Zonal cavity method calculation form (IESNA)

ACTIVITY 2: Zonal Cavity Form (By Group)


Members: (alphabetical order)
1. Evora, Andrea Sollestre
2. Loyola, Francis Luis
3. Salvahan, Elmond
4. Santos, Gwyneth
5. Zablan, Anthony

General Information

1. Project Identification: Grocery Store


2. Average maintained illumination for design: 500 Lux (or Footcandles)
2a. Dimension of the room: 100 X 60 X 3.5

Luminaire Data Lamp Data:


3. Manufacturer: Zumtobel 5. Type and color: Warm white Material all metals
4. Catalog #:PANOS EVOLUTION Q190 H 6. Number per luminaire: 2
7. Total lumens per luminaire: 1800

Selection of Coefficient of Utilization

8. Step 1: Fill in sketch below


p1 ceiling cc = 70% ; hcc = 1
p2 wall = 50% ; hrc= 9.5
p3 Floor =20% ; hfc = 2.5
w = 100
l = 60
Zonal cavity method calculation form (IESNA)

9. Step 2: Determine Cavity Ratios by formula.


9a. Room cavity ratio, RCR: 0.466
9b. Ceiling cavity ratio, CCR: 0.133
9c. Floor cavity ratio, FCR: 0.333

10. Step 3: Obtain effective ceiling cavity reflectance (ρ𝑐𝑐): 0.70

11. Step 4: Obtain effective floor cavity reflectance (ρ𝑓𝑐): 0.20

12. Step 5: Obtain coefficient of utilization (CU): 0.64

Note: Include the following attachment/reference/sources of data


1. Table for Standard Illumination of the area

2. Luminaire Manufacturer data

3. Coefficient of Utilization of luminaire


Zonal cavity method calculation form (IESNA)