Multi V 5 Outdoor Units

1. Specifications
HP 8 10
Combination Unit ARUM080LTE5 ARUM100LTE5
ARUM080LTE5 ARUM100LTE5
Model Name
Independent Unit

kW 22.4 28.0
Cooling
Btu/h 76,400 95,500
Capacity
kW 25.2 31.5
Heating
Btu/h 86,000 107,500
Cooling kW 4.28 5.22
Input
Heating kW 4.78 5.92
EER 5.23 5.36
COP 5.27 5.32
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev 43.8 62.1
Number of Revolution rev/min 3,600 3,600
Compressor
Motor Output x Number W x No. 4,200 × 1 5,300 × 1
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W 1,200 × 1 1,200 × 1
3/min 240 × 1 240 × 1
m
Air Flow Rate(High)
Fan ft3/min 8,476 × 1 8,476 × 1
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 9.52(3/8) 9.52(3/8)
Connections Low Pressure Gas mm(inch) 19.05(3/4) 22.2(7/8)
#1 High Pressure Gas mm(inch) 15.88(5/8) 19.05(3/4)
Pipe Liquid mm(inch) 9.52(3/8) 9.52(3/8)
Connections
#2 Gas mm(inch) 19.05(3/4) 22.2(7/8)
mm (930 × 1,690 × 760) × 1 (930 × 1,690 × 760) × 1
Dimensions(W x H x D)
inch (36-5/8 × 66-17/32 × 29-29/32) × 1 (36-5/8 × 66-17/32 × 29-29/32) × 1
kg 198 × 1 215 × 1
Net Weight
lbs 437 × 1 474 × 1
Sound Cooling dB(A) 58.0 58.0
Pressure Level Heating dB(A) 59.0 59.0
Sound Power Cooling dB(A) 77.0 78.0
Level Heating dB(A) 78.0 79.0
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

2
Multi V 5 Outdoor Units

1. Specifications
HP 8 10
Combination Unit ARUM080LTE5 ARUM100LTE5
ARUM080LTE5 ARUM100LTE5
Model Name
Independent Unit

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Devices Compressor/Fan
Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 7.5 9.5
Precharged Amount
Refrigerant lbs 16.5 20.9
t-CO2 eq 15.7 19.8
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 6.99 - 6.64 - 6.40 8.53 - 8.10 - 7.81
Current Heating A 7.81 - 7.42 - 7.15 9.68 - 9.19 - 8.86
Number of maximum connectable indoor units *** 13(20) 16(25)
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

3
Multi V 5 Outdoor Units

1. Specifications
HP 12 14
Combination Unit ARUM120LTE5 ARUM140LTE5
ARUM120LTE5 ARUM140LTE5
Model Name
Independent Unit

kW 33.6 39.2
Cooling
Btu/h 114,600 133,800
Capacity
kW 37.8 44.1
Heating
Btu/h 129,000 150,500
Cooling kW 6.84 8.39
Input
Heating kW 8.26 9.72
EER 4.91 4.67
COP 4.58 4.54
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev 62.1 62.1
Number of Revolution rev/min 3,600 3,600
Compressor
Motor Output x Number W x No. 5,300 × 1 5,300 × 1
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W 1,200 × 1 900 × 2
3/min 240 × 1 320 × 1
m
Air Flow Rate(High)
Fan ft3/min 8,476 × 1 11,301 × 1
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 12.7(1/2) 12.7(1/2)
Connections Low Pressure Gas mm(inch) 28.58(1-1/8) 28.58(1-1/8)
#1 High Pressure Gas mm(inch) 19.05(3/4) 22.2(7/8)
Pipe Liquid mm(inch) 12.7(1/2) 12.7(1/2)
Connections
#2 Gas mm(inch) 28.58(1-1/8) 28.58(1-1/8)
mm (930 × 1,690 × 760) × 1 (1,240 × 1,690 × 760)×1
Dimensions(W x H x D)
inch (36-5/8 × 66-17/32 × 29-29/32) × 1 (48-13/16 × 66-17/32 × 29-29/32) × 1
kg 215 × 1 237 × 1
Net Weight
lbs 474 × 1 522 × 1
Sound Cooling dB(A) 59.0 60.0
Pressure Level Heating dB(A) 60.0 61.0
Sound Power Cooling dB(A) 79.0 82.0
Level Heating dB(A) 80.0 84.0
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

4
Multi V 5 Outdoor Units

1. Specifications
HP 12 14
Combination Unit ARUM120LTE5 ARUM140LTE5
ARUM120LTE5 ARUM140LTE5
Model Name
Independent Unit

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Devices Compressor/Fan
Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 9.5 13.5
Precharged Amount
Refrigerant lbs 20.9 29.8
t-CO2 eq 19.8 28.2
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 11.17 - 10.62 - 10.23 13.71 - 13.02 - 12.55
Current Heating A 13.49 - 12.82 - 12.36 15.88 - 15.09 - 14.54
Number of maximum connectable indoor units *** 20(30) 23(35)
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

5
Multi V 5 Outdoor Units

1. Specifications
HP 16 18
Combination Unit ARUM160LTE5 ARUM180LTE5
ARUM160LTE5 ARUM180LTE5
Model Name
Independent Unit

kW 44.8 50.4
Cooling
Btu/h 152,900 172,000
Capacity
kW 50.4 56.7
Heating
Btu/h 172,000 193,500
Cooling kW 10.41 9.83
Input
Heating kW 12.39 11.94
EER 4.30 5.13
COP 4.07 4.75
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev 62.1 62.1 × 1 + 43.8 × 1
Number of Revolution rev/min 3,600 3,600 × 2
Compressor
Motor Output x Number W x No. 5,300 × 1 5,300 × 1 + 4,200 × 1
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W 900 × 2 900 × 2
3/min 320 × 1 320 × 1
m
Air Flow Rate(High)
Fan ft3/min 11,301 × 1 11,301 × 1
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 12.7(1/2) 15.88(5/8)
Connections Low Pressure Gas mm(inch) 28.58(1-1/8) 28.58(1-1/8)
#1 High Pressure Gas mm(inch) 22.2(7/8) 22.2(7/8)
Pipe Liquid mm(inch) 12.7(1/2) 15.88(5/8)
Connections
#2 Gas mm(inch) 28.58(1-1/8) 28.58(1-1/8)
mm (1,240 × 1,690 × 760)×1 (1,240 × 1,690 × 760)×1
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 1 (48-13/16 × 66-17/32 × 29-29/32) × 1
kg 237 × 1 300 × 1
Net Weight
lbs 522 × 1 661 × 1
Sound Cooling dB(A) 60.5 61.0
Pressure Level Heating dB(A) 61.5 62.0
Sound Power Cooling dB(A) 83.0 85.0
Level Heating dB(A) 85.0 86.0
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

6
Multi V 5 Outdoor Units

1. Specifications
HP 16 18
Combination Unit ARUM160LTE5 ARUM180LTE5
ARUM160LTE5 ARUM180LTE5
Model Name
Independent Unit

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Devices Compressor/Fan
Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 13.5 16.0
Precharged Amount
Refrigerant lbs 29.8 35.3
t-CO2 eq 28.2 33.4
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 17.01 - 16.16 - 15.57 16.06 - 15.26 - 14.70
Current Heating A 20.24 - 19.23 - 18.53 19.51 - 18.53 - 17.86
Number of maximum connectable indoor units *** 26(40) 29(45)
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

