6347.1.3.69.0 CPYParameterAl_1 Parameter error
.1.3.6.1.4.1.6347.1.3.70.0 CPYHighCurrentAl_1 High electrode current
.1.3.6.1.4.1.6347.1.3.71.0 CPYLowSteamAl_1 Low steam flow rate
.1.3.6.1.4.1.6347.1.3.72.0 CPYDrainAl_1 Failed discharge
.1.3.6.1.4.1.6347.1.3.73.0 CPYMaintAl_1 Maintenance time expired
.1.3.6.1.4.1.6347.1.3.74.0 CPYNoWaterAl_1 No water
- R
.1.3.6.1.4.1.6347.1.3.75.0 CPYCylMaintAl_1 Cylinder maintenance
.1.3.6.1.4.1.6347.1.3.76.0 CPYDirtyCylAl_1 Cylinder burnt out
.1.3.6.1.4.1.6347.1.3.77.0 CPYFoamAl_1 Foam presence
.1.3.6.1.4.1.6347.1.3.78.0 CPYLifeTimeAl_1 Life timer expired
.1.3.6.1.4.1.6347.1.3.79.0 CPYHighWatLevAl_1 High water level
.1.3.6.1.4.1.6347.1.3.80.0 CPYHighWatConductAl_1 High water conductivity
.1.3.6.1.4.1.6347.1.3.81.0 CPYConnectionAl_1 Connection error
.1.3.6.1.4.1.6347.1.3.82.0 Fan1PowerAl_1 Fan 1 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.3.83.0 Fan1CommAl_1 Fan 1 communication down alarm
.1.3.6.1.4.1.6347.1.3.84.0 Fan1HighTempAl_1 Fan 1 regulation module high temperature
.1.3.6.1.4.1.6347.1.3.85.0 Fan1NetComAl_1 Fan 1 no master-slave communication
.1.3.6.1.4.1.6347.1.3.86.0 Fan1InvRegAl_1 Fan 1 regulation module failure
.1.3.6.1.4.1.6347.1.3.87.0 Fan1HighMotTempAl_1 High fan 1 motor temperature
.1.3.6.1.4.1.6347.1.3.88.0 Fan1HallSensAl_1 Fan 1 Hall sensor error
.1.3.6.1.4.1.6347.1.3.89.0 Fan1OverloadAl_1 Fan 1 motor overload
.1.3.6.1.4.1.6347.1.3.94.0 Fan1LowDCAl_1 Low fan 1 DC power supply
.1.3.6.1.4.1.6347.1.3.95.0 Fan2PowerAl_1 Fan 2 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.3.96.0 Fan2CommAl_1 Fan 2 communication down alarm
.1.3.6.1.4.1.6347.1.3.97.0 Fan2HighTempAl_1 Fan 2 regulation module high temperature
.1.3.6.1.4.1.6347.1.3.98.0 Fan2NetComAl_1 Fan 2 no master-slave communication
.1.3.6.1.4.1.6347.1.3.99.0 Fan2InvRegAl_1 Fan 2 regulation module failure
.1.3.6.1.4.1.6347.1.3.100.0 Fan2HighMotTempAl_1 High fan 2 motor temperature
.1.3.6.1.4.1.6347.1.3.101.0 Fan2HallSensAl_1 Fan 2 Hall sensor error
.1.3.6.1.4.1.6347.1.3.102.0 Fan2OverloadAl_1 Fan 2 motor overload
.1.3.6.1.4.1.6347.1.3.107.0 Fan2LowDCAl_1 Low fan 2 DC power supply
.1.3.6.1.4.1.6347.1.3.108.0 Fan3PowerAl_1 Fan 3 no phase/power supply alarm

INSTALLATION AND MAINTENANCE 45


CLOSE CONTROL AIR CONDITIONERS

Unit of
OID Name Description Type
measure
.1.3.6.1.4.1.6347.1.3.109.0 Fan3CommAl_1 Fan 3 communication down alarm
.1.3.6.1.4.1.6347.1.3.110.0 Fan3HighTempAl_1 Fan 3 regulation module high temperature
.1.3.6.1.4.1.6347.1.3.111.0 Fan3NetComAl_1 Fan 3 no master-slave communication
.1.3.6.1.4.1.6347.1.3.112.0 Fan3InvRegAl_1 Fan 3 regulation module failure
.1.3.6.1.4.1.6347.1.3.113.0 Fan3HighMotTempAl_1 High fan 3 motor temperature
.1.3.6.1.4.1.6347.1.3.114.0 Fan3HallSensAl_1 Fan 3 Hall sensor error
.1.3.6.1.4.1.6347.1.3.115.0 Fan3OverloadAl_1 Fan 3 motor overload
.1.3.6.1.4.1.6347.1.3.120.0 Fan3LowDCAl_1 Low fan 3 DC power supply
.1.3.6.1.4.1.6347.1.3.121.0 Fan4PowerAl_1 Fan 4 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.3.122.0 Fan4CommAl_1 Fan 4 communication down alarm
.1.3.6.1.4.1.6347.1.3.123.0 Fan4HighTempAl_1 Fan 4 regulation module high temperature
.1.3.6.1.4.1.6347.1.3.124.0 Fan4NetComAl_1 Fan 4 no master-slave communication
.1.3.6.1.4.1.6347.1.3.125.0 Fan4InvRegAl_1 Fan 4 regulation module failure
.1.3.6.1.4.1.6347.1.3.126.0 Fan4HighMotTempAl_1 High fan 4 motor temperature
.1.3.6.1.4.1.6347.1.3.127.0 Fan4HallSensAl_1 Fan 4 Hall sensor error
.1.3.6.1.4.1.6347.1.3.128.0 Fan4OverloadAl_1 Fan 4 motor overload
.1.3.6.1.4.1.6347.1.3.133.0 Fan4LowDCAl_1 Low fan 4 DC power supply
.1.3.6.1.4.1.6347.1.3.134.0 Fan5PowerAl_1 Fan 5 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.3.135.0 Fan5CommAl_1 Fan 5 communication down alarm
.1.3.6.1.4.1.6347.1.3.136.0 Fan5HighTempAl_1 Fan 5 regulation module high temperature
- R
.1.3.6.1.4.1.6347.1.3.137.0 Fan5NetComAl_1 Fan 5 no master-slave communication
.1.3.6.1.4.1.6347.1.3.138.0 Fan5InvRegAl_1 Fan 5 regulation module failure
.1.3.6.1.4.1.6347.1.3.139.0 Fan5HighMotTempAl_1 High fan 5 motor temperature
.1.3.6.1.4.1.6347.1.3.140.0 Fan5HallSensAl_1 Fan 5 Hall sensor error
.1.3.6.1.4.1.6347.1.3.141.0 Fan5OverloadAl_1 Fan 5 motor overload
.1.3.6.1.4.1.6347.1.3.146.0 Fan5LowDCAl_1 Low fan 5 DC power supply
.1.3.6.1.4.1.6347.1.3.147.0 DFPSBrokenAl_1 Broken dirty filter pressure sensor alarm
.1.3.6.1.4.1.6347.1.3.148.0 DFPSCablingAl_1 Dirty filter pressure sensor cabling alarm
.1.3.6.1.4.1.6347.1.3.149.0 DFPSRangeAl_1 Dirty filter pressure sensor pressure range alarm
.1.3.6.1.4.1.6347.1.3.150.0 DFPSADCAl_1 Dirty filter pressure sensor overload ADC alarm
.1.3.6.1.4.1.6347.1.3.151.0 DFPSSettingAl_1 Dirty filter pressure sensor calibration alarm
.1.3.6.1.4.1.6347.1.3.152.0 DFPSDCOAl_1 Dirty filter pressure sensor DCO alarm
.1.3.6.1.4.1.6347.1.3.153.0 DFPSWatchdogAl_1 Dirty filter pressure sensor watchdog alarm
.1.3.6.1.4.1.6347.1.3.154.0 DFPSCommAl_1 Dirty filter pressure sensor communication alarm
.1.3.6.1.4.1.6347.1.3.155.0 InvCompCommAlarm_1 DC compressor inverter communication alarm
.1.3.6.1.4.1.6347.1.2.130.0 InvCompAlCode1_1 DC compressor inverter alarm code [0] *
.1.3.6.1.4.1.6347.1.2.131.0 InvCompAlCode2_1 DC compressor inverter alarm code [1] *
.1.3.6.1.4.1.6347.1.2.132.0 InvCompAlCode3_1 DC compressor inverter alarm code [2] *
.1.3.6.1.4.1.6347.1.2.133.0 InvCompAlCode4_1 DC compressor inverter alarm code [3] *
.1.3.6.1.4.1.6347.1.2.134.0 InvCompAlCode5_1 DC compressor inverter alarm code [4] *
* 48 = 0; 49 = 1; 50 = 2; 51 = 3; 52 = 4; 53 = 5; 54 = 6; 55 = 7; 56 = 8; 57 = 9; 70 = F

