Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Received: 9 March 2021 Revised: 29 October 2021 Accepted: 2 December 2021 IET Power Electronics

DOI: 10.1049/pel2.12228

ORIGINAL RESEARCH PAPER

Research on power system transient stability with wind generation


integration under fault condition to achieve economic benefits

Muhammad Shahid Mastoi1 M. J. Tahir2 Muhammad Usman1 Delin Wang1


Shenxian Zhuang1 Mannan Hassan1

1
School of Electrical Engineering, Southwest Abstract
Jiaotong University, Sichuan, Chengdu, China
For a few decades, electric power growth and demand have increased globally. To fulfil this
2
School of Electrical Engineering, University Kuala demand, distribution generators (DGs) have been installed in the power system. To get
Lumpur, BMI, Batu 8 Jalan Sungai Pusu, Selengor,
Malaysia
numerous benefits such as comprising reduction of power losses, improvement of (volt-
age, current, rpm) transient stability, leads to economic benefits. DGs integration in the
Correspondence distribution power system (DPS) was reported as an optimal generator placement (OGP)
Delin Wang, School of Electrical Engineering, problem to maximize these benefits. This paper performs wind turbine (WT) integration
Southwest Jiaotong University, Sichuan, Chengdu
while considering the internal generator’s (rpm) transient stability under fault conditions.
611756, China.
Email: wangdelin@swjtu.edu.cn A power loss index (PLI) method is implemented to select potential candidate buses for
generator placement. A self-sorting analytical approach (SSA) is also used to determine
Funding information the optimal bus and WT size. The IEEE 14-bus DPS is used as the OGP test system to
National Natural Science Foundation of China, demonstrate the proposed method’s effectiveness in terms of power losses reduction, sys-
Grant/Award Number: 51777176
tem transient stability, and economic benefits. The IEEE 14 Bus system was considered
using MATLAB with a 3.2 GHz processor to perform the said approach. WT integration
suggested in case-2 results in a 65.80% power losses reduction, which leads to a 60.88%
enhancement of economic benefits of the DPS.

1 INTRODUCTION proposed to increase the system’s transient stability and power


efficiency. The hybrid cascaded IGBT-based converters are
In recent years, integrating renewable resources with DPS has operated using a fuzzy-PI-based technique [6] to improve WT
attracted researchers’ exciting attention due to its matchless eco- stability.
nomic benefits. The optimal DG placement and sizing in the A synchronized current that governs the WT and STAT-
DPS while considering the generator RPM constraints can max- COM is proposed in [7–10] during heavy grid fault timing and
imize these benefits. Using this technology, we can get signifi- increases the transient stability margin. The stability of wind
cant advantages such as reducing power losses, voltage profile farms based on fixed-speed induction generators and the use
improvement, rotor angle stability, and overall system stability. of static Var compensator (SVC) and static synchronous com-
Simultaneously, transient stability study is also crucial for evalu- pensator (STATCOM) for the integration of wind farms and
ating the system stability during fault conditions to gather eco- the impact of transient stability of fixed-speed wind turbine,
nomic benefits [1, 2]. variable-speed wind turbine, synchronous generator, and the
Recently most of the studies and research are going on designation of a fault in the presence of FACTS system [5] is
WT integration with the DPS and different control schemes suggested. Even the critical clearance time is essential in pre-
to enhance the system stability. In a study by [3], a rotor serving the power system’s transient stability [11]. Mohsen Taj-
speed dynamic control model is proposed to minimize the dinian et al. have accessed the system’s transient stability in the
transients affecting the WT in a fault condition, which works presence of WT by critical clearing time dependent on right
based on a time scale. In [4, 5], a new pitch angle control kinetic energy [12]. In [13], WT integration is achieved based
approach based on proportional-integral and fuzzy logic is on crucial clearing times.

This is an open access article under the terms of the Creative Commons Attribution License, which permits use, distribution and reproduction in any medium, provided the original work is
properly cited.
© 2021 The Authors. IET Power Electronics published by John Wiley & Sons Ltd on behalf of The Institution of Engineering and Technology

