Professional Documents
Culture Documents
EEU Notes
EEU Notes
COMMON BUILDING SYSTEM VOLTAGES 208 Y/120 Volt, Alternating Current, Three-
Phase, Four-Wire System (208Y/120 V AC,
A comparison of the number of conductors and 3-4W)
voltages between conductors on common • An older electrical service found in small
building system voltages is found in Table. The commercial buildings and high-rise
following is a description of the common buildings where three-phase motors,
building system voltages used in the United above about 12 horsepower, and
States and Canada. equipment such as large air conditioners
are used. It is not used very often in
120 Volt, Alternating Current, Single-Phase, industry because a 480 V system is more
Two-Wire System economical for largeCmotor loads.
(120 V AC, 1-2W)
• The most basic system voltage used. It was 480 Y/277 Volt, Alternating Current, Three-
used in the first electrical services to Phase, Four-Wire System (480Y/277 V AC,
buildings; however, nearly all have since 3-4W)
been upgraded. The service entrance • Is a common electrical service in most
provided to the switchboard or panelboard modern medium to large commercial
is by two conductors: one ungrounded (hot) buildings. The 480 V three-phase power is
conductor carrying 120 V and one neutral used to power specially designed heavy
conductor. Voltage measured between the machinery. High-voltage, 277 V fluorescent
ungrounded (hot) and neutral conductors is lighting and other single-phase devices
120V. have also been developed specifically for
120/240 Volt, Alternating Current, Single- use with this system. Large retail shopping
Phase, Three-Wire System (120/240 V AC, 1- malls, schools, grocery supermarkets, and
3W) office buildings may use this system for its
• The most common residential electrical 277 V fluorescent lighting capabilities,
service in use today. It is also used on a where fixtures are not located closer than 3
limited basis in light commercial buildings ft away from windows, platforms, and fire
such as small office buildings, churches, escapes.
and retail shops and stores. On a 120/240
V system, a 120 V branch circuit provides 480 Y/277 Volt, Alternating Current, Three-
electrical energy to convenience outlets, Phase, Four-Wire System (480Y/277 V AC,
small appliances, and light fixtures. 3-4W)
• When compared with the 208 Y/120 V
120/240 Volt, Alternating Current, Single- system, the 480Y/277 V system has
Phase, Three-Wire System (120/240 V AC, 1- economic advantages from the standpoint
3W) of equipment and conductors. Because a
• A 240 V branch circuit serves large given conductor can carry more than twice
appliances and equipment such as electric- the VA load at 480 V than at 208 V, the
resistance baseboard heaters, water savings in wire size for feeders can be quite
heaters, and air conditioning equipment. A significant with the 480Y/277 V system.
120/240 V branch circuit provides both 120 Additionally, the smaller current at 480 V
V and 240 V to an appliance such as range for any supply transformer capacity permits
and clothes dryer, controls, and light the use of protective devices with both
fixtures. Typically, small motors run on 120 smaller frame size and interrupting rating.
V and heating elements operate on 240 V. Both factors permit significant savings.
A grounding conductor runs continuously
through all branch circuits and serves as a 600Y/346 Volt, Alternating Current, Three-
safety circuit in case of a short- circuit. Phase, Four-Wire System (600Y/346 V AC,
3-4W)
• Is a less common electrical service in large
commercial and industrial buildings that is
used to power specially designed heavy
machinery. This system is designed like the
Quen - Electrical Engineering Utilities – Chapter 1 to 3
480Y/277 V AC, 3-4W described earlier, standard for the system voltage is actually
except that 600 V and 346 V are available 120/240 V.
in the circuit or feeder configurations.
Utilization Voltage
600Y/346 Volt, Alternating Current, Three- • A voltage drop occurs as current flows from
Phase, Four-Wire System (600Y/346 V AC, the service equipment through the branch
3-4W) circuit conductors to the outlet. On a
• The 600Y/346 V system has additional 120/240 V system, approximately 115/230
economic advantages from the standpoint V is available at the outlet of the Branch
of equipment and conductor sizing in Circuit. Measured voltage at an outlet or
comparison to the 208Y/120 V and connection is called the line voltage.