46 TECHNICAL MANUAL
Unit of
OID Name Description Type
measure
Alarms reset
Water presence sensor alarm reset
.1.3.6.1.4.1.6347.1.1.35.0 WatPresAlRes_1
Condensate discharge pump alarm reset
.1.3.6.1.4.1.6347.1.1.36.0 ElHeatAlRes_1 Electr. coil safety thermostat alarm reset
.1.3.6.1.4.1.6347.1.1.37.0 DamperAlRes_1 Damper status alarm reset
.1.3.6.1.4.1.6347.1.1.38.0 FilterAlRes_1 Clogged air filter alarm reset
Compressor 1 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.1.39.0 C1ThermAlRes_1
reset
Compressor 2 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.1.40.0 C2ThermAlRes_1
reset
.1.3.6.1.4.1.6347.1.1.41.0 C1HighPresAlRes_1 Compressor 1 high pressure alarm reset
.1.3.6.1.4.1.6347.1.1.42.0 C2HighPresAlRes_1 Compressor 2 high pressure alarm reset
Compressor 1 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.1.43.0 C1HighDischAlRes_1
reset
Compressor 2 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.1.44.0 C2HighDischAlRes_1
reset
.1.3.6.1.4.1.6347.1.1.45.0 EEV1AlRes_1 Compressor 1 EEV alarm reset
.1.3.6.1.4.1.6347.1.1.46.0 EEV2AlRes_1 Compressor 2 EEV alarm reset
.1.3.6.1.4.1.6347.1.1.47.0 InverterCompAlRes_1 Compressor 1 inverter alarm reset
.1.3.6.1.4.1.6347.1.1.48.0 C1LoComprRatioAlRes_1 Comp. 1 low compression alarm reset
.1.3.6.1.4.1.6347.1.1.49.0 C2LoComprRatioAlRes_1 Comp. 2 low compression alarm reset
.1.3.6.1.4.1.6347.1.1.50.0 Fan1InverterAlRes_1 Fan 1 inverter alarm reset - RW
.1.3.6.1.4.1.6347.1.1.51.0 Fan2InverterAlRes_1 Fan 2 inverter alarm reset
.1.3.6.1.4.1.6347.1.1.52.0 Fan3InverterAlRes_1 Fan 3 inverter alarm reset
.1.3.6.1.4.1.6347.1.1.53.0 Fan4InverterAlRes_1 Fan 4 inverter alarm reset
.1.3.6.1.4.1.6347.1.1.54.0 Fan5InverterAlRes_1 Fan 5 inverter alarm reset
.1.3.6.1.4.1.6347.1.1.55.0 IntHumidifAlRes_1 Internal humidifier alarm reset
.1.3.6.1.4.1.6347.1.1.56.0 DryCoolerAlRes_1 Dry cooler general alarm reset
.1.3.6.1.4.1.6347.1.1.57.0 ExtHumidifAlRes_1 External humidifier general alarm reset
.1.3.6.1.4.1.6347.1.1.58.0 WaterPumpAlRes_1 General water pump alarm reset
.1.3.6.1.4.1.6347.1.1.59.0 Condenser1AlRes_1 Condenser 1 general alarm reset
.1.3.6.1.4.1.6347.1.1.60.0 Condenser2AlRes_1 Condenser 2 general alarm reset
.1.3.6.1.4.1.6347.1.1.61.0 GasLeakAlRes_1 Refrigerant gas leak detector alarm reset
.1.3.6.1.4.1.6347.1.1.62.0 FansGenAlRes_1 General supply fans alarm reset
.1.3.6.1.4.1.6347.1.1.63.0 FireSmokeAlRes_1 Fire/Smoke presence alarm reset
.1.3.6.1.4.1.6347.1.1.64.0 GenericSoftAlRes_1 Non-critical generic alarm reset
.1.3.6.1.4.1.6347.1.1.65.0 GenericSeriousAlRes_1 Critical generic alarm reset
.1.3.6.1.4.1.6347.1.1.66.0 CondUnitGenAlRes_1 Condensing unit generic alarm reset
.1.3.6.1.4.1.6347.1.1.67.0 PowerSupplyAlRes_1 No power supply alarm reset
.1.3.6.1.4.1.6347.1.1.68.0 C1LowPresAlRes_1 Compressor 1 low pressure alarm reset
.1.3.6.1.4.1.6347.1.1.69.0 C2LowPresAlRes_1 Compressor 2 low pressure alarm reset

INSTALLATION AND MAINTENANCE 47


CLOSE CONTROL AIR CONDITIONERS
6.2.1 ALARM TRAPS

Type Name Description

Alarm traps
.1.3.6.1.4.1.6347.1.0.1 retHumProbAlTrap_1 Broken return humidity probe alarm
.1.3.6.1.4.1.6347.1.0.2 retTempProbAlTrap_1 Broken return temperature probe alarm
.1.3.6.1.4.1.6347.1.0.3 airPrSensorALTrap_1 Broken air differential pressure sensor alarm
.1.3.6.1.4.1.6347.1.0.4 supTempProbAlTrap_1 Broken supply temperature probe alarm
Broken IN 1 water temperature probe alarm
.1.3.6.1.4.1.6347.1.0.5 watIN1ProbAlTrap_1
Broken free cooling temperature probe alarm
.1.3.6.1.4.1.6347.1.0.6 watOUT1ProbAlTrap_1 Broken OUT 1 water temperature probe alarm
Broken water flow 1 sensor alarm
.1.3.6.1.4.1.6347.1.0.7 watFlw1ProbAlTrap_1
Broken liquid 1 temperature probe alarm
.1.3.6.1.4.1.6347.1.0.8 supHumProbAlTrap_1 Broken supply humidity probe alarm
Broken water flow 2 sensor alarm
.1.3.6.1.4.1.6347.1.0.9 watFlw2ProbAlTrap_1
Broken liquid 2 temperature probe alarm
Water presence sensor alarm
.1.3.6.1.4.1.6347.1.0.10 watPresAlTrap_1
Condensate discharge pump alarm
.1.3.6.1.4.1.6347.1.0.11 elHeatAlTrap_1 Electric coil safety thermostat
.1.3.6.1.4.1.6347.1.0.12 damperAlTrap_1 Damper status alarm
.1.3.6.1.4.1.6347.1.0.13 filterAlTrap_1 Clogged air filter alarm
.1.3.6.1.4.1.6347.1.0.14 c1ThermAlTrap_1 Compressor 1 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.0.15 c2ThermAlTrap_1 Compressor 2 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.0.16 c1HighPresAlTrap_1 Compressor 1 high pressure alarm
.1.3.6.1.4.1.6347.1.0.17 c2HighPresAlTrap_1 Compressor 2 high pressure alarm
.1.3.6.1.4.1.6347.1.0.18 c1LowPresAlTrap_1 Compressor 1 low pressure alarm
.1.3.6.1.4.1.6347.1.0.19 c2LowPresAlTrap_1 Compressor 2 low pressure alarm
.1.3.6.1.4.1.6347.1.0.20 c1HighDischAlTrap_1 Compressor 1 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.0.21 c2HighDischAlTrap_1 Compressor 2 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.0.22 eEV1AlTrap_1 EEV 1 alarm
.1.3.6.1.4.1.6347.1.0.23 eEV2AlTrap_1 EEV 2 alarm
.1.3.6.1.4.1.6347.1.0.24 inverterCompAlTrap_1 DC compressor inverter alarm
.1.3.6.1.4.1.6347.1.0.25 fan1InverterAlTrap_1 Fan 1 inverter alarm
.1.3.6.1.4.1.6347.1.0.26 fan2InverterAlTrap_1 Fan 2 inverter alarm
.1.3.6.1.4.1.6347.1.0.27 fan3InverterAlTrap_1 Fan 3 inverter alarm
.1.3.6.1.4.1.6347.1.0.28 fan4InverterAlTrap_1 Fan 4 inverter alarm
.1.3.6.1.4.1.6347.1.0.29 fan5InverterAlTrap_1 Fan 5 inverter alarm
.1.3.6.1.4.1.6347.1.0.30 internalHumidifAlTrap_1 Internal humidifier alarm
.1.3.6.1.4.1.6347.1.0.31 localNetworkAlTrap_1 Local network communication alarm
.1.3.6.1.4.1.6347.1.0.32 regHighTempAlTrap_1 High temperature regulation alarm
.1.3.6.1.4.1.6347.1.0.33 regLowTempAlTrap_1 Low temperature regulation alarm
.1.3.6.1.4.1.6347.1.0.34 retHighHumiAlTrap_1 High return humidity alarm
.1.3.6.1.4.1.6347.1.0.35 retLowHumiAlTrap_1 Low return humidity alarm
.1.3.6.1.4.1.6347.1.0.36 supHighHumiAlTrap_1 High supply humidity alarm
.1.3.6.1.4.1.6347.1.0.37 supLowHumiAlTrap_1 Low supply humidity alarm
.1.3.6.1.4.1.6347.1.0.38 highLimTempAlTrap_1 High limit temperature alarm
.1.3.6.1.4.1.6347.1.0.39 lowLimTempAlTrap_1 Low limit temperature alarm
.1.3.6.1.4.1.6347.1.0.40 dryCoolerAlTrap_1 Dry cooler general alarm
.1.3.6.1.4.1.6347.1.0.41 externalHumidifAlTrap_1 External humidifier general alarm
.1.3.6.1.4.1.6347.1.0.42 waterPumpAlTrap_1 General water pump alarm
.1.3.6.1.4.1.6347.1.0.43 condenser1AlTrap_1 Condenser 1 general alarm
.1.3.6.1.4.1.6347.1.0.44 condenser2AlTrap_1 Condenser 2 general alarm
.1.3.6.1.4.1.6347.1.0.45 gasLeakAlTrap_1 Refrigerant gas leak detector alarm
.1.3.6.1.4.1.6347.1.0.46 fansGenAlTrap_1 General supply fans alarm

