Professional Documents
Culture Documents
Sookrod 2018
Sookrod 2018
Sookrod 2018
Abstract—The conventional structure of distribution systems is embedded DG condition. The operation time interval
evolving rapidly due to the high penetration of distributed between the primary and backup relays would not be
generation (DG). DG may have a detrimental effect on adequate resulting in nuisance tripping and unnecessary
protection coordination of overcurrent relays regarding operation [2]. To maintain the overcurrent relay
varying short circuit levels. Overcurrent relays are necessary coordination, a minimum discrimination time of the main
to ensure the reliability of power system by avoiding and backup relays is considered. The parameters of relay
malfunction and the unnecessary outage of the healthy part of setting need to be adjusted appropriately.
the system. The relay settings have to be changed depending on Coordination failure in relays is a vital issue that needs to
capacity and location of installed DG. It is complexity to
be progressively considered, since the extended penetration
analyze all operating conditions. Therefore, the effects of DG
of DG units causes aberrant operation of the protection
presence on the existent relays must be investigated in order to
maintain protection coordination. To overcome relay system. For mitigating this effect of DG on protection
coordination problem, overcurrent relay coordination tool is coordination, existent overcurrent relays need to be
proposed in this paper. This tool is developed using concept of reorganized themselves for every change on the network.
adaptive protection scheme. Relay setting parameters are set The severity of changes relies on location, capacity and
automatically in response to changing systems. Furthermore, number of DGs. The adaptive protection scheme, in [3], has
this proposed tool is suitable for the complex future radial come up as an appreciable and acceptable solution. This
distribution systems. attractive approach is selected for the relay coordination
improvement in this paper. Aim of adaptive protection
Keywords-overcurrent relay; protection coordination; scheme is modification of relay settings. The technique is
distribution system; distributed generation based on the estimation of short circuit currents and
continued with the evaluation of parameters of a proper
I. INTRODUCTION equivalent circuit of the grid [4]. This concept fulfills the
requirement of future possible relay settings.
New trends of generating electricity at medium voltage As mentioned that the installation of DG adds
grid is known as distributed generation (DG) that will be a complication to conventional protection schemes, the
solution to rapid growth in load demand. Advantages in coordination problems may be more difficult to realize and
using DG include reduced environmental impacts, power take a long time to determine in the real power system. This
loss reduction, improved voltage profile, enhanced power paper will focus on relay setting to successfully protect the
quality, increased overall energy efficiency and many more system with topology change. The overcurrent relay
[1]. However, connection of DG units also has tremendous coordination tool is proposed. It was developed in
impact on short circuit current magnitude, especially DIgSILENT PowerFactory software. In the proposed, all the
considering high DG penetration. This causes significant relays can adapt themselves with the new situations and set
changes in distribution networks. Protection system becomes their settings automatically. It should be pointed out that the
more complex owing to changes in system behavior and proposed tool can solve the overcurrent relay coordination
power flow under short circuit conditions. DG affects problems that DG brings to the protection system. Although,
coordinated protection devices and also brings challenges in changing the settings on existent relays will have associated
settings of original relays. costs but disturbances to existent relay coordination can pose
The most used network structure of distribution system is an additional economic hurdle.
radial distribution system as it is simple to build and easy to
operate. Overcurrent relays are the important protective II. PROBLEM FORMULATION
devices in radial distribution system. Integration of DG into
an existing grid contributes to short circuit current Due to the connection of DG in radial distribution
throughout the system during fault condition. Furthermore, it system, the existent relay coordination is lost [5] and [6].
critically affects protection coordination. The setting of Relay miscoordination can occur, when the fault current
overcurrent relay is not designed to operate under this becomes greater than maximum fault current of the feeder.
This increased current comes from the supply of DG. If the
DigSILENT PowerFactory
© Ip ¹ in form of .dz file
where ISC denotes the short circuit current passing through
relay. A and B are the relay characteristic constants, herein
they are set to be 0.14 and 0.02, respectively [7]. Execute
In general, time of operation of backup relay (tj) is made the DPL scripts
larger than time of operation of primary relay (ti) at least by a
time interval called coordination time interval (CTI). The
primary relay should operate as fast as possible and should Display the results
not trip for a fault outside its zone. The backup relay must in the output window
have sufficient time delay to allow the primary relay to clear
the fault. The protection coordination constraint can be
expressed as follows: Figure 1. Overview of the overcurrent relay coordination tool.
tj ti t CTI (i, j ) : (2)
It is described in detail about the process. For starting,
ZKHUH LV WKH VHW RI WKH SDLUV RI WKH UHOD\V &7, PXVW EH
radial distribution system is created and saved in .dz file
long enough to ensure proper coordination that there is
format. DPL script will figure out a correct solution for the
usually a minimum of 0.2 to 0.5 seconds based on the type
coordination of overcurrent relays. Lastly, the program will
and manufacturer of overcurrent relay. It is set to 0.3 s in this
show the simulated results in output window.
paper.
In this study, electromechanical (IAC) relays are B. The Proposed Relay Coordination Algorithm
concerned. The minimum coordination margins will be The proposed idea for mitigating the impacts of DG on
determined: breaker time, overtravel, and safety factor. For overcurrent relays coordination is based on adaptive
practical purpose, the values of CTI can be given as 0.3 s [8]. protection scheme. Therefore, the relay setting should
The minimum desired time margin between the characteristic guarantee proper protection coordination among possible DG
curves is normally 0.3 s to 0.4 s when coordinating induction installations. The proposed tool is compatible with all radial
disk overcurrent relays with one another in series [9]. If CTI distribution systems. The algorithm is described step-by-step
is found below this threshold value, which means that there process as given in Fig. 2.
is violation of constraints. It is worthy to note that, the
x Step 1: this step performs the measurement of the
proposed tool is applicable to all types of overcurrent relays.
currents of each line, where relays are connected.
