LEGEND :

GENERAL NOTES & SPECIFICATIONS:


a Compact flourescent lamp, 11W
1. POWER SUPPLY SHALL BE 230 VOLTS, SINGLE PHASE, 2-WIRE, 60 Hz.
2. SERVICE ENTRANCE CONDUCTORS SHALL BE EXPOSED WITHOUT ANY SPLICE OR JOINT
2 gang conveniece outlet
FROM THE TAPPING POINT TO THE METER BASE. flush type ( complete )
3. MINIMUM SIZE OF CIRCUIT CONDUCTOR & CONDUIT SHALL BE 2.0mm² TYPE THW Sa switch, subscript letter(s)
indicate the number of device
COPPER WIRE AND 8mm
1 Branch Ckt home run, the Number
indicate the Branch ckt
number
service entrance

Panel board

M kWhr Meter

mm² (#2/0 AWG) THW


COPPER WIRE IN 65mmø21(2
inch) STEEL CONDUIT.
7. ALL WIRING INSTALLATIONS SHALL BE DONE IN ACCORDANCE WITH THE APPLICABLE To San Julian,
Eastern Samar

PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE, PART I, THE
RULES AND REGULATIONS OF THE ESAMELCO AND THE REQUIREMENTS OF THE OTHER
D
POSNECE
PROID E
RES
LOCAL AGENCIES HAVING JURISDICTION OF THE PROJECT.
8. EFFECTIVE SYSTEM AND EQUIPMENT GROUNDING SHALL BE ADEQUATELY PROVIDED.
9. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND ALL OF APPROVED TYPES.
10. ALL WIRING INSTALLATIONS SHALL BE OF GOOD WORKMANSHIP AND SHALL BE DONE Church

IN ACCORDANCE WITH ENGINEERING STANDARDS. Park

11. SIZE OF MAIN CIRVCUIT BREAKER SHALL BE 50 AT, 225 AF, 2P, 230 VOLTS, 60 Hz, WITH Galaxy
NFA
N
Fuel F
22 KAIC MIN. AT 230 VOLTS. A
CS
12. ALL WIRING INSTALLATIONS SHALL BE DONE UNDER THE IMMEDIATE SUPERVISION OF To BORONGAN

A DULY LICENSED ELECTRICAL ENGINEER, PEE, REE OR REGISTERED MASTER


VICINITY MAP
ELECTRICIAN ( RME ).

DRAWN BY: PROJECT TITLE: INSTRUCTOR: SHEET N0.

DILAO, ROJIM A. PROPOSED TWO STOREY THREE BEDROOM


ENGR.ROMEL JUSTIN MADRIAGA E
RESIDENTIAL BUILDING
3
BSCE-3B