48 TECHNICAL MANUAL
Type Name Description

.1.3.6.1.4.1.6347.1.0.47 fireSmokeAlTrap_1 Fire/Smoke presence alarm


.1.3.6.1.4.1.6347.1.0.48 genericSoftAlTrap_1 Non-critical generic alarm
.1.3.6.1.4.1.6347.1.0.49 genericSeriousAlTrap_1 Critical generic alarm
.1.3.6.1.4.1.6347.1.0.50 condUnitGeneralAlTrap_1 Condensing unit generic alarm
.1.3.6.1.4.1.6347.1.0.51 powerSupplyAlTrap_1 No power supply alarm
.1.3.6.1.4.1.6347.1.0.52 c1LowComprRatioAlTrap_1 Compressor 1 low compression alarm
.1.3.6.1.4.1.6347.1.0.53 c2LowComprRatioAlTrap_1 Compressor 2 low compression alarm
.1.3.6.1.4.1.6347.1.0.54 watIN2ProbAlTrap_1 Broken IN 2 water temperature probe alarm
.1.3.6.1.4.1.6347.1.0.55 watOUT2ProbAlTrap_1 Broken OUT 2 water temperature probe alarm
.1.3.6.1.4.1.6347.1.0.56 dirtyFiltPresSensAlTrap_1 Dirty filter pressure sensor alarm
.1.3.6.1.4.1.6347.1.0.57 eEV1CommAlTrap_1 EEV1 communication down alarm
.1.3.6.1.4.1.6347.1.0.58 eEV1SuctProbAlTrap_1 EEV1 suction temperature probe alarm
.1.3.6.1.4.1.6347.1.0.59 eEV1EvapProbAlTrap_1 EEV1 evaporation pressure probe alarm
.1.3.6.1.4.1.6347.1.0.60 eEV1CondProbAlTrap_1 EEV1 condensation pressure probe alarm
.1.3.6.1.4.1.6347.1.0.61 eEV1DischProbAlTrap_1 EEV1 discharge temperature probe alarm
.1.3.6.1.4.1.6347.1.0.62 eEV2CommAlTrap_1 EEV2 communication down alarm
.1.3.6.1.4.1.6347.1.0.63 eEV2SuctProbAlTrap_1 EEV2 suction temperature probe alarm
.1.3.6.1.4.1.6347.1.0.64 eEV2EvapProbAlTrap_1 EEV2 evaporation pressure probe alarm
.1.3.6.1.4.1.6347.1.0.65 eEV2CondProbAlTrap_1 EEV2 condensation pressure probe alarm
.1.3.6.1.4.1.6347.1.0.66 eEV2DischProbAlTrap_1 EEV2 discharge temperature probe alarm
.1.3.6.1.4.1.6347.1.0.67 cPYCommAlTrap_1 CPY communication down alarm
.1.3.6.1.4.1.6347.1.0.68 cPYMemoryAlTrap_1 Internal memory error
.1.3.6.1.4.1.6347.1.0.69 cPYParameterAlTrap_1 Parameter error
.1.3.6.1.4.1.6347.1.0.70 cPYHighCurrentAlTrap_1 High electrode current
.1.3.6.1.4.1.6347.1.0.71 cPYLowSteamAlTrap_1 Low steam flow rate
.1.3.6.1.4.1.6347.1.0.72 cPYDrainAlTrap_1 Failed discharge
.1.3.6.1.4.1.6347.1.0.73 cPYMaintAlTrap_1 Maintenance time expired
.1.3.6.1.4.1.6347.1.0.74 cPYNoWaterAlTrap_1 No water
.1.3.6.1.4.1.6347.1.0.75 cPYCylMaintAlTrap_1 Cylinder maintenance
.1.3.6.1.4.1.6347.1.0.76 cPYDirtyCylAlTrap_1 Cylinder burnt out
.1.3.6.1.4.1.6347.1.0.77 cPYFoamAlTrap_1 Foam presence
.1.3.6.1.4.1.6347.1.0.78 cPYLifeTimeAlTrap_1 Life timer expired
.1.3.6.1.4.1.6347.1.0.79 cPYHighWatLevAlTrap_1 High water level
.1.3.6.1.4.1.6347.1.0.80 cPYHighWatConductAlTrap_1 High water conductivity
.1.3.6.1.4.1.6347.1.0.81 cPYConnectionAlTrap_1 Connection error
.1.3.6.1.4.1.6347.1.0.82 fan1PowerAlTrap_1 Fan 1 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.0.83 fan1CommAlTrap_1 Fan 1 communication down alarm
.1.3.6.1.4.1.6347.1.0.84 fan1HighTempAlTrap_1 Fan 1 regulation module high temperature
.1.3.6.1.4.1.6347.1.0.85 fan1NetComAlTrap_1 Fan 1 no master-slave communication
.1.3.6.1.4.1.6347.1.0.86 fan1InvRegAlTrap_1 Fan 1 regulation module failure
.1.3.6.1.4.1.6347.1.0.87 fan1HighMotTempAlTrap_1 High fan 1 motor temperature
.1.3.6.1.4.1.6347.1.0.88 fan1HallSensAlTrap_1 Fan 1 Hall sensor error
.1.3.6.1.4.1.6347.1.0.89 fan1OverloadAlTrap_1 Fan 1 motor overload
.1.3.6.1.4.1.6347.1.0.94 fan1LowDCAlTrap_1 Low fan 1 DC power supply
.1.3.6.1.4.1.6347.1.0.95 fan2PowerAlTrap_1 Fan 2 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.0.96 fan2CommAlTrap_1 Fan 2 communication down alarm
.1.3.6.1.4.1.6347.1.0.97 fan2HighTempAlTrap_1 Fan 2 regulation module high temperature
.1.3.6.1.4.1.6347.1.0.98 fan2NetComAlTrap_1 Fan 2 no master-slave communication
.1.3.6.1.4.1.6347.1.0.99 fan2InvRegAlTrap_1 Fan 2 regulation module failure
.1.3.6.1.4.1.6347.1.0.100 fan2HighMotTempAlTrap_1 High fan 2 motor temperature
.1.3.6.1.4.1.6347.1.0.101 fan2HallSensAlTrap_1 Fan 2 Hall sensor error
.1.3.6.1.4.1.6347.1.0.102 fan2OverloadAlTrap_1 Fan 2 motor overload

INSTALLATION AND MAINTENANCE 49


CLOSE CONTROL AIR CONDITIONERS

Type Name Description

.1.3.6.1.4.1.6347.1.0.107 fan2LowDCAlTrap_1 Low fan 2 DC power supply


.1.3.6.1.4.1.6347.1.0.108 fan3PowerAlTrap_1 Fan 3 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.0.109 fan3CommAlTrap_1 Fan 3 communication down alarm
.1.3.6.1.4.1.6347.1.0.110 fan3HighTempAlTrap_1 Fan 3 regulation module high temperature
.1.3.6.1.4.1.6347.1.0.111 fan3NetComAlTrap_1 Fan 3 no master-slave communication
.1.3.6.1.4.1.6347.1.0.112 fan3InvRegAlTrap_1 Fan 3 regulation module failure
.1.3.6.1.4.1.6347.1.0.113 fan3HighMotTempAlTrap_1 High fan 3 motor temperature
.1.3.6.1.4.1.6347.1.0.114 fan3HallSensAlTrap_1 Fan 3 Hall sensor error
.1.3.6.1.4.1.6347.1.0.115 fan3OverloadAlTrap_1 Fan 3 motor overload
.1.3.6.1.4.1.6347.1.0.120 fan3LowDCAlTrap_1 Low fan 3 DC power supply
.1.3.6.1.4.1.6347.1.0.121 fan4PowerAlTrap_1 Fan 4 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.0.122 fan4CommAlTrap_1 Fan 4 communication down alarm
.1.3.6.1.4.1.6347.1.0.123 fan4HighTempAlTrap_1 Fan 4 regulation module high temperature
.1.3.6.1.4.1.6347.1.0.124 fan4NetComAlTrap_1 Fan 4 no master-slave communication
.1.3.6.1.4.1.6347.1.0.125 fan4InvRegAlTrap_1 Fan 4 regulation module failure
.1.3.6.1.4.1.6347.1.0.126 fan4HighMotTempAlTrap_1 High fan 4 motor temperature
.1.3.6.1.4.1.6347.1.0.127 fan4HallSensAlTrap_1 Fan 4 Hall sensor error
.1.3.6.1.4.1.6347.1.0.128 fan4OverloadAlTrap_1 Fan 4 motor overload
.1.3.6.1.4.1.6347.1.0.133 fan4LowDCAlTrap_1 Low fan 4 DC power supply
.1.3.6.1.4.1.6347.1.0.134 fan5PowerAlTrap_1 Fan 5 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.0.135 fan5CommAlTrap_1 Fan 5 communication down alarm
.1.3.6.1.4.1.6347.1.0.136 fan5HighTempAlTrap_1 Fan 5 regulation module high temperature
.1.3.6.1.4.1.6347.1.0.137 fan5NetComAlTrap_1 Fan 5 no master-slave communication
.1.3.6.1.4.1.6347.1.0.138 fan5InvRegAlTrap_1 Fan 5 regulation module failure
.1.3.6.1.4.1.6347.1.0.139 fan5HighMotTempAlTrap_1 High fan 5 motor temperature
.1.3.6.1.4.1.6347.1.0.140 fan5HallSensAlTrap_1 Fan 5 Hall sensor error
.1.3.6.1.4.1.6347.1.0.141 fan5OverloadAlTrap_1 Fan 5 motor overload
.1.3.6.1.4.1.6347.1.0.146 fan5LowDCAlTrap_1 Low fan 5 DC power supply
.1.3.6.1.4.1.6347.1.0.147 dFPSBrokenAlTrap_1 Broken dirty filter pressure sensor alarm
.1.3.6.1.4.1.6347.1.0.148 dFPSCablingAlTrap_1 Dirty filter pressure sensor cabling alarm
.1.3.6.1.4.1.6347.1.0.149 dFPSRangeAlTrap_1 Dirty filter pressure sensor pressure range alarm
.1.3.6.1.4.1.6347.1.0.150 dFPSADCAlTrap_1 Dirty filter pressure sensor overload ADC alarm
.1.3.6.1.4.1.6347.1.0.151 dFPSSettingAlTrap_1 Dirty filter pressure sensor calibration alarm
.1.3.6.1.4.1.6347.1.0.152 dFPSDCOAlTrap_1 Dirty filter pressure sensor DCO alarm
.1.3.6.1.4.1.6347.1.0.153 dFPSWatchdogAlTrap_1 Dirty filter pressure sensor watchdog alarm
.1.3.6.1.4.1.6347.1.0.154 dFPSCommAlTrap_1 Dirty filter pressure sensor communication alarm
.1.3.6.1.4.1.6347.1.0.155 invCompCommAlarmTrap_1 DC compressor inverter communication alarm

50 TECHNICAL MANUAL
6.3 CLOSE CONTROL SURVEYEVO MICROPROCESSOR SUPERVISOR VARIABLES (SOFTWARE VERSION 2.0)

Unit of
OID Name Description Type
measure
Digital input status
.1.3.6.1.4.1.6347.1.1.1.0 DamperStatusDI_1 Motorised damper status
.1.3.6.1.4.1.6347.1.1.2.0 DirtyFilterDI_1 Dirty filter alarm
.1.3.6.1.4.1.6347.1.1.3.0 RemoteOffDI_1 Remote OFF status
.1.3.6.1.4.1.6347.1.1.4.0 ElecHeaterAlarmDI_1 Electric coil safety thermostat alarm
.1.3.6.1.4.1.6347.1.1.5.0 WaterAlarmDI_1 Water sensor/Condensate pump alarm
.1.3.6.1.4.1.6347.1.1.6.0 ConfigurableDI1_1 Configurable input 1
.1.3.6.1.4.1.6347.1.1.7.0 ConfigurableDI2_1 Configurable input 2
.1.3.6.1.4.1.6347.1.1.8.0 ConfigurableDI3_1 Configurable input 3 - R
.1.3.6.1.4.1.6347.1.1.9.0 ConfigurableDI4_1 Configurable input 4
.1.3.6.1.4.1.6347.1.1.10.0 Comp1ThermAlarmDI_1 Compressor 1 breaker alarm
.1.3.6.1.4.1.6347.1.1.11.0 Comp1HPAlarmDI_1 Compressor 1 high pressure alarm
.1.3.6.1.4.1.6347.1.1.12.0 Comp1LPAlarmDI_1 Compressor 1 low pressure alarm
.1.3.6.1.4.1.6347.1.1.13.0 Comp2ThermAlarmDI_1 Compressor 2 breaker alarm
.1.3.6.1.4.1.6347.1.1.14.0 Comp2HPAlarmDI_1 Compressor 2 high pressure alarm
.1.3.6.1.4.1.6347.1.1.15.0 Comp2LowPresAlarmDI_1 Compressor 2 low pressure alarm
Digital output status
.1.3.6.1.4.1.6347.1.1.16.0 FansDO_1 Fan control
.1.3.6.1.4.1.6347.1.1.17.0 DamperDO_1 Motorised dampers control
.1.3.6.1.4.1.6347.1.1.18.0 ElecHeaterStage1DO_1 Electric heating coil 1 stage
.1.3.6.1.4.1.6347.1.1.19.0 ElecHeaterStage2DO_1 Electric heating coil 2 stage
.1.3.6.1.4.1.6347.1.1.20.0 ConfigurableDO1_1 Configurable digital output 1
- R
.1.3.6.1.4.1.6347.1.1.21.0 ConfigurableDO2_1 Configurable digital output 2
.1.3.6.1.4.1.6347.1.1.22.0 ConfigurableDO3_1 Configurable digital output 3
.1.3.6.1.4.1.6347.1.1.23.0 ConfigurableDO4_1 Configurable digital output 4
.1.3.6.1.4.1.6347.1.1.24.0 Compressor1DO_1 Compressor 1 control
.1.3.6.1.4.1.6347.1.1.25.0 Compressor2DO_1 Compressor 2 control