480Y/277 V systems. However, the 550 V Maximum Voltage
or 575 V equipment used on the • Wiring devices such as switches,
600Y/346V system is not as readily receptacles, relays and conductors are
available as the 460 V equipment used on designed to endure voltages slightly higher
the 480Y/277 V system. As a result, this than the utilization voltage. The highest
electrical service is used primarily in voltage to which a wiring device can be
industries where the 600Y/346 V systems exposed is known as the maximum
area tradition. voltage.
between a recessed light fixture and a - Bends are limited to no less than five times
box. the diameter.
- Conduit and cable should be installed away
Grounding conductor from locations where building occupants might
- IMC and EMT can be used as use it as a handhold or footstep.
grounding conductor if it is continuous - Drain holes should be provided at the lowest
and properly bonded. point in a conduit run.
- It is required for flexible conduit. - Drilling and culling burrs should be carefully
- It can be bare or insulated. removed to prevent damage to conductor
insulation.
Rigid nonmetallic conduit and tubing (ENT) - It must be supported every 4 to 6 in (1.35 m)
- Cannot be use as the grounding and within 12 in (300 mm) of a box, except up
conductor. to 24 in (600 mm) is allowed at points of usage
- Manufactured from thermoplastics that where flexibility is required (i.e., at a pump
have very high rates of thermal motor).
expansion (over 6 in for a 100°F - AC cannot be embedded in masonry,
temperature change per 100 ft/over concrete, or plaster.
300 mm in a 50°C temperature change
per 30 m). BOX/ENCLOSURE REQUIREMENTS
✓ Provisions must be made if it is
exposed to significant temperature - All electrical connections must be made
changes. in a protective enclosure such as
panelboard, junction, or device box,
Nonmetallic-sheathed cable (NM and NMC) fixture, or appliance.
- Permitted in single- and multifamily - Every switch, outlet, and connection
dwelling units and some other must be contained in an electrical box
buildings. and every lighting fixture must be
mounted in a box.
Restriction of use in: - All wirings must begin or terminate at a
✔Underground panelboard or in a box that is housing
switch, luminaire connection,
✔buildings that are more than three stories
receptacle, conductor junction, or some
above grade or in commercial garages
similar terminal fitting.
✔Motion picture studious - Junction boxes must be mounted so
✔Theaters that the blank cover plate is visible and
✔Places of assembly Elevator hoist ways readily accessible.
✔Other corrosive or hazardous locations - All electrical boxes must be adequately
secure to the building structure.
- NM and NMC must be supported every Any box can be used for any purpose.
4-6 (1.35 m) and within 12 in (300 mm) - There are no requirements that specify
of a box. that a certain type of electrical box be
installed for a specific purpose.
Armored cable (AC) - Typical trade practice:
Is for use in dry, indoor applications. o Octagon and round boxes for
lighting outlets o Normally
Restriction of use in: installed overhead for lightning
✓ commercial garages installation.
✔Motion picture studious o Rectangular and square boxes
for switches and receptacle
✔Theaters
outlets
✔Places of assembly The size and number of conductors to be
✔Elevator hoist ways installed in a box influences selection of type of
✔Other corrosive or hazardous locations box and box size.
Quen - Electrical Engineering Utilities – Chapter 1 to 3
- The more conductors and/or the circuit breaker), wiring, and one or
conductor size, the bigger the box must more outlets.
be.
- The capacity of a box, in cubic inches, Types of branch circuit
is determined by its length, width, and 01 Individual Branch Circuit
depth. - This of branch circuit serves one
- An increase in one or more of these receptacle or piece of equipment such
dimensions increases box capacity. as for a range, clothes dryer, large copy
o Some boxes are designed so machine, or other piece of machinery.
they can be ganged together to These circuits usually lead directly from
increase box capacity. the distribution panel to the appliance
- By convention, a conductor that runs and do not serve any other electrical
through the box is counted as one devices. The individual branch circuit is
conductor and each conductor that sometimes known in the trade as a
terminates in the box counts as one. dedicated or special purpose circuit.