IET Power Electron. 2022;15:263–274. wileyonlinelibrary.com/iet-pel 263


264 MASTOI ET AL.

A method to enhance system rotor angle stability consid- Parizad et al. [23] tried to use two different techniques to
ering WT power constraints under fault conditions is pro- determine the optimal position and size of DG based on reduc-
posed in [14]. Similarly, in [15], the influence of WT integra- tion loss and voltage stability. The first method determines the
tion on the system rotor angle stability is studied. Reference best DG installation location by creating an accurate loss for-
[16] investigates the equipment’s transient stability by checking mula to reduce actual power loss. The voltage stability index
the machine state’s characteristics, including the motor speed, is used to locate the DG in the best position in the second
rotor angle, electrical output, and terminal voltage related to the method. Use forward and backward sweep methods to deter-
fault clearing time after a three-phase fault occurs in the sys- mine the power flow. The study used two 33 bus (radial) and 30
tem. References [17, 18] provide a valuable method for find- bus (loop) control networks. The proposed strategy shows a sig-
ing the most appropriate locations for mounting shunt com- nificant change in the voltage curve and a power loss reduction.
pensators to increase the power system’s transient stability. The Safigianni et al. [24] solved the impact of hybrid DG tech-
stability of the rotor angle is essential for studying the complex nology penetrating the medium voltage distribution network.
behaviour of power systems. Time-domain simulation is a stan- Power flow and short circuit analysis were carried out to deter-
dard method for measuring transient stability. It has two key mine the effect of DG penetration on the current, loss, voltage
drawbacks time-consuming computational requirements and curve, and short circuit level of the controlled grid. Their gen-
the incapacity to include specific knowledge about stability eral conclusion was that arbitrary accommodation by the DG
margins. leads to network sterilization and the infringement of technical
To decide its optimal size, Jamian et al. [19] used many opti- limitations.
mization techniques to control the performance of the DG. A non-heuristic Olympic ranking method was coupled with
A new proposed rank evolutionary particle swarm optimiza- DIgSILENT software in reference [25] to consider various per-
tion method, comparative experiments with evolutionary par- formance indicators, including losses, voltage, loads, and short-
ticle swarm optimization, and a traditional particle swarm opti- circuit currents. However, since this approach splits the issue
mization were conducted. Implementing evolutionary program- into many problems for each index, it does not ensure that the
ming and optimization of particle swarms allowed all particles to minimum solution will be found. An enhanced gravity search
migrate faster towards the desired value. The methodology they method was used in reference [26] to find the best location and
adopted showed a reduction in power loss, which was achieved size for photovoltaic-based DGs with monocrystalline and thin
by choosing the best DG size. sheets. Even though this kind of renewable integration produces
For optimal DG placement and sizing, combined nature- minor environmental damage, only the advantage of reduced
inspired algorithms were used in [20]. A two-step optimization power loss has been recognized.
technique has been proposed for integration with the DG. In The majority of studies [27] utilize population-based meta-
the first step, the best size of DG is calculated using particle heuristic algorithms as solution methods. Evolutionary pro-
swarm optimization metaheuristics, and the results obtained are gramming [28], ant colony optimization [29], artificial bee
tested for reverse power flow using the negative load method. colony optimization [30], and tabu search are all examples of
Then, the best location is determined by the loss sensitivity fac- this [31, 32]. All of these methods have been applied to the
tor and poor bus approaches when looking for potential bus issue of determining the best placement and size for DGs.
locations. In the second step, the optimal size of DGs is cal- These techniques are typically highly effective at finding near-
culated by using three nature-inspired algorithms, that is, parti- optimal solutions, mainly when dealing with complicated prob-
cle swarm optimization, a gravitational search algorithm, and a lems. Although heuristic techniques require a significant amount
combination of the previous two algorithms. of computing work, they often solve DG placement and size
Kotb et al. [21] studied genetic algorithms to determine mul- issues. On the other hand, these methods are only used to
tiple DG devices’ optimal location and size. Three key objec- determine the positions and sizes of DGs and evaluate their
tives were selected, that is, namely voltage, effective and reac- effects on steady-state performance. However, since DGs are
tive power loss, and DG size to reduce overall power loss and only represented by their active and reactive power, this ignores
increase the voltage curve. In their analysis, a 69-bus power dis- the impacts of the DG dynamics and may result in inaccurate
tribution test system was used for research and evaluation. The results.
proposed method shows that three DG devices of the same size Reference [33] introduced a hybrid optimization combining
are installed in three separate locations of the 69-bus power dis- the intelligent water drop technique and ant-lion algorithms to
tribution test system, reducing power loss and drawing a volt- determine DGs’ size and location in micro-grids while consid-
age curve. Reference [22] proposed a similar technology that ering voltage stability and network losses. In contrast, ant-lion
combines genetic algorithm and particle swarm optimization algorithms were combined for the same objectives to solve the
method to install and select DG in the distribution network. optimal allocation of wind turbine DGs [34]. A modified sine
The proposed strategy aims to increase the voltage, stabilize the cosine optimization method based on a chaotic map process
voltage, and reduce the radial system’s power loss. The genetic was used in reference [35] to optimize the allocation of numer-
algorithm is used to find the best DG system position, and the ous DGs in distribution networks. Regardless of how successful
particle swarm optimization process is used to determine the these applications are [34, 35], they disregard load fluctuations
best DG size. and load increases throughout the planning horizon.
MASTOI ET AL. 265

Reference [36] improved the gray wolf optimizer (GWO)


method and applied it to DGs’ optimal placement and size when
automatic voltage regulators were included. The Bat algorithm
was used in reference [37] to reduce power loss and improve the
voltage profile by considering the peak loading level. A modi-
fied Taguchi technique (TM) was proposed in reference [38]. By
analogy to the ideal solution approach for multi-objective opti-
mization, this method has been expanded to combine with the
technique for order of preference [39]. On the other hand, TM
effectiveness of references [38, 39] said that it relied on brain-
storming sessions to arrive at an appropriate selection of the
relevant variables and levels.
A moth-flame optimization method was integrated with the
loss sensitivity factor (LSF) in references [40, 41] to optimize FIGURE 1 Classification of power system stability
the location and size of wind-based renewable DG units to
reduce total losses. The uncertainties of wind generators’ load
and output power were considered in the optimal reactive power research region to optimize the operation’s profit by meeting the
dispatch in reference [42], and the problem was addressed specified demand. Multiple search engines based on hierarchical
using a marine predator’s algorithm (MPA). In reference [43], clustering, as suggested in [58], are potential combinations of
an enhanced tunicate swarm method was devoted to optimal integrating DGs in a network to decrease computation times.
DGs allocation with daily load fluctuations, although this study The injection of reactive power into the grid is an important
treated power losses as a single reduction goal. A multi-objective research topic since it allows for power factor correction and
salp swarm optimizer technique [44] and a coyote optimization avoidance of voltage drops. For example, Quezada et al. [59]
algorithm [45] were also used to achieve various technical and investigated the optimal placement of capacitive banks using
economic advantages. In reference [46], an analytical method heuristic techniques to enhance the characteristics mentioned
used an analytical approach to reduce the Network’s aggregated above; the same goal may also be accomplished using batter-
power losses and voltage stability index. ies, as shown in references [60, 61]. As developed in [62] and
Gil-González, et al. addressed wind power sources’ optimal improved by [63] using algorithms capable of searching for the
location and size in power networks with changing power fac- maximum power point tracking. Current technology allows the
tors [47]. The problem was framed using a mixed-integer non- integration of photovoltaic generators via a three-phase inverter
linear programming (MINLP) model. The wind energy conver- that, in addition to meeting the basic requirements for their inte-
sion system’s converter interfaces supply reactive power to the gration, can inject or absorb reactive power into the distribution
grid as needed through a non-linear controller design [48]. The system.
suggested model was solved with good performance in the gen- Figure 1 shows the general picture of the power system prob-
eral algebraic modelling system (i.e., GAMS) software for radial lems’ stability and determines its category and sub-category. The
distribution grids and meshed power systems. following are the description of the stability of the correspond-
The authors of [49, 50] developed differential evolution algo- ing form phenomenon.
rithms to solve several distributed generators’ optimal location, Here it is noteworthy that most of the researchers who
size, and power factor (DGs) to reduce power losses in a net- worked on WT integration reported in the literature. Mainly
work. A genetic algorithm was used in references [51, 52] to focus on suggesting the remedies for the transients produced
optimize the location and size of DGs. Ganguly and Samaj- in the system in normal and faulty conditions and reduction
pati [53] utilized this method to control DGs’ optimal man- of power losses, improvement voltage profile by optimal place-
agement after connecting to the Network. Hybrid algorithms, ment, and sizing of DGs. However, very few among them con-
such as a combined bee swarm and genetic algorithm for DG sidered WT integration impact on rotor angle stability under
allocation developed by Mahmoud et al. [54], have also been fault conditions. Interestingly, WT optimal placement and siz-
utilized in the specialized literature to enhance voltage con- ing based upon rotor angle stability under fault conditions have
trol and decrease active and reactive power losses in the dis- never been performed.
tribution network. GAMS software has also been used to pro- Therefore, considering this rarely discussed the issue, we
pose and solve algebraic natural mathematical models [55]. Fur- proposed the PLI method integrated with the analytical (SSA)
thermore, as mentioned in [47], sufficient planning for DGs’ technique for optimal placement and sizing of the WT in
optimal location and dimensioning is feasible. In [56], an opti- DPS based upon system DGs rotor angle stability under fault
mization approach for sizing and locating PV, WT, and capac- conditions. The PLI approach is used to determine the possible
itor banks was given, which was applied to a typical radial net- nominee buses for the WT placement. The SSA technique is
work, taking into account the uncertainties of demand induced used to determine the optimal placement by PLI and sizing of
by electric cars as well as changes in irradiation, wind speed, WT among the nominated buses and enhance the system’s tran-
and the average load. Reference [57] developed a virtual power sient stability under fault conditions, which improves economic
plant model that combines the renewable energy available in the benefits.
266 MASTOI ET AL.

