Download as pdf or txt
Download as pdf or txt
You are on page 1of 47

Quen - Electrical Engineering Utilities – Chapter 1 to 3

CHAPTER 1 systems by methods or usage not in


ELECTRICAL THEORY conformity with this code.
(On a separate pdf) ➢ FPN No. 2: It is highly recommended
that a licensed electrical practitioner be
consulted for any electrical
CHAPTER 2
requirements, including changes.
BUILDING ELECTRICAL MATERIALS ➢ FPN No.3: Fire Hazard, electrocution,
AND EQUIPMENT serious injury or even death may also
(naa sa end) occur with lack or improper
maintenance of wiring system.
CHAPTER 3
> Intended as a design specification or an
BUILDING ELECTRICAL DESIGN
instruction manual to qualified persons. >
PRINCIPLES Relation to Other International Standards.
The requirements in this code address the
ELECTRICAL CODES, LICENSES AND fundamental principles of protection for safety
PERMITS contained in Section 131 of IEC 60364- 1,
Electrical Installation of Buildings.
THE ELECTRICAL CODES
-an electrical code specifies for the written ➢ FPN. IEC 60634-1, Section 131.
provisions necessary for protecting people and Encompasses protection against
property from the improper use of electricity thermal effects, protection against
and electrical equipment. overcurrent, protection against fault
currents, and protection against
NATIONAL ELECTRIC CODE overvoltage.
• The National Electrical Code (NEC) is
a set of specifications and standards in SCOPE
the form of a model code that can be • This code covers the installation of
adopted into local law by the local electrical conductors, equipment and
government entity. raceways: signaling and
• The NEC was established in 1897 communications conductors.
through the combined efforts of • Does not cover the (1) installations in
insurance, electrical, architectural, and railway rolling stock, aircraft or
other interested groups. In 1911, the automotive vehicles. (2) installations of
National Fire Protection Association railways for generation, transformation,
(NFPA) became the sponsor of the transmission, or distribution of power
NEC and continues to act in this used.
capacity.
AUTHORITY
PHILIPPINE ELECTRICAL CODE (PEC-
• This code has been approved and adopted
2017)
by the Board of Electrical Engineering and
PRC.
GENERAL PROVISIONS
• By virtue of authority vested the Board
Introduction
under RA 7920, it hereby direct strict
adherence to the provisions of this code.
PURPOSE:
>Practical Safeguarding of persons and ENFORCEMENT
property from hazards arising from the use of • This code intended for mandatory
electricity. application by the office of the Building
>Adequacy - Contains provisions that are Official/EE over electrical installations.
considered minimum requirements necessary • The Office of the Building Official/EE shall
for safety. have the responsibility of implementing, the
provisions of this code.
➢ FPN No. I: Hazards often occur • This code may require new products,
because of overloading of wiring constructions, or materials that may not yet
Quen - Electrical Engineering Utilities – Chapter 1 to 3

be available at the time this code is Americas (CANENA). The purpose of


adopted. CANENA is to facilitate and promote the
development of harmonized
MANDATORY RULES, PERMISSIVE electrotechnical codes and standards and
RULES, uniform conformity assessment methods.
EXPLANATORY MATERIAL AND
APPENDICES LICENSING
• Most municipalities have local laws that
• Mandatory rules-are those that identify require that any person who wishes to
actions that are specifically required or engage in the business of installing
prohibited and are characterized using electrical systems must be licensed. This
terms shall or shall not. means that the person must have a
• Permissive rules-identify actions that are minimum number of years of experience
allowed but not required, are normally used working with a licensed electrician and
to describe options or alternative methods. must pass a written test that deals with the
• Explanatory material- references to other electrical code being used and with
standards, references to related sections of methods of installations.
this code • By requiring a license, it is assured that the
- Information related to a code rule in the electrician knows, at a minimum, the code
form of fine print notes (FPN). requirements, and the installation
• Appendices - are not part of the procedures.
enforceable requirements of the PECI but
are included for information purposes only. PERMITS
• Most municipalities require that a permit be
MANUFACTURING STANDARDS issued before any electrical installations
may be made on a project. A complete
• Today, all electrical equipment, electrical construction drawing may also be
applications, and devices should meet required for review and approval by a plans
specific safety standards based on regular examiner before installation begins.
product testing. An approved product • Municipalities that require a permit will
meets minimum safety standards as have electrical inspectors who check the
determined by extensive testing by an project during regularly scheduled visits.
independent testing company or These inspectors will inspect the
organization. installation after the rough writing is in but
• Underwriters Laboratory, Inc. (UL), is a before it is concealed behind construction
not-for-profit product safety testing and materials.
certification organization. Is the leading
third-party certification org. in the United ELECTRICAL CONSTRUCTION DRAWINGS
States and has been evaluation products in • An Electrical Construction Drawings shows
the interest of public safety since 1894. the layout and design of an electrical
• The National Electrical Manufacturing installation.
Association (NEMA) is the leading trade • In order to convey the desired design
association in U.S. representing the information to the contractor, it is a MUST
interests of electrical manufacturing. to obtain complete set of construction
NEMA'S member companies drawings and specification of the building
manufactured products are used in the electrical system.
generation, transmission and distribution,
control, and end use of electricity. The following construction drawings and
• The Council for Harmonization of details are generally required:
Electrotechnical Standards of the 1. Complete plans and specifications of all
Nations of the Americas is known in most electrical work.
other countries in North and South America 2. Labeling criteria of all electrical
as Consejo de Armonizacion de Normas equipment.
Electrotecnicas de la Naciones de las
Quen - Electrical Engineering Utilities – Chapter 1 to 3

3. Lighting floor plans including electrical conductor or two ungrounded


circuit indicating conduit conductors.
and wiring sizes.
4. Power floor plans including electrical BUILDING SYSTEM VOLTAGES
circuits indicating conduit and wiring sizes,
equipment, and disconnected switches. SUPPLY VOLTAGE
5. Exit sign / means of egress lighting - expressed as a nominal voltage
location and power supply. because it varies slightly. Supply
6. Panel board Schedule. voltages can vary from about 90 to
7. Lighting Fixture Schedule 105% of the nominal voltage under
8. Symbol Schedule Diagrams. normal conditions. Variations from
nominal voltages are caused by a
Specifications and drawings should number of reasons, including variations
include requirements for: in load and changes in conditions in the
1. Race way and conduit with fittings. power supply system.
2. Wire and Cable.
3. Electrical boxes, fittings, and SYSTEM VOLTAGE
installation. The principal voltages available in a building.
4. Electrical Connections. - Medium and high voltage systems
5. Electrical Wiring Devices. carry ages cove 600 V may be used in
6. Circuit and Motor Disconnects. special cases such as for large
7. Hangers and Supporting Devices. signage.
8. Electrical Identification. - Low voltage systems that carry
9. Service Entrance and Details. voltages less than 600 V are typically
10. overcurrent protection used in buildings.
11. Switchboards - System voltage is expressed as a
12. Grounding nominal voltage because it varies
13. Transformers slightly for the reasons mentioned
14. Panel boards earlier.
15. Motor control centers
16. Lighting fixtures CIRCUIT WIRING

Symbols are specifically used in construction • Ungrounded (hot) conductor


drawings to represent lighting and power - is the initial current-carrying conductor
distribution components and equipment. in an AC system. The ungrounded
conductor is frequently known as the
Predominantly there is no specific symbol hot or live conductor because it feeds
universally accepted by the industry the current to the circuit.
symbols on the next slides are typically • Grounded (neutral) conductor
modified by the engineers consulting firm used - is required to complete a single-phase
on their drawings. circuit by connecting the ungrounded
(hot) conductor to ground. The neutral
*Insert Abbv. & acronyms, Electrical symbols conductor is a grounded conductor that
serves more than one circuit.
- Symbols are well-arranged on the • Grounding (ground) conductor
drawings in the form of a one-line - A third conductor that provides
diagram. supplementary but important grounding
- One line represents the conductors protection. The grounding conductor is
extending between two symbols not normally a current-carrying
regardless of the number of conductor, but is energized only on a
conductors. temporary, emergency basis when
- Generally, the single line without any there is a fault between an ungrounded
additional identification indicates a two- (hot) conductor and any metal
wire set of conductors either an associated to the electrical equipment.
ungrounded (hot) and grounded
Quen - Electrical Engineering Utilities – Chapter 1 to 3

COMMON BUILDING SYSTEM VOLTAGES 208 Y/120 Volt, Alternating Current, Three-
Phase, Four-Wire System (208Y/120 V AC,
A comparison of the number of conductors and 3-4W)
voltages between conductors on common • An older electrical service found in small
building system voltages is found in Table. The commercial buildings and high-rise
following is a description of the common buildings where three-phase motors,
building system voltages used in the United above about 12 horsepower, and
States and Canada. equipment such as large air conditioners
are used. It is not used very often in
120 Volt, Alternating Current, Single-Phase, industry because a 480 V system is more
Two-Wire System economical for largeCmotor loads.
(120 V AC, 1-2W)
• The most basic system voltage used. It was 480 Y/277 Volt, Alternating Current, Three-
used in the first electrical services to Phase, Four-Wire System (480Y/277 V AC,
buildings; however, nearly all have since 3-4W)
been upgraded. The service entrance • Is a common electrical service in most
provided to the switchboard or panelboard modern medium to large commercial
is by two conductors: one ungrounded (hot) buildings. The 480 V three-phase power is
conductor carrying 120 V and one neutral used to power specially designed heavy
conductor. Voltage measured between the machinery. High-voltage, 277 V fluorescent
ungrounded (hot) and neutral conductors is lighting and other single-phase devices
120V. have also been developed specifically for
120/240 Volt, Alternating Current, Single- use with this system. Large retail shopping
Phase, Three-Wire System (120/240 V AC, 1- malls, schools, grocery supermarkets, and
3W) office buildings may use this system for its
• The most common residential electrical 277 V fluorescent lighting capabilities,
service in use today. It is also used on a where fixtures are not located closer than 3
limited basis in light commercial buildings ft away from windows, platforms, and fire
such as small office buildings, churches, escapes.
and retail shops and stores. On a 120/240
V system, a 120 V branch circuit provides 480 Y/277 Volt, Alternating Current, Three-
electrical energy to convenience outlets, Phase, Four-Wire System (480Y/277 V AC,
small appliances, and light fixtures. 3-4W)
• When compared with the 208 Y/120 V
120/240 Volt, Alternating Current, Single- system, the 480Y/277 V system has
Phase, Three-Wire System (120/240 V AC, 1- economic advantages from the standpoint
3W) of equipment and conductors. Because a
• A 240 V branch circuit serves large given conductor can carry more than twice
appliances and equipment such as electric- the VA load at 480 V than at 208 V, the
resistance baseboard heaters, water savings in wire size for feeders can be quite
heaters, and air conditioning equipment. A significant with the 480Y/277 V system.
120/240 V branch circuit provides both 120 Additionally, the smaller current at 480 V
V and 240 V to an appliance such as range for any supply transformer capacity permits
and clothes dryer, controls, and light the use of protective devices with both
fixtures. Typically, small motors run on 120 smaller frame size and interrupting rating.
V and heating elements operate on 240 V. Both factors permit significant savings.
A grounding conductor runs continuously
through all branch circuits and serves as a 600Y/346 Volt, Alternating Current, Three-
safety circuit in case of a short- circuit. Phase, Four-Wire System (600Y/346 V AC,
3-4W)
• Is a less common electrical service in large
commercial and industrial buildings that is
used to power specially designed heavy
machinery. This system is designed like the
Quen - Electrical Engineering Utilities – Chapter 1 to 3

480Y/277 V AC, 3-4W described earlier, standard for the system voltage is actually
except that 600 V and 346 V are available 120/240 V.
in the circuit or feeder configurations.
Utilization Voltage
600Y/346 Volt, Alternating Current, Three- • A voltage drop occurs as current flows from
Phase, Four-Wire System (600Y/346 V AC, the service equipment through the branch
3-4W) circuit conductors to the outlet. On a
• The 600Y/346 V system has additional 120/240 V system, approximately 115/230
economic advantages from the standpoint V is available at the outlet of the Branch
of equipment and conductor sizing in Circuit. Measured voltage at an outlet or
comparison to the 208Y/120 V and connection is called the line voltage.
480Y/277 V systems. However, the 550 V Maximum Voltage
or 575 V equipment used on the • Wiring devices such as switches,
600Y/346V system is not as readily receptacles, relays and conductors are
available as the 460 V equipment used on designed to endure voltages slightly higher
the 480Y/277 V system. As a result, this than the utilization voltage. The highest
electrical service is used primarily in voltage to which a wiring device can be
industries where the 600Y/346 V systems exposed is known as the maximum
area tradition. voltage.

