: 21066023BKK-001
Sample Description
Product : Air conditioners
Type of Equipment : Split-system ducted air conditioners using air-cooled condensers
Brand Name : BLUE STAR
Model No. : Indoor unit: DSE60FAI-01 ; Outdoor unit: DSE603CSFAO-01
Serial no. : Indoor unit: DSE60FAI-01DUF00021 ;
Outdoor unit: DSE603CSFAO-01DUF00021
Electrical Rating : 380 - 415V 3 Phase 50Hz
Rated Cooling Capacity (T1) : 58000 Btu/h
Rated Cooling Capacity (T1) : 59000 Btu/h (at DB/WB Outdoor: 35°C/-- ; Indoor: 26.7°C/19.4°C)
Rated Cooling Capacity (T3) : 50900 Btu/h
Refrigerant charged / Amount : R-410A / 5.8 kg
No. of Sample : 1
Client’s Reference No. : 01182704R2
Sample Received Date : 21 October 2021
Received Sample Condition : The samples were in working condition when received.
Test Request : See next page
Referenced standard : See next page
Test Method : Indoor air-enthalpy test method
Testing Laboratory : Intertek Testing Services (Thailand) Ltd.
1285/5 Prachachuen Road, Wongsawang, Bangsue, Bangkok, 10800
THAILAND
Testing Location : BLUE STAR LIMITED
Village-Vasuri Khurd, Khanivali Road, PO - Khupari ,Tal- Wada,
Dist- Palgahr Maharashtra, India,421312, India
Date(s) of performance : 21 – 25 October 2021
Test Result : See the attached sheets
Page 1 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Referenced standard:
- QCC-PCS-ASP017.01: 2016 Abu Dhabi Certification Scheme for Ozone Friendly Air-cooled Unitary Air
Conditioners
- UAE.S 5010-5: 2019 Labeling – Energy efficiency label for electrical appliances - Part five: commercial
and central Air conditioners
- QS 2663: 2020 Energy labelling and minimum energy performance requirements for air conditioners
- REGULATION ON ENERGY LABELLING AND MINIMUM ENERGY PERFORMANCE
REQUIREMENTS FOR AIR-CONDITIONERS (2015)
- GSO 2530: 2016 Energy Labelling and Minimum Energy Performance Requirements for Air-Conditioners
- ISO 13253: 2017 Ducted air conditioners and air-to-air heat pumps -Testing and rating for performance
- UAE.S ISO 13253: 2011 Ducted air-conditioners and air-to-air heat pumps - Testing and rating for
performance
- GSO ISO 13253: 2009 Ducted air conditioners and air-to-air heat pumps -Testing and rating for
performance
- ISO16358-1: 2013/Amd.1: 2019 Cooling seasonal performance factor
- AHRI STANDARD 210/240-2017 Performance Rating of Unitary Air-conditioning & Air-source Heat
Pump Equipment
Test Request:
#1 Cooling capacity test at condition T1
#2 Cooling capacity test at condition T3
#3 Cooling capacity test at condition outdoor dry bulb temperature 35 °C with indoor dry bulb temperature
26.7 °C and wet bulb temperature 19.4 °C
4# Maximum operating condition at 52 °C outdoor dry bulb temperature for at least two (2) hours
continuously
5# Setting lower temperature of the air conditioner (Thermostat 20 ºC Set point Evaluation)
6# Maximum cooling performance test (90 % of the lower rated voltage and 110 % of the higher rated
voltage for units with a dual or extended nameplate voltage)
7# Maximum operating condition at 55 °C outdoor dry bulb temperature for at least two (2) hours
continuously (Test condition specified by applicant)
Page 2 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
General Remark:
- This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement
between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and
conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this
report. Only the Client is authorized to permit copying or distribution of this report and that too only
in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the
tested material, product or service must first be approved in writing by Intertek. The observations
and test results in this report are relevant only to the sample tested. This report by itself does not
imply that the material, product, or service is or has ever been under an Intertek certification
program.
- The test results reported in this test report shall refer only to the sample actually tested and shall
not refer or be deemed to refer to bulk from which such a sample may be said to have been
obtained.
- This report shall not be reproduced except in full without prior authorization from Intertek Testing
Services (Thailand) Limited.
- The services are provided subject to the terms and condition of the company, which can be
furnished upon request.
- The measurement uncertainty has been taken into consideration of the test results.
Regarding to manufacturer information, tested model indoor unit DSE60FAI-01 matching with outdoor
unit: DSE603CSFAO-01 in this report are identical to below models, the difference is model name by
optional suffix for market destination.
