52 · GEA BOCK HG SEMI-HERMETIC COMPRESSORS

OPERATING LIMITS

R22 Operating limits

tC (°C) HG12P, HG22e, HG34e, HG44e, HG56e tC (°C) HG66e, HG88e

70 70

60 60

50 50

40 40
∆t0h<20K
∆t0h<20K t0h+20 °C
30
30 t0h+20 °C
20
20
10
–40 –30 –20 –10 0 10 t0 (°C) –40 –30 –20 –10 0 10 t0 (°C)

t0 Evaporating temperature (°C) Max. permissible operating pressure (LP/HP) 1): 19/28 bar
tC Condensing temperature (°C) LP = low pressure, HP = high pressure
1)

∆t0h Suction gas superheat (K)


t0h Suction gas temperature (°C) Unlimited application range
Motor version -S- (more powerful motor)
Supplementary cooling or reduced suction gas temperature
Supplementary cooling and reduced suction gas temperature

NOTES
R22 Notes

Operating limits Performance data


Compressor operation is possible within the limits shown on the The performance data for R22 are based on European
application diagrams. Please note the colored areas. Compressor Standard EN 12900 with a 50 Hz power supply frequency.
application limits should not be chosen for design purposes or This signifies: 20 °C suction gas temperature without liquid subcooling.
continuous operation.
This results in significant differences compared to specifications with
Restrictions to operating limits may occur when using a frequency liquid undercooling and/or suction-gas temperatures.
converter. A comprehensive modification to 20 °C suction gas temperature will
For further explanations consult www.gea.com. follow at a later date.

Conversion factor for 60 Hz = 1.2


Performance data for other operating points, see GEA VAP software
(vap.gea.com).