240/120 Volt, Alternating Current, Three- GROUNDED AND UNGROUNDED


Phase, Four-Wire System CONDUCTORS
(240/120 V AC, 3-4W) 1. Grounded conductor
• Is another fairly common electrical service 2. Neutral conductor
found in commercial and industrial 3. Load balancing
buildings where three-phase motors,
above about 12horsepower, and WHAT IS GROUNDED CONDUCTOR?
equipment such as large air conditioners • A Grounded conductor is defined as a
are used. On this three- phase, four-wire, system or circuit conductor that is
delta-connected system, the mid-point of intentionally grounded. When something is
one phase winding is neutral to provide 120 "grounded in accordance with the National
V between Phase X and ground and Phase Electrical Code (NEC), it is connected to
Z and ground only. ground of da conductive body that extends
the grounded connection.
240/120 Volt, Alternating Current, Three- • In a single branch circuit, a grounded
Phase, Four-Wire System conductor serves as the grounded leg of
(240/120 V AC, 3-4W) the circuit. It completes the circuit by
• There are 240 V between the windings of connecting the ungrounded (hot) conductor
each phase-that is, between Phases X and to ground. Thus, in circuit design, the
Y, Phases X and Z, or Phases Y and Z. grounded conductor is considered to be a
Between Phase Y and ground there is 208 current carrying conductor because it
V available. Phase Y is known as the high serves as a return path back to the circuit's
leg or wild leg because it has a higher power source.
voltage to ground than the other legs. • Grounded conductors are meant to keep
people from getting shocked when using
SYSTEM, UTILIZATION, AND MAXIMUM electrical devices or appliances.
VOLTAGES • It keeps the metal of the outlet from getting
hot and causing electrical shocks.
System Voltage
• is the target voltage entering the service Neutral conductor
panel. System voltage will vary slightly for • A neutral conductor performs the function
different buildings because of variations of of a grounded conductor for at least two
voltage available at the transformer and ungrounded (hot) conductors that have
voltage drop in the service conductors. The sources from different voltage phases,
Quen - Electrical Engineering Utilities – Chapter 1 to 3

such as on a multiwire branch circuit, conducting bus bar in the service


multiwire feeder, and the electrical service. equipment/main panelboard.
It is a grounded conductor that is shared - Grounding Conductor uses. It safely
between two or more ungrounded carries current to ground in the event of
conductors. Thus, a neutral conductor is a lightning strike or in cases of damage
frequently called a shared neutral or or defect in the circuiting, appliances,
common neutral. devices, or equipment. It also provides
safety feature to the wiring system.
Example:
The neutral load on a 120/240 V, three-wire 2 TYPES OF GROUNDING REQUIREMENTS
feeder circuit carries an unbalanced load
on the ungrounded conductors of 68 A on SYSTEM GROUNDING
Phase A and 58 A on Phase B. Determine - Is the part of a building electrical
the grounded neutral conductor load. system that provides protection against
Unbalanced load = 68 A - 58 A = 10 A electrical shock, lightning, and fires.
The grounded neutral conductor load is - It also relates to bonding (connecting)
10 A for these conditions. all building electrical system
components at the service entrance
Ungrounded conductors are also called the equipment at the neutral bus of the
hot wire. Although both the grounded and main panelboard or switchboard.
ungrounded conductors Com the earth, if an
accident occurs, like an appliance breaking, EQUIPMENT GROUNDING
you can get electrocuted if you come into - It refers to a grounding conductor or
contact with an ungrounded conductor. grounding path that connects the
noncurrent-carrying metal components
Load balancing is the practice of dividing of equipment.
loads as evenly as possible between the
ungrounded conductors on a multiwire circuit, BONDING
feeder, or service. A well-designed neutral is o Both Equipment and System
balanced so that under load little or no current grounding must be bonded. It
flows through the neutral conductor. On a accomplished by installing an
multiwire circuit, each ungrounded conductor additional grounding conductor
should carry loads equally. or by permanently joining metal
components in a circuit.
Example:
In a 120/240 V single-phase, three-wire The equipment-grounding conductor is a bare
circuit, if one ungrounded (hot) conductor conductor or a green- colored, insulated
feeds a 16 A load on one circuit and the conductor that connects (bonds) the outlet
other feeds a 4 A load on the other circuit, boxes, metallic raceways, other enclosures
the common neutral conductor carries 12 A and frames on motors, appliances, and other
to ground is the difference between the two electrical equipment.
loads.
DOUBLE INSULATION
SYSTEM AND CIRCUIT GROUNDING
Double insulation of an appliance or power
GROUNDING tool protects the user from electric shock by
- Grounding offers excess electricity the creating a nonconducting barrier between the
most effective and safest route from an user and the electric components inside the
appliance back to the ground by way of appliance or tool.
an electrical panel. Electrical grounding - Small appliances and power tools with
is a backup pathway that is generally double insulation are not required to
only used if a fault in the wiring system. have a grounding conductor- that is,
- Grounding Conductor is a continuous they are allowed to have a two-prong
conductor that connects the ground to plug.
the neutral bus bar and the grounding
Quen - Electrical Engineering Utilities – Chapter 1 to 3

- The primary difference between an areas (e.g., corridors, laundry rooms,


appliance with a three-prong plug and lobbies, and so forth).
an appliance with a two-prong plug is
the appliance casing. If an appliance COMMERCIAL/INDUSTRIAL SYSTEMS
casing is a good conductor (e.g., made - Large commercial and industrial
of metal), then it must have a grounding facilities have large and varied power
conductor and three-prong plug. requirements that necessitate different
types of systems for different building
THE BUILDING ELECTRICAL SYSTEM occupancies. Essentially there are so
• There are many possible electrical systems many variations that there is no
that can be used to distribute power in a standard type of system. In a typical
building. Typically, system design begins large building, electrical power is
with selection of a building system voltage, provided to a transformer located
which is dependent on sizes and types of outside the building or it enters a
the connected loads, utilities near the transformer vault located at the service
building, local codes and ordinances, level in the building.
economics, and safety.
Examples of Residential Electrical
Subtopics: Installations:
01 Residential Systems
02 Multifamily Dwellings Underground Electrical Distribution
03 Commercial/Industrial Systems - lines serving a residential development
being buried in a trench.
RESIDENTIAL SYSTEMS Underground Distribution Lines
- means a ground-mounted or roof-top - lines readied for connection to exterior
distributed solar generation system transformer.
designed and installed for residential Electrical Meter
applications, which is leased by, or - A 120/240 V-150 A, underground
subject to a power purchase agreement service entrance for a single- family
with, the owner of a residence for the residence.
purpose of generating Electricity for Electrical Meter for Multifamily dwelling
that residence. unit
- Underground service entrance for a
MULTIFAMILY DWELLING multifamily dwelling unit.
- is a single building that's set up Electrical Meter and Main Disconnect
accommodate to more than one family - A service entrance with the electrical
living separately. That can range from meter and main disconnect (below
a duplex, which has two dwellings meter and above circuit breakers).
within a single building, to homes or Circuit breakers are properly marked
small apartment buildings with up to on the panelboard face
four units. Panelboard
- Multifamily dwelling units (e.g., - A close-up view of the inside of the
apartments, condominiums), power is panelboard.
brought from a utility transformer to the Circuit Cables
building service equipment. It is then - Circuit cables can pass through floor
divided at a main distribution panel, and ceiling joists.
passes through Individual meters, and Exposed Lighting
is distributed to the individual dwelling - Exposed lighting fixture.
units through feeders. Exposed Box
- Each dwelling unit is served by a - An Exposed box in finished drywall.
separate panelboard located in the Receptacle and Faceplate
dwelling unit. Branch circuits extend - Unattached receptacle and faceplate
from a panelboard to feed outlets within Outlet
the unit. A house panelboard has - Covered convenience receptacle.
branch circuits that serve common
Quen - Electrical Engineering Utilities – Chapter 1 to 3

CONDUCTOR REQUIREMENTS Temperature Correction


Factor
CONDUCTOR MATERIALS ▪ ambient temperature is
- Copper and aluminum are the most the temperature of a
common conductor materials used in surrounding medium
building electrical wiring, although other (e.g., air, soil)
materials can be used. ▪ In the case of electrical
- As a general rule, solid copper wiring, it is the
conductors are used in small conductor temperature of the
sizes (up to about 8 AWG) because medium surrounding.
safety issues associated with aluminum ▪ As ambient temperature
are avoided and weight and cost are rises, less current
not significantly affected. generated heat is
- Stranded aluminum conductors larger needed to reach the
(above 30 A) circuits equipment, and temperature rating of
appliances are serving. the insulation.
Therefore, ampacity is
CONDUCTOR INSULATION governed by
- Conductors are covered with insulation contribution of ambient
to provide electrical isolation and heat.
physical protection of the conductor ▪ The ambient
material. temperature rating of a
- The type of insulation material conductor refers to the
determines the environment in which a normal temperature
wire or cable can be used safely. range in the
- Insulators like plastic and rubber are environment in which
used as a covering for electric wires. that conductor is to be
- This makes electric wires safer to used (e.g., the
handle because the insulator protects temperature of the
you from the current surrounding air, water,
or earth).
CONDUCTOR AMPACITY REQUIREMENTS ▪ Conductor ampacity is
- In building electrical systems, the adjusted for changes in
ampacity of a conductor may need to ambient temperature,
be adjusted with correction factors including temperatures
when conditions related to the below 78°F (26°C) and
temperature of the surroundings and above 86°F (30°C).
the number of conductors in a raceway ▪ A temperature
(e.g., conduit or cable) fall outside correction factor (F) for
normal operating ranges. conductors is applied
- Correction factors typically applied are based on the ambient
addressed in the following sections. temperature of the
- The succeeding tables contain conductor.
ampacities for various conductors, Bundling Correction Factor
conductor insulations, and sheathings. ▪ When several current-
- Ampacities provided in these tables are carrying contained in a
values based on a normal operating raceway or cable, the
temperature of 86°F (30°C). temperature of the
- Ampacity values for each conductor conductors will increase
size are for different equipment under normal loading
terminal (where connections of wiring conditions.
are made) temperatures. ▪ A bundling correction
- Heat generated at the equipment factor (FN) must be
terminals can damage the conductors if applied for four or more
it is not properly dissipated. conductors in a raceway
Quen - Electrical Engineering Utilities – Chapter 1 to 3

or cable installed in the • The basic formula for determining voltage


same raceway or drop (Edrop) in a two-wire AC circuit or three-
conduit or any bundled wire AC single-phase circuit with a
cables that are more balanced load at 100% power factor
than 24 in (0.63 m) long. (neglecting reactance) is based on the one-
way circuit length (L), in feet or meters;
Example conductor resistance (R), in 0/1000 ft or
Determine the ampacity of a Q/1000 m; and the circuit load (1) in
No. 8 AWG copper amperes:
conductor with THHN Edrop = 2 LRI / 1000
insulation that will be used • The percentage of voltage drop is
in a 120 V, two-wire circuit in determined by the ratio of voltage drop and
an industrial environment system voltage.
with an average ambient air
temperature of no greater *Insert example*
than 125°F (51.7°C). Three
similar circuits will be INSULATION COLOR CODING &
carried in a conduit. IDENTIFICATION MARKINGS
Assume that a shared • The insulation on small- and medium-size
neutral is not used. conductors is color coded for identification.
• Larger conductors requiring color
Solution: identification are marked at the terminal
From the main body of ends with a hand-painted stripe or colored
the text, the temperature tape wrapped around the conductor
correction factor for insulation.
THHN insulation in an • The grounding (ground) conductor
ambient temperature insulation must be color coded green,
range of 123° to 131°F green with one or more yellow stripes, or
(51° to 55°C) is 0.67. may be a bare conductor on small
From the main body of conductors in cables.
the text, the temperature
correction factor for The North American standard for color coding
more than 6 conductors is black or any color, except white, gray, and
in a raceway is 0.80. As green (ungrounded/hot); white
in Example 19.2, circuit (grounded/neutral); and green (ground).
conductors are sized The commonly used but not mandatory
according to 140°F color sequence of conductors serving
(60°C) for equipment single-phase circuiting is:
rated 100 A and less.
From Table, the
ampacity of this
conductor is 40 A.

*Insert continued solution*

CONDUCTOR VOLTAGE DROP


REQUIREMENTS
• In addition to ampacity requirements,
branch circuits and feeders should be
analyzed for voltage drop because of the
adverse effect it can have on performance
and operating life of appliances and
equipment.
• Total voltage drop in the feeders and
branch circuits should not exceed 5%.
Quen - Electrical Engineering Utilities – Chapter 1 to 3

CABLE, RACEWAY, AND REQUIREMENTS - are favorite raceway materials used to


protect conductors in all types of
Cable and Raceway Requirements buildings.
All building wiring must be enclosed in a cable, - it is available in straight lengths,
conduit, wireway, or raceway. therefore, must be bent to
• During installation: accommodate changes in direction.
✓conductors are snaked through conduit or ✔ bends must be made no
tubing, are laid in a wireway, or are smaller than the minimum
contained in cables, and radius specified by code, about
✔secured to structural framing. 6 to 8 times the conduit
• Care must be exercised in placing diameter. ✓conduit and tubing
conductors, as conductors and insulation can have up to four 90° bends
can be easily damaged. or the equivalent 360° total in
• Example: If a conductor is pulled through a one run.
tight conduit, it can stretch. (Deformation ✔ In runs requiring more bends,
caused by stretching reduces the cross- a pull box is added in the run to
sectional area of the wire, thereby reducing assist in pulling conductors and
its ampacity. This creates an unsafe to allow access.
condition because the conductor can ✔ Bends can be made at the
overheat). factory or at the job site for small
to medium conduits.
Conductors that are run through a raceway
must have sufficient open-air space to prevent Flexible conduit
overheating. ✔flexible metal conduit
• The number of current-carrying conductors ✔liquid tight flexible metal
that can run through a raceway is limited by
✔nonmetallic conduit
code.
- offers the advantage of easier
• A current-carrying conductor found in a
installation and can be salvaged easily
raceway is any ungrounded conductor or
when circuits are rearranged.
grounded conductor.
- It is used where mechanical protection
- Equipment grounding (bare or green-
is needed and easy relocation of
colored) and shared neutral conductors
equipment is desired. It can have up to
are not current carrying and are not
four 90° bends or the equivalent (360°
counted.
total) in one run.
These recommended values are less than
Conduit should be supported to prevent
those typically established as maximum
wearing away against structure and to avoid
values in the electrical code.
stressing its end fittings.
- They are recommendable because:
✓ Allow for less cumbersome - Rigid conduit and tubing must be
installation supported within 3 ft of a box or other
✓ Based on industry experience connection and at intervals of 10 ft
- They allow for future expansion. (about 3 m).
- Continuous, metal conduit can be used
CABLE AND RACEWAY REQUIREMENTS as the grounding conductor.
- Flexible conduit must be supported
Rigid conduit and tubing every 4 to 6 in (1.35 m) and within 12 in
✔rigid metal and nonmetallic (300 mm) of a box, except up to 36 in
conduit (about 1 m) is allowed at usage points
✔IMC where flexibility is required (e.g., a
✔EMT pump motor or air conditioner
✔ENT condensing unit) and 6 ft (about 2 m)
Quen - Electrical Engineering Utilities – Chapter 1 to 3

between a recessed light fixture and a - Bends are limited to no less than five times
box. the diameter.
- Conduit and cable should be installed away
Grounding conductor from locations where building occupants might
- IMC and EMT can be used as use it as a handhold or footstep.
grounding conductor if it is continuous - Drain holes should be provided at the lowest
and properly bonded. point in a conduit run.
- It is required for flexible conduit. - Drilling and culling burrs should be carefully
- It can be bare or insulated. removed to prevent damage to conductor
insulation.
Rigid nonmetallic conduit and tubing (ENT) - It must be supported every 4 to 6 in (1.35 m)
- Cannot be use as the grounding and within 12 in (300 mm) of a box, except up
conductor. to 24 in (600 mm) is allowed at points of usage
- Manufactured from thermoplastics that where flexibility is required (i.e., at a pump
have very high rates of thermal motor).
expansion (over 6 in for a 100°F - AC cannot be embedded in masonry,
temperature change per 100 ft/over concrete, or plaster.
300 mm in a 50°C temperature change
per 30 m). BOX/ENCLOSURE REQUIREMENTS
✓ Provisions must be made if it is
exposed to significant temperature - All electrical connections must be made
changes. in a protective enclosure such as
panelboard, junction, or device box,
Nonmetallic-sheathed cable (NM and NMC) fixture, or appliance.
- Permitted in single- and multifamily - Every switch, outlet, and connection
dwelling units and some other must be contained in an electrical box
buildings. and every lighting fixture must be
mounted in a box.
Restriction of use in: - All wirings must begin or terminate at a
✔Underground panelboard or in a box that is housing
switch, luminaire connection,
✔buildings that are more than three stories
receptacle, conductor junction, or some
above grade or in commercial garages
similar terminal fitting.
✔Motion picture studious - Junction boxes must be mounted so
✔Theaters that the blank cover plate is visible and
✔Places of assembly Elevator hoist ways readily accessible.
✔Other corrosive or hazardous locations - All electrical boxes must be adequately
secure to the building structure.
- NM and NMC must be supported every Any box can be used for any purpose.
4-6 (1.35 m) and within 12 in (300 mm) - There are no requirements that specify
of a box. that a certain type of electrical box be
installed for a specific purpose.
Armored cable (AC) - Typical trade practice:
Is for use in dry, indoor applications. o Octagon and round boxes for
lighting outlets o Normally
Restriction of use in: installed overhead for lightning
✓ commercial garages installation.
✔Motion picture studious o Rectangular and square boxes
for switches and receptacle
✔Theaters
outlets
✔Places of assembly The size and number of conductors to be
✔Elevator hoist ways installed in a box influences selection of type of
✔Other corrosive or hazardous locations box and box size.
Quen - Electrical Engineering Utilities – Chapter 1 to 3