The size and number of conductors to be 02 General Purpose Branch Circuit
installed in a box influences selection of type of - A branch circuit supplies two or more
box and box size. outlets for lighting and appliances. This
- Fixture wires and conductors that do type of circuit may be referred to as a
not leave the box, such as an internal lighting circuit; this is a carryover from
grounding wire, are not counted. the days when electricity was first used
- One conductor is deducted for one or in buildings and its predominant
more grounding conductors that enter purpose was lighting. There are usually
the box. a number of general-purpose branch
- Conductors in an electrical box must circuits supplying lights and outlets in
have sufficient open-air space to different rooms around a residence,
prevent overheating. commercial or industrial building.
These recommended values are less than 03 Appliance Branch Circuit
those typically established as maximum values - This is the type of branch circuit that
in the electrical code. supplies energy to one or more outlets
- They are recommendable because: to which appliances are to be
✓ Allow for less cumbersome connected. They supply fixed electric
installation equipment, such as refrigerators,
✓ Based on industry experience washers, and other large appliances
- They allow for future expansion. and electrical devices. Appliance
branch do not supply lighting fixtures.
BRANCH CIRCUIT REQUIREMENTS Appliance branch circuits cannot
exceed 20 A.
Branch circuiting 04 Multiwire Branch Circuit
A building electrical system consists of several - A branch circuit consisting of two or
circuits that extend out from the switchboard or more undergrounded (hot) conductor
panel board. A branch circuit is that portion of having a voltage between them and a
the building wiring system that extends beyond common neutral (grounded) conductor
the final over current protection device that is that is shared between the ungrounded
protecting the circuit. conductors such as in a 120/240 V
- It provides power from a circuit breaker three-wire circuit. Other branch circuits
or fuse in the panel board to single or specific to a particular occupancy may
multiple points of use called outlets. also be required. For example, the
- An outlet is a point in a wiring system following branches are required in
where current is taken to supply an health care facilities such as hospitals,
appliance, piece of equipment, or nursing homes, and dental facilities.
lighting installation. 05 Life Safety Branch Circuit
- A branch circuit is composed of an - An emergency system of feeders and
overcurrent protection device (fuse or branch circuit that provides adequate
power to patients and personnel. It
Quen - Electrical Engineering Utilities – Chapter 1 to 3
circuit serving only receptacles to its rating These circuits serve two or more outlets to
divided by 11/2 A. which only appliances are connected. In
• A 20 A, 120 V branch circuit would have a dwelling units, two or more 20 A small
theoretical maximum of 2400 VA (20 A 120 appliance circuits for convenience receptacle
V 2400 VA), but it is common practice to outlets in the kitchen, dining room, pantry, and
limit the connected load to 80% of the breakfast room are required. These are in
circuit rating (e.g., 20 A 120 V - 80% 1920 addition to the other outlets required. Small
VA). appliance circuits can supply any refrigerators
• When the load on the circuit will be a and freezers, but not an electric range or oven.
continuous operating load (e.g., for store
lights), the total load should not exceed Tables 19.12 through 19.17 provide
80% of the circuit rating. The lighting load recommendations for circuiting common
must include any ballasts, transformers, or appliances and pieces of equipment.
autotransformers, which are part of the Manufacturers' data should always be used in
lighting system. Because a 15 A branch computations.
has a full rating of 1800 VA, the limit would
be 80%, or 12 A and 1440 VA (e.g., 15 A Continuous Load
120 V 80% 1440 VA). A 20 A, 2400 VA A continuous load is a connected load that
branch would be limited to 16 A and 1920 operates for 3 hr or more at any time. Many
VA of connected load. electrical loads fit within this category such as
circuits serving office and classroom lighting
Individual Circuits installations. When determining a circuit rating,
These circuits provide power to a single outlet most loads deemed continuous must have a
such as a receptacle serving a range, clothes circuit rating calculated at 125% of the circuit's
dryer, or copy machine. Although there are no connected load.
size limitations for an individual circuit rating,
appliances and equipment rated at above 25 A The intent behind the 125% factor is from
must be placed on a separate individual circuit the inability of the overcurrent protection
because of the 50% maximum single load device to handle a continuous load without
limitation in general purpose circuiting. Usually overheating; that is, most circuit breakers
connected loads above 20 A are placed on an trip if they carry their rated load for any
individual circuit. It is good practice to provide significant time period. In many
individual circuits for loads above 1500 W. installations, it is good practice for all
Motors above 1/8 hp should also be placed on connected loads not to exceed 80% of the
an individual circuit. individual circuit rating.
