Express Installation Guide

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

For Additional Technical Assistance Call +1.509.332.

1890

Express Installation Guide


SEL-710 Motor Protection Relay

Package Contents
SEL-710 Blank Pushbutton LED Label

Product Literature

7.36 Contents: CD Installation:


• Express Installation Guide 1. Insert the CD into the drive.
(187.0) • Instruction Manual 2. If Windows autorun is
• Configurable Label enabled, the Contents.html file Blank Target LED Label
Instructions & Template will load automatically.
• Option Cards Instruction Sheet 3. If Windows autorun is not
• DeviceNet User’s Guide enabled, access files via Label Removal Tool
• DeviceNet Eleectronic Data Windows Explorer.
Sheet (EDS)
• ReadMe.txt
• Adobe® Reader®

2350 NE Hopkins Court • Pullman, WA 99163 USA


Tel: +1.509.332.1890 • Fax: +1.509.332.7990
www.selinc.com • info@selinc.com UP UP
LEFT 198-0424 RIGHT 198–0424
© 2009 Schweitzer Engineering Laboratories, Inc.
All rights reserved PM710-01-CD/UCD02076
5.47 *UCD02076*
(139.0) 20090327

Panel Cutout Template Product Literature CD No. 8-32 Mounting Screws Configurable Label Kit
& Gasket
Safety Information
Dangers, Warnings, and Cautions
See the product manual for additional safety information. The product documentation uses three kinds of hazard statements, defined as
follows:

DANGER WARNING CAUTION


Indicates an imminently hazardous situation that, if not Indicates a potentially hazardous situation that, if not Indicates a potentially hazardous situation that, if not
avoided, will result in death or serious injury. avoided, could result in death or serious injury. avoided, may result in minor or moderate injury or
equipment damage.

Safety Symbols
The following symbols are often marked on SEL products.

CAUTION ATTENTION
Refer to accompanying documents. Se reporter à la documentation.

Earth (ground) Terre

Protective earth (ground) Terre de protection

Direct current Courant continu

Alternating current Courant alternatif

Both direct and alternating current Courant continu et alternatif

Instruction manual Manuel d’instructions

Safety Marks
The following statements apply to this device.

General Safety Marks

Motor Overload: Class 10, 20, and 30. Surcharge du Moteur: Classe 10, 20 et 30.
For use in Pollution Degree 2 environment. Pour l'utilisation dans un environnement de Degré de Pollution 2.
Ambient air temperature shall not exceed 50°C (122°F). La température ambiante de l'air ne doit pas dépasser 50°C (122°F).
For use on a flat surface of a Type 12 enclosure. Pour l’utilisation sur une surface plane d'un boîtier de Type 12.
Terminal Ratings Valeurs nominales des bornes
Wire Material Matériau de fil
Use 75°C (167°F) copper conductors only. Utiliser seulement conducteurs en cuivre 75°C (167°F).

Tightening Torque Couple de serrage


Terminal Block: 0.9–1.4 Nm (8–12 in-lb) Bornier : 0,9–1,4 Nm (8–12 livres-pouce)
Compression Plug: 0.5–1.0 Nm (4.4–8.8 in-lb) Fiche à compression : 0,5–1,0 Nm (4,4–8,8 livres-pouce)
Compression Plug Mounting Ear Screw: 0.18–0.25 Nm Vis à oreille de montage de la fiche à compression : 0,18–0,25 Nm
(1.6–2.2 in-lb) (1,6–2,2 livres-pouce)

2
Safety Information
Hazardous Locations Safety Marks

WARNING – EXPLOSION HAZARD AVERTISSEMENT – DANGER D'EXPLOSION


Open circuit before removing cover. Ouvrir le circuit avant de déposer le couvercle.

WARNING – EXPLOSION HAZARD AVERTISSEMENT – DANGER D'EXPLOSION


Substitution of components may impair suitability for Class I, Division 2. La substitution de composants peut détériorer la conformité à Classe I, Division 2.

Operating Temperature Range: –40°C to +85°C (–40°F to +185°F). Plage de température de fonctionnement : –40°C à +85°C (–40°F à +185°F).
Hazardous Locations Operating Temperature Range: –20°C to +40°C Emplacements Plage de température de fonctionnement d’emplacements
(–4°F to +104°F). dangereux : –20°C à +40°C (–4°F à +104°F).