- The more conductors and/or the circuit breaker), wiring, and one or
conductor size, the bigger the box must more outlets.
be.
- The capacity of a box, in cubic inches, Types of branch circuit
is determined by its length, width, and 01 Individual Branch Circuit
depth. - This of branch circuit serves one
- An increase in one or more of these receptacle or piece of equipment such
dimensions increases box capacity. as for a range, clothes dryer, large copy
o Some boxes are designed so machine, or other piece of machinery.
they can be ganged together to These circuits usually lead directly from
increase box capacity. the distribution panel to the appliance
- By convention, a conductor that runs and do not serve any other electrical
through the box is counted as one devices. The individual branch circuit is
conductor and each conductor that sometimes known in the trade as a
terminates in the box counts as one. dedicated or special purpose circuit.
The size and number of conductors to be 02 General Purpose Branch Circuit
installed in a box influences selection of type of - A branch circuit supplies two or more
box and box size. outlets for lighting and appliances. This
- Fixture wires and conductors that do type of circuit may be referred to as a
not leave the box, such as an internal lighting circuit; this is a carryover from
grounding wire, are not counted. the days when electricity was first used
- One conductor is deducted for one or in buildings and its predominant
more grounding conductors that enter purpose was lighting. There are usually
the box. a number of general-purpose branch
- Conductors in an electrical box must circuits supplying lights and outlets in
have sufficient open-air space to different rooms around a residence,
prevent overheating. commercial or industrial building.
These recommended values are less than 03 Appliance Branch Circuit
those typically established as maximum values - This is the type of branch circuit that
in the electrical code. supplies energy to one or more outlets
- They are recommendable because: to which appliances are to be
✓ Allow for less cumbersome connected. They supply fixed electric
installation equipment, such as refrigerators,
✓ Based on industry experience washers, and other large appliances
- They allow for future expansion. and electrical devices. Appliance
branch do not supply lighting fixtures.
BRANCH CIRCUIT REQUIREMENTS Appliance branch circuits cannot
exceed 20 A.
Branch circuiting 04 Multiwire Branch Circuit
A building electrical system consists of several - A branch circuit consisting of two or
circuits that extend out from the switchboard or more undergrounded (hot) conductor
panel board. A branch circuit is that portion of having a voltage between them and a
the building wiring system that extends beyond common neutral (grounded) conductor
the final over current protection device that is that is shared between the ungrounded
protecting the circuit. conductors such as in a 120/240 V
- It provides power from a circuit breaker three-wire circuit. Other branch circuits
or fuse in the panel board to single or specific to a particular occupancy may
multiple points of use called outlets. also be required. For example, the
- An outlet is a point in a wiring system following branches are required in
where current is taken to supply an health care facilities such as hospitals,
appliance, piece of equipment, or nursing homes, and dental facilities.
lighting installation. 05 Life Safety Branch Circuit
- A branch circuit is composed of an - An emergency system of feeders and
overcurrent protection device (fuse or branch circuit that provides adequate
power to patients and personnel. It
Quen - Electrical Engineering Utilities – Chapter 1 to 3

must automatically connect to an amperage (1), in amps (A) and volt-amps


alternate power source such as a (VA) in volts and amperes.
generator when the normal power
source is interrupted. All electric-resistant appliance or pieces of
05 Critical Branch Circuit equipment such as an oven, water-heater,
- An emergency system of feeders and and space-heater (no blower) and lights
branch circuits intended to provide generally have power (wattage) ratings
power to task illumination, special equal to their connected loading (VA
power circuits, and selected rating).
receptacles serving areas and
functions related to patient care. It must Design of a branch circuit involves sizing
automatically connect to an alternate conductors and over current protection
power source such as a generator (fuse or circuit breaker) that match the
when the normal power source is circuit rating.
interrupted.
In contrast, all electromechanical (having a
Split Wiring Receptacles motor) appliances or pieces of equipment
- Split wired duplex receptacles are fed generally will have a VA rating larger than
with a 120/240 V circuit having two the power (P) rating.
ungrounded (hot) conductors, a
grounded neutral conductor, and a General Purpose Circuits
grounding conductor.
- One grounded (hot) conductor feed General purpose circuits feed more than one
power to upper outlet and the and the outlet for lighting or other purpose. According
other ungrounded (hot) conductor to requirements, the rating of general-purpose
feeds the lower outlet. branch circuits must be 15 A, 20 A, 30 A, 40 A,
- The grounded (neutral) conductor is or 50 A. Maximum connected loads, voltages,
shared between both circuits. and other requirements for general purpose
- Split wiring allows power to be drawn circuit ratings are shown in Table 19.11.
from two separate circuits on one
duplex receptacle. General purpose circuits typically provide
power to convenience receptacles and lighting
BRANCH CIRCUIT RATING AND LOADS outlets with ratings of 20 A and 15 A because
of their ease of running and pulling the slender
The branch circuit rating is determined by conductors required (No. 12 AWG and No. 14
the rating of the overcurrent protection AWG copper, respectively).
device (fuse or circuit breaker) used to
protect the wiring in the circuit from General purpose circuits are typically
excessive current flow. limited according to what will be connected
to them:
The wiring in the circuit must safely deliver • When a general-purpose circuit feeds fixed
current to the connected load and the over appliances and luminaires or portable
current protection device protects this appliances, the total of the fixed appliances
wiring, so the circuit rating matches the should be no more than 50% of the branch
rating of the over current protection device. circuit rating.
• When portable appliances will be used on
The connected load on a branch circuit is a general-purpose circuit, the limit for any
the sum of all loads connected in a circuit. one portable appliance is 80% of the
It is found by totaling the connected volt- branch circuit rating.
amp (VA) load at each outlet connected to • In commercial applications, convenience
the circuit. receptacles are computed at a load of 1.5
A (180 VA) per receptacle and are limited
Design of a building electrical installations to 80% of the rating. This limits a branch
computations with power (P), expressed in
Watts (W); voltage (E), in volts (V);
Quen - Electrical Engineering Utilities – Chapter 1 to 3

circuit serving only receptacles to its rating These circuits serve two or more outlets to
divided by 11/2 A. which only appliances are connected. In
• A 20 A, 120 V branch circuit would have a dwelling units, two or more 20 A small
theoretical maximum of 2400 VA (20 A 120 appliance circuits for convenience receptacle
V 2400 VA), but it is common practice to outlets in the kitchen, dining room, pantry, and
limit the connected load to 80% of the breakfast room are required. These are in
circuit rating (e.g., 20 A 120 V - 80% 1920 addition to the other outlets required. Small
VA). appliance circuits can supply any refrigerators
• When the load on the circuit will be a and freezers, but not an electric range or oven.
continuous operating load (e.g., for store
lights), the total load should not exceed Tables 19.12 through 19.17 provide
80% of the circuit rating. The lighting load recommendations for circuiting common
must include any ballasts, transformers, or appliances and pieces of equipment.
autotransformers, which are part of the Manufacturers' data should always be used in
lighting system. Because a 15 A branch computations.
has a full rating of 1800 VA, the limit would
be 80%, or 12 A and 1440 VA (e.g., 15 A Continuous Load
120 V 80% 1440 VA). A 20 A, 2400 VA A continuous load is a connected load that
branch would be limited to 16 A and 1920 operates for 3 hr or more at any time. Many
VA of connected load. electrical loads fit within this category such as
circuits serving office and classroom lighting
Individual Circuits installations. When determining a circuit rating,
These circuits provide power to a single outlet most loads deemed continuous must have a
such as a receptacle serving a range, clothes circuit rating calculated at 125% of the circuit's
dryer, or copy machine. Although there are no connected load.
size limitations for an individual circuit rating,
appliances and equipment rated at above 25 A The intent behind the 125% factor is from
must be placed on a separate individual circuit the inability of the overcurrent protection
because of the 50% maximum single load device to handle a continuous load without
limitation in general purpose circuiting. Usually overheating; that is, most circuit breakers
connected loads above 20 A are placed on an trip if they carry their rated load for any
individual circuit. It is good practice to provide significant time period. In many
individual circuits for loads above 1500 W. installations, it is good practice for all
Motors above 1/8 hp should also be placed on connected loads not to exceed 80% of the
an individual circuit. individual circuit rating.

Generally, individual circuits are required Another way of looking at this is that the
for the following appliances and connected load on a continuous-load
equipment: circuit should not exceed 80% of the
•Kitchen range individual circuit rating. Thus, the maximum
•Oven continuous load on a 20 A circuit is 16 A
•Electric water heater (80% of 20 is 16).
•Microwave (built-in)
• Waste disposal There are several exceptions to application
• Furnace of the continuous-load multiplier. On
• Boiler circulating pump motor circuits involving electric space heating, the
• Dishwasher connected load is taken at 100% of the load
•HVAC air-handling unit even though it may operate for more than 3
•Large machinery hr at a time. Any branch circuit serving a
•Large equipment single motor or a device containing a motor
• Clothes washer should have an ampacity (amperage
• Clothes dryer rating) of not less than 125% of the motor's
full load current rating (this is the same as
Appliance Circuits saying that no motor can exceed 80% of
the branch circuit rating).
Quen - Electrical Engineering Utilities – Chapter 1 to 3

Branch Circuit Conductor Size The circuit rating is found by


On a branch circuit, conductor size is tied to algebraically manipulating the power
circuit rating. Generally, ungrounded (hot) and equation, PIE:
grounded (neutral) conductors in the circuit
must be sized so that conductor ampacity is at 1-P/E-2000 VA/120-16.7 A
least the branch circuit rating. The ampacity of
a conductor can be larger than the circuit rating A 20 A circuit breaker is the closest
but not smaller. For example, the No. 8 AWG circuit breaker available for overcurrent
copper conductor with THW insulation that will protection (see Chapter 18 for sizes
be used in a 120 V, two-wire circuit in an available). The rating for this circuit is
environment with an average ambient air 20 A.
temperature of no greater than 86°F (30°C)
has an ampacity of 50 A. It can safely carry up *Insert continuation of solution*
to 50 A without overheating.
DEVICE AND EQUIPMENT
Residential Branch Circuit Wiring REQUIREMENTS
Type NMB cable (e.g., Romex) is the most
widely used wiring method in residential Requirements for switches and receptacles
dwellings. NM cable must have 194°F (90°C) 01 Switches must be selected to match the
conductor insulation rating, which is load they control.
designated by a "B" on the cable sheath. 02 A panelboard-like enclosure called
Typically, AWG No. 12, and AWG No. 14 are lighting control panel is used huge lighting
used for receptacle and lighting circuits; AWG installations that require many switches.
No. 10/2 is commonly used for electric water 03 Receptacles must be selected to match
heaters; AWG No. 10/3 with ground for the appliance or equipment they serve.
electrical dryers and cooktops; and AWG No. 04 Ordinary convenience receptacles and
8/3 with ground or AWG No. 6/3 with ground switches are general wall mounted and
for ranges and wall mounted ovens. Type SER there are no specific
or other four-wire cable is used for electrical height requirements for switches and
ranges, cooktops, wall ovens, and clothes receptacles.
dryers. 05 Normally, switches are mounted
approximately 2 m) above finished floor
Example (AFF), convenience receptacles at 16 in.
A 120 V, 20 A, two-wire branch circuit feeds (400 mm) AFF and convenience
incandescent lighting that stays on for 3 hr receptacles in bathrooms and restrooms at
or more. Determine the maximum 44 in. (1.1 m) AFF, unless otherwise
continuous load permitted on this branch specified.
circuit. 06 Receptacles are customarily installed
with the lot oriented downward.
P= E*I 07 Unless the receptacle is controlled by a
P= E*I = 120V 20 A 1.0 = 2400 VA switch, the receptacle is frequently aligned
with the grounding slot upward.
A lighting installation containing 16 to 100 08 Ordinary convenience receptacles and
W incandescent luminaires on one circuit switches are general wall mounted and
will be operated approximately 10 hr per there are no specific height requirements
workday. Determine the circuit rating. for switches and receptacles.
09 In contrast to historical practice, it is
The 1600 W connected load is a recommended that receptacles be installed
continuous load because it operates for with the grounding slot oriented upward to
3 hr or more. The continuous load improve safety.
multiplier (125%) must be applied: 10 By orienting the grounding slot upward,
1600 VA-1.25-2000 VA the grounding pin would be the first blade
to contact the object, which would not
create a short-circuit.
Quen - Electrical Engineering Utilities – Chapter 1 to 3