TABLE 1 Parameters of objective function

Parameters Kp T Kic Kom Kc

Case study 0.06$ 8760 hr/year 1000$ 300$ 3$

FIGURE 2 Power flow in the presence of a DG in a branch K


Further, in Section 2, problem formulation is done consider-
ing system limitations for the stated objective. Then methodol-
ogy is expressed in Section 3, starting from power flow in each
branch to determine each bus’s power loss index and working
While maximizing the economic benefits, system voltage
flow of the self-sorting approach in subsections. Results are dis-
lemmatized between 0. 95 p.u. and 1.05 p.u.
cussed in Section 4 for the considered IEEE 14 bus DPS. In the
last, the paper is concluded for the presented problem.
∙ Maximum apparent power injection:


n ∑
n
2 PROBLEM FORMULATION SDG ( j ) ≤ Sload ( j ) (4)
i=1 j =1
2.1 Objective function
Apparent power injection is optimum lemmatized to load
DPS faces a drop in high voltage due to its complex structure, apparent power, and if it reaches this limit, power loss begins
which causes high power loss in the system. Reducing these to escalate again.
power losses by OGP in a DPS leads to economic advantages,
which this research paper takes on an analytical basis and can be ∙ Apparent injection:
expressed as:
( ) Smin ≤ SDG ≤ Smax (5)
OF = max Economic Bene fits

= max (CostbWT − CostaWT ) (1) The apparent power of the generators is lemmatized up to the
Smin 1 MVA and Smax 151 MVA for the power losses reduction
up to a minimal point and gather maximum economic benefits.
where CostbWT is the total annual cost of the DPS before OGP
and CostaWT is the total annual cost of DPS after OGP. The cost
∙ RPM stability:
function considered for this paper is stated as below.
RPMmin ≤ RPMDG ≤ RPMmax (6)
Total Annual Costb∕a = K p × T × TAPloss (b∕a )


n This is an important and unique constraint considered in
+ Kic × Nwt + Kom × Nwt + (Kc × W Tr ) (2) this paper for optimal DPS placement synchronous genera-
wt = 1 tor (OPSG). The existing generators are considered constraints
under the fault condition while suggesting DGs placement and
where K p is the coefficient of active power price in $∕kWh and sizing RPM. RPM of the generators are lemmatized up to the
T is operating time in hr/year and TAPloss (b∕a) is the total active RPMmin 1830 and RPMmax 1770 for the enhancement of eco-
power losses of the DPS before and after OGP and Kic is the nomic benefits up to a significant index.
installation cost of Nwt number of wind turbines and Kom is the
maintenance cost of Nwt number of wind turbines and Kc is the
wind turbine cost in $/kW of W Tr Wind turbine rating. For 3 METHODOLOGY
more details, refer to Table 1.
3.1 Power flow
2.2 System limitations The power flow of a DPS in the presence of additional genera-
tors is essential to consider for achieving the optimal minimum
It is imperative to take into consideration certain constraints in power losses. The flow of power within the branch and the load
order to maximize the economic benefits of i-e DGs rpm, volt- in DG’s presence shown in Figure 2 can be expressed as [64]
age, apparent rating, and maximum apparent power.
Psupply∕i = Pload ∕ j + Pline−loss∕k − PDG ∕ j (7)
∙ Voltage constraints:

Vi min ≤ Vi ≤ Vi max (3) Qsupply∕i = Qload ∕ j + Qline−loss∕k − QDG ∕ j (8)


MASTOI ET AL. 267

where Psupply∕i does the substation supply the power on the bus TABLE 2 Potential buses indexing by PLI method
i, Pline−loss∕k is the in-branch power loss k, PDG ∕ j is the additional Bus index PLI
generator supplying the power of the apartment on bus j, Pload ∕ j
2 1.000
is the power consumed by the load. Power losses in a branch
depending on the supply source vector and additional generator 5 0.6878
resulting from it, which is expressed as follows: 3 0.5794
4 0.4151
Pline−loss∕k = Iline∕k
2
× Rline∕k (9) 13 0.0392
14 0.0224
Qline−loss∕k = Iline∕k
2
× Xline∕k (10) 12 0.0149
11 0.0088

