T8602A,B,C,D and TS8602A,C ®

Chronotherm III Fuel Saver Thermostats


INSTALLATION INSTRUCTIONS

APPLICATION RECYCLING NOTICE


These thermostats provide energy saving control for If this control is replacing a control that contains
24 Vac conventional heating/cooling system or 750 mV mercury in a sealed tube, do not place your old
heating and 24 Vac cooling as indicated in Table 1. control in the trash. Contact your local waste
management authority for instructions regarding
Power is supplied for the device by three AA alkaline recycling and the proper disposal of your old
batteries (included). This allows the thermostat to be com- control.
patible with all control applications.
If you have any questions, call Honeywell Inc.
Cycle rates are adjustable for heating. at 1-800-468-1502.
The TS8602 current rating in heating is 0.1A at 750 mV.
The current rating on all other models is 1.6A maximum, INSTALLATION
up to 30 Vac.
When Installing This Product…
Adaptive Intelligent Recovery™/Conventional Recovery 1 Read these instructions carefully. Failure to follow
selection screw is included on the back of the thermostat. them could damage the product or cause a hazard-
ous condition.
Fan operation switch is included on the back of some 2 Check the ratings given on the product to make sure
T8602C models to select either independent or direct the product is suitable for your application.
thermostat control of the fan in heating. 3 Installer must be a trained, experienced service
technician.
12/24 hour clock conversion and °C/°F conversion are 4 After installation is complete, check out product
available on some models only. operation as provided in these instructions.
5 Allow thermostat to warm to room temperature
before operating.

Table 1. Thermostat Models.


Stages Switching
Thermostat Heat Cool System Fan Application
T8602A 1 — — — Gas, oil or electric with independently
controlled fan.
T8602B 1 — — ON-AUTO
T8602B 1 — HEAT-OFF —
T8602C 1 1 HEAT-OFF-COOL ON-AUTO
T8602D 1 1 HEAT-OFF-COOL-AUTO ON-AUTO
T8602C 1 1 HEAT-OFF-COOL ON-AUTO Fan operation in heating selectable for
thermostat or independent control; with O
and B terminals for changeover control.
TS8602A 1 — — — Millivolt heating system.
a
TS8602C 1 1 HEAT-OFF-COOL ON-AUTO Millivolt heating and 24 Vac cooling
system.
a
Available only in Canada.

®U.S. Registered Trademark


Copyright © 1995 Honeywell Inc. • • All Rights Reserved X-XX UL 69-0309-9
T8602A,B,C,D AND TS8602A,C Chronotherm ® III FUEL SAVER THERMOSTATS

WALL
CAUTION ANCHORS
(2)
WALL
Disconnect power supply to prevent electrical
shock or equipment damage. WIRES THROUGH
WALL OPENING

Location
Install thermostat and wallplate about 5 ft (1.5m) above the
floor in an area with good air circulation at room
temperature.

Do not install the thermostat where it can be affected by:


— drafts or dead spots behind doors, in corners, or
under cabinets.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
MOUNTING
— concealed pipes and chimneys. HOLES (3)
1
— unheated (uncooled) areas such as an outside wall,
behind the thermostat.
WALLPLATE MOUNTING
SCREWS (2)
If Replacing An Existing Thermostat 1 USE TWO MOUNTING HOLES THAT
Turn off power to the thermostat at the furnace or boiler. A BEST FIT APPLICATION. M2917