OVERCURRENT PROTECTION Additional capacity may be warranted


• An overcurrent protection (OCP) device, a for future expansion.
fuse, or circuit breaker serves to limit
current levels in a conductor by interrupting SWITCHBOARD AND PANELBOARD
power when current limitations are REQUIREMENTS
exceeded. It prevents excessive heat from • Switchboards and panelboards can be
damaging conductors and related used as distribution equipment, at a point
equipment. downstream from the service entrance
• The voltage rating of a fuse or circuit equipment.
breaker must be equal to or greater than • Panelboards feeding lighting and
the voltage of the circuit in which the fuse convenience receptacles and having at
is applied. least 10% of the circuits rated at 30 A or
• The current carried (amperage) by the less are identified as lighting and appliance
electrical circuit or system protected by an panelboards.
OCP device must not exceed the maximum • In a single panelboard, not more than 42
current rating of the circuit breaker. overcurrent protection devices may be
• Furthermore, the amperes interruption used for protecting lighting and appliance
current (AIC) rating for circuit breakers branch circuits.
should be at least 5000 A and 10 000 A for • Power distribution panelboards feed other
fuses. panelboards (called subpanelboards),
motors, and transformers, but not circuits
- The fuse or circuit breaker must be powering lights and convenience
installed at a location in the circuit receptacles.
where the conductors receive power
(generally at the panelboard). When locating overcurrent protection in a
- The OCP device must protect the panelboard, it is important to balance the
ungrounded conductors in a circuit to anticipated load so that both bus bars are
ensure that power to the circuit is carrying a similar load.
interrupted by the OCP device.
- Lastly, the neutral (grounded) and In service equipment panelboards, the neutral
grounding conductors are not protected and equipment grounding conductors are
by overcurrent protection. bonded (connected) together. In
subpanelboards, the neutral is isolated from
FEEDER REQUIREMENTS ground.
1. A feeder is a set of conductors that
carry comparatively large amount of In general, a fuse or circuit breaker must be
power from the service equipment to a installed at a location in the circuit where the
second panelboard, called a sub panel conductors receive power. Generally, this
board, where branch circuits further location is in the panelboard or load center
distribute the power. before the conductors leave to convey current
2. Feeders designed to provide sufficient to the outlets in the circuit.
power to the branch circuit they supply
so feeder conductor size is based on SERVICE ENTRANCE EQUIPMENT
the maximum load to be supplied by the
feeder. Service Equipment
3. Feeders should be capable of carrying Large enough to supply the compute load of
the amount of current required by the the building or area of the building being
load, plus any current that may be served.
required in the future. - All service equipment and electrical
4. It is not likely that all connected loads panels shall have clear area 30 in (0.75
on a feeder will be in operation at a m) wide and 36 in (0.9 m) deep in front.
specific time. Thus, feeder conductors - An 8 ft (2.4 m) clearance is required
do not need to be sized to carry the total above low-sloped (less than 4 In 12
connected load served by the feeder.
Quen - Electrical Engineering Utilities – Chapter 1 to 3

slope) rooflines. A3 ft (0.9 m) clearance construction to be tamper-resistant


is required for steep- sloped roofs. receptacles.
Commonly used aluminum conductors • Products such as plastic plug-in inserts and
- RHW, THWN, THIN, XHHW, and USE. wall plates with contact shutters are
Residential service equipment available For tamper resistance, but do not
The most common sizes of residential service meet these requirements.
equipment are 100, 125, 150, and 200. • There are many other settings where
children may be at risk, including; day care
Service Equipment centres, children's play areas, elementary
- It is also necessary to bury and nursery schools, doctor's offices and
underground conductors sufficiently lobbies, and retail establishments featuring
below grade to reduce the hazard of children's attire or toys.
unintentional contact. • All tamper-resistant receptacles must have
- The required depth of burial can be either the words "tamper resistant" or the
found in the Code. letters "TR" (minimum 3/16 in or 5 mm
- Minimum earth cover varies from 6 to high) on the device as a clear indication
24 in (150 to 600 mm). that this is a tamper-resistant receptacle.

TRANSFORMER REQUIREMENTS GROUND FAULT CIRCUIT PROTECTION


01 Transtormer combinations, such as REQUIREMENTS
wye-wye (Y-Y), delta-delta (-), delta-wye (- • The NEC introduced requirements for use
Y), and we-delta (Y-) are available for use of GFCI in residences in 1973 when it
in buildings. required GFCI protection of outdoor
02 The first symbol (Y or) indicates the convenience receptacles within 6 & 1/2ft or
ration of the primary es and the second the (2 m) of grade level. In residential
configuration of the secondary windings. Installations, GFCI protection is required at
03 A 480 V primary, 208 VY/120 V all 125 V, single phase 15 A and 20 A
secondary, three-phase transformer is a outlets in the locations listed below.
popular unit used in large commercial • The NEC introduced requirements for use
buildings and Industrial facilities. of GFCI in residences in 1973 when it
04 From a four-wire 480/277 V supply, 277 required GFCI protection of outdoor
V lighting and 480 V heavy equipment can convenience receptacles within 6 & 1/2ft or
be powered before being stepped down to (2 m) of grade level. In residential
a 208 Y/120 V, three-phase, four-wire Installations, GFCI protection is required at
system for convenience receptacles and all 125 V, single phase 15 A and 20 A
light-duty equipment and appliances. outlets in the locations listed below.
Primary and secondary conductors are • The requirements do not apply to
sized to carry 100% of the ampere rating of equipment rated at 240 V (e.g., baseboard
the overcurrent protection. The equipment- heater, room air conditioners, welding
grounding conductor size is based on the receptacles, or other outlets that are not
ampacity of the phase conductors. rated at 125 V).
OCCUPANT PROTECTION The NEC introduced these requirements
REQUIREMENTS beginning in the years listed:
• Outdoor convenience outlets within 6 & 1/2
Temper-Resistant Receptacle ft or (2 m) of grade level (1973 edition) and
Requirements revised to include all exterior convenience
• The NEC has required tamper-resistant outlets (1993 edition)
receptacles be installed in all 125-V, 15- • Bathroom convenience outlets (1975
and 20-A electrical receptacles in hospital edition)
pediatric areas for nearly three decades. • Readily accessible convenience outlets in
Recently, the NEC introduced garages (1978 edition), except where not
requirements for all 125-V, 15- and 20-A readily accessible such as outlets
electrical receptacles in new residential
Quen - Electrical Engineering Utilities – Chapter 1 to 3

dedicated to an overhead door opener or the convenience receptacle or portable-type


freezer. GFCI protection is highly recommended.
• Convenience outlets within 6 ft (1.8 m) of
kitchen sink (1987 edition) and revised to ARC FAULT CIRCUIT PROTECTION
include all kitchen convenience outlets that REQUIREMENT
serve countertops, including islands (1996 • Future editions of the Code will likely
edition) but not those serving fixed kitchen expand coverage to include commercial
appliances (e.g., range and oven) and the and industrial applications such as use in
refrigerator or freezer. fire station sleeping areas, military housing,
• Convenience outlets in unfinished hospitals, outpatient clinics, rest homes,
basements and crawl spaces, except retirement homes, and in other locations
laundry (1990 edition) where extension cords or cord- connected
• Convenience outlets within 6 ft (1.8 m) of equipment may be used and where the
laundry, utility room, or wet bar sink (1993 general occupancy may be at risk from arc
edition) faults.
• Buildings wired with solid aluminum
Other locations requiring GFCI protection conductors used in the late 1960s and early
on 120 V, single-phase 15 A and 20 A 1970s are prone to poor connections. Such
outlets include: building electrical systems can also be
Commercial kitchens retrofitted with AFCI protection to identify
Restrooms in commercial, industrial, faulty connections.
and in any other non-dwelling type
buildings ELECTRICAL SYSTEM DESIGN
Receptacles with grade-level access
and at rooftop locations Preliminary Design Guidelines
Commercial garages • Ideally, the electrical designer should be
Elevator pits involved in the of the project from the very
Agricultural buildings beginning.
Aircraft hangers • The electrical designer is the person who
Wet locations in health care facilities could best discuss the electrical
Boathouses, marinas, and boatyards component of project planning with the
Receptacle outlets on roofs (except power company.
dwelling units) • Checking of all of the utilities (whether
Circuits to resistance (impedance) sewer, water storm sewer, natural gas
heating units such swimming pool, lines, and so forth) is needed early in the
spa, hot tub, de-icing and snow- design stage.
melting heaters.
Receptacle and lighting outlets near Before actually beginning the design layout
swimming pools, spas, hot tubs, and of the project, the designer will need to
fountains accumulate certain information:
Receptacles in temporary locations 1 Determine whether electrical service is
(i.e., on construction sites, available at the site, and what type of
carnivals, circuses, and fairs) system voltage is available (e.g.,
120/240 V AC,, 10-3W, 208 Y/120 V
Some types of equipment (e.g., appliances AC, 3-4W, and so forth)
with large motors) have inherent leakage 2 Obtain a list from the owner of all the
current levels that exceed the standard trip types and locations of equipment and
setting of a GFCI. This will cause nuisance appliances to be used in the building
tripping of GFCI devices. that will require electricity.
3 Work with the architectural designer to
GFCI circuit breakers may be added in panel best locate all the electrical equipment
boards of older buildings to replace ordinary and appliances on the floor plan.
circuit breakers. For homes protected by fuses, 4 Review with the architect where the
basic mechanical equipment (e.g.,
Quen - Electrical Engineering Utilities – Chapter 1 to 3

HVAC and plumbing), the service or three-way switching) at each


entrance equipment, the power and principal entrance. If this
lighting panels, and the conduit or cable recommendation would result in the
will be located. placing of switches controlling the
5 Discuss with the owners any future same lighting installation within 8 ft (2.5
plans for changing or 5 expanding the m) of each other, multiple-switch
facilities (e.g. remodeling, constructing controls may not be required.
additions or other buildings, future - Wall switches should be located at the
equipment requirements) and anything lockset or latch side of doors or at the
else that could potentially affect the traffic side of arches, and within the
size and location of the electrical room or area where the lighting outlets
service. are located.
- Convenience receptacles in living
BASIC DESIGN CONSIDERATIONS rooms, bedrooms, dining areas, and
Experience guides the designer to a solution other habitable spaces should be
that best suits the need of the building placed so that no point along the floor
occupant. The designer achieves a solution by: line in any usable wall space is more
• Observing and evaluating existing than 6 ft (1.8 m) from an outlet in that
installations and adapting them to meet space. The intent is to eliminate cords
the project requirements. having to pass over hot or conductive
• Applying electrical systems theory surfaces wherever possible.
• Applying Code requirements
Design of an electrical system begins with the Building Exterior
layout of all outlets or outlet connections. See • One or more lighting outlets should be
Figure Symbols are used to indicate the located at or near all exterior entrances.
approximate location of convenience Outlets should be switched or
receptacles, lighting outlets, and special automatically controlled.
purpose outlets. • For each single-family dwelling, at least
one duplex receptacle shall be installed
*Insert symbols* outdoors to be readily available from
ground level.
DESIGN GUIDELINES FOR COMMON • One or more outlets may be required for
SPACES exterior equipment (e.g., swimming pool
pump, well pump, and so on).
Convenience Outlets and Switches
- The number and type of lighting outlets Common Areas and Living Rooms
should be fitted to the various seeing • Outlets for ambient and task lighting should
tasks. be provided. General illumination outlets
- All convenience receptacles on 15 A should be wall switch controlled.
and 20 A general purpose circuits • Convenience receptacles in living areas
should be of the grounding type, should be placed so that no point along the
minimizing the hazard of shock from floor line in any usable wall space is more
short circuits. than 6 ft (0.6 m) from a receptacle outlet in
- GFCI protection should be provided on that space.
convenience receptacles where • One or more receptacles for entertainment
required by local code (e.g., where the equipment should be provided at
occupant is exposed to water). bookcases, shelves, or other suitable
- AFCI protection should be used on locations.
convenience receptacles where • When general illumination is to be provided
required by local code (e.g., in bedroom from portable lamps, then at least two
circuits). separate wall-switched plug-in positions
- All rooms that have more than one should be provided.
entrance should be equipped with • An outlet for a fireplace may be required.
multiple-switch controls (e.g., two-way
Quen - Electrical Engineering Utilities – Chapter 1 to 3

• A smoke detector/alarm on a 120 V circuit other outlets. Where the 20 A circuit


should be considered. supplies only a single bathroom, it can
supply power to outlets for other equipment
Food Preparation/Kitchen/Cooking Areas within the same bathroom (i.e., lighting
• Lighting design should provide for ambient outlets or an exhaust fan).
and local/task illumination of the work • A wall-switched or timer-operated, built-in
areas, sink, range, counters, and tables. ventilating fan capable of providing a
• Special purpose receptacles should be minimum of 8 to 10 air changes per hour
provided for all fixed appliances (e.g., per water closet (50 cfm/water closet)
range, built-in microwave, exhaust hood, should be provided where no natural
dishwasher, trash disposal unit, waste ventilation through windows is included.
disposal, and so on). • Wall switches should be located so as not
• At least two 20 A small appliance circuits to be readily accede while standing in the
for kitchen countertops should be provided. tub or shower stall.
Outlets on these circuits should serve only
the kitchen, pantry, and/or dining room Laundry Areas
areas. • Outlets for fixed lights should be installed
• Convenience receptacles serving to provide illumination of work areas, such
countertop areas (e.g., except behind as laundry tubs, sorting tables, washing,
refrigerator and those serving fixed ironing, and drying centers. Lighting outlets
appliances) should be GFCI protected. It is should be wall-switched controlled.
recommended that receptacles serving • In the laundry area, one 20 A receptacle for
countertop areas be split wired. the clothes washer and a special
• A smoke detector/alarm on a 120 V circuit receptacle for the clothes dryer are
should be considered. required.
• One outlet and one switch for a ventilation
Sleeping Areas/Bedrooms fan should be provided.
• General illumination should be provided • A smoke detector/alarm on a 120 V circuit
from either ceiling or wall outlets, controlled should be considered.
by one or more wall switches.
• A convenience receptacle should be Halls/Corridors
placed on each side and within 6 ft (1.8 m) • Ceiling fixtures should be installed for
of the centerline of each probable individual proper illumination of the entire area with
bed location. particular attention paid to irregularly
• All 120 V branch circuits that supply outlets shaped spaces.
in dwelling unit bedrooms must be • Convenience receptacles in hallways
protected by an AFCI device. A smoke within a dwelling unit should be placed so
detector/alarm must be provided on a 120 that no point in the hallway shall be more
V circuit and should be AFCI protected. than 10 ft (1.0 m) from a duplex receptacle.
• In master bedrooms, outlets should be Each hall over 25 ft2 (2.3 m2) in floor space
considered for a television and should have at least one receptacle.
entertainment equipment (e.g., DVD/VCR • In entrance foyers, convenience
player). receptacles should be placed so that no
• In master bedrooms, an outlet for a point along the floor line in any usable wall
fireplace may be required. space is more than 10 ft (3.1 m) from a
receptacle in that space.
Bathrooms/Restrooms
• Lighting sources at the mirror should be Stairways
capable of illuminating both sides of the • Fixed wall or ceiling lighting outlets should
face. be installed to provide adequate
• At least one GFCI-protected receptacle illumination of each stair flight.
within 3 ft of the outside edge of each • Outlets should be so arranged that the stair
lavatory basin should be provided. The system can be fully illuminated from either
circuit serving bathrooms should have no floor.
Quen - Electrical Engineering Utilities – Chapter 1 to 3