Generally, individual circuits are required Another way of looking at this is that the
for the following appliances and connected load on a continuous-load
equipment: circuit should not exceed 80% of the
•Kitchen range individual circuit rating. Thus, the maximum
•Oven continuous load on a 20 A circuit is 16 A
•Electric water heater (80% of 20 is 16).
•Microwave (built-in)
• Waste disposal There are several exceptions to application
• Furnace of the continuous-load multiplier. On
• Boiler circulating pump motor circuits involving electric space heating, the
• Dishwasher connected load is taken at 100% of the load
•HVAC air-handling unit even though it may operate for more than 3
•Large machinery hr at a time. Any branch circuit serving a
•Large equipment single motor or a device containing a motor
• Clothes washer should have an ampacity (amperage
• Clothes dryer rating) of not less than 125% of the motor's
full load current rating (this is the same as
Appliance Circuits saying that no motor can exceed 80% of
the branch circuit rating).
Quen - Electrical Engineering Utilities – Chapter 1 to 3
drawings as a luminaire (light fixture) • This load includes the total of all general
schedule. lighting, appliance, and equipment loads in
- The architectural designer or even the the building.
building owner may decide the fixtures • The demand load allowed by the code
that are to be used, often with takes into account that all of the electrical
assistance of the electrical designer. connections will not be in use at one time
4.) Lay out the switches required to control 1. Compute the general lighting load. This is
the lights, appliances, equipment, and any calculated for all types of occupancies based
desired receptacles. The discussion of on the unit load given in the table (in watts)
switches outlines where they are most times the square footage of the building
commonly used, and the symbols used. • The minimum general lighting load, based
5.) Locate the panelboard in a convenient on the specified 3 VA/ft2 for residence:
location. The location must be accessible table (in watts) times the square footage of
(e.g., not in a closet or storage room, the building
unless dedicated). Follow the requirements • 3 VA ft x 2214 ft² = 6642 VA
outlined earlier. 2. Compute the appliance and laundry circuit
6.) Layout circuiting for large appliances load. Code requires at least two 20 A appliance
and equipment served by an individual branch circuits for the kitchen. The load is
branch circuit. Examples of individual based on 1500 VA for each appliance branch
branch circuits would be circuits from the circuit in the kitchen. In addition, one 20 A
panelboard to a dishwasher (120 V), circuit is required for laundry room appliances.
electric clothes dryer (120/240 V), an • For the residential system example, this
electric oven or range (120/240 V), or an results in a total of three 20 A branch
electric water heater (240 V). circuits for appliances:
7.) Layout circuiting for lighting and Appliance and laundry load = 3 circuits x
convenience receptacles on general 1500 VA = 45000 V
purpose (lighting) branch circuits. Usually
15 A and 20 A general purpose branch SERVICE ENTRANCE DESIGN
circuits are used for convenience The service entrance conductors and
receptacles, luminaires, and small equipment are designed based on the
appliances. computed total demand load.
- The designer must comply with code
requirements. In practice, a good designer 1. The minimum service entrance size is found
tends to be a little more conservative. by dividing the demand load for the building by
Because more and more small appliances the voltage serving the building. Most
and equipment are being purchased and commonly, 240 V service is used. For the
connected to receptacles, the designer residential system example, the total demand
must anticipate future requirements... load of 33 175 VA is divided by the 240 V
8.) Lay out the panel circuits, either on the service for a mini- mum service entrance of 143
drawing or in a table. A:
- In large designs, with more than one
panel, this provides the electrician with a minimum service entrance = 33 175
schedule of what circuits will be served VA/240 V = 138.2 or 138 A
from what box. Although a panel board
layout is not often done for a residence, it 2. The next step is sizing the service entrance
is helpful to both the electrician and the conductors and any conductors between the
designer if one is included. For commercial service equipment and the branch overcurrent
projects, a panel layout is almost always device (circuit breaker or fuse). The feeder size
included. is based on the computed demand load.
