40 · GEA BOCK HG SEMI-HERMETIC COMPRESSORS

OPERATING LIMITS

R407A Operating limits

tC (°C) HGX12P, HGX22e, HGX34e, HGX44e/-4, HGX56e tC (°C) HGX44e/-4 S

60 60

50 50
40
40
∆t0h<20K
∆t0h<20K t0h+20 °C
30
t0h+20 °C 30
20
20
10
10
–40 –30 –20 –10 0 10 t0 (°C) –40 –30 –20 –10 0 10 t0 (°C)

tC (°C) HGX66e, HGX88e


t0 Evaporating temperature (°C)
tC Condensing temperature (°C)
60 ∆t0h Suction gas superheat (K)
t0h Suction gas temperature (°C)
50

40 Max. permissible operating pressure (LP/HP) 1): 19/28 bar


∆t0h<20K LP = low pressure, HP = high pressure
1)

30
t0h+20 °C
Unlimited application range
20
Motor version -S- (more powerful motor)
10 Supplementary cooling or reduced suction gas temperature
Supplementary cooling and reduced suction gas temperature
–40 –30 –20 –10 0 10 20 t0 (°C)

NOTES

R407A Notes

Operating limits ASERCOM certified performance data


Compressor operation is possible within the limits shown on the
application diagrams. Please note the colored areas. Compressor
application limits should not be chosen for design purposes or
continuous operation.

Restrictions to the operating limits may occur when using a For compressors with this label, the performance data are certified
frequency converter. according to the strict requirements of ASERCOM.

Performance data ASERCOM is the Association of European Refrigeration Compressors


The performance data for R407A are based on European Standard and Controls Manufacturers.
EN 12900 50 Hz power supply frequency. Information about the Association and the constantly updated
This signifies: 20 °C suction gas temperature without liquid subcooling. overview of certified GEA compressors can be found at
Evaporation and condensing temperatures are based on the dew www.asercom.org and www.gea.com.
point values (saturated vapour conditions).

Conversion factor for 60 Hz = 1.2


Performance data for other operating points, see GEA VAP software
(vap.gea.com).