INSTALLATION AND MAINTENANCE 51


CLOSE CONTROL AIR CONDITIONERS

Unit of
OID Name Description Type
measure
Analogue inputs
.1.3.6.1.4.1.6347.1.2.1.0 ReturnHumidity_1 Return humidity %Rh
.1.3.6.1.4.1.6347.1.2.2.0 ReturnTemperature_1 Return temperature °C
.1.3.6.1.4.1.6347.1.2.3.0 SupplyHumidity_1 Supply humidity %Rh
.1.3.6.1.4.1.6347.1.2.4.0 SupplyTemperature_1 Supply temperature °C
.1.3.6.1.4.1.6347.1.2.5.0 AirPressure_1 Air pressure Pa
.1.3.6.1.4.1.6347.1.2.6.0 WaterINTemperature_1 Water inlet 1 temperature/Free cooling °C
.1.3.6.1.4.1.6347.1.2.7.0 WaterOUTTemperature_1 Water outlet temperature 1 °C
.1.3.6.1.4.1.6347.1.2.8.0 Comp1CondPress_1 Compressor 1 condensation pressure BarG
.1.3.6.1.4.1.6347.1.2.9.0 Compr2CondPress_1 Compressor 2 condensation pressure BarG
.1.3.6.1.4.1.6347.1.2.10.0 Compr1CondTemp_1 Compressor 1 condensation temperature °C
.1.3.6.1.4.1.6347.1.2.11.0 Comp2CondTemp_1 Compressor 2 condensation temperature °C
.1.3.6.1.4.1.6347.1.2.12.0 Comp1DischTemp_1 Compressor 1 discharge temperature °C
.1.3.6.1.4.1.6347.1.2.13.0 Comp2DischTemp_1 Compressor 2 discharge temperature °C
.1.3.6.1.4.1.6347.1.2.14.0 Comp1SuctionTemp_1 Compressor 1 suction temperature °C
.1.3.6.1.4.1.6347.1.2.15.0 Comp2SuctionTemp_1 Compressor 2 suction temperature °C R
.1.3.6.1.4.1.6347.1.2.16.0 Comp1EvapPres_1 Compressor 1 evaporation pressure BarG
.1.3.6.1.4.1.6347.1.2.17.0 Comp2EvapPres_1 Compressor 2 evaporation pressure BarG
.1.3.6.1.4.1.6347.1.2.18.0 Comp1EvapTemp_1 Compressor 1 evaporation temperature °C
.1.3.6.1.4.1.6347.1.2.19.0 Comp2EvapTemp_1 Compressor 2 evaporation temperature °C
.1.3.6.1.4.1.6347.1.2.20.0 Comp1LiquidTemp_1 Compressor 1 liquid temperature °C
.1.3.6.1.4.1.6347.1.2.21.0 Compr2LiquidTemp_1 Compressor 2 liquid temperature °C
.1.3.6.1.4.1.6347.1.2.22.0 WaterFlow1_1 Water flow rate 1) l/h
.1.3.6.1.4.1.6347.1.2.23.0 WaterFlow2_1 Water flow rate 2 l/h
.1.3.6.1.4.1.6347.1.2.24.0 TotalWaterFlow_1 Total water flow rate l/h
.1.3.6.1.4.1.6347.1.2.25.0 ReturnHumidityAvg_1 Return humidity (local network average) %Rh
.1.3.6.1.4.1.6347.1.2.26.0 ReturnTempAvg_1 Return temperature (local network average) °C
.1.3.6.1.4.1.6347.1.2.27.0 SupplyHumidityAvg_1 Supply humidity (local network average) %Rh
.1.3.6.1.4.1.6347.1.2.28.0 SupplyTempAvg_1 Supply temperature (local network average) °C
.1.3.6.1.4.1.6347.1.2.29.0 AirPressureAvg_1 Air pressure (local network average) °C
Analogue outputs
.1.3.6.1.4.1.6347.1.2.30.0 UnitFansDryCoolerAO_1 Supply Fan / Dry cooler modulation %
.1.3.6.1.4.1.6347.1.2.31.0 CoolingAO_1 Cooling valve / Free cooling / External inverter %
.1.3.6.1.4.1.6347.1.2.32.0 HeatingAO_1 Heating valve / Modulating electrical coil %
R
.1.3.6.1.4.1.6347.1.2.33.0 TwoSourcesAO_1 Two sources water valve %
.1.3.6.1.4.1.6347.1.2.34.0 Condenser1AO_1 Condenser 1 %
.1.3.6.1.4.1.6347.1.2.35.0 Condenser2HumidifAO_1 Condenser 2 / External humidifier %

52 TECHNICAL MANUAL
Unit of
OID Name Description Type
measure
Unit status
.1.3.6.1.4.1.6347.1.2.36.0 UnitStatus_1 Unit status * - R
* 1 = Unit OFF - 2 = OFF Remote - 3 = OFF from supervisor - 4 = Off from alarm - 5 = Stand-by - 6 = Unit ON - 7 = Ultracap
Supply air flow
.1.3.6.1.4.1.6347.1.2.37.0 AirFlow_1 Air flow m3/h R
Working hours
.1.3.6.1.4.1.6347.1.2.38.0 UnitWorkingHours_1 Unit hours of operation h
.1.3.6.1.4.1.6347.1.2.39.0 Comp1WorkingHours_1 Compressor 1 hours of operation h
.1.3.6.1.4.1.6347.1.2.40.0 Compr2WorkingHours_1 Compressor 2 hours of operation h
.1.3.6.1.4.1.6347.1.2.41.0 HeatingWorkingHours_1 Hours of heating operation h
.1.3.6.1.4.1.6347.1.2.42.0 DryCoolerWorkHours_1 Hours of dry cooler operation h
R
.1.3.6.1.4.1.6347.1.2.43.0 HumidifWorkingHours_1 Hours of humidifier operation h
.1.3.6.1.4.1.6347.1.2.44.0 CoolValveWorkHours_1 Hours of cooling valve operation h
.1.3.6.1.4.1.6347.1.2.45.0 Cond1WorkingHours_1 Condenser 1 hours of operation h
.1.3.6.1.4.1.6347.1.2.46.0 Cond2WorkingHours_1 Condenser 2 hours of operation h
.1.3.6.1.4.1.6347.1.2.47.0 FreeCoolWorkHours_1 Free Cooling hours of operation h
Electronic expansion valves state
.1.3.6.1.4.1.6347.1.2.48.0 EEV1SuperheatSet_1 Current EEV1 superheating set-point K
.1.3.6.1.4.1.6347.1.2.49.0 EEV2SuperheatSet_1 Current EEV2 superheating set-point K
.1.3.6.1.4.1.6347.1.2.50.0 EEV1Superheat_1 Current EEV1 superheating K
.1.3.6.1.4.1.6347.1.2.51.0 EEV2Superheat_1 Current EEV2 superheating K
.1.3.6.1.4.1.6347.1.2.52.0 EEV1Position_1 Current EEV1 position %
R
.1.3.6.1.4.1.6347.1.2.53.0 EEV2Position_1 Current EEV2 position %
.1.3.6.1.4.1.6347.1.2.54.0 EEV1PDesuperheat_1 Current EEV1 desuperheating K
.1.3.6.1.4.1.6347.1.2.55.0 EEV2Desuperheat_1 Current EEV2 desuperheating K
.1.3.6.1.4.1.6347.1.2.56.0 EEV1PSubcooling_1 Current EEV1 sub-cooling K
.1.3.6.1.4.1.6347.1.2.57.0 EEV2Subcooling_1 Current EEV2 sub-cooling K
Internal humidifier status
.1.3.6.1.4.1.6347.1.2.58.0 HumidifSteamProd_1 Current humidifier production kg/h
.1.3.6.1.4.1.6347.1.2.59.0 HumidifWaterConduct_1 Supply water conductivity μS/cm
R
.1.3.6.1.4.1.6347.1.2.60.0 HumidifierCurrent_1 Absorbed humidifier current A
.1.3.6.1.4.1.6347.1.2.61.0 HumidifWorkingMode_1 Humidifier operating mode * -
* 1 = Not active; 2 = Soft-start; 3 = Start full production after reduced production; 4 = Full production; 5 = Reduced production; 6,
7, 8 = Soft-start
.1.3.6.1.4.1.6347.1.2.62.0 HumidifWorkStatus_1 Humidifier operating status * - R
* 1 = Not active (no demand or blocked or disabled); 2 = Start evaporation cycle; 3 = Water charging in progress; 4 = Evaporation
in progress; 5 = AFS discharge; 6 = Water discharge (through dilution or manual); 7 = End of water discharge; 8 = Full discharge for
long period of downtime; 9 = Full discharge from manual or network request; 10 = No water control; 11 = Pre-wash; 12 = Periodic
discharge
.1.3.6.1.4.1.6347.1.1.26.0 HumidifierPowerDO_1 Humidifier control
.1.3.6.1.4.1.6347.1.1.27.0 HumidifDrainValveDO_1 Discharge valve
- R
.1.3.6.1.4.1.6347.1.1.28.0 HumidifFillValveDO_1 Charging valve
.1.3.6.1.4.1.6347.1.1.29.0 HumidifWaterLevel_1 High water level