7
Multi V 5 Outdoor Units

1. Specifications
HP 20 22
Combination Unit ARUM200LTE5 ARUM220LTE5
ARUM200LTE5 ARUM220LTE5
Model Name
Independent Unit

kW 56.0 61.6
Cooling
Btu/h 191,100 210,200
Capacity
kW 63.0 69.3
Heating
Btu/h 215,000 236,500
Cooling kW 11.51 14.15
Input
Heating kW 14.69 16.76
EER 4.87 4.35
COP 4.29 4.13
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev 62.1 × 1 + 43.8 × 1 62.1 × 1 + 43.8 × 1
Number of Revolution rev/min 3,600 × 2 3,600 × 2
Compressor
Motor Output x Number W x No. 5,300 × 1 + 4,200 × 1 5,300 × 1 + 4,200 × 1
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W 900 × 2 900 × 2
3/min 320 × 1 320 × 1
m
Air Flow Rate(High)
Fan ft3/min 11,301 × 1 11,301 × 1
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 15.88(5/8) 15.88(5/8)
Connections Low Pressure Gas mm(inch) 28.58(1-1/8) 28.58(1-1/8)
#1 High Pressure Gas mm(inch) 22.2(7/8) 28.58(1-1/8)
Pipe Liquid mm(inch) 15.88(5/8) 15.88(5/8)
Connections
#2 Gas mm(inch) 28.58(1-1/8) 28.58(1-1/8)
mm (1,240 × 1,690 × 760)×1 (1,240 × 1,690 × 760)×1
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 1 (48-13/16 × 66-17/32 × 29-29/32) × 1
kg 300 × 1 300 × 1
Net Weight
lbs 661 × 1 661 × 1
Sound Cooling dB(A) 62.0 64.5
Pressure Level Heating dB(A) 64.5 65.5
Sound Power Cooling dB(A) 86.0 86.0
Level Heating dB(A) 87.0 88.0
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

8
Multi V 5 Outdoor Units

1. Specifications
HP 20 22
Combination Unit ARUM200LTE5 ARUM220LTE5
ARUM200LTE5 ARUM220LTE5
Model Name
Independent Unit

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Devices Compressor/Fan
Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 16.0 16.0
Precharged Amount
Refrigerant lbs 35.3 35.3
t-CO2 eq 33.4 33.4
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 18.80 - 17.86 - 17.22 23.12 - 21.96 - 21.17
Current Heating A 23.99 - 22.79 - 21.97 27.39 - 26.02 - 25.08
Number of maximum connectable indoor units *** 32(50) 35(56)
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

9
Multi V 5 Outdoor Units

1. Specifications
HP 24 26
Combination Unit ARUM240LTE5 ARUM260LTE5
ARUM240LTE5 ARUM260LTE5
Model Name
Independent Unit

kW 67.2 72.8
Cooling
Btu/h 229,300 248,400
Capacity
kW 74.3 74.3
Heating
Btu/h 253,400 253,400
Cooling kW 15.91 18.03
Input
Heating kW 18.80 19.15
EER 4.22 4.04
COP 3.95 3.88
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev 62.1 × 2 62.1 × 2
Number of Revolution rev/min 3,600 × 2 3,600 × 2
Compressor
Motor Output x Number W x No. 5,300 × 2 5,300 × 2
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W 900 × 2 900 × 2
3/min 320 × 1 320 × 1
m
Air Flow Rate(High)
Fan ft3/min 11,301 × 1 11,301 × 1
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 15.88(5/8) 19.05(3/4)
Connections Low Pressure Gas mm(inch) 34.9(1-3/8) 34.9(1-3/8)
#1 High Pressure Gas mm(inch) 28.58(1-1/8) 28.58(1-1/8)
Pipe Liquid mm(inch) 15.88(5/8) 19.05(3/4)
Connections
#2 Gas mm(inch) 34.9(1-3/8) 34.9(1-3/8)
mm (1,240 × 1,690 × 760)×1 (1,240 × 1,690 × 760)×1
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 1 (48-13/16 × 66-17/32 × 29-29/32) × 1
kg 310 × 1 310 × 1
Net Weight
lbs 683 × 1 683 × 1
Sound Cooling dB(A) 65.0 65.0
Pressure Level Heating dB(A) 67.0 67.0
Sound Power Cooling dB(A) 88.0 88.0
Level Heating dB(A) 90.0 90.0
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

10
Multi V 5 Outdoor Units

1. Specifications
HP 24 26
Combination Unit ARUM240LTE5 ARUM260LTE5
ARUM240LTE5 ARUM260LTE5
Model Name
Independent Unit

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Devices Compressor/Fan
Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 17.0 17.0
Precharged Amount
Refrigerant lbs 37.5 37.5
t-CO2 eq 35.5 35.5
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 25.99 - 24.69 - 23.80 29.46 - 27.98 - 26.97
Current Heating A 30.71 - 29.18 - 28.12 31.29 - 29.72 - 28.65
Number of maximum connectable indoor units *** 39(61) 42(64)
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

11
Multi V 5 Outdoor Units

1. Specifications
HP 22' 24'
Combination Unit ARUM221LTE5 ARUM241LTE5
ARUM120LTE5 ARUM120LTE5
Model Name ARUM100LTE5 ARUM120LTE5
Independent Unit

kW 61.6 67.2
Cooling
Btu/h 210,200 229,300
Capacity
kW 69.3 75.6
Heating
Btu/h 236,500 257,900
Cooling kW 12.06 13.68
Input
Heating kW 14.18 16.52
EER 5.11 4.91
COP 4.89 4.58
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev 62.1 × 2 62.1 × 2
Number of Revolution rev/min 3,600 × 2 3,600 × 2
Compressor
Motor Output x Number W x No. 5,300 × 2 5,300 × 2
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W (1200 × 1) + (1,200 × 1) (1200 × 1) + (1,200 × 1)
3/min (240 × 1) + (240 × 1) (240 × 1) + (240 × 1)
m
Air Flow Rate(High)
Fan ft3/min (8,476 × 1) + (8,476 × 1) (8,476 × 1) + (8,476 × 1)
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 15.88(5/8) 15.88(5/8)
Connections Low Pressure Gas mm(inch) 28.58(1-1/8) 34.9(1-3/8)
#1 High Pressure Gas mm(inch) 28.58(1-1/8) 28.58(1-1/8)
Pipe Liquid mm(inch) 15.88(5/8) 15.88(5/8)
Connections
#2 Gas mm(inch) 28.58(1-1/8) 34.9(1-3/8)

mm (930 × 1,690 × 760) × 1 + (930 × 1,690 × (930 × 1,690 × 760) × 1 + (930 × 1,690 ×
760) × 1 760) × 1
Dimensions(W x H x D)
inch (36-5/8 × 66-17/32 × 29-29/32) × 1 + (36-5/8 × 66-17/32 × 29-29/32) × 1 +
(36-5/8 × 66-17/32 × 29-29/32) × 1 (36-5/8 × 66-17/32 × 29-29/32) × 1
kg (215 × 1) + (215 × 1) (215 × 1) + (215 × 1)
Net Weight
lbs (474 × 1) + (474 × 1) (474 × 1) + (474 × 1)
Sound Cooling dB(A) 61.5 62.0
Pressure Level Heating dB(A) 62.5 63.0
Sound Power Cooling dB(A) 81.5 82.0
Level Heating dB(A) 82.5 83.0
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

12
Multi V 5 Outdoor Units

1. Specifications
HP 22' 24'
Combination Unit ARUM221LTE5 ARUM241LTE5
ARUM120LTE5 ARUM120LTE5
Model Name ARUM100LTE5 ARUM120LTE5
Independent Unit

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Devices Compressor/Fan
Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 19.0 19.0
Precharged Amount
Refrigerant lbs 41.9 41.9
t-CO2 eq 39.7 39.7
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 19.70 - 18.72 - 18.04 22.35 - 21.23 - 20.46
Current Heating A 23.17 - 22.01 - 21.22 26.99 - 25.64 - 24.71
Number of maximum connectable indoor units *** 35(44) 39(48)
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

