ADMINISTRATION 25-7

NFPA 25 automatic fre detection equipment used to activate preaction


and deluge systems that are addressed by NFPA 72.
Standard for the
1 .1 .2 Types of Systems.

Inspection, Testing, and Maintenance of Water- 1 .1 .2.1 The types of systems addressed by this standard
include, but are not limited to, sprinkler, standpipe and hose,
Based Fire Protection Systems fxed water spray, private fre hydrants, water mist, and foam
water.
2020 Edition
1 .1 .2.2 Water supplies that are part of these systems, such as

IMPORTANT NOTE: This NFPA document is made available for private fre service mains and appurtenances, fre pumps and
use subject to important notices and legal disclaimers. These notices water storage tanks, and valves that control system fow, are also
and disclaimers appear in all publications containing this document included in this standard.
and may be found under the heading “Important Notices and 1 .1 .3* This standard addresses the operating condition of f re
Disclaimers Concerning NFPA Standards.” They can also be viewed protection systems as well as impairment handling and report‐
at www.nfpa.org/disclaimers or obtained on request from NFPA. ing and applies to fre protection systems that have been prop‐
UPDATES, ALERTS, AND FUTURE EDITIONS: New editions of erly installed in accordance with generally accepted practice.
NFPA codes, standards, recommended practices, and guides (i.e., 1 .1 .3.1 * This standard does not require the inspector to verify
NFPA Standards) are released on scheduled revision cycles. This the adequacy of the design of the system.
edition may be superseded by a later one, or it may be amended
outside of its scheduled revision cycle through the issuance of Tenta‐ 1 .1 .4* Corrective action needed to ensure that a system oper‐
tive Interim Amendments (TIAs). An offcial NFPA Standard at any ates in a satisfactory manner shall be in accordance with this
point in time consists of the current edition of the document, together standard unless this standard specifcally refers to an appropri‐
with all TIAs and Errata in effect. To verify that this document is the ate installation standard.
current edition or to determine if it has been®amended by TIAs or
Errata, please consult the National Fire Codes Subscription Service 1 .1 .5 Unless required by Chapter 16, this standard shall not
or the “List of NFPA Codes & Standards” at www.nfpa.org/docinfo. apply to sprinkler systems designed, installed, and maintained
In addition to TIAs and Errata, the document information pages also in accordance with NFPA 13D.
include the option to sign up for alerts for individual documents and
to be involved in the development ofthe next edition. 1 .2* Purpose.

NOTICE: An asterisk (*) following the number or letter 1 .2.1 The purpose of this document is to provide require‐
designating a paragraph indicates that explanatory material on ments that ensure a reasonable degree of protection for life
the paragraph can be found in Annex A. and property from fre through minimum inspection, testing,
A reference in brackets [ ] following a section or paragraph and maintenance methods for water-based fre protection
indicates material that has been extracted from another NFPA systems.
document. Extracted text may be edited for consistency and
style and may include the revision of internal paragraph refer‐ 1 .2.2 In those cases where it is determined that an existing
ences and other references as appropriate. Requests for inter‐ situation involves a distinct hazard to life or property, the
pretations or revisions of extracted text shall be sent to the authority having jurisdiction shall be permitted to require
technical committee responsible for the source document. inspection, testing, and maintenance methods in excess of
Information on referenced and extracted publications can those required by the standard.
be found in Chapter 2 and Annex H. 1 .3* Application.

1 .3.1 It is not the intent of this standard to limit or restrict the


Chapter 1 Administration use of other inspection, testing, or maintenance programs that
provide an equivalent level of system integrity and perform‐
1 .1 Scope. This document establishes the minimum require‐ ance to that detailed in this standard.
ments for the periodic inspection, testing, and maintenance of
water-based fre protection systems and the actions to under‐ 1 .3.2 The authority having jurisdiction shall be consulted and
take when changes in occupancy, use, process, materials, approval obtained for such alternative programs.
hazard, or water supply that potentially impact the perform‐ 1 .4* Units. Metric units of measurement in this standard are
ance of the water-based system are planned or identifed. in accordance with the modernized metric system known as the
Δ 1 .1 .1 Coordination with NFPA 72 Testing Requirements. International System of Units (SI).
The inspection, testing, and maintenance required by
1 .1 .1 .1 1 .4.1 If a value for measurement as given in this standard is
this standard and NFPA 72 shall be coordinated so that the followed by an equivalent value in other units, the frst stated
system operates as intended. shall be regarded as the requirement. A given equivalent value
shall be considered to be approximate.
1 .1 .1 .2* All inspections, testing, and maintenance required by
NFPA 72 shall conform to NFPA 72, and all inspections, testing, 1 .4.2 SI units have been converted by multiplying the quantity
and maintenance required by this standard shall conform to by the conversion factor and then rounding the result to the
this standard. appropriate number of signifcant digits. Where nominal or
trade sizes exist, the nominal dimension has been recognized
N 1 .1 .1 .3 This standard does not address all of the inspection, in each unit.
testing, and maintenance of the electrical components of the

Shaded text = Revisions. Δ = Text deletions and fgure/table revisions. • = Section deletions. N = New material. 2020 Edition