two-transformer system can require turning off two


switches or disconnects. Remove any existing wallplate or Fig. 2. Mounting wallplate on wall.
subbase from the wall. Write down the letter or number on
each wiring terminal, as the wire is removed, to avoid
miswiring later.
Wiring
CAUTION
If New Installation The TS8602A,C can only be used on 750 mV
Run cable to the hole in the selected wall location, and pull heating applications. The TS8602A,C will not
about 3 in. (76 mm) of wire through the opening. Color- function properly on 250 mV, 500 mV or 24 Vac
coded, 18 gauge thermostat cable with at least one heating applications.
conductor for each wiring terminal is recommended.
All wiring must comply with local electrical codes and
Push excess wire back into the hole, and plug the hole ordinances.
with nonhardening caulk, putty or insulation to prevent
drafts from affecting the thermostat operation. Disconnect power before wiring to prevent electrical shock
or equipment damage.
Mounting Wallplate The shape of the terminal barrier permits insertion of
Remove thermostat from wallplate. See Fig. 1. straight or conventional wraparound wiring connections.
Either method is acceptable.
The wallplate does not require leveling for operation, but
for appearance only. The wallplate mounts directly onto Refer to Fig. 4 through 15 for typical wallplate and
the wall with the screws included. Using the wallplate as a thermostat hookups.
template, with a pencil, mark two (of three) mounting
screw positions on the wallplate that fit the application. See NOTE: • Keep all wiring restricted to the ribbed area
Fig. 2. Use a 3/16 in. bit to drill holes for the anchors. surrounding the terminals (Fig. 3) to assure
Gently tap anchors into the holes until flush with the wall thermostat/wallplate contact.
surface. Thread wires through the center opening of the • For single transformer applications, jumper
wallplate. Mount the wallplate using the two screws terminals R and RC for proper operation.
provided. Gently tighten the screws, level the top surface
of the wallplate, and then securely tighten the screws.

M2918

Fig. 1. Removing thermostat from wallplate.

69-0309—9 2
T8602A,B,C,D AND TS8602A,C Chronotherm ® III FUEL SAVER THERMOSTATS

FOR STRAIGHT HEATING-ONLY WALLPLATE


INSERTION – FOR WRAPAROUND –
STRIP 5/16 in. (8 mm) STRIP 7/16 in. (11 mm)

RESTRICT
WIRING TO W G R
THIS AREA

GAS FAN
VALVE RELAY
FRONT VIEW OF 1
TERMINAL AREA L2 2

L1
WIRING TO BE BELOW TOP SURFACE (HOT)
THIS SURFACE OF SUBBASE
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

2 MODELS WITH ON-AUTO FAN SWITCH. M2928

CROSS-SECTIONAL VIEW OF
TERMINAL AREA M2927 Fig. 6. T8602A,B heating-only circuit in a continuous
pilot gas system.
Fig. 3. Keep wiring restricted to the ribbed area
surrounding terminals.

HEATING-ONLY WALLPLATE

MILLIVOLT HEATING-ONLY
WALLPLATE
W R
PILOTSTAT
W R
CONTROL
(IF USED) 1
L1
TH (HOT) T T
L2
TH/ LIMIT OIL PRIMARY
PP CONTROL
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
PP MILLIVOLTAGE AND OVERLOAD PROTECTION AS REQUIRED.
GAS CONTROL M2929
MILLIVOLTAGE M2931
GENERATOR
Fig. 7. T8602A,B heating-only circuit in an oil system.
Fig. 4. TS8602 in typical millivoltage heating circuit.

HEATING ONLY WALLPLATE

MILLIVOLT HEATING-24Vac
COOLING WALLPLATE W R

PILOTSTAT G RC Y O BLACK
W R L1
CONTROL
(IF USED) (HOT)
RED

1
WHITE

TH L2

TH/ BLUE
PP

LIMIT CHANGEOVER
PP CONTROL RELAY
RED R841C
MILLIVOLTAGE SWITCH
GENERATOR MILLIVOLTAGE BIMETAL
RESISTANCE SWITCH HEATER
GAS CONTROL FAN COOLING HEATER
RELAY CONTACTOR
1
L1 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
(HOT) AND OVERLOAD PROTECTION AS REQUIRED.
M2923
L2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS


AND OVERLOAD PROTECTION AS REQUIRED.
M2942 Fig. 8. T8602A,B heating-only circuit in an electric
baseboard or ceiling cable system.
Fig. 5. TS8602C in typical millivoltage heating and
24 Vac cooling circuit.

3 69-0309—9
T8602A,B,C,D AND TS8602A,C Chronotherm ® III FUEL SAVER THERMOSTATS

S8610U
5 VENT
GND 24V DAMPER
MV MV/PV PV (BURNER) GND 24V TH-W PLUG SENSE SPARK

AIR 6 3
PROVING W R
MV MV/PV MV SWITCH THERMOSTAT

VR8345
2

DUAL VALVE COMBINATION


GAS CONTROL COMBUSTION
AIR BLOWER
4
RELAY

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS


SENSOR
AND OVERLOAD PROTECTION AS REQUIRED.