⎛ 2 ⎞ 10 0.0007
⎜ Pload ∕ j + Qload ∕ j − PDG ∕ j − QDG ∕ j ⎟
2 2 2
Pline−loss∕k =⎜ ⎟ × RLine∕k
⎜ | |2 ⎟
⎝ |V | ⎠
| j| Table 2.
(11)
LRbus (i ) − LRmin
⎛ 2 ⎞ PLIbus (i ) = (15)
⎜ Pload ∕ j + Qload ∕ j − PDG ∕ j − QDG ∕ j ⎟
2 2 2
LRmax − LRmin
Qline−loss∕k =⎜ ⎟ × XLine∕k
⎜ | |2 ⎟
⎝ |V j | ⎠ where LRbus(i ) is the loss reduction at bus(i ). LRmin and
| |
LRmax are the minimum and maximum loss reduction values.
(12)

where Pline−loss∕k and Qline−loss∕k are the real and reactive power 3.3 Self-sorting algorithm
losses of a particular branch in the presence of DG.
The enhancement of economic benefits in a DPS is an essen-
⎛ 2 ⎞ tial task that OPSG has gained. To accomplish this task, this
⎜ Pload ∕ j + Qload ∕ j − PDG ∕ j − QDG ∕ j ⎟
2 2 2

TAPloss = ⎜ ⎟ paper proposes a self-sorting analytical (SSA) approach. Previ-
⎜ | |2 ⎟ ously, flower pollination algorithm (FPA), particle swarm opti-
2 ≤ j ≤ Nb ⎝ |V | ⎠
| | j
mization (PSO) approaches were used to minimize total annual
1 < k < Nb − 1
costs by proposing optimal capacitor placement and sizing in
× RLine∕k (13) [66, 67]. SSA approach expressed for the OGP problem in a
flow chart below, as shown in Figure 3. The approach begins
⎛ 2 ⎞ with the initial load-flow analysis of the IEEE DPS being con-
⎜ Pload ∕ j + Qload ∕ j − PDG ∕ j − QDG ∕ j ⎟
2 2 2
∑ sidered. Using Equations (13) and (14), total active and reac-
TRPloss = ⎜ ⎟ tive power losses of the DPS can be cumulated. After finding
⎜ | |2 ⎟
2 ≤ j ≤ Nb ⎝ |V | ⎠
| j| initial power losses, potential buses are considered, suggested
1 < k < Nb − 1 by the PLI method see Table 1 using Equation (15) for DG
× XLine∕k (14)
placement.
The SSA approach applied to the considered test system,
considering the system limitations, particularly the rpm limita-
where TAPloss and TRPloss are the sum of real and reactive power
tion of the DGs rotor system under fault conditions. It is neces-
losses that occurred in k branches of the DPS.
sary to mention here that placement by DG is divided into two
cases. In case-1, only a top-order bus is selected as a potential
bus using PLI, and the SSA approach has suggested the DG rat-
3.2 Power loss index
ing for that particular bus. In case-2, SSA itself decides the DG
and candidate bus rating among all the potential buses suggested
In the literature, many analytical approaches are mentioned
by the PLI method to achieve the DPS’ maximum economic
which are used to solve the problem of OGPs. The PLI method
benefits. As initially, potential candidate buses are highlighted by
has been used in this paper to nominate the potential buses
the PLI method; this helps to reduce the overall computational
for optimal placement of DG. The power loss index (PLI) rep-
time. Once candidate buses are highlighted, SSA starts inserting
resents the loss reduction of that specific bus concerning the
WT with minimum rating on each bus and reaches maximum
system’s maximum and minimum loss reductions. When DG
until the system remains stable and power losses are minimized
units are installed on buses with high PLI, maximum loss reduc-
maximally. This means the SSA algorithm will not insert a higher
tion can be anticipated. The indexing of the potential buses
rating of WT if the next iteration result is poor than the previ-
can be done by using the expression given below [65], refer to
ous iteration result. This approach helps the SSA algorithm to
268 MASTOI ET AL.

TABLE 3 Self-sorting algorithm approach steps

Approach
steps Case-1 Case-2

1 Perform initial load flow Perform initial load flow


2 Treat top-tier buses as Treat all buses as candidate buses
candidate buses suggested suggested by the PLI method
by the PLI method
3 Start from Smin rating for WT Start from Smin rating for WT
sizing sizing
4 If constraints are satisfied to If constraints are satisfied to go to
go to the next iteration the next iteration
5 Increase WT size in each Increase WT size in each iteration
iteration until constraints until constraints are satisfied,
are satisfied, and losses and losses reduction with
reduction with maximum maximum economic benefits
economic benefits achieved achieved
6 SSA recommends WT rating SSA also recommends WT
placement, and its rating as well

4 RESULTS AND DISCUSSION

The efficiency of the proposed approach is demonstrated by


the IEEE 14 Bus system and MATLAB 2015 with CPU @
3.20 GHz 64 bit is used as a platform. Optimal DG position-
ing and sizing are conducted using the SSA method to ful-
fil the objective function, that is, maximizing economic ben-
efits. To stabilize the DPS, it is necessary to mention before
discussing the results here that other existing generators’ rpm
stability under fault conditions in DPS is mainly taken as a
constraint while suggesting the DG placement and its sizing.
FIGURE 3 The flow chart of the proposed self-sorting algorithm WT type 4 is considered for placement and sizing of DG.
It delivers active power but also absorbs reactive power. The
magnitude of this WT reactive absorption depends on this
expression:
( )
reduce the operating time again. As a result, the overall com- Wind Turbineq = − 0.05 + 0.04 × PWT
2
(16)
putational time is well managed. See Table 3 for a step-by-step
approach to both cases. Pseudocode of the proposed approach DG capacity and its configuration are done based on the
is a list below: transient stability of the system. For example, our algorithm
suggested 135 MW DG capacity with bus 3 configuration
Step 1: Defines the data for the load case and initial load when transient stability is not considered. Although more power
flow run. losses can be minimized in the DPS with this sizing and place-
Step 2: Find candidate buses using data from PLI and ment, the system will not be stable in transient or fault condi-
defining system constraints. tions. So, considering transient stability, our algorithm proposed
Step 3: idx(i), wt(j). a 115 MW capacity of the DG on bus 3. This approach can help
Step 4: Connect DG to a given bus for each test DG, per- stabilize DPS in transient or fault conditions, as expressed in
form TAPloss(i) load flow analysis and store the results Figures 5–8.
as a scenario.
Step 5: [idx(i), WT(j)] = max {Economic Benefits(i)}.
Step 6: Store [idx(i), WT(j)] until Swt ≤ Smax . 4.1 IEEE 14 DPS
Step 7: Select a scenario for optimal WT sizing and place-
ment with the lowest power loss. The system expressed in Figure 4 is IEEE 14 bus system; it is
a modified American distribution system [68] that contains five
Figure 3 presents the flow chart of a self-sorting algorithm synchronous machines, three for reactive support only. There
and has the following structure. are 20 branches in the network. It operates at 1 kV and 259
MASTOI ET AL. 269

FIGURE 4 IEEE 14 bus single line diagram

FIGURE 5 Generators RPM without WT IEEE 14 DPS with 0.100 CCT

FIGURE 6 Generators RPM with 66 MW WT at bus 3 IEEE-14 DPS with 0.115 CCT
270 MASTOI ET AL.