LOAD COMPUTATIONS For the residential system example,
• Load computations involve computing the using XHHW 175 C 167 F) aluminum
demand load for a building system or a service entrance conductors and a 150
distribution system extending from a A load, as calculated:
panelboard.
Quen - Electrical Engineering Utilities – Chapter 1 to 3
GENERATORS
-a mechanical device that converts mechanical
energy into electrical energy
ELECTRIC METER
-an instrument that is used by the utility company to
measure and record electrical energy consumed.
Quen - Electrical Engineering Utilities – Chapter 1 to 3
PANELBOARD
FEED-THROUGH METER -Wall-mounted, single unit of one or more metal
-used in building services rated up to about 400 A cabinets, including buses, automatic overcurrent
-this meter is a small electric motor protection devices (fuses or circuit breakers).
-with a speed that is proportional to the power ▪ Equipped with or without controlling
consumed switches for light, heat, and power circuits,
▪ It consists of a sheet of a metal box, a
CURRENT-TRANSFORMER (C/T) cabinet, and a cover that encloses and
-used in building services rated above about 400 A protects the interior section containing
-measure amperage through each ungrounded vertical buses used to distribute power.
(hot) conductor. ▪ It may be referred to as a power panel or
-housed in an enclosure called a C/T cabinet that is load center typically used in residential
part of the service entrance equipment applications.
SERVICE DISCONNECT
-a required part of the service entrance equipment
allows electrical service from the utility company to
be switched off so that power is disconnected to the
building installation. It is a set of fuses or a circuit
breaker that protects the service entrance
conductors.
TRANSFORMERS
SWITCH BOARD -Usually, it works as a regulator to change the
-a large cabinet or assembly of metal cabinets with voltage, current and phase of electrical power
electrical switches and devices transmitted and distributed from the primary power
connects/disconnects electric circuits, either source to a specific substation.
manual or automatic. ▪ A building transformer is rated in kVA.
Commonly from 3, 6, 9, 15, 25, 30, 37.5,
▪ Generally distributes power to 45, 50. 75. 112.5, 150, 225, 300, 500, 750,
transformers, panelboards, control 1000, 1500 kVA, and larger.
equipment, and ultimately to individual
system loads. EVERY TRANSFORMER COMES WITH A
▪ Contains overcurrent protection devices NAMEPLATE THAT TYPICALLY IDENTIFIES:
(fuses or circuit breakers) and instruments
designed to neutralize/divide a large kVA
amount of electrical power into suitable Primary and secondary voltage
levels for other electrical equipment. Impedance (if 25 KVA or larger)
Required clearances (if it has ventilating
-Floor mounted, rated for current levels of 1200 to openings
6000 amperes (A), and voltages below 600 volts
(V). STEP-DOWN TRANSFORMER
-has a secondary voltage that is less than its
primary voltage.
Quen - Electrical Engineering Utilities – Chapter 1 to 3
STEP-UP TRANSFORMER
-one with a secondary voltage that is greater than
its primary voltage.
DELTA-CONNECTED TRANSFORMER (A)
▪ windings are connected in series, forming a
TRANSFORMERS HEAT HAZARD
triangle, thus resembling the Greek letter
▪ Heat build up prematurely deteriorates a
Delta (A). only a single voltage level is
transformer. The transformer's desirable
available: the phase-to- phase voltages.
operation level is at only 20°F (11°C):
▪ Obtaining other voltages can only be done
above this rate will cut the transformer's life
using step-up or step-down transformers.
by half.
▪ It is caused by internal losses from loading,
high ambient air temperature, and solar
radiation in exterior locations
-A 7200/240/120 V AC is a single-phase
transformer commonly used in most
residential and small commercial DELTA-WYE (A-Y) TRANSFORMER
applications. -an electrical device that converts three-phase
electric power without a neutral wire into three-
-A 7200 V, two-wire power is transformed phase power with a neutral wire.
and stepped down to a 120/240 V AC, -Additional transformer combinations such as wye-
three-wire system. wye (Y-Y), delta- delta (A-A), and wye- delta (Y-A)
are available.
closet transformers have efficiencies of load to 80% when the load is continuous for
98% or above. over 3 hours.
heating, or lighting function through the use - typically connected to a flexible cord that is
of electrical energy. attached to a portable appliance, light. or
▪ Electric motors, air conditioning. equipment
refrigeration and heating units. signs,
industrial machinery, cranes, hoists, Receptacles and plugs offer a simple way to
elevators, and escalators fit in the category attach or detach an appliance or piece of equipment
equipment. of utilization to/from an electrical outlet.