2 ALTERNATE LIMIT CONTROLLER LOCATION. LIMIT


1
CONTROLLER
3 MAXIMUM CABLE LENGTH 3 FT (0.9M ). IGNITER L1 L2 COMBUSTION
(HOT) AIR BLOWER
4 CONTROLS IN 24V CIRCUIT MUST NOT BE MOTOR
GROUND LEG TO TRANSFORMER. PILOT
BURNER 1 L2 L1
5 GROUND (HOT)
LEAVE VENT DAMPER PLUG CONNECTED.
PILOT GAS
6 REMOVE JUMPER AND CONNECT SENSE CONTROLLER
SUPPLY
TERMINAL ON TWO ROD APPLICATION ONLY.

M8600

Fig. 9. T8602A,B heating-only circuit in a Honeywell Intermittent Pilot Gas Burner Ignition System.

ZONE 1 ZONE 2 ZONE 3 ZONE 4


HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE

W R W R W R W R

2 R8239A1052 R8222B1067 R8222B1067 R8222B1067

C W Y R G

L2

1
L1 3 3 3
(HOT) ZONE 2 ZONE 3 ZONE 4
VALVE OR VALVE OR VALVE OR
DAMPER DAMPER DAMPER
MOTOR MOTOR MOTOR

3 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS 2 USE ONE R8239 FOR EVERY FOUR ZONES.
ZONE 1 AND OVERLOAD PROTECTION AS REQUIRED.
VALVE OR 3 USE FOR 3-WIRE ZONE VALVE OR DAMPER.
DAMPER
M2921
MOTOR

Fig. 10. T8602A,B circuit for controlling incompatible or three-wire zone valves or dampers. Heating or cooling
equipment is operated by an end switch on the zone valve or motor, or by a thermostat in a master zone.

69-0309—9 4
T8602A,B,C,D AND TS8602A,C Chronotherm ® III FUEL SAVER THERMOSTATS

ZONE 1 ZONE 2 ZONE 3 ZONE 4


HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE HEATING ONLY WALLPLATE

W R W R W R W R

2 R8239A1052

C W Y R G ZONE 2 ZONE 3 ZONE 4


VALVE OR VALVE OR VALVE OR
DAMPER DAMPER DAMPER
L2 MOTOR
MOTOR MOTOR
1
L1
(HOT)

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS


ZONE 1 AND OVERLOAD PROTECTION AS REQUIRED.
VALVE OR
DAMPER 2 USE ONE R8239 FOR EVERY FOUR ZONES. M2922
MOTOR

Fig. 11. T8602A,B circuit for controlling Honeywell or compatible two-wire zone valves or dampers. Heating or
cooling equipment is operated by an end switch on the zone valve or motor, or by a thermostat in a master zone.

HEATING-COOLING WALLPLATE HEATING-COOLING WALLPLATE

3 3

W G R RC Y W G R Y
1
L1
(HOT) 2
HEATING
L2 HEATING PRIMARY FAN COOLING
PRIMARY FAN COOLING CONTROL RELAY CONTACTOR
1
CONTROL RELAY CONTACTOR
L1
1 2 (HOT)
L1 L2
(HOT)
L2 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED. 2 PRIMARY CONTROL, SUCH AS GAS VALVE OR ELECTRONIC
IGNITION MODULE. M2925
2 PRIMARY CONTROL, SUCH AS GAS VALVE OR ELECTRONIC
IGNITION MODULE.
Fig. 13. T8602C,D heating/cooling circuit in a single
3 CURRENT DRAW FOR W OR Y PLUS G MUST BE
LESS THAN 1.6A. M2924 transformer system with gas heat/electric cooling and
electric furnace/electric cool. Controls fan in cooling
only (typical multi-speed fan application).
Fig. 12. T8602C,D heating/cooling circuit in a
two-transformer (one for heating, one for
cooling) system with gas heat and electric cooling,
RC and R terminals.