FIGURE 7 Generators RPM with 1 MW WT at bus 2 IEEE-14 DPS with 0.100 CCT

FIGURE 8 Generators RPM with 115 MW WT at bus 3 on IEEE-14 DPS with 0.135 CCT

MW, with loads of 73.5 MVAr with an initial power loss of losses and 7,039,504$ total annual cost with zero economic ben-
13.393 MW and a minimum voltage of 1.01 p.u. at bus 3. efits and 1835 rpm for all DGs; see Tables 4 and 5 for more
Moreover, its interlocking type of distribution system makes details.
it capable of allowing megawatts of power to flow in the sys- For the comparative study, see Table 4, an analytical approach
tem. PLI-suggested busses for case-1 and case-2 are regarded [13] suggested 66 MW WT with 115 ms CCT is to get transient
as WT candidate buses. WT placement and sizing were per- stability which eventually leads to economic benefits. A fault is
formed using the SSA approach to achieve optimal power loss inserted at 0.5 s and cleared at 0.615 s to stabilize the system. G1
reduction turns and DPS stability to maximize the economic and G2 get stable rpm i-e 1825 and 1826 at 1.5 s with the sug-
benefits. To observe the initial stability conditions of the DPS, gested 66 MW WT, and all DGs get stable 1823 rpm at 3 s, see
a 3-phase fault is inserted on bus 5 (maximum loaded). Criti- Figure 6. This WT integration results in a 50.56% power loss
cal clearing time (when the system remains stable) of the DPS reduction, which leads to a 47.73% enhancement of the eco-
without WT is considered 100 ms, so the fault is inserted at nomic benefits of the DPS see Table 4.
0.5 s and cleared at 0.6 s Initial stability condition of the rotor In this paper, case-1 see Table 4, bus 2 suggested by the PLI
rpm of the system DGs under fault condition is presented in method is taken as the optimal bus, and the 151 MW WT rating
Figure 5. The DGs rotor gets high rpm under fault condition suggested by the SSA technique is integrated with the DPS to
(G4-1927 rpm at 0.741 s); these oscillatory RPMs take time to gain the maximum economic benefits. It is impressive to see that
stabilize and reach up to 1838 rpm in 3 s, which are still not the even integrating 1 MW WT with 100 ms CCT on bus 2 while
normal rpm. So, without WT, DPS has 13.393 MW active power inserting the fault at 0.500 s clearing it at 0.600 s, RPMs of the
MASTOI ET AL. 271

TABLE 4 Results suggested by SSA

DG type Type-4 (WT)

Base case AM [13 ] PLI PLI-SSA

Active power losses (kW) 13.393 6.622 8.840 4.581


Reactive power losses (kVAr) 30.122 6.244 14.815 1.468
Power losses reduction (%) — 50.56 33.99 65.80
Minimum bus voltage (p.u), and bus index 1.01 (3) 1.01 (3) 1.01 (3) 1.01 (3)
Total WT power generation (MW/MVAr) — 66/174 151/986 115/529
Generator bus index — 3 2 3
Power losses cost 7,039,504 3,480,278 4,646,127 2,407,867
Saving WT placement — 3,559,226 2,393,377 4,631,637
WT power generation cost — 199,000 454,000 346,000
Total Annual Cost 7,039,504 3,679,578 5,100,427 2,754,167
Economic benefits — 3,359,926 1,939,077 4,285,337
(%) Economic benefits — 47.73 27.55 60.88

TABLE 5 Results suggested by SSA rpm remains in the rpm upper and lower limit, due to which
DG type Type-4 (WT) the system remains in a stable condition shown in Figure 8. WT
integration suggested in case-2 results in a 65.80% power loss
Base case PLI-SSA reduction, which leads to a 60.88% enhancement of economic
Active power losses (kW) 13.393 4.581 benefits of the DPS, as shown in Table 4. From Table 4, it is
Reactive power losses (kVAr) 30.122 1.468
clear that the SSA approach gives much better results in case-2
compared with case-1 and the analytical method [13]. It is nec-
Power losses reduction (%) — 65.80
essary to ensure that the top-order bus (2) suggested by the PLI
Minimum bus voltage (p.u), and bus index 1.01 (3) 1.01 (3) method in case *1 has a greater capacity than other buses. Still,
Total WT power generation (MW/MVAr) — 115/529 that bus cannot stabilize the machine and gain economic bene-
Generator bus index — 3 fits instead of the bus i-e (3), suggested by the SSA approach in
Power losses cost 7,039,504 2,407,867 case-2.
Saving WT placement — 4,631,637
Figure 9 illustrates the impact of WT placement for all cases
stated in Table 4 as a minimum voltage at bus 3 for all cases
WT power generation cost — 346,000
are the same. So, there is no such improvement in the voltage
Total annual cost 7,039,504 2,754,167 profile as the objective is to stabilize the system DGs under fault
Economic benefits — 4,285,337 conditions by the optimal placement of WT, which enhances net
(%) Economic benefits — 60.88 savings.

5 CONCLUSIONS
DGs of the DPS goes high (2150 rpm at 3 s), which takes the
system into an unstable condition see Figure 7. Although WT In this paper, an economic enhancement-based analytical SSA
integration suggested in case-1 results in 33.99% power losses technique was effectively proposed for the optimal placement
reduction, it leads to 27.55% enhancement of economic benefits and sizing of the WT while considering the rotor stability of
of the DPS see Table 4. The proposed approach in case-1 i-e bus the system DGs. The proposed technique (case 2) has achieved
2 with the suggested WT rating is not recommended due to the an infamous enhancement of the economic benefits. The sug-
factors mentioned above. gested approach was tested for the OPSG problem on consid-
In this paper, case-2 (see Table 4) bus 3 taken as an optimal ered IEEE 14 bus DPS to show the effectiveness. Our sug-
bus and 115 MW WT rating suggested by the SSA technique is gested case-1 and case-2 techniques have been compared with
integrated with the DPS to obtain the system’s transient stabil- the analytical approach recently reported in the literature (see
ity, which leads to maximum economic benefits. It is interesting Table 3). The results tabulated in Table 4 and Figure 8 reflect
to see the integration of 115 MW WT with 135 ms CCT on bus the proposed technique’s performance regarding the power
3 to insert the fault at 0.500 s and clearing at 0.635 s. RPMs of system’s transient stability, reduction of losses, and economic
the DGs of the DPS go stable (1800 rpm at 3 s), and all DGs benefits.
272 MASTOI ET AL.

