Danfos RT 101 017A1764
Danfos RT 101 017A1764
Features • Waterproof versions, enclosure IP66 • Suitable for alternating and direct current
• Wide regulating range • Interchangeable contact system
• Wide range of units for industrial • Special versions for PLC applications
and marine applications • Safety Integrity Level:
SIL 2 according to IEC 61508
Approvals
RT 140L
RT 140
RT 270
RT 102
RT 107
RT 101
RT 16L
RT 14L
RT 34
RT 23
RT 24
RT 8L
RT 14
RT 15
RT 13
RT 12
RT 17
RT 11
RT 2
RT 3
RT 4
RT 7
RT 8
RT 9
• Lloyd’s Reg. of Shipping, LR
• • • • • • • • • • • • Germanischer Lloyd, GL
• Bureau Veritas, BV
Overview
[°C] Range
-50 0 50 100 150 200 250 300
Type
[°C]
-45 – -15 RT 9
Vapour-charged with remote bulb (bulb coldest)
-30 – 0 RT 13
-25 – 15 RT 3
-25 – 15 RT 2, RT 7
-20 – 12 RT 8
-5 – 10 RT 12
-5 – 30 RT 14
Ordering Thermostats
Differential ∆t Max.
Capillary
Regulation At min. At max. bulb
Bulb tube
Charge Type range range range Reset temp. Code no.
type length
setting setting
[°C] [K] [K] [°C] [m]
RT 9 A -45 – 15 2.2 – 10.0 1.0 – 4.5 auto 150 2 017-506666
RT 3 A -25 – 15 2.8 – 10.0 1.0 – 4.0 auto 150 2 017-501466
RT 17 B -50 – -15 2.2 – 7.0 1.5 – 5.0 auto 100 – 017-511766
Vapour 1)
RT 11 B -30 – 0 1.5 – 6.0 1.0 – 3.0 auto 66 – 017-508366
017-503666
RT 4 B -5 – 30 1.5 – 7.0 1.2 – 4.0 auto 75 –
017-503766 4)
RT 13 A -30 – 0 1.5 – 6.0 1.0 – 3.0 auto 150 2 017-509766
RT 2 A -25 – 15 5.0 – 18.0 6.0 – 20.0 auto 150 2 017-500866
RT 8 A -20 – 12 1.5 – 7.0 1.5 – 7.0 auto 145 2 017-506366
RT 12 A -5 – 10 1.0 – 3.5 1.0 – 3.0 auto 65 2 017-508966
RT 23 A 5 – 22 1.1 – 3.5 1.0 – 3.0 auto 85 2 017-527866
RT 15 A 8 – 32 1.6 – 8.0 1.6 – 8.0 auto 150 2 017-511566
Adsorption 2) RT 24 A 15 – 34 1.4 – 4.0 1.4 – 3.5 auto 105 2 017-528566
RT 140 C 15 – 45 1.8 – 8.0 2.5 – 11.0 auto 240 2 017-523666
RT 102 D 25 – 90 2.4 – 10.0 3.5 – 20.0 auto 300 2 017-514766
RT 34 B -25 – 15 2.0 – 10.0 2.0 – 12.0 auto 100 – 017-511866
RT 7 A -25 – 15 2.0 – 10.0 2.5 – 14.0 auto 150 2 017-505366
RT 14 A -5 – 30 2.0 – 8.0 2.0 – 10.0 auto 150 2 017-509966
RT 101 A 25 – 90 2.4 – 10.0 3.5 – 20.0 auto 300 2 017-500366
Partial 3) RT 107 A 70 – 150 6.0 – 25.0 1.8 – 8.0 auto 215 2 017-513566
1
) The sensor must be located colder than thermostat housing and capillary tube.
2
) The sensor can be located warmer or colder than thermostat housing.
3
) The sensor must be located warmer than thermostat housing and capillary tube.
4
) With built-in heating coil − reduces the thermal differential.
Cylindrical remote sensor Room sensor Duct sensor Capillary tube sensor
Switches
Version Symbol Description Contact rating Reset Code no.
SPDT Inductive:
AC 3 = 4 A, 400 V
AC 15 = 3 A, 400 V
For manual reset of unit after
Man. contact changeover on falling
Dir. current: Min. 017-404166
reset temperature.