5 69-0309—9
T8602A,B,C,D AND TS8602A,C Chronotherm ® III FUEL SAVER THERMOSTATS

HEATING-COOLING WALLPLATE
RECOVERY
SELECTION 3A
ADAPTIVE IN
INTELLIGENT ™ (FACTORY SETTING)

W G R Y CONVENTIONAL OUT 1/2 TO 1 TURN

RELAY

1 FAN AIR
L1 RELAY COND.
(HOT) T T EQUIP.
L2
1 OIL PRIMARY 2 3A 1A 1B
L1 1
2A 2B
(HOT)
L2

4A
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED. M2926

Fig. 14. T8602C,D heating/cooling circuit in an oil


heating and electric cooling system. Heating trans- TIME/TEMP
SYSTEM 1A 1B DISPLAY 2A 2B
former is in oil primary. GRAVITY OUT 1/2 OUT 1/2
AIR/WATER TO 1 TURN TO 1 TURN 24 HR IN

HOT IN OUT 1/2 OUT 1/2


WATER TO 1 TURN 12 HR TO 1 TURN
HEATING-COOLING WALLPLATE
GAS/OIL IN IN
(FACTORY SETTING) oC
WARM AIR IN
ELECTRIC OUT 1/2 IN o OUT 1/2
2 3 WARM AIR TO 1 TURN F TO 1 TURN

O W G R RC B Y
1 SCREWS 2A, 2B AVAILABLE ON SOME MODELS ONLY.

2 SWITCH 4A FOR FAN OPERATION SELECTION AVAILABLE ON


COOLING SOME MODELS ONLY. M2082C
COOLING FAN
DAMPER RELAY CONTACTOR

Fig. 16. Cycle rate adjustment.


HEATING HEATING
PRIMARY DAMPER
CONTROL

1
SETTING AND ADJUSTMENTS
L1
(HOT) L1
Adjusting Cycle Rate
(HOT)
L2 1
L2 NOTE: MOST APPLICATIONS WILL NOT REQUIRE A
CHANGE IN CYCLE RATE.
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
The room air temperature will vary slightly from the comfort
2 FOR SYSTEMS WHERE THERMOSTAT MUST CONTROL temperature setting with the cycling of the furnace or air
FAN DIRECTLY IN HEATING, SET FAN OPERATION SWITCH
TO ELEC POSITION. USE ONLY ONE TRANSFORMER, AND conditioner. The equipment cycles off and on as the room
JUMPER R AND RC. temperature approaches the setpoint.
3 FOR SINGLE TRANSFORMER SYSTEM, JUMPER R AND RC.
M319A The cycle rate of this thermostat is set for heating at six
cycles per hour and for cooling at three cycles per hour as
Fig. 15. T8602C heating/cooling circuit in a two- shipped from the factory. The cooling cycle rate cannot be
transformer system (gas heating and electric cooling). adjusted. On all models, except the TS8602, the heating
Includes O and B terminals for changeover control. cycle rate can be adjusted by turning one or both cycle
See Table 2 to set fan operation switch. rate adjustment screws located on the back of the ther-
mostat. See Fig. 16. The screws should only be backed
out about one-half to one turn, or be turned in until tight.

Adaptive Intelligent Recovery™/


Conventional Recovery
The thermostat is factory-set for Adaptive Intelligent
Recovery™, but may be converted to conventional
recovery using screw 3A on the back of the thermostat as
in-dicated in Fig. 16.

69-0309—9 6
T8602A,B,C,D AND TS8602A,C Chronotherm ® III FUEL SAVER THERMOSTATS

With Adaptive Intelligent Recovery™, the room will reach IMPORTANT


the comfort temperature at the exact time programmed The low battery warning will be displayed about
into the thermostat. The control temperature will increase two months before the batteries are dead. When
gradually, and turn the equipment on and off several times the batteries are dead, the system will shut down.
to reach the comfort temperature slowly and on time. After batteries are replaced, thermostat will
There will be no wasted of energy associated with rapid require reprogramming.
temperature changes and temperature overshoot.