• A smoke detector/alarm on a 120 • A minimum of two dedicated convenience


considered at the top of the stairs. receptacles on separate circuits is
required. Additional duplex convenience
Utility Rooms receptacles should be placed at 6 ft (1.8 m)
• Lighting outlets should be placed to intervals around the perimeter.
illuminate furnace/boiler area and work • Rooms should be located away from
area. At least one lighting outlet should be sources of electromagnetic interference
wall-switch controlled. (e.g., transformers, motors, x-ray
• Convenience receptacles should be equipment, induction heaters, arc welders,
provided. Outlets should be provided for radios, radar systems, and so forth).
each piece of mechanical equipment • Emergency power should be considered
requiring electrical connections such as the and supplied.
boiler, chiller, furnace, water pump, or • A smoke detector/alarm on a 120 V circuit
compressor. should be considered.
• A special purpose outlet may be required
for electric resistance water heater, and/or DESIGN EXAMPLE
an electric-resistance furnace. An example of system design of a 61 ft-6 in by
36 ft., single-story, single-family residence is
Shops/Garages used in the explanation. This residence
• Lighting outlets should be placed to contains general lighting outlets), equipment,
illuminate the work areas. Task lighting and appliances, including what follows: water
should be provided above workbenches. heater, clothes dryer, dishwasher, range,
Lighting outlet should be wall-switch waste disposal, air conditioner, and garage
controlled. door opener.
• At least one duplex receptacle should be
provided for each space in a garage or CIRCUIT DESIGN
carport. 1.) Locate the receptacles on the floor plan
• Convenience outlets should be provided at following the guidelines provided. GFCI
workbenches. In garages or near water, and AFCI-protected receptacles should be
these outlets should be GFCI protected. located following the requirements
• Outlets should be provided for automatic specified.
overhear (garage door operators in the 2.) Locate all Locate all appliance and
ceiling above each bay equipment outlets on the floor plan using
• Special purpose outlets should be provided the appropriate symbols for the various
for special equipment such as air receptacles required.
compressors, welding equipment, tire - This process calls for coordination with
hanger, dust collection equipment, the architectural designer because each
machining equipment anon. Check with appliance and piece of equipment must be
owner on equipment voltage requirements, known to locate the outlets properly.
load, and placement. - The electrical designer should also check
• A smoke detector/alarm on a 120 V circuit the number of appliances or equipment
should be considered. required. The Electrical designer will need
to know the specified voltage and
Storage Rooms/Closets amperage requirements for equipment and
• Generally, one lighting outlet for each large appliances.
closet or storage room should be provided. 3.) Locate the lighting fixtures, using the
appropriate symbols to represent each.
• Wall switches or automatic door switches
- The electrical designer should make a
are preferred, but pull switches are
list of types of luminaires and the load
acceptable.
requirements.
- This list will be used later when
Electrical/Telecommunications Closet
grouping circuits. It may also be
• Lighting outlets should be placed to
included in the specifications or on the
illuminate the area.
Quen - Electrical Engineering Utilities – Chapter 1 to 3

drawings as a luminaire (light fixture) • This load includes the total of all general
schedule. lighting, appliance, and equipment loads in
- The architectural designer or even the the building.
building owner may decide the fixtures • The demand load allowed by the code
that are to be used, often with takes into account that all of the electrical
assistance of the electrical designer. connections will not be in use at one time
4.) Lay out the switches required to control 1. Compute the general lighting load. This is
the lights, appliances, equipment, and any calculated for all types of occupancies based
desired receptacles. The discussion of on the unit load given in the table (in watts)
switches outlines where they are most times the square footage of the building
commonly used, and the symbols used. • The minimum general lighting load, based
5.) Locate the panelboard in a convenient on the specified 3 VA/ft2 for residence:
location. The location must be accessible table (in watts) times the square footage of
(e.g., not in a closet or storage room, the building
unless dedicated). Follow the requirements • 3 VA ft x 2214 ft² = 6642 VA
outlined earlier. 2. Compute the appliance and laundry circuit
6.) Layout circuiting for large appliances load. Code requires at least two 20 A appliance
and equipment served by an individual branch circuits for the kitchen. The load is
branch circuit. Examples of individual based on 1500 VA for each appliance branch
branch circuits would be circuits from the circuit in the kitchen. In addition, one 20 A
panelboard to a dishwasher (120 V), circuit is required for laundry room appliances.
electric clothes dryer (120/240 V), an • For the residential system example, this
electric oven or range (120/240 V), or an results in a total of three 20 A branch
electric water heater (240 V). circuits for appliances:
7.) Layout circuiting for lighting and Appliance and laundry load = 3 circuits x
convenience receptacles on general 1500 VA = 45000 V
purpose (lighting) branch circuits. Usually
15 A and 20 A general purpose branch SERVICE ENTRANCE DESIGN
circuits are used for convenience The service entrance conductors and
receptacles, luminaires, and small equipment are designed based on the
appliances. computed total demand load.
- The designer must comply with code
requirements. In practice, a good designer 1. The minimum service entrance size is found
tends to be a little more conservative. by dividing the demand load for the building by
Because more and more small appliances the voltage serving the building. Most
and equipment are being purchased and commonly, 240 V service is used. For the
connected to receptacles, the designer residential system example, the total demand
must anticipate future requirements... load of 33 175 VA is divided by the 240 V
8.) Lay out the panel circuits, either on the service for a mini- mum service entrance of 143
drawing or in a table. A:
- In large designs, with more than one
panel, this provides the electrician with a minimum service entrance = 33 175
schedule of what circuits will be served VA/240 V = 138.2 or 138 A
from what box. Although a panel board
layout is not often done for a residence, it 2. The next step is sizing the service entrance
is helpful to both the electrician and the conductors and any conductors between the
designer if one is included. For commercial service equipment and the branch overcurrent
projects, a panel layout is almost always device (circuit breaker or fuse). The feeder size
included. is based on the computed demand load.
LOAD COMPUTATIONS For the residential system example,
• Load computations involve computing the using XHHW 175 C 167 F) aluminum
demand load for a building system or a service entrance conductors and a 150
distribution system extending from a A load, as calculated:
panelboard.
Quen - Electrical Engineering Utilities – Chapter 1 to 3

150 A fender demand load, 3/0 AWG


XHHW aluminum

3.The size of the neutral conductor may be


determined as 70% of the demand load
calculated for the range plus all other demand
loads on the system.

For the residential system example, the


neutral feeder demand load would be:
Range load (8000 W x 70%) =
5600 VA
All other demand loads =
25.175 VA
Neutral demand load = 30 778
VA

Neutral net computed demand load =


30 778 VA/240 V = 128.2 A
Quen - Electrical Engineering Utilities – Chapter 1 to 3

CHAPTER 2 -the steam is produced by heating water through


BUILDING ELECTRICAL MATERIALS burning of coals, all, natural gas or heat coming
from nuclear reaction.
AND EQUIPMENT The most economical power stations typically
generate power continuously, unless off line for
2.1 POWER GENERATION AND
maintenance or repairs. During periods of heavy
TRANSMISSION
demand, less-economical power stations are
brought on-line. If one generating station is off- line
Nearly all of the electrical energy consumed is
or fails, another is brought on line to take over the
generated, transmitted and distributed by large
load.
public or privately owned utility companies.
Consumers purchase electricity from these utility
▪ For economical transmission, a step-up
companies, either directly or through a cooperative
transformer steps up the voltage to above
association.
39 KV, usually between 115 kV to 765 kV
▪ Ultra high-voltage transmission is now
Electricity is usually produced at a power station
being explored for equipment and lines
and is conveyed through a transmission system of
rated for 1100 kV.
overhead metal cables supported on high towers.
▪ Distribution line voltages are generally
At the power station, electricity is usually generated
4160 V, 4800 V, 6900 V or 13,200 V,
in the range of 2.4 to 13.2 kV.
although higher voltages can be made
available if loads are large enough.
POWER STATION
▪ Power transmission at high voltages
-is an industrial facility that house equipment to
requires less amperage, and
generate electricity from primary energy.
subsequently, there are lower power losses
in the transmission lines.
Most power plants use one or more generators that
convert mechanical energy into electrical energy in
POWER SUBSTATIONS
order to supply power to the electrical grid for
society's electrical needs.

Efficacy rate of converting heat energy to


mechanical energy:
40% fossil fuel plant
30% nuclear plant

GENERATORS
-a mechanical device that converts mechanical
energy into electrical energy

▪ Power substations are small facilities in


ARMATURE
fenced yards that contain transformers,
-rotated by the generator, is a shaft with conductor
switches and other electrical equipment.
windings wrapped around an iron core, through
▪ created to avoid danger of high-voltage
stationary magnetic field, to produce current flow.
power transmission in populated areas.
▪ to reduce or step down the transmission
TURBINE
voltages to safer distribution levels.
-a rotary engine, is connected to the generator and
drives the rotation of the armature shaft.
POWER UTILITIES
-generally generate, transmit, and distribute three-
STEAM TURBINE
phase AC power. Single-phase AC power is
-high-pressure steam moves through turbine thus
obtained from ONE phase of a set of three phase
rotating the discs attached to turbine shaft.
line.
Quen - Electrical Engineering Utilities – Chapter 1 to 3

▪ Utilities use highest transmission and


distribution voltages consistent with safe
and economical use. It is very economical
to carry power at high voltage because
it requires smaller conductors. However,
high voltages introduce safety clearance
hazards, so high voltages are reserved
for use in unpopulated areas or special
applications.
OVERHEAD SERVICE ENTRANCE
CONDUCTOR (SERVICE DROP)
The relationship between the generated.
▪ extend from a pole-mounted distribution
Transmission, and distribution voltages and
transformer to the building's service
associated current (amperage) for a 2000 kVA load
entrance
and a power factor of 1.0.
▪ the penetration is sealed with a roof boot to
keep from leaking.
▪ Connections at the weatherhead is
extended at least 2 to 3 feet above the
roofline and at least 10 feet above the
ground.

2.2. BUILDING ELECTRICAL SERVICE


EQUIPMENT

SERVICE ENTRANCE UNDERGROUND SERVICE ENTRANCE


- passageway where wires are connected to the CONDUCTORS (SERVICE LATERAL)
load side of the meter enters the house or building. ▪ are direct burial cables and usually has
three conductors: two hot wires and a
▪ commonly used to supply power to your neutral.
home-carrying power from the ▪ The feeder wire is attached to the
transformer through a metering device to transformer and is fed through a PVC
the building's service disconnects conduit sleeve attached to the utility
company's power pole.
▪ comprises three cables (two hot and one ▪ It should be trenched at least 4 feet
neutral) that run from the utility lines to the underground so to avoid damage.
point of attachment at the weatherhead,
then down an entrance cable or conduit to SERVICE ENTRANCE EQUIPMENT
the meter socket. In this type of system, the -receives the service entrance conductors. The
utility company's equipment ends at the service equipment includes measuring power
point of attachment to the house. through an electric meter, a method of cutting off
power, and overcurrent protection devices (circuit
breakers or fuses) that protect the service entrance
conductors.

ELECTRIC METER
-an instrument that is used by the utility company to
measure and record electrical energy consumed.
Quen - Electrical Engineering Utilities – Chapter 1 to 3

▪ as the current flows, the disc rotates, and


pointers on dials revolve to record the
amount of power used in kilowatt-hours
(kWh).

PANELBOARD
FEED-THROUGH METER -Wall-mounted, single unit of one or more metal
-used in building services rated up to about 400 A cabinets, including buses, automatic overcurrent
-this meter is a small electric motor protection devices (fuses or circuit breakers).
-with a speed that is proportional to the power ▪ Equipped with or without controlling
consumed switches for light, heat, and power circuits,
▪ It consists of a sheet of a metal box, a
CURRENT-TRANSFORMER (C/T) cabinet, and a cover that encloses and
-used in building services rated above about 400 A protects the interior section containing
-measure amperage through each ungrounded vertical buses used to distribute power.
(hot) conductor. ▪ It may be referred to as a power panel or
-housed in an enclosure called a C/T cabinet that is load center typically used in residential
part of the service entrance equipment applications.