DC 13 = 12 W, 220 V
For units with reset facility.
SPDT
Available only
Single-pole changeover as a component
Neutral switch with dead zone part of RT
–
zone and terminal board proof controls with
against leakage current. adjustable
neutral zone
SPDT
Ordering Switches
(continued)
Version Symbol Description Contact rating Reset Code no.
Alternating current
With
non-snap Single-pole changeover switch Alternating
action with non-snap action changeover or direct current – 017-018166
change- over contacts. 25 VA, 24 V
contacts
SPDT
) If current is led through contacts 2 – 4, i.e. terminals 2 – 4 connected but not 1, max. permissible load is increased
1
to 90 W, 220 V.
The switches are shown in the position they An exception is RT with switch, code no.
assume on falling temperature, i.e. after 017-404266, with max. reset where the setting
downward movement of the RT main spindle. pointer shows the scale value at which contact
The setting pointer of the control shows the scale changeover occurs on rising temperature.
value at which contact changeover occurs on
falling temperature.
5
5. Setting knob 5 25
9. Regulation range scale 9
17-156.14
10. Loop terminal 10
Danfoss
44
11. Pg 13.5 screwed cable 44 11
entry 12 12 14
12. Main spring
14. Terminals 4 17
17 1 15
15. Main spindle 2 16
26 29
16. Switch 15 16 18
17. Upper guide bush
18. Contact arm 19
19 18
19. Differential temperature 23 38 25
setting nut 23
23. Bellows element 28
25. Fixing hole 28
26. Sensor (bulb) clip 31
28. Capillary tube
29
29. Sensor (bulb)
30. Sensor (bulb) pocket 30
17-372.11
31. Capillary tube gland
Danfoss
38. Earth terminal
44. Temperature setting
spindle
The thermostatic element consists of a sensor A rise in temperature at the sensor compresses
(29) capillary tube (28) and bellows element (23). the bellows and moves the main spindle (15)
The element contains a charge that reacts to upwards until spring force and element pressure
temperature variations at the sensor so that the are in equilibrium.
pressure on the moving bellows rises when The main spindle (15) is fitted with a guide bush
temperature rises. (17) and a differential setting nut (19) that
By turning the setting knob (5) the main spring together transfer the main spindle movement
(12) can be set to balance the pressure to the switch (16).
in the element.
Design / Function Key sketch RT L thermostat with neutral zone RT L thermostat with neutral zone
(continued)
44
12
15 5
18a
17-428.19
Danfoss
17 4
16
9
1
20 2
5. Setting knob 18a
9. Regulation range scale 40 25
12. Main spring 16
15. Main spindle 23
44
16. Switch
18b
17. Upper guide bush 28 18b
18a and 18b. Contact arm 17
29 25
20. Lower guide bush
23. Bellows element 20
40
25. Fixing hole
17-331.15
28. Capillary tube Danfoss
29. Sensor (bulb)
40. Neutral zone setting nut
44. Temperature setting
spindle
RT L thermostats are fitted with a switch with an The upper guide bush (17) is fixed while the
adjustable neutral zone. This enables the units to lower guide bush (20) can be moved up or down
be used for floating control. by the setting nut (40). In this way the neutral
The neutral zone switch contact arms (18a) and zone can be varied between a minimum value
(18b) are operated by the spindle guide bushes (equal to the mechanical differential of the unit)
(17) and (20). and a maximum value (depending on the type of
RT unit).
temperature
17-429.13
Neutral zone 4 4 4 4 4 Danfoss
1 1 1 1 1
2 2 2 2 2
Differential
Mechanical
differential
NZ ~NZ minimum
Differential
17-301.12
be able to take place from the free liquid surface
Danfoss
Pressure
in the bulb (within the operation range of the
thermostat), and where at the same time, the
bellows must be protected against deformation
when kept at normal ambient temperatures.
Since the pressure in the element depends on
the temperature at the free liquid surface, the
thermostat must always be placed so that the
Temperature
[t] bulb is colder than the rest of the thermostatic
t0 t1 t2 t3 element.