Outdoor unit model: DSE603CSFAO(++)-(*)
Indoor unit model: DSE60FAI(+)-(*)
where
Optional Suffix (*) Optional suffix
(+) 00 : Other region
01 : UAE
C – Advance Controller 03 : Qatar
T- TXV 04 : Bahrain
TC- Advance controller and TXV 12 : Oman
(++)
G – Metallic Guard
S – Oil separator
SG – Oil separator and Metallic Guard
Page 3 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
General Remark: (Cont’d)
This test report includes the following sections:
1. : Installation
2. : Test Condition
#1 Cooling capacity test at condition T1 (400V 50Hz)
#2 Cooling capacity test at condition T3 (400V 50Hz)
#3 Cooling capacity test at condition outdoor dry bulb temperature 35 °C with indoor
dry bulb temperature 26.7 °C and wet bulb temperature 19.4 °C
#4 Maximum operating condition at 52 °C outdoor dry bulb temperature for at least
two (2) hours continuously
#5 Setting lower temperature of the air conditioner (Thermostat 20 ºC Set point
Evaluation)
#6 Maximum cooling performance test (90 % of the lower rated voltage and 110 %
of the higher rated voltage for units with a dual or extended nameplate voltage)
#7 Maximum operating condition at 55 °C outdoor dry bulb temperature for at least
two (2) hours continuously (Test condition specified by applicant)
3. : Test result
Annex A : Marking label
Annex B : General unit picture
Annex C : Component list
Annex D : Control Settings
Page 4 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Section 1: Installation
The equipment was installed in accordance with the manufacturer's installation instructions, using
recommended installation procedures and accessories. Pipe length 7.5 m was used for connection between
indoor and outdoor unit. The refrigerant R410A was charged 5.8 kg according to the marking label, which
may affect the validity of the test result. No additional refrigerant was charged or discharged during the test
Test voltage (V) V 400 400 400 456.5 400 342/456.5 400
Note: The wet-bulb temperature of air entering outdoor side during the cooling capacity test was not controlled because
the tested unit is air-cooled condensers which do not evaporate the condensate.
Page 5 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Section 2: Test Condition (Cont’d)
Setting lower temperature of the air conditioner (Thermostat 20ºC Set point Evaluation) (Clause 5
UAE.S 5010-5: 2019)
All appliances subject for certification shall comply with the thermostat temperature setting limit that limiting
the lowest allowable cooling temperature set point to 20 ºC.
The minimum cut-off temperature measured during the test shall not be lower than 18 ºC when thermostat
set at 20 ºC.
Maximum cooling performance test (Clause 6.2 ISO 13253: 2017)
Preconditions:
- The controls of equipment shall be set for maximum cooling and, if provided, all ventilating air dampers and
exhaust air dampers shall be closed
Duration of test: The equipment shall be operated continuously for 1 h after the specified air temperature
have been established, all power to the equipment shall be cut off for 3 mins and then restored. The
operation of this equipment may be restarted either automatically or through the use of a remote controller or
similar device. The test shall continue for 60 mins after the equipment restarts
Page 6 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Section 3: Test result - Cooling capacity test
Test Results (at 400V 50Hz)
Items Unit
Condition T1 Condition T3
Dry – bulb temperature of air entering indoor side °C 27.00 29.01
Wet – bulb temperature of air entering indoor side °C 19.00 19.00
Dry – bulb temperature of air entering outdoor side °C 35.00 46.02
Wet – bulb temperature of air entering outdoor side °C 20.76 26.32
Dry – bulb temperature of air leaving equipment °C 14.15 15.96
Wet – bulb temperature of air leaving equipment °C 12.98 14.02
Nozzle pressure difference Pa 281.95 294.37
External static pressure Pa 50.01 50.01
Dehumidify weight kg/h 5.73 1.72
Inlet Enthalpy kJ/kg 54.19 54.17
Outlet Enthalpy kJ/kg 36.83 39.57
Enthalpy Differential kJ/kg 17.36 14.60
Air flow rate m3/s 0.802 0.823
Air Speed m/s 21.58 22.12
Barometric pressure kPa 100.67 100.59
Latent Capacity W 4074.42 1233.58
Sensible Capacity W 12672.53 13097.30
W 16746.95 14330.88
Total Cooling Capacity
Btu/h 57140.593 48896.963