3
Typical Connections
Stop Start
120/240 Vac
50/60 Hz
CR

CR

A01 A02 A03 A04 A05 A06 A07 A08 A09 A10 A11 A12
GND +/H -/N
OUT_01* OUT_02* OUT_03*(TRIP) IN_01 IN_02
OUTPUT CONTACTS CONTROL
INPUT POWER (Trip Fail-Safe Contactor Wiring Shown) INPUTS
Front
SEL-710
5 4 3 2 1

9 8 7 6

Port 3
5 4 3 2 1 Motor Relay
9 8 7 6

Optional Input Output Cards

PTC Thermistor IRIG-B Time Source


10 RTDs
IRIG-B/PTC
+ + + + + + + + + +


Optional Ethernet (single or dual)
1–12 RTDs 4 Digital Inputs / 4 Digital Outputs
OR
Winding
Copper Wire Multimode Fiber
Bearing SEL-2600 ≤ 1000 m
External RX Fiber-Optic
3 Digital Inputs / 4 Digital Outputs / 1 Analog Output
Others
RTD Module Input
(Optional) FO Cable**
TX Fiber-Optic
Output 8 Analog Inputs
Ambient
Port 4 DeviceNet

V—
Spare
(Optional)

CAN_L
Input SHIELD
4 Analog Inputs / 4 Analog Outputs
CAN_H
V+

TX+
Port 4A EIA-485
(Optional)

TX—
8 Digital Inputs
RX+
RX—
SHIELD

CURRENT INPUTS
VOLTAGE INPUTS (Optional) IA IB IC IN
* Factory Default Function
VA VB VC N
** SEL Fiber Optic Cables E01 E02 E03 E04 Z01 Z02 Z03 Z04 Z05 Z06 Z07 Z08
240-1506 – 1 m (3.3 feet) ST/ST
240-1507 – 5 m (16.4 feet) ST/ST
240-1508 – 15 m (49.2 feet) ST/ST
Other lengths available by request
* CR
A diagram from a four-wire Wye A
connection also available in the
B MOTOR
instruction manual. Also,
differential elements connections
C
are shown in the manual.
Open-Delta Potential and Residual Ground CT Connections

4
Rack Mounting
You can mount the SEL-710 in a sheltered indoor environment (a building or an enclosed cabinet) that does not exceed the temperature
rating of –40°C to +85°C. For mounting consideration the relay dimensions are shown below.

7.56 7.36
(192.0) (187.0)

5.67 1.12 5.80 5.47


(144.0) (28.5) (147.4) (139.0)

New Control Center

1. Place the enclosed panel 2. Make smooth cut around 3. Place mounting gasket 4. Fasten relay to mounting
cutout over desired mounting cutout. around relay and insert plate with included screws.
location and trace. unit into hole. (The
photo displays optional
appearance bezel.)

Retrofitting

1. Remove old relay. 2. Insert retrofitting plate and 3. Place mounting gasket 4. Fasten relay to mounting
fasten (see www.selinc.com/ around relay and insert unit plate with included screws.
sel-710.htm for retrofits). into retrofitting plate.
5
Connections
Shown for SEL-710 with IRIG-B, Ethernet, EIA-232, Fiber Optic, Voltage Option, RTD option, and 4 DO/3 DI/1 AO option. Refer to
the SEL-710 manual for additional details and other options.

Wire sizes for connections are dictated by the terminal blocks and expected load currents. You may use the following table as a guide in
selecting wire sizes:
Connection Type Minimum Wire Size Maximum Wire Size
2
Grounding (Earthing) Connection 18 AWG (0.8 mm ) 14 AWG (2.1 mm2)
Current Connection 16 AWG (1.3 mm2) 12 AWG (3.3 mm2)
Potential (Voltage) Connection 18 AWG (0.8 mm2) 14 AWG (2.1 mm2)
Contact I/O 18 AWG (0.8 mm2) 14 AWG (2.1 mm2)
Other Connection 18 AWG (0.8 mm2) 14 AWG (2.1 mm2)

Card Slot A: Power Supply Card With 2 DI/3 DO


Step 1. Connect appropriate power supply to terminal 01 (+/H) and terminal 02 (-/N). Note that power terminals are isolated from
chassis ground.
Step 2. Connect ground terminal GND to a rack frame or switchgear ground for proper safety and performance.
Step 3. Connect as many as 2 digital inputs per application requirements, to optoisolated inputs IN_01
(terminals 10 and 11), and IN_02 (terminals 11 and 12).
Step 4. Connect the 3 output contacts per application requirements to OUT_01 (terminals 03 and 04), OUT_02
(terminals 05 and 06), and OUT_03 (terminals 07, 08, and 09).

Card Slot B: Main Board With IRIG-B, Ethernet, EIA-232, Fiber Optic
Step 1. Connect communications devices as required to front DB-9 serial Port F (EIA-232), rear DB-9 serial Port 3 (EIA-232),
10/100BASE-T Ethernet port (RJ45 connector) and fiber-optic (ST® connector) serial Port 2.
Step 2. Connect IRIG-B time-code input to terminals 01 (+) and 02 (-).