SERVICE DISCONNECT
-a required part of the service entrance equipment
allows electrical service from the utility company to
be switched off so that power is disconnected to the
building installation. It is a set of fuses or a circuit
breaker that protects the service entrance
conductors.
TRANSFORMERS
SWITCH BOARD -Usually, it works as a regulator to change the
-a large cabinet or assembly of metal cabinets with voltage, current and phase of electrical power
electrical switches and devices transmitted and distributed from the primary power
connects/disconnects electric circuits, either source to a specific substation.
manual or automatic. ▪ A building transformer is rated in kVA.
Commonly from 3, 6, 9, 15, 25, 30, 37.5,
▪ Generally distributes power to 45, 50. 75. 112.5, 150, 225, 300, 500, 750,
transformers, panelboards, control 1000, 1500 kVA, and larger.
equipment, and ultimately to individual
system loads. EVERY TRANSFORMER COMES WITH A
▪ Contains overcurrent protection devices NAMEPLATE THAT TYPICALLY IDENTIFIES:
(fuses or circuit breakers) and instruments
designed to neutralize/divide a large kVA
amount of electrical power into suitable Primary and secondary voltage
levels for other electrical equipment. Impedance (if 25 KVA or larger)
Required clearances (if it has ventilating
-Floor mounted, rated for current levels of 1200 to openings
6000 amperes (A), and voltages below 600 volts
(V). STEP-DOWN TRANSFORMER
-has a secondary voltage that is less than its
primary voltage.
Quen - Electrical Engineering Utilities – Chapter 1 to 3

-typically used in buildings to reduce building


system voltages to useable levels

STEP-UP TRANSFORMER
-one with a secondary voltage that is greater than
its primary voltage.
DELTA-CONNECTED TRANSFORMER (A)
▪ windings are connected in series, forming a
TRANSFORMERS HEAT HAZARD
triangle, thus resembling the Greek letter
▪ Heat build up prematurely deteriorates a
Delta (A). only a single voltage level is
transformer. The transformer's desirable
available: the phase-to- phase voltages.
operation level is at only 20°F (11°C):
▪ Obtaining other voltages can only be done
above this rate will cut the transformer's life
using step-up or step-down transformers.
by half.
▪ It is caused by internal losses from loading,
high ambient air temperature, and solar
radiation in exterior locations

VARIOUS HEAT REDUCTION FEATURES


• small transformers use air cooling by ventilation WYE- CONNECTED TRANSFORMER (Y)
while larger ones are liquid-cooled -has three independent transformer windings
• ventilated dry-type transformer has its coils and connected at a common point, called a neutral or
core in a gaseous or dry compound. star point.
• Liquid-immersed transformer has its core and coils - the angular displacement of each winding
immersed in an insulating liquid. is at 120°, resembling a Y-shaped physical
arrangement of the winding.
SINGLE-PHASE TRANSFORMER
-has a single primary winding and single
secondary winding

-A 7200/240/120 V AC is a single-phase
transformer commonly used in most
residential and small commercial DELTA-WYE (A-Y) TRANSFORMER
applications. -an electrical device that converts three-phase
electric power without a neutral wire into three-
-A 7200 V, two-wire power is transformed phase power with a neutral wire.
and stepped down to a 120/240 V AC, -Additional transformer combinations such as wye-
three-wire system. wye (Y-Y), delta- delta (A-A), and wye- delta (Y-A)
are available.

▪ Historically, standardized system voltages


related to delta transformers' use were
based on multiples of 120 V (e.g.. 120 V.
240 V, 480 V, 7200 V). Voltages that have
the 1.732 as a multiplier are wye
THREE-PHASE TRANSFORMERS connections (e.g., 208 V. 4160 V 12.47
-A three-phase transformer has three primary and KV).
three secondary windings
▪ It has two main types: ▪ New distribution transformers are very
the delta and wye system. efficient. with losses of less than 0.25% in
-Other subtypes are a combination of both systems large units. Most large facility distribution
transformers convert at least 95% of input
power into useable output power. Smaller
Quen - Electrical Engineering Utilities – Chapter 1 to 3

closet transformers have efficiencies of load to 80% when the load is continuous for
98% or above. over 3 hours.

2.3 OVERCURRENT PROTECTION The UL (Underwriters Laboratories, Inc.)


Standard circuit breaker ratings for electrical
OVERCURRENT PROTECTION (OCP) DEVICE current:
-safeguards the circuit components from
overheating when the current flowing through the For Alternating Current
circuit reaches an amperage that will cause an 120 V. 120/240 V, 277 V.
excessive or dangerous temperature rise in 277/480 V, 480 V. and 600 V
conductors For Direct Current
125 V, 250 V, and 600 V

Circuit breakers that protect the ungrounded


OVERCURRENT PROTECTION (OCP) DEVICE (hot) conductors in a circuit:
-Fuses and circuit breakers serve as automatic
overcurrent protection devices that are designed to SINGLE POLE (SP)
open a circuit if the amount of current, in amps, that -protecting a single ungrounded conductor.
flows through the circuit exceeds the OCP device TWO POLE (2P)
rating -when protecting two ungrounded
conductors such as on a 240 V circuit.
CIRCUIT BREAKER THREE POLE (3P)
-an OCP that acts as a switch that can be opened -used when protecting three ungrounded
and closed manually, and it automatically "trips off." conductors on a three- phase circuit.
which opens the circuit when the current flowing
through it exceeds the circuit rating.
- A voltage rating classifies it in volts (V) and
current-carrying capacity in amperage (A).
- The voltage rating is the maximum voltage
the circuit breaker can carry.
- The voltage of the electrical circuit or
system being protected by the circuit
breaker must not exceed the circuit FUSES
breaker voltage rating. -an overcurrent protective device with a circuit-
opening fusible part that is heated and severed by
TYPES OF CIRCUIT BREAKER the passage of overcurrent through it (Smith, 2007).
- A reliable and simple OCPD made in
THERMAL- MAGNETIC TYPE various configurations fundamentally
-most popular type of circuit breaker comprised of "fusible" links encapsulated in
- It consists of the bimetallic strip that bends a tube or housing connected to terminals.
when heated by power loss The link's electrical resistance is so low that
- When current flow is excessive. the circuit it acts as a conductor until it encounters
breaker heats up. bends, and trips a current levels above its amp rating. Then it
release that opens contacts and interrupts melts and opens the circuit to protect
the current flow. conductors, components and loads
- When tested in the open air, it can carry a (Campbell, 2020).
load of about 10% above its rating and hold - act as "electricity's safety valve" by
50% above its rating for a minute. providing a weak link in the circuit path that,
- Other characteristics include the current- when properly applied, will melt and open
limiting feature that instantly trips at its the circuit to minimize or eliminate any
rating and the 100% rated part limiting the damage that can be caused by an
excessive flow of current (Sharma, 2018).
Quen - Electrical Engineering Utilities – Chapter 1 to 3

- They are desirable on circuits serving


TYPES OF FUSES
electric motors such as air conditioners and
machinery because motors draw much
PLUG FUSES
more current at a startup than during
-It comes in a screw-type configuration with a sight
regular operation.
glass that shows if the fuse is blown or not (Hanvey.
2015).
OVERCURRENT PROTECTION DEVICE
- The older type fuses have a brass screw
RATINGS
thread on the side and a central contact
point. The more contemporary style.
OVERCURRENT RATING
Edison-based, has a plastic line with a
-An OCP device's overcurrent rating is the highest
spring-type contact and a centre contact
amperage it can carry continuously without
(Hanvey, 2015).
exceeding a specific temperature limit.
-The overcurrent rating of an OCP is listed
in amperes, such as 15 A, 20 A. or 30 A.
-If the current (amperage) flowing through
the protection device exceeds the device
setting for a significant period, the OCP
device will open.
-The amperage carried by the electrical
CARTRIDGE FUSES circuit or system protected by an OCP
-cylindrical in shape and have the contact points at device must not exceed the circuit
either end. These fuses are used in fuse panels and breaker's maximum current rating.
disconnect for amperages over 30 amps (Sharma,
2018). INTERRUPTING RATING
- It is used to protect electrical appliances -The highest current at rated voltage that a device
such as motors, air-condition, refrigerators. is intended to interrupt under standard test
pumps etc. where high voltage ratings and conditions (Edvard, 2015)
currents are required (Thiele, 2019). - An OCPD must be able to interrupt
- They are available up to 600A and 600V destructive fault current energy safely. If a
AC and widely used in industries, fault current exceeds a level beyond the
commercial and home distribution panels OCPD's capability, it may rupture. causing
(Thiele, 2019). damage and posing a safety hazard
(Edvard, 2015).
- The amperes interruption current (AIC)
rating for circuit breakers is 5000 A and 10
000 A for fuses Circuit breakers and fuses
typically have an AIC rating of 10 000 A

2.4 UTILIZATION EQUIPMENT AND DEVICES


TIME DELAY FUSE
-A special kind of fuse that allows electrical surge
UTILIZATION EQUIPMENT
for a short time before it blows. Its unique design
▪ It is a broad category of electrical or
can bear electricity overload in a repeated cycle for
electronic machine or instrument designed
a short period without blowing (Andrew, 2010).
to perform a specific mechanical, chemical,
Quen - Electrical Engineering Utilities – Chapter 1 to 3

heating, or lighting function through the use - typically connected to a flexible cord that is
of electrical energy. attached to a portable appliance, light. or
▪ Electric motors, air conditioning. equipment
refrigeration and heating units. signs,
industrial machinery, cranes, hoists, Receptacles and plugs offer a simple way to
elevators, and escalators fit in the category attach or detach an appliance or piece of equipment
equipment. of utilization to/from an electrical outlet.

APPLIANCE
-end-use piece of utilization equipment designed to
perform a specific function such as cooking,
cleaning, cooling, or heating.

E.g., Electric ranges, refrigerators, clothes


washers and dryers, freezers blenders,
toasters, and hair dryers.

FIXED APPLIANCES
-permanently attached installations such as a built-
in electric cook top or oven
STATIONARY APPLIANCES
-situated and used at a specific location but can be
moved to another outlet such as a refrigerator,
clothes washer, or clothes dryer.
PORTABLE APPLIANCES
-appliances that can be easily carried or moved
such as a hair dryer or toaster

ELECTRICAL DEVICE
-An electrical device is a component in an electrical
system that is designed to carry but not use According to National Electrical Manufacturing
electricity. Association (NEMA) standards:
- This includes components such as - The different types of receptacles and plugs are
switches, receptacles, and relays. identified by a specific designation. The NEMA
designation ties the number and configuration of the
OUTLET slots in the receptacle and the matching slots in a
-the location in a branch circuit where electricity is plug to the voltage and amperage permitted.
used. For example, a lighting outlet is the location
in a branch circuit where conductors provide power E.g., 5-15R and 5-15P designation is
to a light fixture. associated with the matching receptacle
- female connecting device with slotted (R) and plug (P) that are rated at 15
contacts. Installed at an outlet or on amperes and 125 V and have equipment-
equipment, where it is intended to easily grounding capability. These devices are the
establish an electrical connection with an matching receptacles and plugs commonly
inserted plug. associated with residential and commercial
wall-mounted outlets
PLUG
-a male connecting device that has two or more -Different receptacles and plug combinations are
prongs that are inserted into a receptacle to connect generally tied to a specific application.
to an electrical circuit.
E.g., The 5-15R receptacle discussed
earlier serves as a common outlet for
portable lights and small appliances, while
Quen - Electrical Engineering Utilities – Chapter 1 to 3

the 14-50R and 14-50R receptacle/plug divert current from one conductor path to
configuration is typically used to connect a another.
kitchen range or other heavy-duty electrical - Switches are rated by purpose, voltage,
equipment to an outlet. and amperage, and are classified for AC or
DC.
The screw terminals on a receptacle are color
coded: - Safety switches are used in building
electrical systems. They are designed to
BRASS-COLORED SCREWS reduce the possibility of contact with bare
-are for connection to the ungrounded conductor. electrical conductors and have current
SILVER-COLORED SCREWS are for the grounded interrupting capability.
or neutral conductor: and
GREEN-COLORED SCREWS are for the KINDS OF SWITCHES
equipment grounding conductor.

Receptacles marked "CO/ALR" can be connected


to copper, aluminum, or copper-clad aluminum
conductors. Those marked "CU/AL" were
formerly allowed for use with copper or aluminum
conductors, but can only be connected to copper
conductors. They are no longer deemed
acceptable for use with aluminum conductors.

SAFETY SWITCHES CATEGORY

HEAVY-DUTY SAFETY SWITCHES


-designed for heavy industry, commercial, and
institutional applications where safety.
performance, and continuity of service are
required. These are enclosed and may be fused or
unfused. They are used extensively as motor
SWITCHES circuit switches, service entrance switches, and
-A simple switch is a device placed between two feeder disconnects, as well as for industrial
or more electrical conductors in a circuit to safely furnaces, capacitors, transformers, and
and intentionally open or close the circuit or to welders. Ratings up to 1200 A, 600 V are available.
redirect the path of current in a circuit.
- Contacts in a switch open (switches off) a GENERAL DUTY SAFETY SWITCHES
circuit, close (switches on) a circuit, or -intended for industrial, general commercial and
residential loads where economy is important
Quen - Electrical Engineering Utilities – Chapter 1 to 3

and requirements are less stringent. They are -used to provide control from one point by opening
used on lighting, heating, appliance, and or closing the ungrounded conductor in the circuit
intermittent motor loads. Ratings up to 600 V are THREE-WAY (S3) & FOUR-WAY (54)
available. -used when multiple control points are needed.

SWITCHING TERMINOLOGIES 18.8 through 18.14. common switching


configurations are described in the following:
POLE
-refers to the number of conductors the switch is CONTROL FROM ONE POINT: One single-pole,
opening and closing single-throw switch (S) is required. See Figures
18.8 through 18.10. Control from two points: Two
THROW three-way switches (S3) are required. See Figures
-refers to the number of operations a switch can 18.11 and 18.12.
perform
CONTROL FROM THREE POINTS: Two three-way
SINGLE-POLE, SINGLE-THROW (SPST) switches (53) and a four-way switc (54) are
SWITCH required. The Four-way switch must be wired
- a simple on/off switch. between the three-way switches.
- It opens or closes a single ungrounded
conductor in a circuit. It is the most CONTROL FROM FOUR OR MORE TWO THREE-
commonly used switch found in buildings, WAY SWITCHES POINTS: (53) and two or more
where it is typically used to control a lighting Four-way switches (54) are required.. The four-way
installation from a single location. switches must be wired between the three-way
switches.
SINGLE-POLE, DOUBLE-THROW (SPDT)
SWITCH
- diverts current from one conductor path to
another.
- A special type of SPDT switch is known as
a three-way switch (S3), which allows the
control of an installation from two locations
(for instance, tuming a light on or off from
either end of a flight of stairs).

DOUBLE-POLE, SINGLE-THROW (DPST)


SWITCH
- opens or closes two conductors in a
circuit. It is equivalent to two SPST
switches controlled by a single mechanism.
- It can be used to switch off the ungrounded
and grounded conductors in a single
lighting circuit that is serving a paint spray
booth containing explosive vapors.