With conventional recovery, the start time should be Mounting The Thermostat
programmed to be earlier than the desired comfort time. It Hang the thermostat on the tabs at the top of the base.
may require some trial and error to arrive at the best See Fig. 18A. Swing down and press on the lower edge
starting time. until the thermostat snaps into place. See Fig. 18B. Open
the cover, and tighten the captive mounting screws. See
Fig. 18C.
Setting Time/Temperature (Some Models)
The display readout may be converted between a 12 and
24 hour clock or °C and °F using screws 2A and 2B as Setting Day and Time
indicated in Fig. 16. Set the present day and time. When the thermostat is first
turned on, the display will read 1:00 PM and the room
temperature. It will go off for only a few seconds, then
Setting Fan Operation begin to flash on and off.
Some T8602C models include a fan operation switch on SET
the back of the thermostat on the lower left corner. See Press PRESENT .
DAY/TIME
Fig. 15. See Table 2 to determine correct setting of fan
operation switch. BACK
Press TIME or to set the current
AHEAD
time.
CAUTION SET
The fan operation switch, which is available on Press PRESENT .
DAY/TIME
some T8602C models, is factory set to the NON
ELEC. position. If the system requires direct
Press to set the current day. Each press of the
thermostat control of the fan in heat mode, the DAY
switch must be set to the ELEC. position. See DAY key advances the display one day.
Table 2.
If the display will not come on:
Table 2. T8602C Fan Operation Switch Setting. • Check mounting of thermostat to wallplate. If loose or
misaligned, remove thermostat and reinstall on the
Fan Operation wallplate, making sure it is firmly attached.
Switch Setting • Check to see that all the batteries are good and
Fan Operation (4A) Comments installed correctly.
Fan controlled Set to ELEC. Use only one
directly by position. system
thermostat in heat transformer
mode (typically jumper R and
electric furnaces). RC.
Fan has Set to NON System may
independent ELEC. position have one or two
control in heat transformers;
mode (typically if one
gas, oil, millivolt transformer,
and some electric jumper R and
furnaces). RC.

BATTERY
Installing Batteries PLACEMENT
(NOTE CORRECT PLUS
Power is supplied for the thermostat by three AA alkaline M2083
AND MINUS DIRECTION)
batteries. Batteries are included with thermostat. Install
batteries in back of thermostat as shown in Fig. 17. The Fig. 17. Battery placement.
display will flash 1:00 PM and room temperature.

When the batteries are going dead, the display will flash
REPL BAT. If device has system switch, set to OFF.
Remove the thermostat from the wall and install three new
AA alkaline batteries. We recommend Energizer®
batteries. Change batteries within approximately 30
seconds from the time the batteries are removed to
prevent program loss and the necessity to reprogram.

7 69-0309—9
T8602A,B,C,D AND TS8602A,C Chronotherm ® III FUEL SAVER THERMOSTATS

A. B.
PM
MON
RETURN HEAT ON

C. MON
RETURN
PM
HEAT ON

TEMPERATURE

RUN PRESENT
PROGRAM SETTING
TIME
SET SKIP
PRESENT DAY LEAVE NEXT
DAY/TIME WAKE AHEAD WARMER
PERIOD

HOLD SET BACK COOLER CHANGE


TEMP HEAT/COOL SLEEP RETURN TO LAST
PERIOD

M2919

Fig. 18. Mounting thermostat on wallplate.

NOTE: On an AUTO changeover thermostat (T8602D),


CHECKOUT the heating temperature must be set at least 3°F
NOTE: On models without system or fan switch, (2°C) below the cooling temperature, or the
disregard instructions about moving the switch. display will flash.

Heating Fan
Move the system switch to HEAT and the fan switch to Move the system switch to OFF, and the fan switch to ON.
AUTO. Press WARMER key until the setting is about 10°F The fan should run continuously. When the fan switch is in
(6°C) above room temperature. Heating should start and the AUTO position, the fan cycles with the heating or
the fan should run (may be a short delay on forced air cooling system.
systems). Press COOLER key until the setting is about
10°F (6°C) below room temperature. The heating equip-
ment should shut off. Installer Self-Test (Optional)
Perform the following test as a check of all thermostat
functions. If thermostat does not respond as indicated,
Cooling replace the thermostat.
1 Press AHEAD and BACK keys at the same time.
While holding down the keys, all segments of the
CAUTION display should be on. See Fig. 19.
Do not operate cooling if outdoor temperature is 2 Set system switch to OFF, where applicable. Press
below 50°F (10°C). Refer to manufacturer recom- AHEAD and BACK and PRESENT SETTING keys
mendations. at the same time to enter self-test.
3 Press each key as listed below, and look for
NOTE: When cooling setting is changed, thermostat will responses listed as key is held down and released.
wait up to five minutes before turning on the air
conditioner. This delay protects the compressor.
REPL
AM SET
Move the system switch to COOL and the fan switch to PM BAT PT
AUTO. Press COOLER key until the setting is about 10°F SUN MON TUE WED THU FRI SAT COOL ON HEAT ON
(6°C) below room temperature. The cooling equipment WAKE LEAVE RETURN SLEEP TEMPORARY
and fan should start. Press the WARMER key until the
setting is about 10°F (6°C) above room temperature. The M410C
M410C