FIGURE 9 Voltage profile IEEE-14 DPS

The significant point of the conclusion is listed as follows: M. J. Tahir https://orcid.org/0000-0002-9594-6194


Delin Wang https://orcid.org/0000-0003-0387-5251
∙ WT integration suggested in case-2 results in a 65.80% Mannan Hassan https://orcid.org/0000-0001-8256-8449
power loss reduction, leading to a 60.88% enhancement of
the economic benefits of the DPS (see Table 5). REFERENCES
1. Kavitha, R.: Transient stability of IEEE-30 bus system using E-TAP Soft-
CONFLICT OF INTEREST ware. Int. J. Sci. Eng. Res. 3(12), (2012) (2012)
The authors declare no conflict of interest regarding this paper’s 2. Kumar, A., Dubey, S.B.: Enhancement of transient stability in transmis-
sion line using SVC facts controller. Int. J. Recent Technol. Eng. 2, 51–56
publication. (2013)
3. Tang, W., Hu, J., Chang, Y., Liu, F.: Modeling of DFIG-based wind tur-
ABBREVIATIONS bine for power system transient response analysis in rotor speed control
CCT Critical clearing time timescale. IEEE Trans. Power Syst. 33, 6795–6805 (2018)
DGs Distribution generators 4. Tajdinian, M., Seifi, A.R., Allahbakhshi, M.: Transient stability of power
grids comprising wind turbines: New formulation, implementation, and
DPS Distribution power system application in real-time assessment. IEEE Syst. J. 13, 894–905 (2019)
FPA Flower pollination algorithm 5. Duong, M.Q., Grimaccia, F., Leva, S., Musetta, M., Le, K.H.: Improving
GAMS General algebraic modelling system transient stability in a grid-connected squirrel-cage induction generator
GWO Gray wolf optimizer wind turbine system using a fuzzy logic controller. Energies 8, 6328–6349
IGBT Insulated-gate bipolar transistor (2015)
6. Reddy, S.S., Prathipati, K., Lho, Y.H.: Transient stability improvement of
LSF Loss sensitivity factor a system connected with wind energy generators. Int. J. Emerging Electr.
MINLP Mixed-integer non-linear programming Power Syst. 18, 1–15 (2017)
MPA Marine predator’s algorithm 7. Duong, M.Q., Leva, S., Mussetta, M., Le, K.H.: A comparative study on
MVAr Reactive power losses controllers for improving transient stability of DFIG wind turbines during
MW Active power losses large disturbances. Energies 11, 480 (2018)
8. Geng, H., Liu, L., Li, R.: Synchronization and reactive current support of
OGP Optimal generator placement PMSG-based wind farm during severe grid fault. IEEE Trans. Sustainable
OPSG Optimal placement synchronous generator Energy 9, 1596–1604 (2018)
P.L.I. Power loss index 9. Gaztañaga, H., Etxeberria-Otadui, I., Ocnasu, D., Bacha, S.: Real-time
P.U. Per unit analysis of the transient response Improvement of fixed-speed wind farms
PSO Particle swarm optimization using a reduced-scale STATCOM prototype. IEEE Trans. Power Syst. 22,
658–666 (2007)
PV Photovoltaic 10. Molinas, M., Suul, J.A., Undeland, T.: Low voltage ride-through of wind
RPM Revolutions per minute farms with cage generators: STATCOM versus SVC. IEEE Trans. Power
SSA Self-sorting analytical approach Electron. 23, 1104–1117 (2008)
STATCOM Static synchronous compensator 11. Molinas, M., Vazquez, S., Takaku, T., Carrasco, J.M., Shimada, R., Unde-
SVC Static var compensator land, T.: Improvement of transient stability margin in power systems with
integrated wind generation STATCOM: An experimental verification. In:
TM Taguchi technique 2005 International Conference on Future Power Systems. Amsterdam, pp.
WT Wind turbine 1–6 (2005)
12. Medina-Domínguez, E.J., Medina-Padrón, J.F.: Critical clearing time and
wind power in small isolated power systems considering inertia emulation.
ORCID
Energies 8, 12669–12684 (2015)
Muhammad Shahid Mastoi https://orcid.org/0000-0003-4752- 13. Zheng, D., Ouyang, J., Xiong, X., Xiao, C., Li, M.: A system transient sta-
949X bility enhancement control method using doubly-fed induction generator
wind turbine considering its power constraints. Energies 11, 945 (2018)
MASTOI ET AL. 273