INSTALLATION AND MAINTENANCE 53


CLOSE CONTROL AIR CONDITIONERS

Unit of
OID Name Description Type
measure
Fan status
.1.3.6.1.4.1.6347.1.2.63.0 Fan1SpeedRPM_1 Fan 1 speed RPM
.1.3.6.1.4.1.6347.1.2.64.0 Fan2SpeedRPM_1 Fan 2 speed RPM
.1.3.6.1.4.1.6347.1.2.65.0 Fan3SpeedRPM_1 Fan 3 speed RPM
.1.3.6.1.4.1.6347.1.2.66.0 Fan4SpeedRPM_1 Fan 4 speed RPM
.1.3.6.1.4.1.6347.1.2.67.0 Fan5SpeedRPM_1 Fan 5 speed RPM
.1.3.6.1.4.1.6347.1.2.68.0 Fan1Speed_1 Fan 1 speed %
.1.3.6.1.4.1.6347.1.2.69.0 Fan2Speed_1 Fan 2 speed %
.1.3.6.1.4.1.6347.1.2.70.0 Fan3Speed_1 Fan 3 speed %
.1.3.6.1.4.1.6347.1.2.71.0 Fan4Speed_1 Fan 4 speed %
.1.3.6.1.4.1.6347.1.2.72.0 Fan5Speed_1 Fan 5 speed %
R
.1.3.6.1.4.1.6347.1.2.73.0 Fan1Current_1 Fan 1 absorbed current A
.1.3.6.1.4.1.6347.1.2.74.0 Fan1Power_1 Fan 1 absorbed electrical power W
.1.3.6.1.4.1.6347.1.2.75.0 Fan2Current_1 Fan 2 absorbed current A
.1.3.6.1.4.1.6347.1.2.76.0 Fan2Power_1 Fan 2 absorbed electrical power W
.1.3.6.1.4.1.6347.1.2.77.0 Fan3Current_1 Fan 3 absorbed current A
.1.3.6.1.4.1.6347.1.2.78.0 Fan3Power_1 Fan 3 absorbed electrical power W
.1.3.6.1.4.1.6347.1.2.79.0 Fan4Current_1 Fan 4 absorbed current A
.1.3.6.1.4.1.6347.1.2.80.0 Fan4Power_1 Fan 4 absorbed electrical power W
.1.3.6.1.4.1.6347.1.2.81.0 Fan5Current_1 Fan 5 absorbed current A
.1.3.6.1.4.1.6347.1.2.82.0 Fan5Power_1 Fan 5 absorbed electrical power W
DC compressor inverter status
.1.3.6.1.4.1.6347.1.2.83.0 InverterCompSpeed_1 Current compressor speed Hz
.1.3.6.1.4.1.6347.1.2.84.0 InverterCompPower_1 Current compressor electrical power kW R
.1.3.6.1.4.1.6347.1.2.85.0 InverterCompCurrent_1 Current compressor absorbed current A
Water cooling power
.1.3.6.1.4.1.6347.1.2.86.0 WaterCoolingCap_1 Chilled water cooling capacity kW
R
.1.3.6.1.4.1.6347.1.2.87.0 EER_1 EER -
Electric coil status
.1.3.6.1.4.1.6347.1.2.88.0 HeaterActiveStages_1 Number of active stages -
R
.1.3.6.1.4.1.6347.1.2.89.0 ElecHeaterPower_1 Electrical power requirement kW

54 TECHNICAL MANUAL
Unit of
OID Name Description Type
measure
Set-point
.1.3.6.1.4.1.6347.1.2.90.0 TemperatureSetpoint_1 Temperature set-point °C
R/W
.1.3.6.1.4.1.6347.1.2.91.0 HumiditySetpoint_1 Humidity set-point %Rh
Ventilation set-point
.1.3.6.1.4.1.6347.1.2.92.0 AirFlowSetpoint_1 Supply air flow rate set-point m3/h
R/W
.1.3.6.1.4.1.6347.1.2.93.0 AirPressureSetpoint_1 Air pressure set-point Pa
Temperature Regulation
.1.3.6.1.4.1.6347.1.2.94.0 TempControlSel_1 Regulation sensor * - R/W
* 1 = Return; 2 = Supply
.1.3.6.1.4.1.6347.1.2.95.0 TempControlType_1 Regulation type - R/W
1 = Proportional (P); 2 = Proportional + Integral (PI); 3 = Proportional + Integral + Derivative (PID)
.1.3.6.1.4.1.6347.1.2.96.0 ProportionalBand_1 Proportional Band °C
.1.3.6.1.4.1.6347.1.2.97.0 IntagrativeTime_1 Integration time s
.1.3.6.1.4.1.6347.1.2.98.0 DerivativeTime_1 Derivative time s R/W
.1.3.6.1.4.1.6347.1.2.99.0 HighTempAlarmOffset_1 High temperature alarm offset °C
.1.3.6.1.4.1.6347.1.2.100.0 LowTempAlarmOffset_1 Low temperature alarm offset °C
Limit temperature regulation
.1.3.6.1.4.1.6347.1.2.101.0 HighLimitTempThr_1 Upper temperature limit °C
R/W
.1.3.6.1.4.1.6347.1.2.102.0 HighLimitTempMng_1 High limit temperature management * -
* 1 = Alarm only; 2 = Stop component; 3 = Reduction; 4 = Cold activation
.1.3.6.1.4.1.6347.1.2.103.0 LowLimitTempThr_1 Lower temperature limit °C
R/W
.1.3.6.1.4.1.6347.1.2.104.0 LowLimitTempMng_1 Low limit temperature management * -
1 = Alarm only; 2 = Stop component; 3 = Reduction; 4 = Hot activation
Humidity regulation
.1.3.6.1.4.1.6347.1.2.105.0 DehumidifPropBand_1 Dehumidification proportional band %RH
.1.3.6.1.4.1.6347.1.2.106.0 HumidifPropBand_1 Humidification proportional band %RH
.1.3.6.1.4.1.6347.1.2.107.0 HighRetHumAlOffset_1 High return humidity alarm offset %RH
R/W
.1.3.6.1.4.1.6347.1.2.108.0 LowRetHumAlOffset_1 Low return humidity alarm offset %RH
.1.3.6.1.4.1.6347.1.2.109.0 HighSupHumThr_1 Upper supply humidity limit %RH
.1.3.6.1.4.1.6347.1.2.110.0 LowSupHumThr_1 Lower supply humidity limit %RH
Humidifier regulation
.1.3.6.1.4.1.6347.1.1.30.0 EnableHumidifier_1 Humidification enabling
.1.3.6.1.4.1.6347.1.1.31.0 HumidifManualDrain_1 Manual discharge - R/W
.1.3.6.1.4.1.6347.1.1.32.0 HumidifCylWashing_1 Cylinder pre-wash
Free cooling and two sources regulation
.1.3.6.1.4.1.6347.1.2.111.0 FreeCoolingDelta_1 Free cooling delta °C
.1.3.6.1.4.1.6347.1.2.112.0 TSWaterSetpoint_1 Two sources water set-point °C
R/W
.1.3.6.1.4.1.6347.1.2.113.0 TSWaterPropBand_1 Two sources water band °C
.1.3.6.1.4.1.6347.1.1.33.0 TSEchange_1 Two sources source exchange -
Condenser regulation
.1.3.6.1.4.1.6347.1.2.114.0 Cond1ActualSet_1 Current condenser 1 set-point °C
.1.3.6.1.4.1.6347.1.2.115.0 Cond2ActualSet_1 Current condenser 2 set-point °C
.1.3.6.1.4.1.6347.1.2.116.0 CondSetpoint_1 Condensation set-point °C
R/W
.1.3.6.1.4.1.6347.1.2.117.0 CondPropoBand_1 Condensation proportional band °C
.1.3.6.1.4.1.6347.1.2.118.0 CondSetIncrease_1 Condensation set-point increase °C
.1.3.6.1.4.1.6347.1.2.119.0 MaxCondSetpoint_1 Maximum condensation set-point °C

INSTALLATION AND MAINTENANCE 55


CLOSE CONTROL AIR CONDITIONERS

Unit of
OID Name Description Type
measure
Dry cooler regulation
.1.3.6.1.4.1.6347.1.2.120.0 DryCoolerActualSet_1 Current dry cooler set-point °C
.1.3.6.1.4.1.6347.1.2.121.0 DryCoolerSetpoint_1 Dry cooler set-point °C
.1.3.6.1.4.1.6347.1.2.122.0 DryCoolerPropBand_1 Dry Cooler proportional band °C R/W
.1.3.6.1.4.1.6347.1.2.123.0 DryCoolerSetIncr_1 Dry Cooler set-point increase °C
.1.3.6.1.4.1.6347.1.2.124.0 MaxDryCoolerSet_1 Maximum dry Cooler set-point °C

56 TECHNICAL MANUAL
Unit of
OID Name Description Type
measure
Alarms
.1.3.6.1.4.1.6347.1.3.1.0 RetHumProbAl_1 Broken return humidity probe alarm
.1.3.6.1.4.1.6347.1.3.2.0 RetTempProbAl_1 Broken return temperature probe alarm
.1.3.6.1.4.1.6347.1.3.3.0 AirPrSensorAl_1 Broken air differential pressure sensor alarm
.1.3.6.1.4.1.6347.1.3.4.0 SupTempProbAl_1 Broken supply temperature probe alarm
Broken IN 1 water temperature probe alarm
.1.3.6.1.4.1.6347.1.3.5.0 WatIN1ProbAl_1
Broken free cooling temperature probe alarm
.1.3.6.1.4.1.6347.1.3.6.0 WatOUT1ProbAl_1 Broken OUT 1 water temperature probe alarm
Broken water flow 1 sensor alarm
.1.3.6.1.4.1.6347.1.3.7.0 WatFlw1ProbAl_1
Broken liquid 1 temperature probe alarm
.1.3.6.1.4.1.6347.1.3.8.0 SupHumProbAl_1 Broken supply humidity probe alarm
Broken water flow 2 sensor alarm
.1.3.6.1.4.1.6347.1.3.9.0 WatFlw2ProbAl_1
Broken liquid 2 temperature probe alarm
Water presence sensor alarm
.1.3.6.1.4.1.6347.1.3.10.0 WatPresAl_1
Condensate discharge pump alarm
.1.3.6.1.4.1.6347.1.3.11.0 ElHeatAl_1 Electric coil safety thermostat
.1.3.6.1.4.1.6347.1.3.12.0 DamperAl_1 Damper status alarm
.1.3.6.1.4.1.6347.1.3.13.0 FilterAl_1 Clogged air filter alarm
.1.3.6.1.4.1.6347.1.3.14.0 C1ThermAl_1 Compressor 1 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.3.15.0 C2ThermAl_1 Compressor 2 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.3.16.0 C1HighPresAl_1 Compressor 1 high pressure alarm
.1.3.6.1.4.1.6347.1.3.17.0 C2HighPresAl_1 Compressor 2 high pressure alarm
.1.3.6.1.4.1.6347.1.3.18.0 C1LowPresAl_1 Compressor 1 low pressure alarm
.1.3.6.1.4.1.6347.1.3.19.0 C2LowPresAl_1 Compressor 2 low pressure alarm
.1.3.6.1.4.1.6347.1.3.20.0 C1HighDischAl_1 Compressor 1 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.3.21.0 C2HighDischAl_1 Compressor 2 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.3.22.0 EEV1Al_1 EEV 1 alarm
.1.3.6.1.4.1.6347.1.3.23.0 EEV2Al_1 EEV 2 alarm - R
.1.3.6.1.4.1.6347.1.3.24.0 InverterCompAl_1 DC compressor inverter alarm
.1.3.6.1.4.1.6347.1.3.25.0 Fan1InverterAl_1 Fan 1 inverter alarm
.1.3.6.1.4.1.6347.1.3.26.0 Fan2InverterAl_1 Fan 2 inverter alarm
.1.3.6.1.4.1.6347.1.3.27.0 Fan3InverterAl_1 Fan 3 inverter alarm
.1.3.6.1.4.1.6347.1.3.28.0 Fan4InverterAl_1 Fan 4 inverter alarm
.1.3.6.1.4.1.6347.1.3.29.0 Fan5InverterAl_1 Fan 5 inverter alarm
.1.3.6.1.4.1.6347.1.3.30.0 InternalHumidifAl_1 Internal humidifier alarm
.1.3.6.1.4.1.6347.1.3.31.0 LocalNetworkAl_1 Local network communication alarm
.1.3.6.1.4.1.6347.1.3.32.0 RegHighTempAl_1 High temperature regulation alarm
.1.3.6.1.4.1.6347.1.3.33.0 RegLowTempAl_1 Low temperature regulation alarm
.1.3.6.1.4.1.6347.1.3.34.0 RetHighHumiAl_1 High return humidity alarm
.1.3.6.1.4.1.6347.1.3.35.0 RetLowHumiAl_1 Low return humidity alarm
.1.3.6.1.4.1.6347.1.3.36.0 SupHighHumiAl_1 High supply humidity alarm
.1.3.6.1.4.1.6347.1.3.37.0 SupLowHumiAl_1 Low supply humidity alarm
.1.3.6.1.4.1.6347.1.3.38.0 HighLimTempAl_1 High limit temperature alarm
.1.3.6.1.4.1.6347.1.3.39.0 LowLimTempAl_1 Low limit temperature alarm
.1.3.6.1.4.1.6347.1.3.40.0 DryCoolerAl_1 Dry cooler general alarm
.1.3.6.1.4.1.6347.1.3.41.0 ExternalHumidifAl_1 External humidifier general alarm
.1.3.6.1.4.1.6347.1.3.42.0 WaterPumpAl_1 General water pump alarm
.1.3.6.1.4.1.6347.1.3.43.0 Condenser1Al_1 Condenser 1 general alarm
.1.3.6.1.4.1.6347.1.3.44.0 Condenser2Al_1 Condenser 2 general alarm
.1.3.6.1.4.1.6347.1.3.45.0 GasLeakAl_1 Refrigerant gas leak detector alarm
.1.3.6.1.4.1.6347.1.3.46.0 FansGenAl_1 General supply fans alarm
.1.3.6.1.4.1.6347.1.3.47.0 FireSmokeAl_1 Fire/Smoke presence alarm
.1.3.6.1.4.1.6347.1.3.48.0 GenericSoftAl_1 Non-critical generic alarm