13
Multi V 5 Outdoor Units

1. Specifications
HP 26' 28
Combination Unit ARUM261LTE5 ARUM280LTE5
ARUM140LTE5 ARUM160LTE5
Model Name ARUM120LTE5 ARUM120LTE5
Independent Unit

kW 72.8 78.4
Cooling
Btu/h 248,400 267,500
Capacity
kW 81.9 88.2
Heating
Btu/h 279,400 300,900
Cooling kW 15.23 17.26
Input
Heating kW 17.98 20.65
EER 4.78 4.56
COP 4.56 4.27
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev 62.1 × 2 62.1 × 2
Number of Revolution rev/min 3,600 × 2 3,600 × 2
Compressor
Motor Output x Number W x No. 5,300 × 2 5,300 × 2
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W (900 × 2) + (1,200 × 1) (900 × 2) + (1,200 × 1)
3/min (320 × 1) + (240 × 1) (320 × 1) + (240 × 1)
m
Air Flow Rate(High)
Fan ft3/min (11,301 × 1) + (8,476 × 1) (11,301 × 1) + (8,476 × 1)
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections Low Pressure Gas mm(inch) 34.9(1-3/8) 34.9(1-3/8)
#1 High Pressure Gas mm(inch) 28.58(1-1/8) 28.58(1-1/8)
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections
#2 Gas mm(inch) 34.9(1-3/8) 34.9(1-3/8)

mm (1,240 × 1,690 × 760) × 1 + (930 × 1,690 (1,240 × 1,690 × 760) × 1 + (930 × 1,690
× 760) × 1 × 760) × 1
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 1 + (48-13/16 × 66-17/32 × 29-29/32) × 1 +
(36-5/8 × 66-17/32 × 29-29/32) × 1 (36-5/8 × 66-17/32 × 29-29/32) × 1
kg (237 × 1) + (215 × 1) (237 × 1) + (215 × 1)
Net Weight
lbs (522 × 1) + (474 × 1) (522 × 1) + (474 × 1)
Sound Cooling dB(A) 62.5 62.8
Pressure Level Heating dB(A) 63.5 63.8
Sound Power Cooling dB(A) 83.8 84.5
Level Heating dB(A) 85.5 86.2
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

14
Multi V 5 Outdoor Units

1. Specifications
HP 26' 28
Combination Unit ARUM261LTE5 ARUM280LTE5
ARUM140LTE5 ARUM160LTE5
Model Name ARUM120LTE5 ARUM120LTE5
Independent Unit

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Devices Compressor/Fan
Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 23.0 23.0
Precharged Amount
Refrigerant lbs 50.7 50.7
t-CO2 eq 48.0 48.0
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 24.88 - 23.64 - 22.78 28.20 - 26.79 - 25.82
Current Heating A 29.37 - 27.91 - 26.90 33.74 - 32.05 - 30.89
Number of maximum connectable indoor units *** 42(52) 45(56)
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

15
Multi V 5 Outdoor Units

1. Specifications
HP 30 32
Combination Unit ARUM300LTE5 ARUM320LTE5
ARUM180LTE5 ARUM200LTE5
Model Name ARUM120LTE5 ARUM120LTE5
Independent Unit

kW 84.0 89.6
Cooling
Btu/h 286,600 305,700
Capacity
kW 94.5 100.8
Heating
Btu/h 322,400 343,900
Cooling kW 16.68 18.35
Input
Heating kW 20.20 22.95
EER 5.04 4.89
COP 4.68 4.39
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev (62.1 × 2) + (43.8 × 1) (62.1 × 2) + (43.8 × 1)
Number of Revolution rev/min 3,600 × 3 3,600 × 3
Compressor
Motor Output x Number W x No. (5,300 × 2) + (4,200 × 1) (5,300 × 2) + (4,200 × 1)
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W (900 × 2) + (1,200 × 1) (900 × 2) + (1,200 × 1)
3/min (320 × 1) + (240 × 1) (320 × 1) + (240 × 1)
m
Air Flow Rate(High)
Fan ft3/min (11,301 × 1) + (8,476 × 1) (11,301 × 1) + (8,476 × 1)
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections Low Pressure Gas mm(inch) 34.9(1-3/8) 34.9(1-3/8)
#1 High Pressure Gas mm(inch) 28.58(1-1/8) 28.58(1-1/8)
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections
#2 Gas mm(inch) 34.9(1-3/8) 34.9(1-3/8)

mm (1,240 × 1,690 × 760) × 1 + (930 × 1,690 (1,240 × 1,690 × 760) × 1 + (930 × 1,690
× 760) × 1 × 760) × 1
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 1 + (48-13/16 × 66-17/32 × 29-29/32) × 1 +
(36-5/8 × 66-17/32 × 29-29/32) × 1 (36-5/8 × 66-17/32 × 29-29/32) × 1
kg (300 × 1) + (215 × 1) (300 × 1) + (215 × 1)
Net Weight
lbs (661 × 1) + (474 × 1) (661 × 1) + (474 × 1)
Sound Cooling dB(A) 63.1 63.8
Pressure Level Heating dB(A) 64.1 65.8
Sound Power Cooling dB(A) 86.0 86.8
Level Heating dB(A) 87.0 87.8
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

16
Multi V 5 Outdoor Units

1. Specifications
HP 30 32
Combination Unit ARUM300LTE5 ARUM320LTE5
ARUM180LTE5 ARUM200LTE5
Model Name ARUM120LTE5 ARUM120LTE5
Independent Unit

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Devices Compressor/Fan
Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 25.5 25.5
Precharged Amount
Refrigerant lbs 56.2 56.2
t-CO2 eq 53.2 53.2
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 27.25 - 25.89 - 24.95 29.98 - 28.48 - 27.45
Current Heating A 33.0 - 31.35 - 30.22 37.49 - 35.61 - 34.33
Number of maximum connectable indoor units *** 49(60) 52(64)
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

17
Multi V 5 Outdoor Units

1. Specifications
HP 34 36
Combination Unit ARUM340LTE5 ARUM360LTE5
ARUM220LTE5 ARUM240LTE5
Model Name ARUM120LTE5 ARUM120LTE5
Independent Unit

kW 95.2 100.8
Cooling
Btu/h 324,800 343,900
Capacity
kW 107.1 112.1
Heating
Btu/h 365,400 382,300
Cooling kW 21.00 22.76
Input
Heating kW 25.02 27.06
EER 4.55 4.45
COP 4.28 4.14
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev (62.1 × 2) + (43.8 × 1) 62.1 × 3
Number of Revolution rev/min 3,600 × 3 3,600 × 3
Compressor
Motor Output x Number W x No. (5,300 × 2) + (4,200 × 1) 5,300 × 3
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W (900 × 2) + (1,200 × 1) (900 × 2) + (1,200 × 1)
3/min (320 × 1) + (240 × 1) (320 × 1) + (240 × 1)
m
Air Flow Rate(High)
Fan ft3/min (11,301 × 1) + (8,476 × 1) (11,301 × 1) + (8,476 × 1)
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections Low Pressure Gas mm(inch) 34.9(1-3/8) 41.3(1-5/8)
#1 High Pressure Gas mm(inch) 28.58(1-1/8) 28.58(1-1/8)
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections
#2 Gas mm(inch) 34.9(1-3/8) 41.3(1-5/8)

mm (1,240 × 1,690 × 760) × 1 + (930 × 1,690 (1,240 × 1,690 × 760) × 1 + (930 × 1,690
× 760) × 1 × 760) × 1
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 1 + (48-13/16 × 66-17/32 × 29-29/32) × 1 +
(36-5/8 × 66-17/32 × 29-29/32) × 1 (36-5/8 × 66-17/32 × 29-29/32) × 1
kg (300 × 1) + (215 × 1) (310 × 1) + (215 × 1)
Net Weight
lbs (661 × 1) + (474 × 1) (683 × 1) + (474 × 1)
Sound Cooling dB(A) 65.6 66.0
Pressure Level Heating dB(A) 66.6 67.8
Sound Power Cooling dB(A) 86.8 88.5
Level Heating dB(A) 88.6 90.4
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