cooling equipment and fan should stop. Fig. 19. All segments on display.

69-0309—9 8
T8602A,B,C,D AND TS8602A,C Chronotherm ® III FUEL SAVER THERMOSTATS

System Press Look For This Response Cycle Rate Setting


Switch This First Digit (cph At 50% On Time)
Key
Position Key Down Key Released 0 or 1 1
OFF CHANGE 03 Blank 2 or 3 3
TO LAST
PERIOD
4 or 5 9
SKIP
NEXT
07 Blank 6 or 7 6
PERIOD

PRESENT 15 Blank
SETTING
Second Clock Recovery
15 Cooling, fan and Digit (Hr.) Degrees Setting
COOL or PRESENT
SETTING
AUTO SYSTEM LED on. 0 12 F Conventional
(with fan PRESENT 15 Cooling, fan and 1 12 C Conventional
in AUTO) SETTING
SYSTEM LED off. 2 12 F Adaptive Intelligent
OFF 06 Blank Recovery™
WARMER
3 12 C Adaptive Intelligent
Recovery™
COOLER 02 Blank
4 24 F Conventional
05 Blank 5 24 C Conventional
AHEAD
6 24 F Adaptive Intelligent
BACK 04 Blank Recovery™
7 24 C Adaptive Intelligent
Recovery™
LEAVE
01 Blank

RETURN
00 Blank H H

(Check 12 A
See note A
G G
Each WAKE

position)
M1612
M1612

OFF SLEEP
08 Blank

13 Microprocessor mask Third Thermostat System


Digit Type No. Switch Position
DAY no. and revision no.
0 C or D OFF or AUTO
SET 09 Blank
HEAT/COOL 1 B OFF

PRESENT 14 Blank 2 C or D COOL


SETTING
4 C or D HEAT
HEAT PRESENT 14 Heating and SYSTEM 5 A or B HEAT or no switch
SETTING
m1 LED on.
PRESENT 14 Heating and SYSTEM
SETTING
LED off. Fourth Thermostat System
Digit Model Switch Position
OFF HOLD 10 Blank
TEMP 0 TS8602A; Any position.
T8602A,B or C
RUN 11 Normal operating
PROGRAM 1 T8602D HEAT, OFF, or COOL
display
3 T8602D AUTO
End Self-Test 4 TS8602C; T8600, 01, Any position.
m1For electric heat fan operation, the fan will operate with or 03A,B or C
the heating system when the fan switch is in AUTO.
A HEAT displayed when system switch is in HEAT, 5 T8600, 01, or 03D HEAT, OFF, or COOL
COOL when in COOL, HEAT and COOL when in 7 T8600, 01, or 03D AUTO
AUTO, neither when in OFF. Also, a four-digit code is
displayed, with each digit explained as follows.

This equipment is a Class B digital apparatus which complies with Canadian Radio Interference Regulations, CRC c.1374.

9 69-0309—9
T8602A,B,C,D AND TS8602A,C Chronotherm ® III FUEL SAVER THERMOSTATS

69-0309—9 10
T8602A,B,C,D AND TS8602A,C Chronotherm ® III FUEL SAVER THERMOSTATS

11 69-0309—9
T8602A,B,C,D AND TS8602A,C Chronotherm ® III FUEL SAVER THERMOSTATS

Home and Building Control Home and Building Control Helping You Control Your World
Honeywell Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 740 Ellesmere Road
Golden Valley, MN 55422 Scarborough, Ontario
M1P 2V9 QUALITY IS KEY

69-0309—9 J.H. Rev. 7-95 Printed in Taiwan R.O.C. 12