APPLIANCE
-end-use piece of utilization equipment designed to
perform a specific function such as cooking,
cleaning, cooling, or heating.
FIXED APPLIANCES
-permanently attached installations such as a built-
in electric cook top or oven
STATIONARY APPLIANCES
-situated and used at a specific location but can be
moved to another outlet such as a refrigerator,
clothes washer, or clothes dryer.
PORTABLE APPLIANCES
-appliances that can be easily carried or moved
such as a hair dryer or toaster
ELECTRICAL DEVICE
-An electrical device is a component in an electrical
system that is designed to carry but not use According to National Electrical Manufacturing
electricity. Association (NEMA) standards:
- This includes components such as - The different types of receptacles and plugs are
switches, receptacles, and relays. identified by a specific designation. The NEMA
designation ties the number and configuration of the
OUTLET slots in the receptacle and the matching slots in a
-the location in a branch circuit where electricity is plug to the voltage and amperage permitted.
used. For example, a lighting outlet is the location
in a branch circuit where conductors provide power E.g., 5-15R and 5-15P designation is
to a light fixture. associated with the matching receptacle
- female connecting device with slotted (R) and plug (P) that are rated at 15
contacts. Installed at an outlet or on amperes and 125 V and have equipment-
equipment, where it is intended to easily grounding capability. These devices are the
establish an electrical connection with an matching receptacles and plugs commonly
inserted plug. associated with residential and commercial
wall-mounted outlets
PLUG
-a male connecting device that has two or more -Different receptacles and plug combinations are
prongs that are inserted into a receptacle to connect generally tied to a specific application.
to an electrical circuit.
E.g., The 5-15R receptacle discussed
earlier serves as a common outlet for
portable lights and small appliances, while
Quen - Electrical Engineering Utilities – Chapter 1 to 3
the 14-50R and 14-50R receptacle/plug divert current from one conductor path to
configuration is typically used to connect a another.
kitchen range or other heavy-duty electrical - Switches are rated by purpose, voltage,
equipment to an outlet. and amperage, and are classified for AC or
DC.
The screw terminals on a receptacle are color
coded: - Safety switches are used in building
electrical systems. They are designed to
BRASS-COLORED SCREWS reduce the possibility of contact with bare
-are for connection to the ungrounded conductor. electrical conductors and have current
SILVER-COLORED SCREWS are for the grounded interrupting capability.
or neutral conductor: and
GREEN-COLORED SCREWS are for the KINDS OF SWITCHES
equipment grounding conductor.
and requirements are less stringent. They are -used to provide control from one point by opening
used on lighting, heating, appliance, and or closing the ungrounded conductor in the circuit
intermittent motor loads. Ratings up to 600 V are THREE-WAY (S3) & FOUR-WAY (54)
available. -used when multiple control points are needed.
SWITCHING CONFIGURATIONS
-switches provide control from one or more points
in a circuit
SINGLE-POLE, SINGLE-THROW SWITCH (S)
Quen - Electrical Engineering Utilities – Chapter 1 to 3
TIME CLOCKS
-can be used to control the time period that a
piece of equipment or a lighting installation
operates.
ELECTRONIC TIMERS
-allow greater flexibility as they can easily be set for
7-day cycles.
2.5 CONDUCTORS
- They do require relay switching on large
loads.
CONDUCTORS
-any material that conducts electrical current.
-A wire is a common electrical conductor.
-Electrical conductors are either solid or stranded.
PHOTOCELL CONTROLS
-sense light and open or close a circuit with the
presence of light. •They can be used to control night
lighting in lieu of a time clock.
- more likely to break if subjected to frequent -contains more than one conductor bundled
flexing than stranded conductors together in a factory assembly of wires.
- An outer sheathing encases and protects
CONDUCTOR MATERIALS the conductors. simplifying the installation
of multiple wiring.