18
Multi V 5 Outdoor Units

1. Specifications
HP 34 36
Combination Unit ARUM340LTE5 ARUM360LTE5
ARUM220LTE5 ARUM240LTE5
Model Name ARUM120LTE5 ARUM120LTE5
Independent Unit

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Devices Compressor/Fan
Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 25.5 26.5
Precharged Amount
Refrigerant lbs 56.2 58.4
t-CO2 eq 53.2 55.3
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 34.31 - 32.59 - 31.41 37.18 - 35.32 - 34.05
Current Heating A 40.88 - 38.84 - 37.43 44.21 - 42.0 - 40.48
Number of maximum connectable indoor units *** 55(64) 58(64)
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

19
Multi V 5 Outdoor Units

1. Specifications
HP 38 40
Combination Unit ARUM380LTE5 ARUM400LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM140LTE5 ARUM160LTE5
Independent Unit

kW 106.4 112.0
Cooling
Btu/h 363,000 382,100
Capacity
kW 118.4 124.7
Heating
Btu/h 403,800 425,300
Cooling kW 24.30 26.32
Input
Heating kW 28.52 31.19
EER 4.39 4.25
COP 4.15 4.00
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev 62.1 × 3 62.1 × 3
Number of Revolution rev/min 3,600 × 3 3,600 × 3
Compressor
Motor Output x Number W x No. 5,300 × 3 5,300 × 3
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W 900 × 4 900 × 4
3/min 320 × 2 320 × 2
m
Air Flow Rate(High)
Fan ft3/min 11,301 × 2 11,301 × 2
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections Low Pressure Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
#1 High Pressure Gas mm(inch) 34.9(1-3/8) 34.9(1-3/8)
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections
#2 Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
mm (1,240 ×1,690 × 760) × 2 (1,240 ×1,690 × 760) × 2
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 2 (48-13/16 × 66-17/32 × 29-29/32) × 2
kg (310 × 1) + (237 × 1) (310 × 1) + (237 × 1)
Net Weight
lbs (683 × 1) + (522 × 1) (683 × 1) + (522 × 1)
Sound Cooling dB(A) 66.2 66.3
Pressure Level Heating dB(A) 68.0 68.1
Sound Power Cooling dB(A) 89.0 89.2
Level Heating dB(A) 91.0 91.2
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

20
Multi V 5 Outdoor Units

1. Specifications
HP 38 40
Combination Unit ARUM380LTE5 ARUM400LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM140LTE5 ARUM160LTE5
Independent Unit

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Devices Compressor/Fan
Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 30.5 30.5
Precharged Amount
Refrigerant lbs 67.2 67.2
t-CO2 eq 63.7 63.7
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 39.70 - 37.71 - 36.35 43.0 - 40.85 - 39.37
Current Heating A 46.59 - 44.26 - 42.66 50.95 - 48.41 - 46.66
Number of maximum connectable indoor units *** 61(64) 64
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

21
Multi V 5 Outdoor Units

1. Specifications
HP 42 44
Combination Unit ARUM420LTE5 ARUM440LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM180LTE5 ARUM200LTE5
Independent Unit

kW 117.6 123.2
Cooling
Btu/h 401,300 420,400
Capacity
kW 131.0 137.3
Heating
Btu/h 446,800 468,300
Cooling kW 25.74 27.41
Input
Heating kW 30.74 33.48
EER 4.61 4.52
COP 4.26 4.10
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev (62.1 × 3) + (43.8 × 1) (62.1 × 3) + (43.8 × 1)
Number of Revolution rev/min 3,600 × 4 3,600 × 4
Compressor
Motor Output x Number W x No. (5,300 × 3) + (4,200 × 1) (5,300 × 3) + (4,200 × 1)
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W 900 × 4 900 × 4
3/min 320 × 2 320 × 2
m
Air Flow Rate(High)
Fan ft3/min 11,301 × 2 11,301 × 2
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections Low Pressure Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
#1 High Pressure Gas mm(inch) 34.9(1-3/8) 34.9(1-3/8)
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections
#2 Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
mm (1,240 ×1,690 × 760) × 2 (1,240 ×1,690 × 760) × 2
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 2 (48-13/16 × 66-17/32 × 29-29/32) × 2
kg (310 × 1) + (300 × 1) (310 × 1) + (300 × 1)
Net Weight
lbs (683 × 1) + (661 × 1) (683 × 1) + (661 × 1)
Sound Cooling dB(A) 66.5 66.8
Pressure Level Heating dB(A) 68.2 68.9
Sound Power Cooling dB(A) 89.8 90.1
Level Heating dB(A) 91.5 91.8
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

22
Multi V 5 Outdoor Units

1. Specifications
HP 42 44
Combination Unit ARUM420LTE5 ARUM440LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM180LTE5 ARUM200LTE5
Independent Unit

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Devices Compressor/Fan
Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 33.0 33.0
Precharged Amount
Refrigerant lbs 72.8 72.8
t-CO2 eq 68.9 68.9
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 42.05 - 39.95 - 38.50 44.78 - 42.54 - 41.0
Current Heating A 50.22 - 47.71 - 45.98 54.70 - 51.97 - 50.09
Number of maximum connectable indoor units *** 64 64
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

23
Multi V 5 Outdoor Units

1. Specifications
HP 46 48
Combination Unit ARUM460LTE5 ARUM480LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM220LTE5 ARUM240LTE5
Independent Unit

kW 128.8 134.4
Cooling
Btu/h 439,500 458,600
Capacity
kW 143.6 148.5
Heating
Btu/h 489,800 506,700
Cooling kW 30.06 31.82
Input
Heating kW 35.56 37.60
EER 4.28 4.22
COP 4.04 3.95
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev (62.1 × 3) + (43.8 × 1) 62.1 × 4
Number of Revolution rev/min 3,600 × 4 3,600 × 4
Compressor
Motor Output x Number W x No. (5,300 × 3) + (4,200 × 1) 5,300 × 4
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W 900 × 4 900 × 4
3/min 320 × 2 320 × 2
m
Air Flow Rate(High)
Fan ft3/min 11,301 × 2 11,301 × 2
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections Low Pressure Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
#1 High Pressure Gas mm(inch) 34.9(1-3/8) 34.9(1-3/8)
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections
#2 Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
mm (1,240 ×1,690 × 760) × 2 (1,240 ×1,690 × 760) × 2
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 2 (48-13/16 × 66-17/32 × 29-29/32) × 2
kg (310 × 1) + (300 × 1) 310 × 2
Net Weight
lbs (683 × 1) + (661 × 1) 683 × 2
Sound Cooling dB(A) 67.8 68.0
Pressure Level Heating dB(A) 69.3 70.0
Sound Power Cooling dB(A) 90.1 91.0
Level Heating dB(A) 92.1 93.0
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

24
Multi V 5 Outdoor Units

1. Specifications
HP 46 48
Combination Unit ARUM460LTE5 ARUM480LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM220LTE5 ARUM240LTE5
Independent Unit

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Devices Compressor/Fan
Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 33.0 34.0
Precharged Amount
Refrigerant lbs 72.8 75.0
t-CO2 eq 68.9 71.0
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 49.11 - 46.65 - 44.97 51.98 - 49.39 - 47.60
Current Heating A 58.10 - 55.19 - 53.20 61.42 - 58.35 - 56.24
Number of maximum connectable indoor units *** 64 64
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

