IEC 104 and 61850 Training

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 50

Programming and configuration for

IEC 60870-5-104 using TIA Portal


Configuration and Programming
CP 1542SP-1 IRC and CP1243-1

Page 2
Configuration and Programming
PLC IP Addressing

Page 3
Configuration and Programming
Station IP Addressing

Page 4
Configuration and Programming
Select communication type

Page 5
Configuration and Programming
Service port

Page 6
Configuration and Programming
ASDU Address

Page 7
Configuration and Programming
Setting max time between S and O for testing

Page 8
Configuration and Programming
IEC 104 Clients

Page 9
Configuration and Programming
IEC 104 Redundant Clients

Page 10
Configuration and Programming
Time sync for RTUs

Page 11
Configuration and Programming
Data source

Page 12
Configuration and Programming
Data mapping

Page 13
Configuration and Programming
Setting for SBO

Page 14
// Simulate Single Point Info
Configuration and Programming "SCADA".SP_Info := ("SCADA".SP_Info OR "SCADA".SP_CMD_Close) AND NOT "SCADA".SP_CMD_Open;
Output simulation // Simulate Messurement value
"R_TRIG_Sim"(CLK:="Clock_5Hz");
"Random"(#RandomNumber);
IF "SCADA".SP_Info AND "R_TRIG_Sim".Q THEN
"SCADA".Measurement := "SCADA".Measurement + 0.5;
IF "SCADA".Measurement >= "SCADA".Setpoint THEN
// Simulate TAP "SCADA".Measurement := "SCADA".Setpoint + #RandomNumber;
IF "SCADA".TAP_Cmd[0] = 0 AND "SCADA".TAP_Cmd[1] = 1 THEN END_IF;
"SCADA".TAP_Position := "SCADA".TAP_Position + 1; END_IF;
IF "SCADA".TAP_Position >= 255 THEN // Simulate Double Point Info
"SCADA".TAP_Position := 255; IF "SCADA".DP_Cmd[0] = 0 AND "SCADA".DP_Cmd[1] = 1 THEN
END_IF; "DP_Cmd".Now := 1;
"SCADA".TAP_Cmd[0] := "SCADA".TAP_Cmd[1] := 0; END_IF;
END_IF; IF "SCADA".DP_Cmd[0] = 1 AND "SCADA".DP_Cmd[1] = 0 THEN
"DP_Cmd".Now := 2;
IF "SCADA".TAP_Cmd[0] = 1 AND "SCADA".TAP_Cmd[1] = 0 THEN END_IF;
"SCADA".TAP_Position := "SCADA".TAP_Position - 1; "R_TRIG_DP_Cmd"(CLK:="DP_Cmd".Now <> "DP_Cmd".Prev);
IF "SCADA".TAP_Position <= 0 THEN IF "R_TRIG_DP_Cmd".Q THEN
"SCADA".TAP_Position := 0; "SCADA".DP_Info[0] := "SCADA".DP_Cmd[0];
END_IF; "SCADA".DP_Info[1] := "SCADA".DP_Cmd[1];
"SCADA".TAP_Cmd[0] := "SCADA".TAP_Cmd[1] := 0; "DP_Cmd".Prev := "DP_Cmd".Now;
END_IF; END_IF;

Page 15
Commissioning

Page 16
Commissioning
IEC Client setting before connect

Page 17
Commissioning
Single point command testing

Page 18
Commissioning
Single point command testing

Page 19
Commissioning
Server -> Client data flow

Page 20
Commissioning
Double point command testing

Page 21
Commissioning
Double point command testing

Page 22
Commissioning
Regulating Step Command testing

Page 23
Commissioning
Regulating Step Command testing

Page 24
Commissioning
Setpoint Command testing

Page 25
Commissioning
Setpoint Command testing

Page 26
Commissioning
Select Before Operate testing

Page 27
Commissioning
Select Before Operate testing

Page 28
Commissioning
Select Before Operate testing

Page 29
Commissioning
Select Before Operate testing

Page 30
Commissioning
Select Before Operate testing

Page 31
Commissioning
Connect to 2 RTUs

Page 32
Commissioning
2 Clients

Page 33
Commissioning
Testing using Freyr IEC104 Client

Page 34
Commissioning
Freyr IEC104 Client. Server -> Client data flow and Menu to Point Command