SILVER
-the best electrical conductor material (other than a TYPES OF CABLE
superconductor material) it has the least resistance
of common materials Nonmetallic-Sheathed Cable
- silver wiring was used in the first mainframe Underground Feeder Cable
computer. Service Entrance Cable
- just like gold (excellent conductor), silver is Armored Cable
too costly for building installation. Metal-Clad Cable
COPPER
-used in building conductor (wiring) installations as
a compromise between good conductivity and
economy.
- The wire core is aluminum with a thin
coating of copper that is metallurgically
bonded to the core
ALUMINUM
- has significant weight and cost advantages over
copper. Copper does, however, conduct electricity OTHER TYPES OF CABLE
better than aluminum, so an aluminum wiring
installation requires a thicker gauge. FLAT CONDUCTOR CABLE
- Also, extra care in splicing and terminating -a wiring system conductors and special connectors
aluminum wire is important. and terminals.
- composed of very thin cable with three or
CONDUCTOR INSULATION more
-covered with insulation that provides protection of - designed to rest between the topside of a
the conductor material. smooth continuous subfloor and carpet
- prevents loss of power and the danger squares.
electrical isolation and some physical of
short circuits and ground faults.
THERMOSTAT CABLE
COMMON CONDUCTORS - used in applications with voltages less than 30 V.
such as wiring to doorbells, chimes, and
thermostats.
- generally contains No. 16 AWG or No. 18
AWG conductors that are bundled in a thin
plastic sheathing.
CABLE
Quen - Electrical Engineering Utilities – Chapter 1 to 3
CONDUCTOR AMPACITY
-the maximum current that a conductor can carry
continuously under the conditions of use without
exceeding its temperature rating.
- Current is measured in amperes or "amps."
You must use the correct size wire for the
current (load) requirement of the circuit to
prevent the wire from overheating. ELECTRICAL BOXES
-are metal and non-metallic enclosures that hold
AMPACITY IS BASED ON THE FOLLOWING: devices such as switches or outlets and safety
permit wiring connections boxes are in four primary
Wire thickness (thicker wires have larger shapes: square, rectangular. octagonal, or round
cross-sectional areas and can carry more electrical - boxes can be joined together to
current without overheating) accommodate multiple outlets or switches.
Type of conductor material (at a specific gangs, or four gang boxes namely, two-
current and conductor size, aluminum produces gang, three gangs, four gang boxes
more heat than copper)
Insulation and sheathing type (some
insulation materials handle heat better than others)
Number of conductors bundled in the
sheathing or in the proximity of one another (more
conductors concentrate heat in an area)
Quen - Electrical Engineering Utilities – Chapter 1 to 3
PULLBOX
-kind of junction box that allows access to a
raceway for snaking conductors through
the raceway
KNOCKOUT
-in most boxes and enclosures, it con be
easily removed to allow wiring to enter the
box
COVER PLATES
-required for various single or combinations
of switches, convenience outlets, blank CONDUIT AND RACEWAYS
covers, and dimmers; plastic is a commonly
used material RACEWAY
-attached with screws to the switch or -an enclosed channel such as conduit, tube, or
receptacles gutter used for holding wires, cables, or bus bars
-all the boxes should be finished with a - in some cases, metal raceways that are
cover plate fully bonded serve to provide a path for the
flow of fault current to ground
Quen - Electrical Engineering Utilities – Chapter 1 to 3
FEEDER BUSWAY
-A type of busway system that used to deliver a
large amount of power with low voltage drop
- available in sizes from 600 A to several
thousand amps
INDUCTION MOTORS
-These motors use electromagnetic induction to
cause the motor rotor to turn.
- Repulsion-start induction motors are
capable of handling heavy starting loads.
CAPACITOR MOTOR
-This type of motor operates on single-phase AC
only.
- Capacitor-start motors have a capacitor The specifications of an electric motor are
that stores and discharges energy to help typically listed on the nameplate. Information
start the motor rotor. provided may include:
- Capacitor-run motors have one or more
- Manufacturer's type and frame designation
capacitors to help start and run the motor.