Card Slot C: 3 Digital Inputs, 4 Digital Outputs, 1 Analog Output Card (3 DI/4 DO/1 AO)
Step 1. Connect additional digital inputs (IN_01, IN_02, IN_03) and outputs (OUT_01, OUT_02, OUT_03, OUT_04), if required
by application, using the connection diagram.
Step 2. Connect the analog (transducer) output AO_01 using terminals 09 and 10.

6
Connections
Card Slot D: 10 RTD Inputs Card
Connect as many as ten RTDs as required by application. Example: Connect RTD1 (+) to terminal 01, RTD1 (-) to terminal 02, RTD1
(common or return) and RTD1 (shield, if available) to terminal 03.
v

Card Slot E: Voltage Inputs Card


Connect 4-wire wye-connected PTs or open-delta connected PTs as shown in the typical connections diagram. For other PT connec-
tion options refer to Section 2 of the SEL-710 manual.

Card Slot Z: Current Inputs Card


Connect phase current and neutral current inputs as shown in the typical connections diagram.

Step 1. Connect Phase A, Phase B, and Phase C current inputs to terminals 01 and 02; terminals 03 and 04; and terminals 05 and 06,
respectively, following the convention shown in the typical connections diagram.
Step 2. Connect neutral current IN inputs to terminals 07 and 08.

Refer to Section 2 of the SEL-710 manual for additional details and other connection options.

7
Communication With Relay
There are two ways of communicating with the SEL-710 Motor Relay. You can communicate with the relay using the human-machine
interface (HMI) on the front panel or through serial port communications with a computer. For communications, the computer must
have a serial port and the operating system should be Windows® 2000 or newer. A standard EIA-232 crossover cable or an SEL-234A
cable will also be required.

HMI Pushbuttons
Press the TARGET RESET pushbutton Press the directional (up, down, left, right)
to clear targets that have been alarmed. pushbuttons to scroll through options.

TARGET ESC
RESET ENT

Press the ESC pushbutton Press the ENT pushbutton


to return to previous menu. for selection to see next menu.

Computer Connection Steps


Step 1. Connect the PC and the relay using a serial communications cable.
Step 2. Apply power to both the PC and the relay.
Step 3. Open a terminal emulation program.
Option 1: ACSELERATOR QuickSet SEL-5030 Software
Open ACSELERATOR QuickSet and proceed to Step 4. If you do not
have ACSELERATOR QuickSet, you can download the program from
www.selinc.com/sel-5030.htm. Refer to Section 3 of the SEL-710
manual for more information about ACSELERATOR QuickSet.
Option 2: HyperTerminal
To open HyperTerminal go to Start > Programs > Accessories >
Communications > HyperTerminal. Once there you will be
prompted to enter a name of your choice for the connection. Then
you will choose which port to connect through. Make sure you select
the same port that you connected the cable to, then click OK.

Step 4. Set the PC terminal emulation program to the same communications


port settings as shown in the figure to the right and click OK.
Step 5. Press the <Enter> key on the PC keyboard to check the
communications link. You should see the = prompt. If you do not see
the = prompt, check the cable connections, confirm that the settings
in the terminal emulation program are the default values, and that the
emulation mode is set to VT100.
Step 6. Once connected, you can set all other relay settings and obtain values
as needed. Refer to Section 6 in the SEL-710 manual for more
information.

SEL-710 Relays are shipped with default passwords. To prevent unauthorized access, change default passwords
to private passwords at installation. SEL shall not be responsible for damage resulting from unauthorized access.

8
Relay Settings
This section of the Express Installation Guide provides a step-by-step process to set the SEL-710 for basic protection purposes. For
more in-depth relay setting procedures, please refer to the SEL-710 manual or contact your local SEL representative. To get more direc-
tions on relay setting using PC configuration, please refer to Section 3 of the SEL-710 manual.
Step 1. Locate the values listed below. Some of the values needed are located on the control center nameplate while others can be
found directly on the motor nameplate.
Find the Values:
CT Ratio (CTR1) =
Full Load Amps (FLA1) =
Service Factor (SF) =
CT Ratio to Ground (CTRN) =
Phase PT Ratio (PTR) =
Line Voltage (VNOM) =
Delta/Wye Connection (DELTA_Y) =
Single V Input (SINGLEV) =

Step 2. Enter Access Level 2. Whenever prompted for a password, enter the corresponding password. To change the
character, use the arrow keys and press the ENT pushbutton to select the character. Once the full password has been
entered, scroll to Accept and press the ENT pushbutton.
Valid Password Characters Factory Default Passwords for Access Levels 1 and 2