As indicated earlier, the rate of change of the DG
Input system data without DG will be checked. If the
penetration level leads to the change in CTI. Relays should
relay coordination is lost, the program will set new
adapt themselves to new situations of system. The relay
TDS and Ip parameters.
operating times for both primary and backup need to
recalculate in order to maintain minimum CTI. The short x Step 2: the user defines DG capacity, desired
circuit current is inputted as a parameter in (1) depending on location and type of DG. Different DG combinations
DG. This variations in short circuit current values affect might change various parts of the grid. This is the
other parameters. It is necessary to revise relays settings beginning of the system changes and the causes of
under possible changes. Thus, the proposed overcurrent relay the problem.
coordination tool is developed. x Step 3: after the DG is connected to the selected
node, short circuit analysis is calculated at the end of
III. PROPOSED RELAYS COORDINATION TOOL each line considering maximum fault current.
x Step 4: the first relay is estimated that is close to the
In this paper proposed the tool to deal with relay
fault. The operating time of operated relays is
coordination issues related to the distribution changes. The
accumulated.
14
x Step 5: the primary relay must have the least 1.08
800
808
812
RG01
824
828
830
854
820
822
890
848
820[1]
relay coordination.
x Step 7: the first relay coordination is achieved from Line-Ground Voltage, Magnitude A Line-Ground Voltage, Magnitude B
Line-Ground Voltage, Magnitude C
Step 5 that will be sent to Step 7. All relays must be
considered according to the criteria. Figure 3. Voltage profile of the test system without DG.
x Step 8: if there is any modification of DG, process 848
15
overcurrent protection and coordination due to providing
R7 3.203 3.203 minimal fault current. For instance, three-phase fault at node
826 (B) 0.395 0.395 806, the primary relay R2 and the backup relay R1 might not
R6 3.598 3.598
R3 3.399 3.399 need to modify the settings. The pair of relays can maintain
810 (B) 0.332 0.332 CTI value above 0.3 s after introduction of DG in
R2 3.731 3.731
conventional system.
TABLE II. OPERATING TIMES OF OVERCURRENT RELAYS FOR THREE- I =234.238
=234.895 pri.A
PHASE FAULTS 10
Conventional Proposed
Fault Relay operation operation
Location No. CTI CTI
t (sec) t (sec)
(sec) (sec)
R2 3.271 3.271
806 0.315 0.315 [s] 3.126 s
R1 3.586 3.586 2.838 s
CTI = 0.288 s
R4 3.452 3.452
812 0.327 0.327
R3 3.779 3.779
R6 3.258 3.258
850 0.328 0.328
R5 3.586 3.586
R11 2.756 2.756 24.90 kV
1
10 100 1000 [pri.A] 10000
828 0.346 0.346 820\Cub_2\R10 818\Cub_2\R9
R7 3.102 3.102
R13 2.362 2.362 Figure 5. Coordination graph of R10 and R9 before adjusting.
854 0.31 0.31
R12 2.672 2.672 10
I =234.238
=234.895 pri.A
16
This proposed tool is suitable for future system and changing [4] M. Ojaghi, Z. Sudi, and J. Faiz, “Implementation of full adaptive
structures in presence of DG. Last but not least, this technique to optimal coordination of overcurrent relays,” IEEE Trans.
Power Del., vol. 28, no. 1, pp. 235-244, 2013.
approach can be applied to various radial distribution
[5] N. K. Choudhary, S. R. Mohanty, and R. K. Singh, “Protection
systems. coordination of over current relays in distribution system with DG
and superconducting fault current limiter,” in Proc. National Power
ACKNOWLEDGMENT Systems Conference, 2014, pp. 1-5.
The authors would like to thank Faculty of Engineering [6] S. P George, S Ashok, and M N Bandyopadhyay, “Impact of
and the Graduate School, Chiang Mai University for distributed generation on protective relays,” in Proc. IEEE
International Renewable Energy and Sustainable Energy, 2013, pp.
financial supports. 157–161.
REFERENCES [7] H. H. Zeineldin, Y.-R. Mohamed, V. Khadkikar, and V. Pandi, “A
protection coordination index for evaluating distributed generation
[1] P. Barker and R. W. de Mello, “Determining the impact of distributed impacts on protection for meshed distribution systems,” IEEE Trans.
generation on power systems: Part 1—Radial power systems,” in Smart Grid, vol. 4, no. 3, 2013, pp. 1523-1532.
Proc. IEEE Power Eng. Soc. Summer Power Meeting 2000, pp. [8] “Distribution feeder overcurrent protection,” in Appl. Manual GET-
1645–1658. 6450, GE Power Management, Schenectady, NY, USA, 1979.
[2] A. Heidari, V. G. Agelidis, H. Zayandehroodi, and M. [9] IEEE Recommended Practice for Protection and Coordination of
Hasheminamin, “Prevention of overcurrent relays miscoordination in Industrial and Commercial Power Systems, IEEE Std. 242-2001,
distribution system due to high penetration of distributed generation,” 2001.
in Proc. IEEE International Conference Renewable Energy Research
and Applications, 2013, pp. 342–346. [10] Radial Test Feeders - IEEE Distribution System Analysis
Subcommittee. [Online]. Available: www.ewh.ieee.org/soc/pes/
[3] F &RIIHOH & %RRWK DQG $ '\ĞNR, “An adaptive overcurrent dsacom/testfee- ders.html
protection scheme for distribution networks,” IEEE Trans. Power
Del., vol. 30, no. 2, pp. 5217-5228, 2015.
17