Insulation system designation
- It is more efficient and has a better starting
- Horsepower output
torque than the split-phase motor.
- Revolutions/minute at rated load
THREE-PHASE MOTORS - Power factor
-Large motors operate more efficiently on three- - Frequency
phase AC power. - Number of phases
- A single-phase motor rated at 71/2 hp - Maximum ambient temperature for which
motor is designed
draws a large amount of instantaneous
- Rated load current
current at startup (up to 200 A on a 240 V
- Voltage
single-phase circuit).
PORTABLE TYPE
-frequently used in construction and outdoor
GROUND FAULT INTERRUPTION settings with electric tools. mowers, trimmers, and
-Unintentional flow of electrical current between a similar devices.
power source, such as ungrounded (hot) wire, and - It should not be used as a permanent
a grounded surface. alternative to a regular GFCI.
- Occurs when electrical current leaks - They are intended to be used when you
escapes to the ground. must bring power from an unprotected
outlet into a hazardous situation
A ground fault becomes a danger because:
- Only a very low current is required to affect ARC FAULT PROTECTION
human heart rhythm.
Quen - Electrical Engineering Utilities – Chapter 1 to 3
Arc Fault
-unintentional electrical discharge characterized by
the low and erratic current.
- arcing generates high-intensity heat and
expels burning particles, which can easily
ignite combustible materials.
PARALLEL ARCING FAULTS
- caused by loose, damaged, or corroded
-Result from direct contact of two wires of opposite
wires and terminals.
polarity.
- Current residential breakers only detect
- Frayed/ruptured appliances or extension
and react to power overloads. not arc faults
cords
- staples or other fasteners that pierce or
COMMON CAUSES OF FAULT ARCS AND THUS
pinch insulation on construction wire and
POSSIBLE FIRE IN WIRING
appliance or extension cords
- Cracked wire or cord insulation caused by
age, heat, corrosion, or bending stress
EXTREMELY LOW-FREQUENCY
ELECTROMAGNETIC FIELDS
-silent, invisible magnetic fields produced any time
electricity runs through a wire, an appliance, or
piece of equipment.
ZENER DIODE
-A secondary surge protection component used for
accurate clamping of surge voltages.
-It has a quicker response time than the GDTS and
provides a more accurate clamping voltage than
MOVS.
THERMISTORS
-are the most used inrush current limiter for power
supplies and motors.
-a thermally sensitive resistor with a resistance that
changes significantly and predictably due to
temperature changes.
-When equipment is first turned on. the NTC
thermistor is cooled, and its resistance is high,
HYBRID CIRCUIT limiting current flow.
-A circuit comprising different types of surge -Resistance decreases rapidly as the thermistor
protection components, taking advantage of each self-heats, allowing near-full current to flow (at 612).
component's strengths. A hybrid may combine the -A disadvantage is that when the NTC thermistor is
high surge capability of a GDT with the accurate switched off, it initially retains heat, so, it offers little
voltage clamping of a surge diode. resistance and cannot limit the inrush current until
heat is dissipated. .
-The cooldown time varies according to the device,
its mounting method, and ambient temperature.
LIGHTNING PROTECTION
INRUSH CURRENT OR INPUT SURGE - -Lightning discharges have been measured
CURRENT from 2000 A to more than 200 000 A, with
rise times to peak current of less than 10
microseconds (10 millionths of a second).
As a result, lightning causes more damage,
injuries. and deaths each year than
fornadoes, hurricanes, or floods.
- -Lightning discharges have been measured
from 2000 A to more than 200 000 A. with
rise times to peak current of less than 10
microseconds (10 millionths of a second).
- It refers to the peak instantaneous current, As a result, lightning causes more damage.
measured in amperes (A), drawn by an injuries, and deaths each year than
electrical appliance or piece of equipment tornadoes, hurricanes, or floods.
(e.g. power supplies, AC motors, lamps,
and lighting ballasts) is first turned on. BENJAMIN FRANKLIN
- An inrush current can also be reduced by -He first suggested protecting buildings and other
an inrush current limiter, which protects structures from the effects of direct lightning strikes
circuits that encounter high inrush loads up by the use of protective conductors.
Quen - Electrical Engineering Utilities – Chapter 1 to 3