W 17098.94 14683.22
Gross Cooling Capacity
Btu/h 58341.583 50099.147
Voltage V 400.70 400.30
Frequency Hz 50.3 50.0
Current A 7.62 9.15
Effective Power Input W 4926.26 5999.31
IDU Fan Power Input W 351.99 352.34
Power factor % 93.3 94.6
W/W 3.400 2.389
EER
(Btu/(h.W)) 11.599 8.150
W/W 3.471 2.447
Gross EER
(Btu/(h.W)) 11.843 8.351
Page 7 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Section 3: Test result (Cont’d) - Cooling capacity test
Test Results Outdoor dry bulb
temperature 35 °C with indoor dry
Items Unit
bulb temperature 26.7 °C and wet
bulb temperature 19.4 °C
Dry – bulb temperature of air entering indoor side °C 26.67
Wet – bulb temperature of air entering indoor side °C 19.44
Dry – bulb temperature of air entering outdoor side °C 35.00
Wet – bulb temperature of air entering outdoor side °C 20.80
Dry – bulb temperature of air leaving equipment °C 14.47
Wet – bulb temperature of air leaving equipment °C 13.39
Nozzle pressure difference Pa 279.18
External static pressure Pa 50.01
Dehumidify weight kg/h 7.17
Inlet Enthalpy kJ/kg 55.70
Outlet Enthalpy kJ/kg 37.90
Enthalpy Differential kJ/kg 17.80
Air flow rate m3/s 0.799
Air Speed m/s 21.49
Barometric pressure kPa 100.60
Latent Capacity W 5096.09
Sensible Capacity W 11950.10
W 17046.19
Total Cooling Capacity
Btu/h 58161.600
W 17396.7
Gross Cooling Capacity
Btu/h 59357.54
Voltage V 400.70
Frequency Hz 50.3
Current A 7.62
Effective Power Input W 4931.21
IDU Fan Power Input W 350.51
Power factor % 93.4
W/W 3.457
EER
(Btu/(h.W)) 11.795
W/W 3.528
Gross EER
(Btu/(h.W)) 12.037
Page 8 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Section 3: Test result (Cont’d) - Maximum operating condition at 52 °C outdoor dry bulb temperature
for at least two (2) hours continuously
Items Unit Test Condition
Dry – bulb temperature of air entering outdoor side °C 52.01
Wet – bulb temperature of air entering outdoor side °C --
Dry – bulb temperature of air entering indoor side °C 32.00
Wet – bulb temperature of air entering indoor side °C 23.00
Test voltage (V) V 456.73
Test frequency (Hz) Hz 50.30
External Static Pressure (Pa) Pa 50.00
Test Result: The appliances operated at 52 °C outdoor dry bulb temperature for at least two (2) hours
continuously
Page 9 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Section 3: Test result (Cont’d) - Setting lower temperature of the air conditioner (Thermostat 20ºC Set
point Evaluation)
All appliances subject for certification shall comply with the thermostat temperature setting limit that limiting
the lowest allowable cooling temperature set point to 20ºC.
The minimum cut-off temperature measured during the test shall not be lower than 18ºC when thermostat
set at 20ºC.
Sample 1
Thermostat temperature Unit cut-off temperature Minimum cut-off
Cut-off no. Conclusion
setting limit (°C) (°C) temperature (°C)
1 20 18.65 ≥ 18 Pass
2 20 18.65 ≥ 18 Pass
3 20 18.83 ≥ 18 Pass
Page 10 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Section 3: Test result (Cont’d) - Maximum cooling performance test
Test Result
Items Unit
342 V 456.5 V
Test Conditions:
Dry – bulb temperature of air entering outdoor side °C 51.99 52.01
Wet – bulb temperature of air entering outdoor side °C -- --
Dry – bulb temperature of air entering indoor side °C 32.00 32.00
Wet – bulb temperature of air entering indoor side °C 23.00 23.00
Applied voltage V 342.17 456.73
Frequency Hz 50.30 50.30
Total current input to equipment A 11.62 11.00
Total power input to equipment W 6774.73 7368.81
Test Result:
The equipment shall operate without any indication of damage No damage No damage
Motors operated continuously for the 1st hr of the test without tripping of
No tripping No tripping
the motor-overload protective devices
Tripping duration of the motor-overload protective device after the 0:00 min 0:00 min
shutdown period of 3 min ( No tripping) ( No tripping)
The equipment shall remain operating with no motor-overload device
No tripping No tripping
tripping for the remainder of 1 hr re-stored period
Conclusion Pass Pass
Page 11 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Section 3: Test result (Cont’d) - Maximum operating condition at 55 °C outdoor dry bulb temperature
for at least two (2) hours continuously
Items Unit Test Condition
Dry – bulb temperature of air entering outdoor side °C 55.02