14. Edrah, M., Lo, K.L., Anaya-Lara, O.: Impacts of high penetration of DFIG 33. Moradi, M.H., Abedini, M.: A novel method for optimal DG unit’s capacity
wind turbines on rotor angle stability of power systems. IEEE Trans. Sus- and location in Microgrids. Int. J. Electr. Power Energy Syst. 75, 236–244
tainable Energy 6, 759–766 (2015) (2016)
15. Hashim, N., Hamzah, N., Abdul Latip, M.F., Sallehhudin, A.A.: Transient 34. Samala, R.K., Kotapuri, M.R.: Optimal allocation of distributed genera-
stability analysis of the IEEE 14-bus test system using dynamic computa- tions using a hybrid technique with fuzzy logic controller radial distribution
tion for power systems (DCPS). In: Proceedings of 3rd International Con- system. SN Appl. Sci. 2(2), 1–14 (2020)
ference on Intelligent System Modelling and Simulation, ISMS 2012. Kota 35. Selim, A., Kamel, S., Jurado, F.: Efficient optimization technique for multi-
Kinabalu, Malaysia, pp. 481–486 (2012) ple DG allocation in distribution networks. Appl. Soft Comput. 86, 105938
16. Bose, A., Concordia, C., Dunlop, R.D., Fouad, A.A., Kundur, P., Schulz, (2020)
R.P., Anderson, P.M., Robb, D.D., Lamont, J.W.: Proposed terms and defi- 36. Shaheen, A.M., El-Sehiemy, R.A.: Optimal coordinated allocation of dis-
nitions for power system stability. IEEE Power Eng. Rev. PER-2, 28 (1982) tributed generation units/capacitor banks/voltage regulators by EGWA.
17. Nasri, A., Ghandhari, M., Eriksson, R.: Transient stability assessment of IEEE Syst. J. 15(1), 257–264 (2020)
power systems in the presence of shunt compensators using trajectory 37. Kumar, Y.A., Prema Kumar, N.: Optimal allocation of distribution genera-
sensitivity analysis. In: IEEE Power and Energy Society General Meeting. tion units in radial distribution systems using nature-inspired optimization
Vancouver, BC, Canada (2013) techniques. In: 2018 International Conference on Power, Energy, Control
18. Maria, G.A., Tang, C.T., Kim, J.: Hybrid transient stability analysis. IEEE and Transmission Systems (ICPECTS). Chennai, India, pp. 1–6 (2018)
Trans. Power Syst. 5, 384–393 (1990) 38. Meena, N.K., Swarnkar, A., Gupta, N., Niazi, K.R.: Multi-objective
19. Jamian, J.J.: Comparative study on distributed generator sizing using three Taguchi approach for optimal DG integration in distribution systems. IET
types of particle swarm optimization. In: 2012 Third International Con- Gener. Transm. Distrib. 11(9), 2418–2428 (2017)
ference on Intelligent Systems Modelling and Simulation. Kota Kinabalu, 39. Meena, N.K., Swarnkar, A., Yang, J., Gupta, N., Niazi, K.R.: Modified
Malaysia (2012) taguchi-based approach for optimal distributed generation mix in distri-
20. Ambika, R., Rajeswari, R.: Optimal siting and sizing of multiple DG units bution networks. IEEE Access 7, 135689–135702 (2019)
for the enhancement of voltage profile and loss minimization in trans- 40. Abdel-mawgoud, H., Kamel, S., Ebeed, M., Youssef, A.-.R.: Optimal allo-
mission systems using nature-inspired algorithms. Sci. World J. 2016, 1–16 cation of renewable dg sources in distribution networks considering load
(2016) growth. In: 2017 Nineteenth International Middle East Power Systems
21. Kotb, M.F., Shebl, K.M., El Khazendar, M., El Husseiny, A.: Genetic algo- Conference (MEPCON). Cairo, Egypt, pp. 1236–1241 (2017)
rithm for optimum siting and sizing of distributed generation. In: Proceed- 41. Abdel-mawgoud, H., Kamel, S., Ebeed, M., Aly, M.M.: An efficient hybrid
ings of the 14th International Middle East Power Systems Conference. approach for optimal allocation of DG in radial distribution networks. In:
Cairo, Egypt, pp. 433–440 (2010) 2018 International Conference on Innovative Trends in Computer Engi-
22. Moradi, M.H. & Abedinie, M.: A combination of genetic algorithm and neering (ITCE). Aswan, Egypt, pp. 311–316 (2018)
particle swarm optimization for optimal DG location and sizing in distri- 42. Ebeed, M., Alhejji, A., Kamel, S., Jurado, F.: Solving the optimal reactive
bution systems. Int. J. Electr. Power Energy Syst. 34(1), 66–74 (2011) power dispatch using marine predator’s algorithm considering the uncer-
23. Parizad, A., Khazali, A., Kalantar, M.: Optimal placement of distributed tainties in load and wind-solar generation systems. Energies 13(17), 4316
generation with sensitivity factors considering voltage stability and losses (2020)
indices. In: 2010 18th Iranian Conference on Electrical Engineering. Isfa- 43. Fetouh, T., Elsayed, A.M.: Optimal control and operation of fully auto-
han, Iran (2010) mated distribution networks using improved tunicate swarm intelligent
24. Safigianni, A.S., Koutroumpezis, G.N., Poulios, V.C.: Mixed distributed algorithm. IEEE Access 8, 129689–129708 (2020)
generation technologies in a medium voltage network. Electr. Power Syst. 44. Shaheen, A.M., El-Sehiemy, R.A.: A multi-objective salp optimization
Res. 96, 75–80 (2013) algorithm for techno-economic-based performance enhancement of dis-
25. Abu-Mouti, F.S., El-Hawary, M.E.: Optimal distributed generation alloca- tribution networks. IEEE Syst. J. 15(1), 1458–1466 (2020)
tion and sizing in distribution systems via artificial bee colony algorithm. 45. El-Ela, A.A.: Optimal allocation of distributed generation units correlated
IEEE Trans. Power Delivery 26(4), 2090–2101 (2011) with fault current limiter sites in distribution systems. IEEE Syst. J. 15(2),
26. Sambaiah, K.S.A.: Review on optimal allocation and sizing techniques for 2148–2155 (2021)
DG in distribution systems. Int. J. Renewable Energy Res. 8(3), 1236–1256 46. Kayal, P., Chanda, S., Chanda, C.K.: An analytical approach for allocation
(2018) and sizing of distributed generations in the radial distribution network. Int.
27. Souza, D., Albuquerque, J.: Optimal placement of distributed genera- Trans. Electr. Energy Syst. 27(7), e2322 (2017)
tors networks using evolutionary programming. In: Transmission & Dis- 47. Gil-González, W., Montoya, O.D., Grisales-Noreña, L.F., Perea-Moreno,
tribution Conference & Exposition: Latin America. Caracas, Venezuela A.-J., Hernandez-Escobedo, Q.: Optimal placement and sizing of wind
(2007) generators in AC grids considering reactive power capability and wind
28. Sheidaei, F., Shadkam, M., Zarei, M.: Optimal distributed generation alloca- speed curves. Sustainability 12(7), 2983 (2020)
tion in distribution systems employing ant colony to reduce losses. In: 2008 48. Gil-González, W., Montoya, O.D., Escobar-Mejía, A., Hernández, J.C.:
43rd International Universities Power Engineering Conference. Padova, LQR-based adaptive virtual inertia for grid integration of wind energy con-
Italy, pp. 1–5 (2008) version system based on synchronverter model. Electronics 10(9), 1022
29. Maciel, R.S., Padilha-Feltrin, A.: Distributed generation impact evaluation (2021)
using a multi-objective tabu search. In: International Conference on Intel- 49. Arya, L.D., Koshti, A., Choube, S.C.: Distributed generation planning
ligent Systems Applications to Power Systems. Curitiba, Brazil, pp. 1–5 using differential evolution accounting voltage stability consideration. Int.
(2009) J. Electr. Power Energy Syst. 42(1), 196–207 (2012)
30. Pereira Junior, B.R., Cossi, A.M., Contreras, J., et al.: Multi-objective multi- 50. Huy, P.D., Ramachandaramurthy, V.K., Yong, J.Y., Tan, K.M., Ekanayake,
stage distribution system planning using tabu search. IET Gener. Transm. J.B.: Optimal placement, sizing and power factor of distributed generation:
Distrib. 8(1), 35–45 (2014) A comprehensive study spanning from the planning stage to the operation
31. Gholami, M., Zakariazadeh, A.: Olympic ranking–based allocation of stage. Energy 195, 117011 (2020)
distributed generation units in distribution networks. Int. Trans. Electr. 51. El-Ela, A., Allam, A., Allam, S.M., Shatla, M.M.: Maximal optimal benefits
Energy Syst. 30(2), e12220 (2020) of distributed generation using genetic algorithms. Electr. Power Syst. Res.
32. Kadir, A., Fazliana, A., Khatib, T., Lii, L.S., Hassan, E.E.: Optimal place- 80(7), 869–877 (2010)
ment and sizing of photovoltaic based distributed generation considering 52. Yang, N.-C., Chen, T.-H.: Evaluation of the maximum allowable capacity
costs of operation planning of monocrystalline and thin-film technologies. of distributed generations connected to a distribution grid by dual genetic
J. Sol. Energy Eng. 141(1), 1–8 (2019) algorithm. Energy Build. 43(11), 3044–3052 (2011)
274 MASTOI ET AL.

