Professional Documents
Culture Documents
Alfc N Avr
Alfc N Avr
Alfc N Avr
ΔPV 1
• GH(s) = --------- = ---------
ΔPg 1+ sTH
Solution ΔPT,0 = 0
ΔPref,0 = (1/R) Δf0
= (1/0.024)(-0.1)
= -4.17MW
We must command the speed changer to
lower by 4.17 MW
Example Two generators are supplying power to a
system. Their ratings are 50 and 500 MW
respectively. The frequency is 60 Hz and each
generator is half loaded. The system load
increases by 110 MW and as a result the
frequency drops to 59.5 Hz. What must the
individual regulations be if the two generators
should increase their turbine powers in proportion
to their ratings?
Solution
R = -(-0.5)/10 = 0.05 Hz/MW (smaller unit)
R = -(-0.5)/100 = 0.005 Hz/MW (larger unit)
Or
R = -(-0.5/60)/(10/50)=0.0417 pu Hz/ pu MW (both)
Assignment Problem
• Two 500 kW alternators run in parallel.
The governors on the prime movers are so
set that the frequency drops from 51 Hz to
49 Hz from no load to full load in one,
while in the other from 51 to 49.5 Hz.
Calculate the load on each machine when
the total load is 750 kW and the frequency
at this load.
Closing the ALFC Loop
2
f
Wkin W 0 kin 0
f
P
D D
f
dWkin
PT PD Df
dt
f f 0 f
2
f 0 f
Wkin W kin
0
0
f
f
W 0 kin 1 2 0
f
W 0 kin d
PT PD Df 2 0 f
f dt
H d
PT PD Df 2 0 f (in pu )
f dt
H
PT ( s ) PD ( s ) Df ( s ) 2 0 sf s
f
f s Kp
G p ( s)
PT ( s ) PD ( s ) 1 sTp
2H
Tp 0
f D
1
Kp
D
Closing the ALFC Loop