Double-pole, double-throw (DPDT) and three-


pole, single-throw switches are also available:

SWITCHING CONFIGURATIONS
-switches provide control from one or more points
in a circuit
SINGLE-POLE, SINGLE-THROW SWITCH (S)
Quen - Electrical Engineering Utilities – Chapter 1 to 3

Single-pole, single-throw (S). Three-way (53)


and Four-way ($4) switches generally control
operation of lighting installations.

Dimmer switches (sometimes identified as SD)


-can used to adjust brightness of a lighting
installation by adjusting the current flowing through
the circuit.

Key-operated switches (SK) require a key to


operate the switch. These are used where
operation of a lighting installation or other piece of
equipment must be further controlled by limiting
operation to personnel holding a key such as in
lighting in a high school gymnasium or large
Quen - Electrical Engineering Utilities – Chapter 1 to 3

meeting room and equipment in a manufacturing


plant. INFRARED SENSORS
-respond to the motion of an Infrared heat source,
SPECIALTY SWITCHES such as a person or animal,

AUTOMATIC SWITCHES ULTRASONIC SENSORS


-deactivate a circuit after a preset time period has -emit a high-frequency sound that is in the range of
lapsed. 25 to 40 kilohertz and well above the capacity of
- Available as a twist-turn device where the normal human hearing.
operator determines the operating time - they do not require a direct line of sight to
interval by how far the switch is twisted or the occupant.
as an electronic device that looks like a
normal on/off switch but is designed to Both infrared and ultrasonic sensors work well in
automatically switch off after a preset inferior spaces such as classrooms and offices.
time.

DIMMER SWITCHES (SD)


-is a device in the electrical circuit for varying power
to a circuit.
- Dimmers are usually included in a lighting
installation to vary the intensity of light
emitted by the lights.

TIME CLOCKS
-can be used to control the time period that a
piece of equipment or a lighting installation
operates.

ELECTRONIC TIMERS
-allow greater flexibility as they can easily be set for
7-day cycles.
2.5 CONDUCTORS
- They do require relay switching on large
loads.
CONDUCTORS
-any material that conducts electrical current.
-A wire is a common electrical conductor.
-Electrical conductors are either solid or stranded.
PHOTOCELL CONTROLS
-sense light and open or close a circuit with the
presence of light. •They can be used to control night
lighting in lieu of a time clock.

PHOTOCELL SWITCHES STRANDED CONDUCTORS


-Recent advancements in photocell technology -consist of smaller wire strands. The basic reason
allow them to be used effectively to control for using a stranded conductor is to make the
illumination levels in spaces that have daylight conductor flexible.
available.
SOLID CONDUCTORS
OCCUPANCY SENSORS -Constructed of one single piece of metal.
-control a lighting or equipment installation by - tougher than a stranded conductor but
sensing occupants in a space. These are usually rigid and less flexible.
mounted on the wall or ceiling.
Quen - Electrical Engineering Utilities – Chapter 1 to 3

- more likely to break if subjected to frequent -contains more than one conductor bundled
flexing than stranded conductors together in a factory assembly of wires.
- An outer sheathing encases and protects
CONDUCTOR MATERIALS the conductors. simplifying the installation
of multiple wiring.
SILVER
-the best electrical conductor material (other than a TYPES OF CABLE
superconductor material) it has the least resistance
of common materials Nonmetallic-Sheathed Cable
- silver wiring was used in the first mainframe Underground Feeder Cable
computer. Service Entrance Cable
- just like gold (excellent conductor), silver is Armored Cable
too costly for building installation. Metal-Clad Cable

COPPER
-used in building conductor (wiring) installations as
a compromise between good conductivity and
economy.
- The wire core is aluminum with a thin
coating of copper that is metallurgically
bonded to the core

ALUMINUM
- has significant weight and cost advantages over
copper. Copper does, however, conduct electricity OTHER TYPES OF CABLE
better than aluminum, so an aluminum wiring
installation requires a thicker gauge. FLAT CONDUCTOR CABLE
- Also, extra care in splicing and terminating -a wiring system conductors and special connectors
aluminum wire is important. and terminals.
- composed of very thin cable with three or
CONDUCTOR INSULATION more
-covered with insulation that provides protection of - designed to rest between the topside of a
the conductor material. smooth continuous subfloor and carpet
- prevents loss of power and the danger squares.
electrical isolation and some physical of
short circuits and ground faults.

THERMOSTAT CABLE
COMMON CONDUCTORS - used in applications with voltages less than 30 V.
such as wiring to doorbells, chimes, and
thermostats.
- generally contains No. 16 AWG or No. 18
AWG conductors that are bundled in a thin
plastic sheathing.

CABLE
Quen - Electrical Engineering Utilities – Chapter 1 to 3

CORD Temperature and exposure of the


-made of stranded conductors within a flexible conductor (e.g., buried, in free air, in the affic, in
insulated sheathing material crawl space, and so forth).
- They are designed for flexibility and
bending. Voltage Drops in Conductors
-Because of power losses, voltage is reduced in a
CONCEALED KNOB-AND-TUBE WIRING closed circuit - that is, the voltage across two
- A wiring method uses knobs, tubes, and conductors is lower at the usage end than at the
flexible nonmetallic tubing to protect and power supply end of the circuit.
support single insulated conductors. - Voltage drop is directly proportional to
power loss
CONDUCTOR POWER LOSS
-Heat generated by current flow through the 2.6 ENCLOSURES AND RACEWAYS
conductor results in a loss of power. This lost power
is referred to as power loss or line loss. Power loss ENCLOSURES
(Ploss) in a conductor can be computed with -are electrical boxes and cabinets that are made of
amperage (1) or voltage (V) and resistance (R) by metal or non-metallic materials that protect
the following formula: conductors, connections. controls, and other
equipment
- they protect wiring, devices, and equipment
- Power loss is converted directly to heat. from damage from accidental contact,
Power loss is equivalent to the heat wear, corrosive, atmospheric exposure,
produced. The relationship between power and sunlight.
and heat is 1 W 3.413 Blu/hr. The following - for faulty enclosed conductors.
formula can compute the heat created (a) connections, controls, and electrical
for a known power loss (Ploss): equipment, enclosures contain the arc and
flaming, thereby confining damage from
fire.

CONDUCTOR AMPACITY
-the maximum current that a conductor can carry
continuously under the conditions of use without
exceeding its temperature rating.
- Current is measured in amperes or "amps."
You must use the correct size wire for the
current (load) requirement of the circuit to
prevent the wire from overheating. ELECTRICAL BOXES
-are metal and non-metallic enclosures that hold
AMPACITY IS BASED ON THE FOLLOWING: devices such as switches or outlets and safety
permit wiring connections boxes are in four primary
Wire thickness (thicker wires have larger shapes: square, rectangular. octagonal, or round
cross-sectional areas and can carry more electrical - boxes can be joined together to
current without overheating) accommodate multiple outlets or switches.
Type of conductor material (at a specific gangs, or four gang boxes namely, two-
current and conductor size, aluminum produces gang, three gangs, four gang boxes
more heat than copper)
Insulation and sheathing type (some
insulation materials handle heat better than others)
Number of conductors bundled in the
sheathing or in the proximity of one another (more
conductors concentrate heat in an area)
Quen - Electrical Engineering Utilities – Chapter 1 to 3

JUNCTION BOXES (J-BOXES)


-special type of electrical box used to enclose
conductor connections
-connections are commonly called junctions in the
trade

PULLBOX
-kind of junction box that allows access to a
raceway for snaking conductors through
the raceway
KNOCKOUT
-in most boxes and enclosures, it con be
easily removed to allow wiring to enter the
box
COVER PLATES
-required for various single or combinations
of switches, convenience outlets, blank CONDUIT AND RACEWAYS
covers, and dimmers; plastic is a commonly
used material RACEWAY
-attached with screws to the switch or -an enclosed channel such as conduit, tube, or
receptacles gutter used for holding wires, cables, or bus bars
-all the boxes should be finished with a - in some cases, metal raceways that are
cover plate fully bonded serve to provide a path for the
flow of fault current to ground
Quen - Electrical Engineering Utilities – Chapter 1 to 3

EXAMPLES OF RACEWAY MATERIALS OR


SYSTEMS

RIGID METAL CONDUIT


-a heavy galvanized steel or aluminum tube that
looks like the galvanized steel pipe used for
plumbing applications. except it is much smoother
and is labeled with a UL Listed stamp or label
- permitted in damped locations and can be
set in concrete above ground
- can also be solvent welded to rigid polyvinyl
chloride (PVC) conduit
- can be used in any building, but special
precautions are required when used more
than three floors above grade
- has threaded connections much like a pipe
RIGID NONMETALLIC CONDUIT
- can be used in contact with the earth and
-thin-walled pipe of PVC
embedded in concrete
-joined with fittings that are solvent welded
INTERMEDIATE METAL CONDUIT (IMC)
FLEXIBLE METAL CONDUIT
-a galvanized steel or aluminum tube that has a
-similar to armored cable yet, installed without
thinner wall than rigid metal conduit
cables or wiring in it; wiring must be pulled
- has threaded connections much like pipe or
threadless connectors and couplings
LIQUID TIGHT FLEXIBLE METAL CONDUIT
- can be used in contact with earth and
-similar to flexible metal conduit but covered with
embedded in concrete
plastic, a watertight jacket that is sunlight resistant
unlike flexible metal conduit, the special connectors
ELECTRICAL METALLIC TUBING (EMT)
are watertight
-thin-walled galvanized steel or aluminum tube in
nominal diameters up to 4 in.
LIQUID TIGHT FLEXIBLE NONMETALLIC
- cannot be threaded
CONDUIT
-a flexible plastic conduit used similarly to flexible
ELECTRICAL METALLIC TUBING (EMT)
metal conduit
-labeled with UL Listed stamp or label
- cannot be used over 6 ft. in length
- joined with threadless compression
couplings. couplings that are crimped into
CELLULAR CONCRETE FLOOR RACEWAYS
the tubing with a special indenting tool, or
-are hollow voids in floors made of precast concrete
fittings that are tightened with screws
slabs (core slabs) found in certain precast concrete
buildings
ELECTRICAL NONMETALLIC TUBING (ENT)
-a flame-retardant corrugated plastic tube that is
semi flexible such that it can be bent by hand. must
be used behind fire-rated finish materials
Quen - Electrical Engineering Utilities – Chapter 1 to 3

- busway systems are used in service


equipment or as feeders because they are
designed to carry a large amount of current

FEEDER BUSWAY
-A type of busway system that used to deliver a
large amount of power with low voltage drop
- available in sizes from 600 A to several
thousand amps

CONDUIT AND OTHER RACEWAYS PLUG-IN BUSWAY


▪ the use of rigid conduit, EMC, EMT, and -Another type of busway system used to provide
ENT involves cutting, bending, and power top-offs at multiple points
threading lengths - available in 100 A-3000 A sizes make
▪ cutting is typically done with a saw power distribution flexible
▪ bands must be made to avoid damage so
that the internal diameter of a conduit will BUSWAY
not be reduced -Power is available anywhere along the busway
▪ bends can be made at the factory or field without necessitating the major service interruption.
with a manual bender called hickey, or a hot - Connections may be made at any point
box heater for plastic conduit along the busway.
▪ a run of conduit should be straight and - Rigid and flexible conduit or flexible bus
system before any direct drop cable extends from the busway to the
▪ raceways must be installed as a complete equipment piece.
conductors are pulled into them - are only used in large commercial and
▪ straps or hangers must support the conduit industrial installations where large loads
in the entire run are concentrated (600 A and above), where
▪ the number of supports needed and large numbers of tops are required, or
spacing depends on the type of condult where superior fire. and mechanical injury
used protection is desirable.
▪ the number of conductors is based on the - can also be salvaged and moved more
size of the conduit, type of conductor easily and cost-effectively than ordinary
insulation, and size of conductors conductors.
▪ several conductors fed into conduit should
be kept parallel, straight, and kinks and WIREWAYS
bends-free -wire gutters or wireways are sheet metal or
nonmetallic, flame-resistant plastic through that
BUSWAY serve as housing that protects conductors
-is of a standardized, factory- assembled enclosure - access to the enclosure interior is through
consisting of outer duct-like housing, bus bars, and a hinge door or removable cover
insulators - wire gutters or wireways carry large
conductors
Quen - Electrical Engineering Utilities – Chapter 1 to 3

For example, a 1 hp motor draws about 1400 W.


much more than the theoretical equivalent of 746
W.

A 230 V. I hp motor that normally draws about 1000


W (4.3 A) under full load may draw 6000 W (26.1 A)
or more at startup.

2.7 ELECTRIC MOTORS It is an advantage over fuel-powered motors. It does


require more power, 230 V 1 hp motor can deliver
11/2 hp, but it will draw more power (about 1700 W)
and amperage (7.4 A).

An electric motor's locked rotor amperage (LRA)


is the highest amperage that a motor pulls.

- A motor operating at its rated speed,


voltage, and horsepower draws current at
ELECTRIC MOTORS its full load amperage (FLA) or running load
- -drive exhaust/ventilation fans, air-handling amperage(RLA)
unit blowers. refrigeration equipment, air - electric motor's LRA is usually four to six
and fluid compressors and pumps. heating times greater than the FLA/RLA.
system circulators, and manufacturing
equipment and machinery. Most electric motors are designed to run at 50% to
- designed to operate at slower speeds are 100% of rated load, with maximum efficiency
larger, run quieter, and last longer because typically near 75% of rated load.
they encounter less friction.
For example, a 10-horsepower (hp) motor has an
Most AC 60 Hz electric motors used in North acceptable load range of 5 to 10 hp: peak efficiency
America are designed to operate at theoretical 1800 is at 7.5 hp.
or 3600 revolutions per minute (rpm).
TYPES OF MOTORS
When delivering its rated horsepower, the actual
speed of a motor will be somewhat less, about 1725 UNIVERSAL MOTOR
and 3450 rpm -It is a fractional horsepower motor designed to
operate on both AC and DC power.
MOTOR RATINGS - It operates at high speeds under light
-Electric motors are rated in horsepower (hp). load and low speeds with a heavy load.
- 1 hp = 33,000 ft-lb (foot-pounds) of work - It can free idle at up to 20 000 rpm.
per minute (550 ft-lb/s). This is about 1/8 - It is used on appliances such as blenders
the power an adult can produce and vacuum cleaners and power tools such
continuously. as routers and electric drills.
- Inrush current - at startup, consumes
substantially more electrical power SPLIT-PHASE MOTOR
-The motor windings are configured so that single-
In theory, one horsepower is equivalent to 746 W. phase AC power is split into two phases that are
However, because of losses from heat and friction, 1/2 out of phase. Available in sizes up to 1/3
an electric motor delivers less work than the horsepower.
theoretical equivalent: more power is consumed - This type of motor starts slowly with low
than is produced. torque, so it cannot begin to heavy loads.
Quen - Electrical Engineering Utilities – Chapter 1 to 3

INDUCTION MOTORS
-These motors use electromagnetic induction to
cause the motor rotor to turn.
- Repulsion-start induction motors are
capable of handling heavy starting loads.