25
Multi V 5 Outdoor Units

1. Specifications
HP 50 52
Combination Unit ARUM500LTE5 ARUM520LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM140LTE5 ARUM160LTE5
Independent Unit
ARUM120LTE5 ARUM120LTE5

kW 140.0 145.6
Cooling
Btu/h 477,700 496,800
Capacity
kW 156.2 162.5
Heating
Btu/h 532,800 554,300
Cooling kW 31.15 33.17
Input
Heating kW 36.78 39.45
EER 4.51 4.40
COP 4.25 4.12
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev 62.1 × 4 62.1 × 4
Number of Revolution rev/min 3,600 × 4 3,600 × 4
Compressor
Motor Output x Number W x No. 5,300 × 4 5,300 × 4
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W (900 × 4) + (1,200 × 1) (900 × 4) + (1,200 × 1)
3/min (320 × 2) + (240 × 1) (320 × 2) + (240 × 1)
m
Air Flow Rate(High)
Fan ft3/min (11,301 × 2) + (8,476 × 1) (11,301 × 2) + (8,476 × 1)
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections Low Pressure Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
#1 High Pressure Gas mm(inch) 34.9(1-3/8) 34.9(1-3/8)
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections
#2 Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)

mm (1,240 × 1,690 × 760) × 2 + (930 × 1,690 (1,240 × 1,690 × 760) × 2 + (930 × 1,690
× 760) × 1 × 760) × 1
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 2 + (48-13/16 × 66-17/32 × 29-29/32) × 2 +
(36-5/8 × 66-17/32 × 29-29/32) × 1 (36-5/8 × 66-17/32 × 29-29/32) × 1
kg (310 × 1) + (237 × 1) + (215 × 1) (310 × 1) + (237 × 1) + (215 × 1)
Net Weight
lbs (683 × 1) + (522 × 1) + (474 × 1) (683 × 1) + (522 × 1) + (474 × 1)
Sound Cooling dB(A) 67.0 67.1
Pressure Level Heating dB(A) 68.6 68.7
Sound Power Cooling dB(A) 89.4 89.6
Level Heating dB(A) 91.3 91.5
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

26
Multi V 5 Outdoor Units

1. Specifications
HP 50 52
Combination Unit ARUM500LTE5 ARUM520LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM140LTE5 ARUM160LTE5
Independent Unit
ARUM120LTE5 ARUM120LTE5

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Compressor/Fan
Devices Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 40.0 40.0
Precharged Amount
Refrigerant lbs 88.2 88.2
t-CO2 eq 83.5 83.5
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 50.89 - 48.35 - 46.60 54.19 - 51.48 - 49.62
Current Heating A 60.09 - 57.08 - 55.02 64.45 - 61.23 - 59.01
Number of maximum connectable indoor units *** 64 64
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

27
Multi V 5 Outdoor Units

1. Specifications
HP 54 56
Combination Unit ARUM540LTE5 ARUM560LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM180LTE5 ARUM200LTE5
Independent Unit
ARUM120LTE5 ARUM120LTE5

kW 151.2 156.8
Cooling
Btu/h 515,900 535,000
Capacity
kW 168.8 175.1
Heating
Btu/h 575,800 597,300
Cooling kW 32.59 34.26
Input
Heating kW 39.00 41.74
EER 4.68 4.60
COP 4.33 4.19
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev (62.1 × 4) + (43.8 × 1) (62.1 × 4) + (43.8 × 1)
Number of Revolution rev/min 3,600 × 5 3,600 × 5
Compressor
Motor Output x Number W x No. (5,300 × 4) + (4,200 × 1) (5,300 × 4) + (4,200 × 1)
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W (900 × 4) + (1,200 × 1) (900 × 4) + (1,200 × 1)
3/min (320 × 2) + (240 × 1) (320 × 2) + (240 × 1)
m
Air Flow Rate(High)
Fan ft3/min (11,301 × 2) + (8,476 × 1) (11,301 × 2) + (8,476 × 1)
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections Low Pressure Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
#1 High Pressure Gas mm(inch) 34.9(1-3/8) 34.9(1-3/8)
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections
#2 Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)

mm (1,240 × 1,690 × 760) × 2 + (930 × 1,690 (1,240 × 1,690 × 760) × 2 + (930 × 1,690
× 760) × 1 × 760) × 1
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 2 + (48-13/16 × 66-17/32 × 29-29/32) × 2 +
(36-5/8 × 66-17/32 × 29-29/32) × 1 (36-5/8 × 66-17/32 × 29-29/32) × 1
kg (310 × 1) + (300 × 1) + (215 × 1) (310 × 1) + (300 × 1) + (215 × 1)
Net Weight
lbs (683 × 1) + (661 × 1) + (474 × 1) (683 × 1) + (661 × 1) + (474 × 1)
Sound Cooling dB(A) 67.2 67.4
Pressure Level Heating dB(A) 68.8 69.5
Sound Power Cooling dB(A) 90.1 90.4
Level Heating dB(A) 91.8 92.0
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

28
Multi V 5 Outdoor Units

1. Specifications
HP 54 56
Combination Unit ARUM540LTE5 ARUM560LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM180LTE5 ARUM200LTE5
Independent Unit
ARUM120LTE5 ARUM120LTE5

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Compressor/Fan
Devices Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 42.5 42.5
Precharged Amount
Refrigerant lbs 93.7 93.7
t-CO2 eq 88.7 88.7
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 53.24 - 50.58 - 48.75 55.97 - 53.17 - 51.25
Current Heating A 63.71 - 60.53 - 58.34 68.20 - 64.79 - 62.45
Number of maximum connectable indoor units *** 64 64
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

29
Multi V 5 Outdoor Units

1. Specifications
HP 58 60
Combination Unit ARUM580LTE5 ARUM600LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM220LTE5 ARUM240LTE5
Independent Unit
ARUM120LTE5 ARUM120LTE5

kW 162.4 168.0
Cooling
Btu/h 554,100 573,200
Capacity
kW 181.4 186.3
Heating
Btu/h 618,800 635,700
Cooling kW 36.91 38.67
Input
Heating kW 43.82 45.86
EER 4.41 4.36
COP 4.14 4.06
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev (62.1 × 4) + (43.8 × 1) 62.1 × 5
Number of Revolution rev/min 3,600 × 5 3,600 × 5
Compressor
Motor Output x Number W x No. (5,300 × 4) + (4,200 × 1) 5,300 × 5
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W (900 × 4) + (1,200 × 1) (900 × 4) + (1,200 × 1)
3/min (320 × 2) + (240 × 1) (320 × 2) + (240 × 1)
m
Air Flow Rate(High)
Fan ft3/min (11,301 × 2) + (8,476 × 1) (11,301 × 2) + (8,476 × 1)
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections Low Pressure Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
#1 High Pressure Gas mm(inch) 34.9(1-3/8) 34.9(1-3/8)
Pipe Liquid mm(inch) 19.05(3/4) 19.05(3/4)
Connections
#2 Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)

mm (1,240 × 1,690 × 760) × 2 + (930 × 1,690 (1,240 × 1,690 × 760) × 2 + (930 × 1,690
× 760) × 1 × 760) × 1
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 2 + (48-13/16 × 66-17/32 × 29-29/32) × 2 +
(36-5/8 × 66-17/32 × 29-29/32) × 1 (36-5/8 × 66-17/32 × 29-29/32) × 1
kg (310 × 1) + (300 × 1) + (215 × 1) (310 × 2) + (215 × 1)
Net Weight
lbs (683 × 1) + (661 × 1) + (474 × 1) (683 × 2) + (474 × 1)
Sound Cooling dB(A) 68.3 68.5
Pressure Level Heating dB(A) 69.8 70.4
Sound Power Cooling dB(A) 90.4 91.3
Level Heating dB(A) 92.4 93.2
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

30
Multi V 5 Outdoor Units

1. Specifications
HP 58 60
Combination Unit ARUM580LTE5 ARUM600LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM220LTE5 ARUM240LTE5
Independent Unit
ARUM120LTE5 ARUM120LTE5

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Compressor/Fan
Devices Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 42.5 43.5
Precharged Amount
Refrigerant lbs 93.7 95.9
t-CO2 eq 88.7 90.8
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 60.30 - 57.28 - 55.21 63.18 - 60.02 - 57.85
Current Heating A 71.59 - 68.01 - 65.55 74.92 - 71.17 - 68.60
Number of maximum connectable indoor units *** 64 64
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