INSTALLATION AND MAINTENANCE 57


CLOSE CONTROL AIR CONDITIONERS

Unit of
OID Name Description Type
measure
.1.3.6.1.4.1.6347.1.3.49.0 GenericSeriousAl_1 Critical generic alarm
.1.3.6.1.4.1.6347.1.3.50.0 CondUnitGeneralAl_1 Condensing unit generic alarm
.1.3.6.1.4.1.6347.1.3.51.0 PowerSupplyAl_1 No power supply alarm
.1.3.6.1.4.1.6347.1.3.52.0 C1LowComprRatioAl_1 Compressor 1 low compression alarm
.1.3.6.1.4.1.6347.1.3.53.0 C2LowComprRatioAl_1 Compressor 2 low compression alarm
.1.3.6.1.4.1.6347.1.3.54.0 EEV1CommAl_1 EEV1 communication down alarm
.1.3.6.1.4.1.6347.1.3.55.0 EEV1SuctProbAl_1 EEV1 suction temperature probe alarm
.1.3.6.1.4.1.6347.1.3.56.0 EEV1EvapProbAl_1 EEV1 evaporation pressure probe alarm
.1.3.6.1.4.1.6347.1.3.57.0 EEV1CondProbAl_1 EEV1 condensation pressure probe alarm
.1.3.6.1.4.1.6347.1.3.58.0 EEV1DischProbAl_1 EEV1 discharge temperature probe alarm
.1.3.6.1.4.1.6347.1.3.59.0 EEV2CommAl_1 EEV2 communication down alarm
.1.3.6.1.4.1.6347.1.3.60.0 EEV2SuctProbAl_1 EEV2 suction temperature probe alarm
.1.3.6.1.4.1.6347.1.3.61.0 EEV2EvapProbAl_1 EEV2 evaporation pressure probe alarm
.1.3.6.1.4.1.6347.1.3.62.0 EEV2CondProbAl_1 EEV2 condensation pressure probe alarm
.1.3.6.1.4.1.6347.1.3.63.0 EEV2DischProbAl_1 EEV2 discharge temperature probe alarm
.1.3.6.1.4.1.6347.1.3.64.0 CPYCommAl_1 CPY communication down alarm
.1.3.6.1.4.1.6347.1.3.65.0 CPYMemoryAl_1 Internal memory error
.1.3.6.1.4.1.6347.1.3.66.0 CPYParameterAl_1 Parameter error
.1.3.6.1.4.1.6347.1.3.67.0 CPYHighCurrentAl_1 High electrode current
.1.3.6.1.4.1.6347.1.3.68.0 CPYLowSteamAl_1 Low steam flow rate
.1.3.6.1.4.1.6347.1.3.69.0 CPYDrainAl_1 Failed discharge
.1.3.6.1.4.1.6347.1.3.70.0 CPYMaintAl_1 Maintenance time expired
.1.3.6.1.4.1.6347.1.3.71.0 CPYNoWaterAl_1 No water
.1.3.6.1.4.1.6347.1.3.72.0 CPYCylMaintAl_1 Cylinder maintenance
.1.3.6.1.4.1.6347.1.3.73.0 CPYDirtyCylAl_1 Cylinder burnt out
.1.3.6.1.4.1.6347.1.3.74.0 CPYFoamAl_1 Foam presence
- R
.1.3.6.1.4.1.6347.1.3.75.0 CPYLifeTimeAl_1 Life timer expired
.1.3.6.1.4.1.6347.1.3.76.0 CPYHighWatLevAl_1 High water level
.1.3.6.1.4.1.6347.1.3.77.0 CPYHighWatConductAl_1 High water conductivity
.1.3.6.1.4.1.6347.1.3.78.0 CPYConnectionAl_1 Connection error
.1.3.6.1.4.1.6347.1.3.79.0 Fan1PowerAl_1 Fan 1 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.3.80.0 Fan1CommAl_1 Fan 1 communication down alarm
.1.3.6.1.4.1.6347.1.3.81.0 Fan1HighTempAl_1 Fan 1 regulation module high temperature
.1.3.6.1.4.1.6347.1.3.82.0 Fan1NetComAl_1 Fan 1 no master-slave communication
.1.3.6.1.4.1.6347.1.3.83.0 Fan1InvRegAl_1 Fan 1 regulation module failure
.1.3.6.1.4.1.6347.1.3.84.0 Fan1HighMotTempAl_1 High fan 1 motor temperature
.1.3.6.1.4.1.6347.1.3.85.0 Fan1HallSensAl_1 Fan 1 Hall sensor error
.1.3.6.1.4.1.6347.1.3.86.0 Fan1OverloadAl_1 Fan 1 motor overload
.1.3.6.1.4.1.6347.1.3.91.0 Fan1LowDCAl_1 Low fan 1 DC power supply
.1.3.6.1.4.1.6347.1.3.92.0 Fan2PowerAl_1 Fan 2 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.3.93.0 Fan2CommAl_1 Fan 2 communication down alarm
.1.3.6.1.4.1.6347.1.3.94.0 Fan2HighTempAl_1 Fan 2 regulation module high temperature
.1.3.6.1.4.1.6347.1.3.95.0 Fan2NetComAl_1 Fan 2 no master-slave communication
.1.3.6.1.4.1.6347.1.3.96.0 Fan2InvRegAl_1 Fan 2 regulation module failure
.1.3.6.1.4.1.6347.1.3.97.0 Fan2HighMotTempAl_1 High fan 2 motor temperature
.1.3.6.1.4.1.6347.1.3.98.0 Fan2HallSensAl_1 Fan 2 Hall sensor error
.1.3.6.1.4.1.6347.1.3.99.0 Fan2OverloadAl_1 Fan 2 motor overload
.1.3.6.1.4.1.6347.1.3.104.0 Fan2LowDCAl_1 Low fan 2 DC power supply
.1.3.6.1.4.1.6347.1.3.105.0 Fan3PowerAl_1 Fan 3 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.3.106.0 Fan3CommAl_1 Fan 3 communication down alarm
.1.3.6.1.4.1.6347.1.3.107.0 Fan3HighTempAl_1 Fan 3 regulation module high temperature
.1.3.6.1.4.1.6347.1.3.108.0 Fan3NetComAl_1 Fan 3 no master-slave communication

58 TECHNICAL MANUAL
Unit of
OID Name Description Type
measure
.1.3.6.1.4.1.6347.1.3.109.0 Fan3InvRegAl_1 Fan 3 regulation module failure
.1.3.6.1.4.1.6347.1.3.110.0 Fan3HighMotTempAl_1 High fan 3 motor temperature
.1.3.6.1.4.1.6347.1.3.111.0 Fan3HallSensAl_1 Fan 3 Hall sensor error
.1.3.6.1.4.1.6347.1.3.112.0 Fan3OverloadAl_1 Fan 3 motor overload
.1.3.6.1.4.1.6347.1.3.117.0 Fan3LowDCAl_1 Low fan 3 DC power supply
.1.3.6.1.4.1.6347.1.3.118.0 Fan4PowerAl_1 Fan 4 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.3.119.0 Fan4CommAl_1 Fan 4 communication down alarm
.1.3.6.1.4.1.6347.1.3.120.0 Fan4HighTempAl_1 Fan 4 regulation module high temperature
.1.3.6.1.4.1.6347.1.3.121.0 Fan4NetComAl_1 Fan 4 no master-slave communication
.1.3.6.1.4.1.6347.1.3.122.0 Fan4InvRegAl_1 Fan 4 regulation module failure
.1.3.6.1.4.1.6347.1.3.123.0 Fan4HighMotTempAl_1 High fan 4 motor temperature
.1.3.6.1.4.1.6347.1.3.124.0 Fan4HallSensAl_1 Fan 4 Hall sensor error
.1.3.6.1.4.1.6347.1.3.125.0 Fan4OverloadAl_1 Fan 4 motor overload
.1.3.6.1.4.1.6347.1.3.130.0 Fan4LowDCAl_1 Low fan 4 DC power supply
.1.3.6.1.4.1.6347.1.3.131.0 Fan5PowerAl_1 Fan 5 no phase/power supply alarm - R
.1.3.6.1.4.1.6347.1.3.132.0 Fan5CommAl_1 Fan 5 communication down alarm
.1.3.6.1.4.1.6347.1.3.133.0 Fan5HighTempAl_1 Fan 5 regulation module high temperature
.1.3.6.1.4.1.6347.1.3.134.0 Fan5NetComAl_1 Fan 5 no master-slave communication
.1.3.6.1.4.1.6347.1.3.135.0 Fan5InvRegAl_1 Fan 5 regulation module failure
.1.3.6.1.4.1.6347.1.3.136.0 Fan5HighMotTempAl_1 High fan 5 motor temperature
.1.3.6.1.4.1.6347.1.3.137.0 Fan5HallSensAl_1 Fan 5 Hall sensor error
.1.3.6.1.4.1.6347.1.3.138.0 Fan5OverloadAl_1 Fan 5 motor overload
.1.3.6.1.4.1.6347.1.3.143.0 Fan5LowDCAl_1 Low fan 5 DC power supply
.1.3.6.1.4.1.6347.1.3.144.0 InvCompCommAlarm_1 DC compressor inverter communication alarm
.1.3.6.1.4.1.6347.1.2.125.0 InvCompAlCode1_1 DC compressor inverter alarm code [0] *
.1.3.6.1.4.1.6347.1.2.126.0 InvCompAlCode2_1 DC compressor inverter alarm code [1] *
.1.3.6.1.4.1.6347.1.2.127.0 InvCompAlCode3_1 DC compressor inverter alarm code [2] *
.1.3.6.1.4.1.6347.1.2.128.0 InvCompAlCode4_1 DC compressor inverter alarm code [3] *
.1.3.6.1.4.1.6347.1.2.129.0 InvCompAlCode5_1 DC compressor inverter alarm code [4] *
* 48 = 0; 49 = 1; 50 = 2; 51 = 3; 52 = 4; 53 = 5; 54 = 6; 55 = 7; 56 = 8; 57 = 9; 70 = F