Wet – bulb temperature of air entering outdoor side °C --
Dry – bulb temperature of air entering indoor side °C 27.00
Wet – bulb temperature of air entering indoor side °C 19.00
Test voltage (V) V 400.09
Test frequency (Hz) Hz 50.30
External Static Pressure (Pa) Pa 50.01
Test Result: The appliances operated at 55 °C outdoor dry bulb temperature for at least two (2) hours
continuously
Page 12 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Calculation of the cooling seasonal performance factor (CSPF) for moderate climates (ISO 16358-1:
2013)
(Reference calculator: 20181107 ISO16358-1_AMD1 Calculation_tool_FINAL.xlsm)
Fixed capacity unit:
The defined cooling load is assumed linearly changing depending on the change in outdoor temperature as
shown below:
Noted: Tested capacity shown here is gross capacity which includes the effect of the evaporator fan motor
heat
Page 13 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Calculation of the cooling seasonal performance factor (CSPF) for hot climates (Annex F, ISO 16358-
1: 2013/Amd.1: 2019)
(Reference calculator: 20181107 ISO16358-1_AMD1 Calculation_tool_FINAL.xlsm)
Fixed capacity unit:
The defined cooling load is assumed linearly changing depending on the change in outdoor temperature as
shown below:
Noted: Tested capacity shown here is gross capacity which includes the effect of the evaporator fan motor
heat
Page 14 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Nameplate data validity and minimum energy performance standard (MEPS) check
Referenced standard: QCC-PCS-ASP017.01: 2016 – Abu Dhabi Certification Scheme for Ozone Friendly
Air-cooled Unitary Air Conditioners
Description Rated Measured Ratio Limit Conclusion
Cooling capacity test at condition T3 (400V 50Hz)
Cooling capacity (Btu/h) 50900 50099.147 0.984 ≥ 0.95 rated Pass
Cooling capacity test at condition Outdoor dry bulb temperature 35 °C with indoor dry bulb
temperature 26.7 °C and wet bulb temperature 19.4 °C
Cooling capacity (Btu/h) 59000 59357.54 1.006 ≥ 0.95 rated Pass
Effective Power Input (W) 4950 4931.21 0.996 ≤ 1.05 rated Pass
Page 15 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Nameplate data validity and minimum energy performance standard (MEPS) check
Referenced standard: UAE.S 5010-5:2019 - Labeling – Energy efficiency label for electrical appliances -
Part five: commercial and central Air conditioners
Description Rated Measured Ratio (%) Limit Conclusion
Cooling capacity test at condition T3 (400V 50Hz)
Cooling capacity (Btu/h) 50900 50099.147 98.43 ≥ 95% rated Pass
Effective Power Input (W) 6020 5999.31 -- -- For reference
Page 16 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Nameplate data validity and minimum energy performance standard (MEPS) check
Referenced standard:
- REGULATION ON ENERGY LABELLING AND MINIMUM ENERGY PERFORMANCE
REQUIREMENTS FOR AIR-CONDITIONERS (2015)
- GSO 2530: 2016 Energy Labelling and Minimum Energy Performance Requirements for Air-
Conditioners
Description Rated Measured Ratio Limit Conclusion
Cooling capacity test at condition T1 (400V 50Hz)
Cooling capacity (Btu/h) 58000 58341.583 1.006 ≥ 0.95 rated Pass
Effective Power Input (W) 4950 4926.26 0.995 < 1.05 rated Pass
Page 17 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Annex A: Marking label – UAE market
Indoor unit
Outdoor unit
Page 18 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Annex A: Marking label – Other region market
Indoor unit
Outdoor unit
Page 19 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Annex A: Marking label – Bahrain market
Indoor unit
Outdoor unit
Page 20 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Annex A: Marking label – Oman market
Indoor unit
Outdoor unit
Page 21 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Page 22 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Annex C: Component list
Page 23 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923
Report No.: 21066023BKK-001
Annex D: Control Settings
Page 24 of 24
Intertek Testing Services (Thailand) Limited.
1285/5 Prachachuen Rd., Wongsawang, Bangsue, Bangkok 10800 THAILAND
th
Tel : +66 2 837 2888Univest
Fax : Complex No.546,
+66 2 837 2889 4 Floor, Ratchadapisek Road, Chankasem, Chatuchak, Bangkok 10900 Rev.0
Tel: (662)www.intertek.com
938-1990 Fax: (662) 938-1923