Bracing Design

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 3

Bracing Design

Job Number : KW-13798 A1


Input:
Braced Bay Width (B) (Min) : 6m
Eave Height (E.H.): 10 m
Wind Load Intensity : 0.67 kN/m2
Roof Slope : 1 :10
No. of Braced Bays : 2
Building Width : 34
No. of End Wall Columns : 5
End Wall Column Spacing : 5.67 m
Wind Load Coefficient : 0.8
11.42
Max. Wind Column Height = 11.42 m

{W.L. Coef. x Wind Load Intensity x


Load P = Trib Area.}/( 2)

P= 17.34 kN
Table 1:
S.No. Type of Bracing Capacity
Member Force : 24.5197918787985 kN
Roof bracing length = Ö B ² + Column spacing ² 1 Cable 60 kN
Wall bracing length = Ö B ² + E.H. ² 2 16Ø Rod 59 kN
3 20Ø Rod 58 kN
Roof Bracing Member Length = 8.25 4 24Ø Rod 57 kN
5 SA 50x50x6 63 kN
Roof Bracing Type : Cable 6 SA 70x70x6 109 kN

7 SA 100x100x10 310 kN
Enter Allowable Capacity Based on Table 1: 60 kN
8 SA 150x150x12 595 kN

9 Double Cable 60 kN
Enter Allowable Length Based on Table 1 : 12 m
10 2-16Ø Rod 59 kN

Checks: 11 2-20Ø Rod 58 kN


Actual Load/Allow. Load : 0.289 12 2-24Ø Rod 57 kN
BRACING PROVIDED IS O.K 13 DA 50x50x6 63 kN
14 DA 70x70x6 109 kN
Actual Len./Allow. Len. : 0.688 15 DA 100x100x10 310 kN
BRACING PROVIDED IS O.K 16 DA 150x150x12 595 kN
Allowable
Length
12.0 m
12.0 m
12.0 m
12.0 m
4.5m
6.45 m

9.15 m

13.8 m

12.0 m

12.0 m
12.0 m
12.0 m
4.5m
6.45 m
9.15 m
13.8 m
TRUE