INSTALLATION AND MAINTENANCE 59


CLOSE CONTROL AIR CONDITIONERS

Unit of
OID Name Description Type
measure
Alarms reset
Water presence sensor alarm reset
.1.3.6.1.4.1.6347.1.1.34.0 WatPresAlRes_1
Condensate discharge pump alarm reset
.1.3.6.1.4.1.6347.1.1.35.0 ElHeatAlRes_1 Electr. coil safety thermostat alarm reset
.1.3.6.1.4.1.6347.1.1.36.0 DamperAlRes_1 Damper status alarm reset
.1.3.6.1.4.1.6347.1.1.37.0 FilterAlRes_1 Clogged air filter alarm reset
Compressor 1 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.1.38.0 C1ThermAlRes_1
reset
Compressor 2 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.1.39.0 C2ThermAlRes_1
reset
.1.3.6.1.4.1.6347.1.1.40.0 C1HighPresAlRes_1 Compressor 1 high pressure alarm reset
.1.3.6.1.4.1.6347.1.1.41.0 C2HighPresAlRes_1 Compressor 2 high pressure alarm reset
Compressor 1 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.1.42.0 C1HighDischAlRes_1
reset
Compressor 2 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.1.43.0 C2HighDischAlRes_1
reset
.1.3.6.1.4.1.6347.1.1.44.0 EEV1AlRes_1 Compressor 1 EEV alarm reset
.1.3.6.1.4.1.6347.1.1.45.0 EEV2AlRes_1 Compressor 2 EEV alarm reset
.1.3.6.1.4.1.6347.1.1.46.0 InverterCompAlRes_1 Compressor 1 inverter alarm reset
.1.3.6.1.4.1.6347.1.1.47.0 C1LoComprRatioAlRes_1 Comp. 1 low compression alarm reset
.1.3.6.1.4.1.6347.1.1.48.0 C2LoComprRatioAlRes_1 Comp. 2 low compression alarm reset
.1.3.6.1.4.1.6347.1.1.49.0 Fan1InverterAlRes_1 Fan 1 inverter alarm reset - R
.1.3.6.1.4.1.6347.1.1.50.0 Fan2InverterAlRes_1 Fan 2 inverter alarm reset
.1.3.6.1.4.1.6347.1.1.51.0 Fan3InverterAlRes_1 Fan 3 inverter alarm reset
.1.3.6.1.4.1.6347.1.1.52.0 Fan4InverterAlRes_1 Fan 4 inverter alarm reset
.1.3.6.1.4.1.6347.1.1.53.0 Fan5InverterAlRes_1 Fan 5 inverter alarm reset
.1.3.6.1.4.1.6347.1.1.54.0 IntHumidifAlRes_1 Internal humidifier alarm reset
.1.3.6.1.4.1.6347.1.1.55.0 DryCoolerAlRes_1 Dry cooler general alarm reset
.1.3.6.1.4.1.6347.1.1.56.0 ExtHumidifAlRes_1 External humidifier general alarm reset
.1.3.6.1.4.1.6347.1.1.57.0 WaterPumpAlRes_1 General water pump alarm reset
.1.3.6.1.4.1.6347.1.1.58.0 Condenser1AlRes_1 Condenser 1 general alarm reset
.1.3.6.1.4.1.6347.1.1.59.0 Condenser2AlRes_1 Condenser 2 general alarm reset
.1.3.6.1.4.1.6347.1.1.60.0 GasLeakAlRes_1 Refrigerant gas leak detector alarm reset
.1.3.6.1.4.1.6347.1.1.61.0 FansGenAlRes_1 General supply fans alarm reset
.1.3.6.1.4.1.6347.1.1.62.0 FireSmokeAlRes_1 Fire/Smoke presence alarm reset
.1.3.6.1.4.1.6347.1.1.63.0 GenericSoftAlRes_1 Non-critical generic alarm reset
.1.3.6.1.4.1.6347.1.1.64.0 GenericSeriousAlRes_1 Critical generic alarm reset
.1.3.6.1.4.1.6347.1.1.65.0 CondUnitGenAlRes_1 Condensing unit generic alarm reset
.1.3.6.1.4.1.6347.1.1.66.0 PowerSupplyAlRes_1 No power supply alarm reset
.1.3.6.1.4.1.6347.1.1.67.0 C1LowPresAlRes_1 Compressor 1 low pressure alarm reset
.1.3.6.1.4.1.6347.1.1.68.0 C2LowPresAlRes_1 Compressor 2 low pressure alarm reset

60 TECHNICAL MANUAL
6.3.1 ALARM TRAPS

Type Name Description

Alarm traps
.1.3.6.1.4.1.6347.1.0.1 retHumProbAlTrap_1 Broken return humidity probe alarm
.1.3.6.1.4.1.6347.1.0.2 retTempProbAlTrap_1 Broken return temperature probe alarm
.1.3.6.1.4.1.6347.1.0.3 airPrSensorALTrap_1 Broken air differential pressure sensor alarm
.1.3.6.1.4.1.6347.1.0.4 supTempProbAlTrap_1 Broken supply temperature probe alarm
Broken IN 1 water temperature probe alarm
.1.3.6.1.4.1.6347.1.0.5 watIN1ProbAlTrap_1
Broken free cooling temperature probe alarm
.1.3.6.1.4.1.6347.1.0.6 watOUT1ProbAlTrap_1 Broken OUT 1 water temperature probe alarm
Broken water flow 1 sensor alarm
.1.3.6.1.4.1.6347.1.0.7 watFlw1ProbAlTrap_1
Broken liquid 1 temperature probe alarm
.1.3.6.1.4.1.6347.1.0.8 supHumProbAlTrap_1 Broken supply humidity probe alarm
Broken water flow 2 sensor alarm
.1.3.6.1.4.1.6347.1.0.9 watFlw2ProbAlTrap_1
Broken liquid 2 temperature probe alarm
Water presence sensor alarm
.1.3.6.1.4.1.6347.1.0.10 watPresAlTrap_1
Condensate discharge pump alarm
.1.3.6.1.4.1.6347.1.0.11 elHeatAlTrap_1 Electric coil safety thermostat
.1.3.6.1.4.1.6347.1.0.12 damperAlTrap_1 Damper status alarm
.1.3.6.1.4.1.6347.1.0.13 filterAlTrap_1 Clogged air filter alarm
.1.3.6.1.4.1.6347.1.0.14 c1ThermAlTrap_1 Compressor 1 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.0.15 c2ThermAlTrap_1 Compressor 2 thermal magnetic protection alarm
.1.3.6.1.4.1.6347.1.0.16 c1HighPresAlTrap_1 Compressor 1 high pressure alarm
.1.3.6.1.4.1.6347.1.0.17 c2HighPresAlTrap_1 Compressor 2 high pressure alarm
.1.3.6.1.4.1.6347.1.0.18 c1LowPresAlTrap_1 Compressor 1 low pressure alarm
.1.3.6.1.4.1.6347.1.0.19 c2LowPresAlTrap_1 Compressor 2 low pressure alarm
.1.3.6.1.4.1.6347.1.0.20 c1HighDischAlTrap_1 Compressor 1 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.0.21 c2HighDischAlTrap_1 Compressor 2 high discharge temperature alarm
.1.3.6.1.4.1.6347.1.0.22 eEV1AlTrap_1 EEV 1 alarm
.1.3.6.1.4.1.6347.1.0.23 eEV2AlTrap_1 EEV 2 alarm
.1.3.6.1.4.1.6347.1.0.24 inverterCompAlTrap_1 DC compressor inverter alarm
.1.3.6.1.4.1.6347.1.0.25 fan1InverterAlTrap_1 Fan 1 inverter alarm
.1.3.6.1.4.1.6347.1.0.26 fan2InverterAlTrap_1 Fan 2 inverter alarm
.1.3.6.1.4.1.6347.1.0.27 fan3InverterAlTrap_1 Fan 3 inverter alarm
.1.3.6.1.4.1.6347.1.0.28 fan4InverterAlTrap_1 Fan 4 inverter alarm
.1.3.6.1.4.1.6347.1.0.29 fan5InverterAlTrap_1 Fan 5 inverter alarm
.1.3.6.1.4.1.6347.1.0.30 internalHumidifAlTrap_1 Internal humidifier alarm
.1.3.6.1.4.1.6347.1.0.31 localNetworkAlTrap_1 Local network communication alarm
.1.3.6.1.4.1.6347.1.0.32 regHighTempAlTrap_1 High temperature regulation alarm
.1.3.6.1.4.1.6347.1.0.33 regLowTempAlTrap_1 Low temperature regulation alarm
.1.3.6.1.4.1.6347.1.0.34 retHighHumiAlTrap_1 High return humidity alarm
.1.3.6.1.4.1.6347.1.0.35 retLowHumiAlTrap_1 Low return humidity alarm
.1.3.6.1.4.1.6347.1.0.36 supHighHumiAlTrap_1 High supply humidity alarm
.1.3.6.1.4.1.6347.1.0.37 supLowHumiAlTrap_1 Low supply humidity alarm
.1.3.6.1.4.1.6347.1.0.38 highLimTempAlTrap_1 High limit temperature alarm
.1.3.6.1.4.1.6347.1.0.39 lowLimTempAlTrap_1 Low limit temperature alarm
.1.3.6.1.4.1.6347.1.0.40 dryCoolerAlTrap_1 Dry cooler general alarm
.1.3.6.1.4.1.6347.1.0.41 externalHumidifAlTrap_1 External humidifier general alarm
.1.3.6.1.4.1.6347.1.0.42 waterPumpAlTrap_1 General water pump alarm
.1.3.6.1.4.1.6347.1.0.43 condenser1AlTrap_1 Condenser 1 general alarm
.1.3.6.1.4.1.6347.1.0.44 condenser2AlTrap_1 Condenser 2 general alarm
.1.3.6.1.4.1.6347.1.0.45 gasLeakAlTrap_1 Refrigerant gas leak detector alarm
.1.3.6.1.4.1.6347.1.0.46 fansGenAlTrap_1 General supply fans alarm