31
Multi V 5 Outdoor Units

1. Specifications
HP 62 64
Combination Unit ARUM620LTE5 ARUM640LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM140LTE5 ARUM160LTE5

kW 173.6 179.2
Cooling
Btu/h 592,300 611,400
Capacity
kW 192.6 198.9
Heating
Btu/h 657,200 678,700
Cooling kW 40.21 42.23
Input
Heating kW 47.32 49.99
EER 4.32 4.24
COP 4.07 3.98
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev 62.1 × 5 62.1 × 5
Number of Revolution rev/min 3,600 × 5 3,600 × 5
Compressor
Motor Output x Number W x No. 5,300 × 5 5,300 × 5
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W 900 × 6 900 × 6
3/min 320 × 3 320 × 3
m
Air Flow Rate(High)
Fan ft3/min 11,301 × 3 11,301 × 3
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections Low Pressure Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
#1 High Pressure Gas mm(inch) 34.9(1-3/8) 34.9(1-3/8)
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections
#2 Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
mm (1,240 ×1,690 × 760) × 3 (1,240 ×1,690 × 760) × 3
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 3 (48-13/16 × 66-17/32 × 29-29/32) × 3
kg (310 × 2) + (237 × 1) (310 × 2) + (237 × 1)
Net Weight
lbs (683 × 2) + (522 × 1) (683 × 2) + (522 × 1)
Sound Cooling dB(A) 68.6 68.7
Pressure Level Heating dB(A) 70.5 70.6
Sound Power Cooling dB(A) 91.5 91.6
Level Heating dB(A) 93.5 93.6
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

32
Multi V 5 Outdoor Units

1. Specifications
HP 62 64
Combination Unit ARUM620LTE5 ARUM640LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM140LTE5 ARUM160LTE5

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Compressor/Fan
Devices Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 47.5 47.5
Precharged Amount
Refrigerant lbs 104.7 104.7
t-CO2 eq 99.2 99.2
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 65.69 - 62.41 - 60.15 68.99 - 65.54 - 63.17
Current Heating A 77.30 - 73.44 - 70.78 81.66 - 77.58 - 74.78
Number of maximum connectable indoor units *** 64 64
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

33
Multi V 5 Outdoor Units

1. Specifications
HP 66 68
Combination Unit ARUM660LTE5 ARUM680LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM180LTE5 ARUM200LTE5

kW 184.8 190.4
Cooling
Btu/h 630,500 649,600
Capacity
kW 205.2 211.5
Heating
Btu/h 700,200 721,700
Cooling kW 41.65 43.32
Input
Heating kW 49.54 52.28
EER 4.47 4.41
COP 4.14 4.05
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev (62.1 × 5) + (43.8 × 1) (62.1 × 5) + (43.8 × 1)
Number of Revolution rev/min 3,600 × 6 3,600 × 6
Compressor
Motor Output x Number W x No. (5,300 × 5) + (4,200 × 1) (5,300 × 5) + (4,200 × 1)
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W 900 × 6 900 × 6
3/min 320 × 3 320 × 3
m
Air Flow Rate(High)
Fan ft3/min 11,301 × 3 11,301 × 3
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections Low Pressure Gas mm(inch) 53.98(2-1/8) 53.98(2-1/8)
#1 High Pressure Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections
#2 Gas mm(inch) 53.98(2-1/8) 53.98(2-1/8)
mm (1,240 ×1,690 × 760) × 3 (1,240 ×1,690 × 760) × 3
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 3 (48-13/16 × 66-17/32 × 29-29/32) × 3
kg (310 × 2) + (300 × 1) (310 × 2) + (300 × 1)
Net Weight
lbs (683 × 2) + (661 × 1) (683 × 2) + (661 × 1)
Sound Cooling dB(A) 68.8 69.0
Pressure Level Heating dB(A) 70.6 71.1
Sound Power Cooling dB(A) 92.0 92.2
Level Heating dB(A) 93.8 94.0
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

34
Multi V 5 Outdoor Units

1. Specifications
HP 66 68
Combination Unit ARUM660LTE5 ARUM680LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM180LTE5 ARUM200LTE5

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Compressor/Fan
Devices Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 50.0 50.0
Precharged Amount
Refrigerant lbs 110.2 110.2
t-CO2 eq 104.4 104.4
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 68.04 - 64.64 - 62.31 70.77 - 67.23 - 64.80
Current Heating A 80.93 - 76.88 - 74.10 85.41 - 81.14 - 78.21
Number of maximum connectable indoor units *** 64 64
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

35
Multi V 5 Outdoor Units

1. Specifications
HP 70 72
Combination Unit ARUM700LTE5 ARUM720LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM220LTE5 ARUM240LTE5

kW 196.0 201.6
Cooling
Btu/h 668,800 687,900
Capacity
kW 217.8 222.8
Heating
Btu/h 743,200 760,100
Cooling kW 45.97 47.73
Input
Heating kW 54.36 56.40
EER 4.26 4.22
COP 4.01 3.95
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev (62.1 × 5) + (43.8 × 1) 62.1 × 6
Number of Revolution rev/min 3,600 × 6 3,600 × 6
Compressor
Motor Output x Number W x No. (5,300 × 5) + (4,200 × 1) 5,300 × 6
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W 900 × 6 900 × 6
3/min 320 × 3 320 × 3
m
Air Flow Rate(High)
Fan ft3/min 11,301 × 3 11,301 × 3
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections Low Pressure Gas mm(inch) 53.98(2-1/8) 53.98(2-1/8)
#1 High Pressure Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections
#2 Gas mm(inch) 53.98(2-1/8) 53.98(2-1/8)
mm (1,240 ×1,690 × 760) × 3 (1,240 ×1,690 × 760) × 3
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 3 (48-13/16 × 66-17/32 × 29-29/32) × 3
kg (310 × 2) + (300 × 1) 310 × 3
Net Weight
lbs (683 × 2) + (661 × 1) 683 × 3
Sound Cooling dB(A) 69.6 69.8
Pressure Level Heating dB(A) 71.3 71.8
Sound Power Cooling dB(A) 92.2 92.8
Level Heating dB(A) 94.2 94.8
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

36
Multi V 5 Outdoor Units

1. Specifications
HP 70 72
Combination Unit ARUM700LTE5 ARUM720LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM220LTE5 ARUM240LTE5

High pressure sensor / High pressure sensor /


High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Compressor/Fan
Devices Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 50.0 51.0
Precharged Amount
Refrigerant lbs 110.2 112.4
t-CO2 eq 104.4 106.5
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 75.10 - 71.35 - 68.77 77.98 - 74.08 - 71.40
Current Heating A 88.81 - 84.37 - 81.32 92.13 - 87.53 - 84.36
Number of maximum connectable indoor units *** 64 64
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