Page 35
Commissioning
Freyr IEC104 Client. Single Point Command

Page 36
Commissioning
Freyr IEC104 Client. Two Clients

Page 37
IEC 61850

Page 38
Intelligent Electronic Devices (IED)

• IEDs act as IEC 61850 server in the IEC


61850 network
• All Siemens SIPROTEC 4, SIPROTEC
Compact and SIPROTEC 5 devices
support IEC 61850
• More than 300,000 SIPROTEC devices
installed worldwide
• Only one SIPROTEC device for all tasks in
the feeder:
Contacting – Controlling – Measuring –
Automating

Page 39 Restricted | © Siemens 2023 | Lifecycle Management Suite | June 2023


Product
Merging the two worlds

Operation and Monitoring Operation and Monitoring


Process Energy

Process Energy
Plant
Field Swg Drive Motor IED1 IED2 IED3 IED4

Page 40
SCADA SCADA Historian
Client Client and Client
Structure
To A0, A2

IEC-60870-5-
104 module S7-1200

SCADA SCADA
Primary Secondary Server
Server

Managed 1517H 1517H


switch
HMI

Switch
Remote I/O

Local

I/Os
Control
system Gateway to others
Modbus devices
IED IED IED IED

Page 41
Topologies S7-1500

S7-1500
S7-1500

IED IED IED IED IED IED IED IED IED IED IED IED IED IED IED IED IED IED IED IED IED IED IED

S7-1500 S7-1500 S7-1500 S7-1500


R/H R/H R/H R/H

IED IED IED IED IED IED IED IED IED IED IED IED IED IED IED IED
Page 42
IEC 61850 Overview

Page 43
IEC 61850
The Hierarchical Data Model

Physical Device

Logical Device

Logical Node

Data Object

Data Attribute

Data or data attributes can be


M Mandatory
O Optional Eg:
C Conditional SEPAM_IED/LD0/XCBR1.Pos.stVal

Page 44
IEC 61850
Device Model
Physical Device Logical Device
Station Bus

GGIO GAPC Limit overflow


HMI
General Input / Output Automatic Process
Control Switch position

PTRC controller
Trip Conditioning Trip Decision

PTOC
Overcurrent Protection Start value

Process Bus

gateway
RDRE
XCBR
Disturbance recorder
RMS
Circuit Breaker
MMXU Measurements

Measurement Unit

Example
for some information
Page 45
IEC 61850
Logical Nodes

 L System LN (2) M Metering and measurement (8)


 P Protection (28) S Sensor and monitoring (4)
 R Protection related (10) X Switchgear (2)
 C Control (5) T Instrument transformers (2)
 G Generic (3) Y Power transformers (4)
 I Interfacing and archiving (4) Z Other power system
 A Automatic control (4) equipment (15)

Examples:

■ PDIF: Differential protection ■ CSWI: Switch controller


■ RBRF: Breaker failure ■ MMXU: Measurement unit
■ XCBR: Circuit breaker ■ YPTR: Power transformer

Page 46
IEC 61850
Data Objects

 Represents the data within a Logical Node


• Voltage, current, breaker position, protection settings…
 Defined by groupings of specific data attribute types
• Description, status, measurements, control…
 Uses standardized names instead of registers
• PhV – Phase to neutral voltage (ie: not 41001)
 Abstract Services functions
• GetDataValues
• GetAllDataValues
• SetDataValues

Page 47
IEC 61850
Data Attributes

 ctlVal Controllable value


 d Textual description of the value
 db Deadband
 mag Value
 q Quality of the attribute represented by the value
 stVal Status value of the data
 t Timestamp of the last data update
 …

Page 48
IEC 61850
Functional Constraints (FC)

ST Status Values ● SP Setpoint


MX Measurands (analogue) ● SV Substitution
CO Control ● SG Setting Group
CF Configuration ● SE Setting Group Editable
DC Descriptions
EX Extended Definition

● BR Buffered Report
● RP Unbuffered Report
● LG Logging
● GO GOOSE Control
● GS GSSE Control
● MS Multicast SV Control
● US Unicast SV Control
Page 49
IEC 61850
Self Description
A standardized device description language
• Substation Configuration Description Language (SCL)
• Based on XML (Extensible Mark up Language)
Describes IED communication and IED parameters to the client
Provides a compatible way to exchange IED and substation automation system
descriptions between IED engineering tools of different manufacturers

What are you?

Client Server
I am… , I have
these models, …

Self description

Now I
Understand it

Page 50