INSTALLATION AND MAINTENANCE 61


CLOSE CONTROL AIR CONDITIONERS

Type Name Description

.1.3.6.1.4.1.6347.1.0.47 fireSmokeAlTrap_1 Fire/Smoke presence alarm


.1.3.6.1.4.1.6347.1.0.48 genericSoftAlTrap_1 Non-critical generic alarm
.1.3.6.1.4.1.6347.1.0.49 genericSeriousAlTrap_1 Critical generic alarm
.1.3.6.1.4.1.6347.1.0.50 condUnitGeneralAlTrap_1 Condensing unit generic alarm
.1.3.6.1.4.1.6347.1.0.51 powerSupplyAlTrap_1 No power supply alarm
.1.3.6.1.4.1.6347.1.0.52 c1LowComprRatioAlTrap_1 Compressor 1 low compression alarm
.1.3.6.1.4.1.6347.1.0.53 c2LowComprRatioAlTrap_1 Compressor 2 low compression alarm
.1.3.6.1.4.1.6347.1.0.54 eEV1CommAlTrap_1 EEV1 communication down alarm
.1.3.6.1.4.1.6347.1.0.55 eEV1SuctProbAlTrap_1 EEV1 suction temperature probe alarm
.1.3.6.1.4.1.6347.1.0.56 eEV1EvapProbAlTrap_1 EEV1 evaporation pressure probe alarm
.1.3.6.1.4.1.6347.1.0.57 eEV1CondProbAlTrap_1 EEV1 condensation pressure probe alarm
.1.3.6.1.4.1.6347.1.0.58 eEV1DischProbAlTrap_1 EEV1 discharge temperature probe alarm
.1.3.6.1.4.1.6347.1.0.59 eEV2CommAlTrap_1 EEV2 communication down alarm
.1.3.6.1.4.1.6347.1.0.60 eEV2SuctProbAlTrap_1 EEV2 suction temperature probe alarm
.1.3.6.1.4.1.6347.1.0.61 eEV2EvapProbAlTrap_1 EEV2 evaporation pressure probe alarm
.1.3.6.1.4.1.6347.1.0.62 eEV2CondProbAlTrap_1 EEV2 condensation pressure probe alarm
.1.3.6.1.4.1.6347.1.0.63 eEV2DischProbAlTrap_1 EEV2 discharge temperature probe alarm
.1.3.6.1.4.1.6347.1.0.64 cPYCommAlTrap_1 CPY communication down alarm
.1.3.6.1.4.1.6347.1.0.65 cPYMemoryAlTrap_1 Internal memory error
.1.3.6.1.4.1.6347.1.0.66 cPYParameterAlTrap_1 Parameter error
.1.3.6.1.4.1.6347.1.0.67 cPYHighCurrentAlTrap_1 High electrode current
.1.3.6.1.4.1.6347.1.0.68 cPYLowSteamAlTrap_1 Low steam flow rate
.1.3.6.1.4.1.6347.1.0.69 cPYDrainAlTrap_1 Failed discharge
.1.3.6.1.4.1.6347.1.0.70 cPYMaintAlTrap_1 Maintenance time expired
.1.3.6.1.4.1.6347.1.0.71 cPYNoWaterAlTrap_1 No water
.1.3.6.1.4.1.6347.1.0.72 cPYCylMaintAlTrap_1 Cylinder maintenance
.1.3.6.1.4.1.6347.1.0.73 cPYDirtyCylAlTrap_1 Cylinder burnt out
.1.3.6.1.4.1.6347.1.0.74 cPYFoamAlTrap_1 Foam presence
.1.3.6.1.4.1.6347.1.0.75 cPYLifeTimeAlTrap_1 Life timer expired
.1.3.6.1.4.1.6347.1.0.76 cPYHighWatLevAlTrap_1 High water level
.1.3.6.1.4.1.6347.1.0.77 cPYHighWatConductAlTrap_1 High water conductivity
.1.3.6.1.4.1.6347.1.0.78 cPYConnectionAlTrap_1 Connection error
.1.3.6.1.4.1.6347.1.0.79 fan1PowerAlTrap_1 Fan 1 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.0.80 fan1CommAlTrap_1 Fan 1 communication down alarm
.1.3.6.1.4.1.6347.1.0.81 fan1HighTempAlTrap_1 Fan 1 regulation module high temperature
.1.3.6.1.4.1.6347.1.0.82 fan1NetComAlTrap_1 Fan 1 no master-slave communication
.1.3.6.1.4.1.6347.1.0.83 fan1InvRegAlTrap_1 Fan 1 regulation module failure
.1.3.6.1.4.1.6347.1.0.84 fan1HighMotTempAlTrap_1 High fan 1 motor temperature
.1.3.6.1.4.1.6347.1.0.85 fan1HallSensAlTrap_1 Fan 1 Hall sensor error
.1.3.6.1.4.1.6347.1.0.86 fan1OverloadAlTrap_1 Fan 1 motor overload
.1.3.6.1.4.1.6347.1.0.91 fan1LowDCAlTrap_1 Low fan 1 DC power supply
.1.3.6.1.4.1.6347.1.0.92 fan2PowerAlTrap_1 Fan 2 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.0.93 fan2CommAlTrap_1 Fan 2 communication down alarm
.1.3.6.1.4.1.6347.1.0.94 fan2HighTempAlTrap_1 Fan 2 regulation module high temperature
.1.3.6.1.4.1.6347.1.0.95 fan2NetComAlTrap_1 Fan 2 no master-slave communication
.1.3.6.1.4.1.6347.1.0.96 fan2InvRegAlTrap_1 Fan 2 regulation module failure
.1.3.6.1.4.1.6347.1.0.97 fan2HighMotTempAlTrap_1 High fan 2 motor temperature
.1.3.6.1.4.1.6347.1.0.98 fan2HallSensAlTrap_1 Fan 2 Hall sensor error
.1.3.6.1.4.1.6347.1.0.99 fan2OverloadAlTrap_1 Fan 2 motor overload
.1.3.6.1.4.1.6347.1.0.104 fan2LowDCAlTrap_1 Low fan 2 DC power supply
.1.3.6.1.4.1.6347.1.0.105 fan3PowerAlTrap_1 Fan 3 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.0.106 fan3CommAlTrap_1 Fan 3 communication down alarm

62 TECHNICAL MANUAL
Type Name Description

.1.3.6.1.4.1.6347.1.0.107 fan3HighTempAlTrap_1 Fan 3 regulation module high temperature


.1.3.6.1.4.1.6347.1.0.108 fan3NetComAlTrap_1 Fan 3 no master-slave communication
.1.3.6.1.4.1.6347.1.0.109 fan3InvRegAlTrap_1 Fan 3 regulation module failure
.1.3.6.1.4.1.6347.1.0.110 fan3HighMotTempAlTrap_1 High fan 3 motor temperature
.1.3.6.1.4.1.6347.1.0.111 fan3HallSensAlTrap_1 Fan 3 Hall sensor error
.1.3.6.1.4.1.6347.1.0.112 fan3OverloadAlTrap_1 Fan 3 motor overload
.1.3.6.1.4.1.6347.1.0.117 fan3LowDCAlTrap_1 Low fan 3 DC power supply
.1.3.6.1.4.1.6347.1.0.118 fan4PowerAlTrap_1 Fan 4 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.0.119 fan4CommAlTrap_1 Fan 4 communication down alarm
.1.3.6.1.4.1.6347.1.0.120 fan4HighTempAlTrap_1 Fan 4 regulation module high temperature
.1.3.6.1.4.1.6347.1.0.121 fan4NetComAlTrap_1 Fan 4 no master-slave communication
.1.3.6.1.4.1.6347.1.0.122 fan4InvRegAlTrap_1 Fan 4 regulation module failure
.1.3.6.1.4.1.6347.1.0.123 fan4HighMotTempAlTrap_1 High fan 4 motor temperature
.1.3.6.1.4.1.6347.1.0.124 fan4HallSensAlTrap_1 Fan 4 Hall sensor error
.1.3.6.1.4.1.6347.1.0.125 fan4OverloadAlTrap_1 Fan 4 motor overload
.1.3.6.1.4.1.6347.1.0.130 fan4LowDCAlTrap_1 Low fan 4 DC power supply
.1.3.6.1.4.1.6347.1.0.131 fan5PowerAlTrap_1 Fan 5 no phase/power supply alarm
.1.3.6.1.4.1.6347.1.0.132 fan5CommAlTrap_1 Fan 5 communication down alarm
.1.3.6.1.4.1.6347.1.0.133 fan5HighTempAlTrap_1 Fan 5 regulation module high temperature
.1.3.6.1.4.1.6347.1.0.134 fan5NetComAlTrap_1 Fan 5 no master-slave communication
.1.3.6.1.4.1.6347.1.0.135 fan5InvRegAlTrap_1 Fan 5 regulation module failure
.1.3.6.1.4.1.6347.1.0.136 fan5HighMotTempAlTrap_1 High fan 5 motor temperature
.1.3.6.1.4.1.6347.1.0.137 fan5HallSensAlTrap_1 Fan 5 Hall sensor error
.1.3.6.1.4.1.6347.1.0.138 fan5OverloadAlTrap_1 Fan 5 motor overload
.1.3.6.1.4.1.6347.1.0.143 fan5LowDCAlTrap_1 Low fan 5 DC power supply
.1.3.6.1.4.1.6347.1.0.144 invCompCommAlarmTrap_1 DC compressor inverter communication alarm

INSTALLATION AND MAINTENANCE 63


CLOSE CONTROL AIR CONDITIONERS
7 TROUBLESHOOTING AND FAULTS ELIMINATION

7.1 NO COMMUNICATION ON THE SERIAL BOARD RS485 RTU MODBUS

In case of no RTU Modbus RS485 serial port communication, verify:

• That the communication LEDs are flashing. If fixed, check the wiring of the serial port.
• Verify the configured Baud Rate.
• Verify the configured ID.
• Verify the configured Word Length, Parity and Stop Bits.

7.2 NO COMMUNICATION ON THE ETHERNET PORT

In case of no communication in the Ethernet port, verify:

• That the IP address is set correctly.


• That the Subnet Mask is set correctly.
• That the Ethernet communication port is configured correctly.

64 TECHNICAL MANUAL
8 NOTES

INSTALLATION AND MAINTENANCE 65


CLOSE CONTROL AIR CONDITIONERS

66 TECHNICAL MANUAL
INSTALLATION AND MAINTENANCE 67
MADE IN ITALY BY:

TECNAIR LV S.p.A
21040 Uboldo (VA) - Italy
Via Caduti della Liberazione, 53

The Manufacturer adopts a policy of continuous development and therefore, reserves the right to make changes and improvements
to any product described in this document without prior notice. Technical data and dimensions are not binding.

Manual code 30344416 “TRANSLATION OF THE ORIGINAL INSTRUCTIONS”

You might also like