CAPACITOR MOTOR
-This type of motor operates on single-phase AC
only.
- Capacitor-start motors have a capacitor The specifications of an electric motor are
that stores and discharges energy to help typically listed on the nameplate. Information
start the motor rotor. provided may include:
- Capacitor-run motors have one or more
- Manufacturer's type and frame designation
capacitors to help start and run the motor.
Insulation system designation
- It is more efficient and has a better starting
- Horsepower output
torque than the split-phase motor.
- Revolutions/minute at rated load
THREE-PHASE MOTORS - Power factor
-Large motors operate more efficiently on three- - Frequency
phase AC power. - Number of phases
- A single-phase motor rated at 71/2 hp - Maximum ambient temperature for which
motor is designed
draws a large amount of instantaneous
- Rated load current
current at startup (up to 200 A on a 240 V
- Voltage
single-phase circuit).

DUAL VOLTAGE MOTORS MOTOR CONTROLLERS


-Motors above 1/4 hp are designed to operate on -a switching device designed to start, stop and
one of two different line voltages such as 115 V or protect the motor.
230 V. - provide functions such as reversing jogging
- Larger motors operate more efficiently on a plugging. operating at several speeds or
reduced current and motor torque levels.
higher line voltage because of lower 12R
- They are grouped together into motor
losses. So, if a higher line voltage is
control centers (MCC)
available, it is used.

MOTOR CONTROL CENTERS (MCC)


-a centrally located, sheet metal, a cabinet-like
enclosure that houses starters and controls that
control and protect several motors,
- The front panel of an MCC contains
operator controls and gauges.
- The interior of the MCC contains plug-in
units such as starters, controls, and
specialized units.
Quen - Electrical Engineering Utilities – Chapter 1 to 3

- The main danger of ground faults comes in


VARIABLE-FREQUENCY DRIVE (VFD) the likelihood of shock.
-a solid-state electronic power conversion device
used for controlling the rotational speed of an AC COMMON CAUSES OF GROUND FAULTS
electric motor
- when a VFD starts a motor, it initially
applies a low frequency (typically 2 Hz or
less) and voltage to the motor.

2.8 OCCUPANT PROTECTION

As an engineer, contractor, manufacturer, or


maintenance personnel, and whether one's
business is electrical or not, electrical safety is a
concern shared by all building industry.
Electricity is a serious workplace hazard resulting in
serious injuries and even fatalities. Water leaking into an electrical box can cause a
ground fault since water is a conductor of electricity.
In the US, hundreds of people are accidentally
electrocuted each year. Worn hot wires or hot wires that are not completely
seated into their terminals may contact ground
Electrocution occurs when a small amount of wires or grounding devices or boxes.
electrical current flows through the heart for 1-
3 seconds. Without proper insulation, power tools or appliances
can cause a ground fault if faulty wiring causes
TAMPER-RESISTANT RECEPTACLES current to flow directly to the ground.
- resemble regular receptacles, but they're
so much more. CIRCUIT BREAKER TYPE
- provide a permanent solution to childhood - By providing overcurrent protection as a
shock caused by tampering with electrical circuit breaker and serving to provide GFCI
outlets. protection, the GFCI circuit breaker serves
- feature built-in safety shutters that block a dual purpose:
foreign objects from being inserted into the o it will interrupt power in the event of
receptacle. a ground fault
o it will trip when a short circuit or a
power overload occurs.

THREE TYPES OF GROUND FAULT CIRCUIT


INTERRUPTER (GFCIS)

PORTABLE TYPE
-frequently used in construction and outdoor
GROUND FAULT INTERRUPTION settings with electric tools. mowers, trimmers, and
-Unintentional flow of electrical current between a similar devices.
power source, such as ungrounded (hot) wire, and - It should not be used as a permanent
a grounded surface. alternative to a regular GFCI.
- Occurs when electrical current leaks - They are intended to be used when you
escapes to the ground. must bring power from an unprotected
outlet into a hazardous situation
A ground fault becomes a danger because:
- Only a very low current is required to affect ARC FAULT PROTECTION
human heart rhythm.
Quen - Electrical Engineering Utilities – Chapter 1 to 3

Arc Fault
-unintentional electrical discharge characterized by
the low and erratic current.
- arcing generates high-intensity heat and
expels burning particles, which can easily
ignite combustible materials.
PARALLEL ARCING FAULTS
- caused by loose, damaged, or corroded
-Result from direct contact of two wires of opposite
wires and terminals.
polarity.
- Current residential breakers only detect
- Frayed/ruptured appliances or extension
and react to power overloads. not arc faults
cords
- staples or other fasteners that pierce or
COMMON CAUSES OF FAULT ARCS AND THUS
pinch insulation on construction wire and
POSSIBLE FIRE IN WIRING
appliance or extension cords
- Cracked wire or cord insulation caused by
age, heat, corrosion, or bending stress

GROUND ARCING FAULTS


-Arcs between a single conductor and ground,
such as:
- wire or cords that touch vibrating metal.
- in appliances, wall plugs, or switches
where the internal wires are not installed
correctly.
- where connections became loose
TYPES OF ARC FAULTS COMMON IN
BUILDING WIRING

ARC FAULT CIRCUIT INTERRUPTER (AFCI)


-provides enhanced protection from fires resulting
from arc faults.
- It uses electronics to recognize an arc fault
and interrupts the circuit when the fault
Occurs.
- detects low-level arc faults that traditional
overcurrent protective devices (fuses and
circuit breakers) cannot see.
SERIES ARCING FAULTS
-Occur across the break of a single conductor
- For example, in the case of an electrical
wire cut by a nail or screw used to mount a
wall hanging.
Quen - Electrical Engineering Utilities – Chapter 1 to 3

FOUR BASIC TYPES OF ARC FAULT CIRCUIT


INTERRUPTER (AFCIS):

CIRCUIT BREAKER TYPE


-A branch/feeder AFCI breaker with protection
provided to branch-circuit wiring in the form of a
circuit breaker.

CONVENIENCE OUTLET TYPE


-An outlet AFCI for protecting connected cord sets
and power supply cords in the form of an outlet
receptacle. NUISANCE TRIPPING

PORTABLE TYPE The tendency of GFCIs and AFCIs to trip frequently


-Portable AFCI for protecting connected cord sets because both of them extremely sensitive. This can
and power- supply cords that can be moved from be caused by: • Appliances that are beginning to fail
outlet to outlet. - should be repaired or replaced. are

CORD-MOUNTED TYPE Lightning for this reason, it is not a recommended


-cord-mounted AFCI for protecting the power- practice to connect essential equipment and
supply cord connected to it (in the form of an appliances that contain perishable products into an
attachment plug on a power-supply cord). outlet with GFCI or AFCI protection

EXTREMELY LOW-FREQUENCY
ELECTROMAGNETIC FIELDS
-silent, invisible magnetic fields produced any time
electricity runs through a wire, an appliance, or
piece of equipment.

ELECTROMAGNETIC INTERFERENCE (EMI)


-Produced by high levels of EMF.
-Are visible screen jitter in video displays,
-humming in telephone/audio equipment and data
errors.
-Higher levels of EMF can cause computer monitor
interference and raise potential health concerns

In the United States, EMF is measured in units


called milligauss (mG).

In most of the world and in scientific community, it


is measured in microtesla (µT).
Quen - Electrical Engineering Utilities – Chapter 1 to 3

1 μT = 10 mG persists beyond the time delay setting. the relay


operates to open the switch or circuit breaker.
ELF (EXTREMELY LOW-FREQUENCY) METER
-Instrument used in measuring EMF radiation levels POWER SURGE
from fans, electrical appliances. wiring, and power -A sudden increase in electrical current or voltage
lines. that is very short in duration.
-The said increase may be caused by a lightning
strike or by a sudden power spike caused by a
problem in the utility transmission and generating
system.
-May damage sensitive equipment such as
computers, televisions, machines, etc.

-The most significant exposure to EMFS is from SURGE RATING


household appliances or business equipment, not -A measure of the level of surge that an SPD can
power lines in the US. withstand.
-Shielding of magnetic fields to reduce EMF levels -Manufacturers specify the surge ratings of their
include: SPDs.

Passive shielding by using a conductive SURGE PROTECTION DEVICE (SPD)


sheet material in front of the appliance or -An electrical device that prevents power surges
equipment. from reaching electric and electronic equipment or
another device.
Active shielding uses a system that -They work by instantly limiting the transient voltage
senses the existence of a magnetic field in the from a power surge to a safe level for the equipment
building area to be shielded. they protect by diverting the large surge current
safely to the ground.
-It also diverts the surge by allowing the current to
flow past rather than through the protected
2.9 EQUIPMENT PROTECTION
equipment.

GROUND FAULT PROTECTION (GFP)


TYPES OF SURGE PROTECTION DEVICES
- designed to detect and rapidly interrupt
(SPDs)
low- level equipment ground faults.
- operates on the same principle as GFCI
METAL OXIDE VARISTOR (MOV)
(ground fault circuit interrupter) protection
-A semiconductor device used mainly on AC power
by monitoring the current drawn through
applications with surge ratings ranging from a few
the conductors of an electrical circuit and
hundred to many thousands of amps.
quickly shutting off power when the current
is not equal.

CURRENT TRANSFORMER (CT)


-A particular type of sensing transformer. It
encircles the conductors in the switchboard or panel
board and produces a low-current output signal if all
current flowing to the load does not return to the
source through the phase or neutral conductors. GAS DISCHARGE TUBES (GDT)
-A primary surge protection component with a surge
CURRENT TRANSFORMER (CT) rating of several thousand amps comprises a
-The low-current output is sensed by a ground fault sealed tube containing a particular gas that breaks
relay with adjustable sensitivity and time delay down at a given voltage rise time.
settings. When a signal above the sensitivity setting
Quen - Electrical Engineering Utilities – Chapter 1 to 3

to 30 times the rated current for the one-


half cycle at 60 Hz and eliminate nuisance
tripping. However, many techniques are
used to limit inrush current.

NEGATIVE TEMPERATURE COEFFICIENT


(NTC)

ZENER DIODE
-A secondary surge protection component used for
accurate clamping of surge voltages.
-It has a quicker response time than the GDTS and
provides a more accurate clamping voltage than
MOVS.
THERMISTORS
-are the most used inrush current limiter for power
supplies and motors.
-a thermally sensitive resistor with a resistance that
changes significantly and predictably due to
temperature changes.
-When equipment is first turned on. the NTC
thermistor is cooled, and its resistance is high,
HYBRID CIRCUIT limiting current flow.
-A circuit comprising different types of surge -Resistance decreases rapidly as the thermistor
protection components, taking advantage of each self-heats, allowing near-full current to flow (at 612).
component's strengths. A hybrid may combine the -A disadvantage is that when the NTC thermistor is
high surge capability of a GDT with the accurate switched off, it initially retains heat, so, it offers little
voltage clamping of a surge diode. resistance and cannot limit the inrush current until
heat is dissipated. .
-The cooldown time varies according to the device,
its mounting method, and ambient temperature.

LIGHTNING PROTECTION
INRUSH CURRENT OR INPUT SURGE - -Lightning discharges have been measured
CURRENT from 2000 A to more than 200 000 A, with
rise times to peak current of less than 10
microseconds (10 millionths of a second).
As a result, lightning causes more damage,
injuries. and deaths each year than
fornadoes, hurricanes, or floods.
- -Lightning discharges have been measured
from 2000 A to more than 200 000 A. with
rise times to peak current of less than 10
microseconds (10 millionths of a second).
- It refers to the peak instantaneous current, As a result, lightning causes more damage.
measured in amperes (A), drawn by an injuries, and deaths each year than
electrical appliance or piece of equipment tornadoes, hurricanes, or floods.
(e.g. power supplies, AC motors, lamps,
and lighting ballasts) is first turned on. BENJAMIN FRANKLIN
- An inrush current can also be reduced by -He first suggested protecting buildings and other
an inrush current limiter, which protects structures from the effects of direct lightning strikes
circuits that encounter high inrush loads up by the use of protective conductors.
Quen - Electrical Engineering Utilities – Chapter 1 to 3

-His theory stated that lightning protection must


provide a direct path for the lightning bolt to follow
to the ground, and it must prevent destruction,
injury, or death as the current travels that path.

VERTICAL LIGHTNING RODS


-sometimes called air terminals, are placed at the
top of the protected structure. These lightning rods
have equally spaced a maximum of 20 ft. apart from
the structure's high points.
-A network of conductive copper or aluminum tape
(thick, flat cable) bonds the rods to grounding
electrodes driven into the earth. Metal roof vents in
the proximity of the lightning rods are also
connected to the conductive tape.
-The system of vertical rods, tape, and ground
electrodes is designed to present a low impedance
(resistance) path to the lightning current that diverts
current away from the building's structural parts.
-A surge protection device can minimize the
damaging effects of a lightning strike. Additionally,
power passing through electrical circuits can
generate relatively high magnetic fields that
damage electronic equipment. Shielding the wiring
can minimize damage.

EQUIPMENT FOR HAZARDOUS LOCATIONS

• In a hazardous location, such as a gasoline


station, paint spray booth, or factory, explosion-
proof or explosion- resistant equipment and wiring
must be Used.

• A hazardous location is when fire or explosion


hazards may exist because of flammable gases or
vapors, flammable liquids, combustible dust, or
quickly ignited fibers under regular operation or
abnormal operating conditions.

• Types of hazardous locations are grouped by


class and division or by zone. Buildings or building
spaces identified as hazardous locations must meet
regulations specific to the group it falls into.

• In contrast, explosion-resistant equipment is


designed to prevent the ignition of explosive or
flammable material. A Nationally Recognized
Testing Laboratory (NRTL), such as UL,
accomplishes testing 254-257/259 explosion-proof
or explosion-resistant equipment and wiring
components.

You might also like