The evaporated liquid will recondense at the
Here the interdependence between the pressure coldest point, i.e. the bulb. Thus, as intended, the
and temperature of saturated vapour is utilized, bulb becomes the temperature-controlling
i.e. the element is charged with saturated vapour element in the system.
plus a small amount of liquid.
The charge is pressure-limited; a further increase Note:
in pressure after evaporation of all the liquid in When the bulb is coldest, the ambient
the bulb, will only result in a small pressure temperature has no effect on regulating
increase in the element. accuracy.
[z]
[p]
17-676.16
Danfoss
17-303.12
Pressure 4
Danfoss
3 o C
70
2 o C
50
1
Temperature 30 C
o
Relative
[t] 20oC scale
t1 tv t2 0
50% 100% setting
10 oC (%)
-1
-10
In this case the charge consists partly of a -2 o
C
superheated gas and partly of a solid having a
-30
large adsorption surface. -3 o
C
The solid is concentrated in the bulb and it is
therefore always the bulb that is the -4
temperature-controlling part of the thermostatic
element.
Curves for different ambient temperatures.
The bulb can thus be placed warmer or colder 0% ~ lowest scale setting temperature,
100% ~ highest scale setting temperature.
than the rest of the thermostatic element.
Such a charge is however to some extent
sensitive to changes in the temperature of the
bellows element and capillary tube. Correction
Type Range [°C]
Under normal conditions this is not important, factor “a”
but if the thermostat is used in extreme RT 2 -25 – 15 2.3
conditions, scale deviation will occur. RT 7 -25 – 15 2.9
The scale can be corrected by using the graph RT 8, RT 8L -20 – 12 1.7
and the table. RT 12 -5 – 10 1.2
Scale correction = Z × a. RT 14, RT 14L -5 – 30 2.4
Z can be found in the graph and "a" in the table. RT 15 8 – 32 1.2
RT 23 5 – 22 0.6
RT 24 15 – 34 0.8
RT 101, RT 102 25 – 90 5.0
RT 140, RT 140L 15 – 45 3.1
Charges Example The correction factor “a” can be found in the table
(continued) Scale correction on an RT 14 (range -5 – 30 °C) for an RT 14, i.e. 2.4.
at activating temperature 12 °C and ambient The scale correction = Z×a=-1.2×2.4=-2.88.
temperature -10 °C. If activation at 12 °C for the same conditions is
The scale temperature, 12 °C, lies approximately required, the thermostat must be set at
in the middle of the scale range, i.e. relative scale 12×2.88=9.12≈9.1.
setting of 50%.
The factor Z can be found in the graph from 50%
and the curve for -10 °C, i.e. approx. -1.2.
3. Partial charge
The partial charge is of such a volume that the
bellows housing, capillary tube and a small part
[p]
of the bulb are filled when the thermostat is in
Pressure operation. The bulb is thus the warmest part of
17-302.12
Danfoss
the system.
The liquid will condense in the remaining,
coldest, part of the system but because of the
volume of the charge the free liquid surface will
always be in the bulb. In this way, the bulb
becomes the temperature-controlling part of the
Temperature system.
[t]
t1 t2 t3
17-378.12
Danfoss
2
1. LT sensor (bulb) 4
2. Capillary tube 5
4. LT bellows element 1
9
5. Setting disc 25
10
9. Regulation range scale 11
10. Loop terminal 12
11. Pg 13.5 screwed cable 14
entry 15
12. Main spring 16
14. Terminals 17
15. Main spindle 32 18
16. Switch 20
25
17. Upper guide bush
38
18. Contact arm 39
20. Lower guide bush 24
24. HT bellows element 28
25. Fixing hole
28. Capillary tube
32. HT sensor (bulb)
38. Earth terminal
39. Blow-out disc
An RT differential thermostat contains a single- Within the operating range the RT 270 can be
pole changeover switch that makes or breaks set for different temperature differentials by the
depending on the temperature difference setting disc (5).
between the two sensors of the unit. When the differential between LT and HT sensor
The RT 270 017D003166 is for use in process temperature falls, the main spindle (15) moves
plant, ventilation plant, and refrigeration and downwards.
heating plant where there is need to maintain The contact arm (18) is moved downwards by
a certain temperature differential, 0 – 15 °C, the guide (17) so that contacts (1-4) break and
between two media. One sensor is used as a contacts (1-2) make when the set temperature
reference and the other as a control sensor. The differential is reached.
temperature differential is the direct controlled The contacts changeover again when the
variable. temperature differential rises to the set value plus
the fixed contact differential of approx. 2 °C.