37
Multi V 5 Outdoor Units

1. Specifications
HP 74 76
Combination Unit ARUM740LTE5 ARUM760LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM140LTE5 ARUM160LTE5
ARUM120LTE5 ARUM120LTE5
kW 207.2 212.8
Cooling
Btu/h 707,000 726,100
Capacity
kW 230.4 236.7
Heating
Btu/h 786,200 807,700
Cooling kW 47.06 49.08
Input
Heating kW 55.58 58.25
EER 4.42 4.35
COP 4.15 4.06
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev 62.1 × 6 62.1 × 6
Number of Revolution rev/min 3,600 × 6 3,600 × 6
Compressor
Motor Output x Number W x No. 5,300 × 6 5,300 × 6
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W (900 × 6) + (1,200 × 1) (900 × 6) + (1,200 × 1)
3/min (320 × 3) + (240 × 1) (320 × 3) + (240 × 1)
m
Air Flow Rate(High)
Fan ft3/min (11,301 × 3) + (8,476 × 1) (11,301 × 3) + (8,476 × 1)
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections Low Pressure Gas mm(inch) 53.98(2-1/8) 53.98(2-1/8)
#1 High Pressure Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections
#2 Gas mm(inch) 53.98(2-1/8) 53.98(2-1/8)

mm (1,240 × 1,690 × 760) × 3 + (930 × 1,690 (1,240 × 1,690 × 760) × 3 + (930 × 1,690
× 760) × 1 × 760) × 1
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 3 + (48-13/16 × 66-17/32 × 29-29/32) × 3 +
(36-5/8 × 66-17/32 × 29-29/32) × 1 (36-5/8 × 66-17/32 × 29-29/32) × 1
kg (310 × 2) + (237 × 1) + (215 × 1) (310 × 2) + (237 × 1) + (215 × 1)
Net Weight
lbs (683 × 2) + (522 × 1) + (474 × 1) (683 × 2) + (522 × 1) + (474 × 1)
Sound Cooling dB(A) 69.1 69.2
Pressure Level Heating dB(A) 70.9 70.9
Sound Power Cooling dB(A) 91.8 91.9
Level Heating dB(A) 93.7 93.8
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

38
Multi V 5 Outdoor Units

1. Specifications
HP 74 76
Combination Unit ARUM740LTE5 ARUM760LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM140LTE5 ARUM160LTE5
ARUM120LTE5 ARUM120LTE5
High pressure sensor / High pressure sensor /
High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Compressor/Fan
Devices Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 57.0 57.0
Precharged Amount
Refrigerant lbs 125.7 125.7
t-CO2 eq 119.0 119.0
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 76.88 - 73.04 - 70.40 80.18 - 76.17 - 73.42
Current Heating A 90.80 - 86.26 - 83.14 95.16 - 90.40 - 87.13
Number of maximum connectable indoor units *** 64 64
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

39
Multi V 5 Outdoor Units

1. Specifications
HP 78 80
Combination Unit ARUM780LTE5 ARUM800LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM180LTE5 ARUM200LTE5
ARUM120LTE5 ARUM120LTE5
kW 218.4 224.0
Cooling
Btu/h 745,200 764,300
Capacity
kW 243.0 249.3
Heating
Btu/h 829,200 850,700
Cooling kW 48.50 50.17
Input
Heating kW 57.80 60.54
EER 4.54 4.49
COP 4.20 4.12
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev (62.1 × 6) + (43.8 × 1) (62.1 × 6) + (43.8 × 1)
Number of Revolution rev/min 3,600 × 6 3,600 × 6
Compressor
Motor Output x Number W x No. (5,300 × 6) + (4,200 × 1) (5,300 × 6) + (4,200 × 1)
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W (900 × 6) + (1,200 × 1) (900 × 6) + (1,200 × 1)
3/min (320 × 3) + (240 × 1) (320 × 3) + (240 × 1)
m
Air Flow Rate(High)
Fan ft3/min (11,301 × 3) + (8,476 × 1) (11,301 × 3) + (8,476 × 1)
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections Low Pressure Gas mm(inch) 53.98(2-1/8) 53.98(2-1/8)
#1 High Pressure Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections
#2 Gas mm(inch) 53.98(2-1/8) 53.98(2-1/8)

mm (1,240 × 1,690 × 760) × 3 + (930 × 1,690 (1,240 × 1,690 × 760) × 3 + (930 × 1,690
× 760) × 1 × 760) × 1
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 3 + (48-13/16 × 66-17/32 × 29-29/32) × 3 +
(36-5/8 × 66-17/32 × 29-29/32) × 1 (36-5/8 × 66-17/32 × 29-29/32) × 1
kg (310 × 2) + (300 × 1) + (215 × 1) (310 × 2) + (300 × 1) + (215 × 1)
Net Weight
lbs (683 × 2) + (661 × 1) + (474 × 1) (683 × 2) + (661 × 1) + (474 × 1)
Sound Cooling dB(A) 69.2 69.4
Pressure Level Heating dB(A) 71.0 71.4
Sound Power Cooling dB(A) 92.2 92.4
Level Heating dB(A) 94.0 94.2
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

40
Multi V 5 Outdoor Units

1. Specifications
HP 78 80
Combination Unit ARUM780LTE5 ARUM800LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM180LTE5 ARUM200LTE5
ARUM120LTE5 ARUM120LTE5
High pressure sensor / High pressure sensor /
High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Compressor/Fan
Devices Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 59.5 59.5
Precharged Amount
Refrigerant lbs 131.2 131.2
t-CO2 eq 124.2 124.2
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 79.23 - 75.27 - 72.55 81.96 - 77.86 - 75.05
Current Heating A 94.42 - 89.70 - 86.46 98.91 - 93.96 - 90.57
Number of maximum connectable indoor units *** 64 64
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

41
Multi V 5 Outdoor Units

1. Specifications
HP 82 84
Combination Unit ARUM820LTE5 ARUM840LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM220LTE5 ARUM240LTE5
ARUM120LTE5 ARUM120LTE5
kW 229.6 235.2
Cooling
Btu/h 783,400 802,500
Capacity
kW 255.6 260.6
Heating
Btu/h 872,100 889,100
Cooling kW 52.82 54.58
Input
Heating kW 62.62 64.66
EER 4.36 4.32
COP 4.08 4.03
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev (62.1 × 6) + (43.8 × 1) 62.1 × 7
Number of Revolution rev/min 3,600 × 6 3,600 × 7
Compressor
Motor Output x Number W x No. (5,300 × 6) + (4,200 × 1) 5,300 × 7
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W (900 × 6) + (1,200 × 1) (900 × 6) + (1,200 × 1)
3/min (320 × 3) + (240 × 1) (320 × 3) + (240 × 1)
m
Air Flow Rate(High)
Fan ft3/min (11,301 × 3) + (8,476 × 1) (11,301 × 3) + (8,476 × 1)
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections Low Pressure Gas mm(inch) 53.98(2-1/8) 53.98(2-1/8)
#1 High Pressure Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections
#2 Gas mm(inch) 53.98(2-1/8) 53.98(2-1/8)

mm (1,240 × 1,690 × 760) × 3 + (930 × 1,690 (1,240 × 1,690 × 760) × 3 + (930 × 1,690
× 760) × 1 × 760) × 1
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 3 + (48-13/16 × 66-17/32 × 29-29/32) × 3 +
(36-5/8 × 66-17/32 × 29-29/32) × 1 (36-5/8 × 66-17/32 × 29-29/32) × 1
kg (310 × 2) + (300 × 1) + (215 × 1) (310 × 3) + (215 × 1)
Net Weight
lbs (683 × 2) + (661 × 1) + (474 × 1) (683 × 3) + (474 × 1)
Sound Cooling dB(A) 70.0 70.1
Pressure Level Heating dB(A) 71.6 72.1
Sound Power Cooling dB(A) 92.4 92.9
Level Heating dB(A) 94.4 94.9
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

42
Multi V 5 Outdoor Units

1. Specifications
HP 82 84
Combination Unit ARUM820LTE5 ARUM840LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM220LTE5 ARUM240LTE5
ARUM120LTE5 ARUM120LTE5
High pressure sensor / High pressure sensor /
High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Compressor/Fan
Devices Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 59.5 60.5
Precharged Amount
Refrigerant lbs 131.2 133.4
t-CO2 eq 124.2 126.3
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 86.29 - 81.98 - 79.01 89.17 - 84.71 - 81.65
Current Heating A 102.30 - 97.19 - 93.67 105.63 - 100.35 - 96.72
Number of maximum connectable indoor units *** 64 64
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