Alpha ABCDEFGHIJKLMNOPQRSTUVWXYZ Access Level Factory Default Password


abcdefghijklmnopqrstuvwxyz
1 OTTER
Numeric 0123456789
2 TAIL
Special !"#$%&'()*+,-./:;<=>?@[\]^_`{|}~

Step 3. There are three settings sections that need to be set in order to provide basic protection. Navigate to ENT >
SET/SHOW > GLOBAL > General Settings. Once in this menu the following parameters can be set. Complete
these settings to fit the motor connected to the SEL-710 making sure to select NAMEPLATE for the APP
parameter. The other settings should be set to the values taken off the motor nameplate and to your preference.
The warning that scrolls across the top lets you know that the relay will only provide basic and default protection,
which is fine for beginning functionality. This setting will need to be changed to FULL at later date.

APPLICATION (FULL, NAMEPLATE) APP :=

PHASE ROTATION (ABC, ACB) PHROT :=

RATED FREQ. (50, 60 Hz) FNOM :=

DATE FORMAT (MDY, YMD, DMY) DATE_F :=

Step 4. The second setting section is Group settings. Navigate to ENT > SET/SHOW > GROUP > 1. In this menu there
are five sections (ID Settings, Config Settings, Thermal Overload, Neutral Overcurrent, Residual Overcurrent) and
there are parameters in each section that must be set. These values can be set from the values taken off the motor
nameplate and control center.
Step 5. The last setting section is Logic settings. The logic output 103 Fail Safe must be set to Y. The default factory
settings are set to Y so there are no changes that need to be made during this step.

9
Relay Settings
When APP = NAMEPLATE the following protection is provided by the SEL-710 based on the settings listed previously and hidden
settings (all other protections and warning functions are disabled):
➤ Thermal stator and rotor protection based on motor ratings
➤ Current unbalance protection (20% unbalance, 5 second delay)
➤ Instantaneous phase overcurrent trip level set based on IEEE C37.96 recommendation for phase overcurrent protection
➤ Ground overcurrent protection
➤ Phase overvoltage protection (1.1*VNOM, 0.5 second delay)
➤ Phase reversal protection
➤ Breaker failure protection
To reference all other applications and exact default settings when in this mode, please refer to Section 4 in the SEL-710 manual. The
nameplate application settings and the HMI menu structure are shown below.

Setting Name (Prompt) Range Main Menu


Meter
Global Settings Press to move
Events
Monitor within the list.
APP (APPLICATION) FULL, NAMEPLATE
Targets
PHROT (PHASE ROTATION) ABC, ACB Control
Set/Show Press to select an
FNOM (RATED FREQ) 50, 60 Hz Status underlined menu item.
Quit
DATE_F (DATE FORMAT) MDY, YMD, DMY
Group Settings
Press to Set/Show Menu
Global
RID (UNIT ID LINE 1) 16 characters return to the
previous list. Group
TID (UNIT ID LINE 2) 16 characters Port
Active Group
CTR1 (PHASE CT RATIO) 1–5000 Date
Time
FLA1 (MOTOR FLA) 0.2–5000.0 A
CTRN (NEUTRAL CT RATIO) 1–2000 Group Menu
GROUP
PTR (PHASE PT RATIO) 1.00–250.00 1
2
VNOM (LINE VOLTAGE) 100–30000 V 3

DELTA_Y (XFMR CONNECTION) Delta, Wye


Group 1 Menu
SINGLEV (SINGLE V INPUT) Y, N ID Settings
Config Settings
SF (SERVICE FACTOR) 1.01–1.50 Thermal Overload

LRA1 (MOTOR LRA) 2.5–12.0 xFLA

LRTHOT1 (LOCKED ROTOR TIME)a 1.0–600.0 sec Trip/Close Logic
Motor Control
50N1P (NEUT OC TRIP LVL) OFF, 0.01–25.00 A
50N1D (NEU OC TRIP DLAY) 0.00–5.00 sec Config Menu
CTR1
50G1P (RES OC TRIP LVL) OFF, 0.10–20.00 xFLA 100
FLA1
50G1D (RES OC TRIP DLAY) 0.00–5.00 sec 250.0 A

Logic Setting •
OUT103FS (OUT103 FAIL-SAFE) Y, N •
SINGLEV
a. N
LRTHOT1 defines the time a motor can safely withstand
locked rotor starting when the motor is at operating tem-
perature. The default setting is 10 seconds at 600 percent FLA1 Setting
overload (Class 10 protection). This setting is adequate for MOTOR FLA
FLA1 = 0250.0 A
typical motor starting.

10
Notes

11
*PLS00012*
© 2006–2015 Schweitzer Engineering Laboratories, Inc. All rights reserved. Date Code 20150130

12

You might also like