53. Ganguly, S., Samajpati, D.: Distributed generation allocation with on-load Power, Electronics and Computing (ROPEC). Ixtapa, Mexico, pp. 1–6
tap changer on radial distribution networks using adaptive genetic algo- (2017)
rithm. Appl. Soft Comput. 59, 45–67 (2017) 63. Carrasco, M., Mancilla-David, F.: Maximum power point tracking algo-
54. Mahmoud Pesaran, H.A., Nazari-Heris, M., Mohammadi-Ivatloo, B., rithms for single-stage photovoltaic power plants under time-varying reac-
Seyedi, H.: A hybrid genetic particle swarm optimization for distributed tive power injection. Sol. Energy 132, 321–331 (2016)
generation allocation in power distribution networks. Energy 209, 118218 64. Tahir, M.J., Bakar, B.A., Alam, M., Su’ud, M.M.: An LSF based DG place-
(2020) ment approach for power losses minimization of the radial distribution
55. Soroudi, A.: Power System Optimization Modeling in GAMS. Springer network. In: 2019 13th International Conference on Mathematics, Actu-
International Publishing, Berlin/Heidelberg (2017) arial Science, Computer Science, and Statistics (MACS). Karachi, Pakistan,
56. Zeynali, S., Rostami, N., Feyzi, M.R.: Multi-objective optimal short-term pp. 1–6 (2019)
planning of renewable distributed generations and capacitor banks in 65. Reddy, P.D.P., Reddy, V., Manohar, T.G.: Optimal renewable resources
power system considering different uncertainties including plug-in electric placement in distribution networks by combined power loss index and
vehicles. Int. J. Electr. Power Energy Syst. 119, 105885 (2020) whale optimization algorithms. J. Electr. Syst. Inf. Technol. 5, 175–191
57. Naval, N., Sánchez, R., Yusta, J.M.: A virtual power plant optimal dispatch (2018)
model with large and small-scale distributed renewable generation. Renew- 66. Tamilselvan, V., Jayabarathi, T., Raghunathan, T., Yang, X.S.: Optimal
able Energy 151, 57–69 (2020) capacitor placement in radial distribution systems using flower pollination
58. Mena, R., Hennebel, M., Li, Y.-F., Zio, E.: Self-adaptable hierarchical clus- algorithm. Alexandria Eng. J. 57, 2775–2786 (2018)
tering analysis and differential evolution for optimal integration of renew- 67. Elsheikh, A., Helmy, Y., Abouelseoud, Y., Elsherif, A.: Optimal capacitor
able distributed generation. Appl. Energy 133, 388–402 (2014) placement and sizing in radial electric power systems. Alexandria Eng. J.
59. Quezada, C., Torres, J., Quizhpi, F.: Optimal location of capacitor banks by 53, 809–816 (2014)
implementing heuristic methods in distribution networks. In: 2019 IEEE 68. Mahapatra, S., Singh, M.: Analysis of symmetrical fault in IEEE 14 bus
CHILEAN Conference on Electrical, Electronics Engineering, Informa- system for enhancing over current protection scheme. Int. J. Future Gener.
tion and Communication Technologies (CHILECON). Valparaiso, Chile, Commun. Networking 9(4), 51–62 (2016)
pp. 1–6 (2019)
60. Adewuyi, O.B., Shigenobu, R., Ooya, K., Senjyu, T., Howlader, A.M.: Static
voltage stability improvement with battery energy storage considering opti-
mal control of active and reactive power injection. Electr. Power Syst. Res. How to cite this article: Mastoi, M.S., Tahir, M.J.,
172, 303–312 (2019) Usman, M., Wang, D., Zhuang, S., Hassan, M.: Research
61. Montoya, O.D., Gil-González, W.: Dynamic active and reactive power on power system transient stability with wind generation
compensation in distribution networks with batteries: A Day-ahead eco- integration under fault condition to achieve economic
nomic dispatch approach. Comput. Electr. Eng. 85, 106710 (2020)
62. Arellanes, A., Rodríguez, E., Orosco, R., Perez, J., Beristáin, J.: Three-
benefits. IET Power Electron. 15, 263–274 (2022).
phase grid-tied photovoltaic inverter with reactive power compen- https://doi.org/10.1049/pel2.12228
sation capability. In: 2017 IEEE International Autumn Meeting on

You might also like