43
Multi V 5 Outdoor Units

1. Specifications
HP 86 88
Combination Unit ARUM860LTE5 ARUM880LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM240LTE5 ARUM240LTE5
ARUM140LTE5 ARUM160LTE5
kW 240.8 246.4
Cooling
Btu/h 821,600 840,700
Capacity
kW 266.9 273.2
Heating
Btu/h 910,600 932,000
Cooling kW 56.12 58.14
Input
Heating kW 66.12 68.79
EER 4.29 4.23
COP 4.04 3.97
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev 62.1 × 7 62.1 × 7
Number of Revolution rev/min 3,600 × 7 3,600 × 7
Compressor
Motor Output x Number W x No. 5,300 × 7 5,300 × 7
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W 900 × 8 900 × 8
3/min 320 × 4 320 × 4
m
Air Flow Rate(High)
Fan ft3/min 11,301 × 4 11,301 × 4
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections Low Pressure Gas mm(inch) 53.98(2-1/8) 53.98(2-1/8)
#1 High Pressure Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections
#2 Gas mm(inch) 53.98(2-1/8) 53.98(2-1/8)
mm (1,240 ×1,690 × 760) × 4 (1,240 ×1,690 × 760) × 4
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 4 (48-13/16 × 66-17/32 × 29-29/32) × 4
kg (310 × 3) + (237 × 1) (310 × 3) + (237 × 1)
Net Weight
lbs (683 × 3) + (522 × 1) (683 × 3) + (522 × 1)
Sound Cooling dB(A) 70.2 70.3
Pressure Level Heating dB(A) 72.1 72.2
Sound Power Cooling dB(A) 93.1 93.2
Level Heating dB(A) 95.1 95.2
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

44
Multi V 5 Outdoor Units

1. Specifications
HP 86 88
Combination Unit ARUM860LTE5 ARUM880LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM240LTE5 ARUM240LTE5
ARUM140LTE5 ARUM160LTE5
High pressure sensor / High pressure sensor /
High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Compressor/Fan
Devices Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 64.5 64.5
Precharged Amount
Refrigerant lbs 142.2 142.2
t-CO2 eq 134.6 134.6
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 91.68 - 87.10 - 83.95 94.98 - 90.23 - 86.97
Current Heating A 108.01 - 102.61 - 98.90 112.38 - 106.76 - 102.90
Number of maximum connectable indoor units *** 64 64
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

45
Multi V 5 Outdoor Units

1. Specifications
HP 90 92
Combination Unit ARUM900LTE5 ARUM920LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM240LTE5 ARUM240LTE5
ARUM180LTE5 ARUM200LTE5
kW 252.0 257.6
Cooling
Btu/h 859,800 878,900
Capacity
kW 279.5 285.8
Heating
Btu/h 953,500 975,000
Cooling kW 57.56 59.23
Input
Heating kW 68.34 71.08
EER 4.40 4.36
COP 4.09 4.02
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev (62.1 × 7) + (43.8 × 1) (62.1 × 7) + (43.8 × 1)
Number of Revolution rev/min 3,600 × 8 3,600 × 8
Compressor
Motor Output x Number W x No. (5,300 × 7) + (4,200 × 1) (5,300 × 7) + (4,200 × 1)
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W 900 × 8 900 × 8
3/min 320 × 4 320 × 4
m
Air Flow Rate(High)
Fan ft3/min 11,301 × 4 11,301 × 4
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections Low Pressure Gas mm(inch) 53.98(2-1/8) 53.98(2-1/8)
#1 High Pressure Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections
#2 Gas mm(inch) 53.98(2-1/8) 53.98(2-1/8)
mm (1,240 ×1,690 × 760) × 4 (1,240 ×1,690 × 760) × 4
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 4 (48-13/16 × 66-17/32 × 29-29/32) × 4
kg (310 × 3) + (300 × 1) (310 × 3) + (300 × 1)
Net Weight
lbs (683 × 3) + (661 × 1) (683 × 3) + (661 × 1)
Sound Cooling dB(A) 70.3 70.4
Pressure Level Heating dB(A) 72.2 72.5
Sound Power Cooling dB(A) 93.4 93.6
Level Heating dB(A) 95.3 95.4
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

46
Multi V 5 Outdoor Units

1. Specifications
HP 90 92
Combination Unit ARUM900LTE5 ARUM920LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM240LTE5 ARUM240LTE5
ARUM180LTE5 ARUM200LTE5
High pressure sensor / High pressure sensor /
High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Compressor/Fan
Devices Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 67.0 67.0
Precharged Amount
Refrigerant lbs 147.7 147.7
t-CO2 eq 139.9 139.9
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 94.04 - 89.33 - 86.11 96.76 - 91.93 - 88.60
Current Heating A 111.64 - 106.06 - 102.23 116.13 - 110.32 - 106.33
Number of maximum connectable indoor units *** 64 64
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

47
Multi V 5 Outdoor Units

1. Specifications
HP 94 96
Combination Unit ARUM940LTE5 ARUM960LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM240LTE5 ARUM240LTE5
ARUM220LTE5 ARUM240LTE5
kW 263.2 268.8
Cooling
Btu/h 898,000 917,100
Capacity
kW 292.1 297.0
Heating
Btu/h 996,500 1,013,400
Cooling kW 61.88 63.64
Input
Heating kW 73.16 75.19
EER 4.25 4.22
COP 3.99 3.95
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev (62.1 × 7) + (43.8 × 1) 62.1 × 8
Number of Revolution rev/min 3,600 × 8 3,600 × 8
Compressor
Motor Output x Number W x No. (5,300 × 7) + (4,200 × 1) 5,300 × 8
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W 900 × 8 900 × 8
3/min 320 × 4 320 × 4
m
Air Flow Rate(High)
Fan ft3/min 11,301 × 4 11,301 × 4
External Static Pressure (Max, Pa) 80 80
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections Low Pressure Gas mm(inch) 53.98(2-1/8) 53.98(2-1/8)
#1 High Pressure Gas mm(inch) 41.3(1-5/8) 41.3(1-5/8)
Pipe Liquid mm(inch) 22.2(7/8) 22.2(7/8)
Connections
#2 Gas mm(inch) 53.98(2-1/8) 53.98(2-1/8)
mm (1,240 ×1,690 × 760) × 4 (1,240 ×1,690 × 760) × 4
Dimensions(W x H x D)
inch (48-13/16 × 66-17/32 × 29-29/32) × 4 (48-13/16 × 66-17/32 × 29-29/32) × 4
kg (310 × 3) + (300 × 1) 310 × 4
Net Weight
lbs (683 × 3) + (661 × 1) 683 × 4
Sound Cooling dB(A) 70.9 71.0
Pressure Level Heating dB(A) 72.7 73.0
Sound Power Cooling dB(A) 93.6 94.0
Level Heating dB(A) 95.6 96.0
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system

48
Multi V 5 Outdoor Units

1. Specifications
HP 94 96
Combination Unit ARUM940LTE5 ARUM960LTE5
ARUM240LTE5 ARUM240LTE5
Model Name ARUM240LTE5 ARUM240LTE5
Independent Unit
ARUM240LTE5 ARUM240LTE5
ARUM220LTE5 ARUM240LTE5
High pressure sensor / High pressure sensor /
High pressure protection
High pressure switch High pressure switch
Protection Over-heat protection / Over-heat protection /
Compressor/Fan
Devices Fan driver overload protector Fan driver overload protector
Over-heat protection / Over-heat protection /
Inverter
Over-current protection Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 67.0 68.0
Precharged Amount
Refrigerant lbs 147.7 149.9
t-CO2 eq 139.9 142.0
Control Electronic Expansion Valve Electronic Expansion Valve
Power Supply V, Ø, Hz 380-400-415, 3, 50/60 380-400-415, 3, 50/60
Running Cooling A 101.09 - 96.04 - 92.57 103.97 - 98.77 - 95.20
Current Heating A 119.52 - 113.54 - 109.44 122.85 - 116.70 - 112.49
Number of maximum connectable indoor units *** 64 64
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
5. Performances are in accordance with ISO 15042.
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
8. #1 : Heat Recovery system, #2 : Heat Pump system