Setting of differential The knob can be used to make a setting on the The differential roller 19 must then be used
range scale for the lowest temperature at which to set the differential. The highest activating
the contact system must be activated temperature at the sensor is equal to the
(cut-out or cut-in). activating temperature + the set differential.
Nomograms for RT 2 RT 3 RT 4
obtained differentials
[°C] [°C] [°C] [°C]
17-790.13
17-435.14
Danfoss
Danfoss
17-436.17
15 5 [°C] [°C] -5 1
Danfoss
6 1.2
1
-25 1
2 1
10 7
3 2
0 2
8 -20 2
5
1
9
5 4
3 5
32
10 -15 3
5 4
0
54
11 4
7 6
-10 10
12
76
-5 5 4
13
7 6
9 8
-5 15
98
-10 14 6
10
15 5
10
0 20
C
8
-15 16 7 C
17 5
10 9
8 25 6
-20 18
C 19 10 9
-25 20 30 7
A B 15 10 A B
A B
RT 7 RT 9 RT 10
17-780.13
17-781.13
Danfoss
Danfoss
Danfoss
15 2 -45 1 -60 1
2 1
1
10 2 -55
3 2
4 2
3 2
4 3
5 5 3
5 4
-50
6 -35 54 4 3
6 5
76
76
7 5 -45
9 8
-5 8 4
9 8
8 7
9 6 -40
10
-10
10
10 -25 C 7 C 5
10 9
-35
-15 11 8
C 12 6
-20 -30
9
13
-25 14 -15 10 -25 7
A B A B A B
RT 11, RT 13 RT 12 RT 24
17-779.13
17-240.19
17-792.13
Danfoss
-30 1 -5 1 1
Danfoss
15
1
Danfoss
-4
1
-3 1,4
3 2
-25 1,5
-2 1,5
3
2
4 3 2
-1 20
5 4
-20 0 2
5
7 6
3 1 2
2
7 6 5
6
-15 25 2,5
9 8
3
7
4 4 2,5
10
-10 5 3
C
10 9 8
6 30
10 9
5 7 3
-5 3,5
8
C
9 C
A = Range setting 0 6 10 3,5 35 4
A B A B A B
B = Obtained differential
C = Differential setting
Nomograms for RT 14 RT 17 RT 23
obtained differentials
(continued) [°C] [°C] [°C] [°C] [°C] [°C]
17-471.18
17-794.13
17-793.13
30 2 -50 1.5 5 1
2 1
Danfoss
Danfoss
Danfoss
2 1
2
2 1
25 3
3
1,5
3
4 3
4 3
5 4
20 -40 10
5 4
5
6 5
2
15 4
7 6
6
8 7
7
10 -30 15 2,5
7 5
10 9 8
10 9
5
10 9
8
C 6 3
0 C 9 -20 20
C
-5 10 -15 7 22 3,5
A B A B A B
RT 34 RT 101 RT 107
17-452.18
17-796.12
15 2 90 2
Danfoss
1,8
1
70
Danfoss
Danfoss
1
2
10 4
80
3 2
80
4 5
3
1
5 6
32
90
5 4
4
70 8
54
0
5
6 100 10
7 6
10
6
60
7 6
87
-5 110
9 8
12
10 9
-10 8 50 15
10
120
8
14 C
C
-15
10 9
40 16 130
10 20
-20 18 140
C 30
-25 12 25 20 150 25
A B A B A B
RT 140
[°C] [°C]
17-319.18
45 1
Danfoss
2
2 1
40
3
4 3
4
35
5
6 5
30 6
8 7
7
25
8
10 9
9
20
C
10
A = Range setting 15 11
B = Obtained differential A B
C = Differential setting
Dimensions [mm]
RT thermostat housing
and weights [kg]