Lighting Layout Plan Lighting Layout Plan: General Notes

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

GENERAL NOTES:

SERVICE ENTRANCE
230 V, 1Ø, 3W, 60Hz 1. THE ELECTRICAL INSTALLATION HEREIN SHALL BE DONE
IN ACCORDANCE WITH THE PROVISIONS OF THE LATEST
LEGEND: EDITION OF THE PHILIPPINE ELECTRICAL CODE, THE
EXISTING ELECTRICAL CODE, THE EXISTING LOCAL
SERVICE ENTRANCE ORDINANCES REQUIREMENTSOF THE LOCAL POWER
CIRCUIT BREAKER M KW-HR METER COMPANY AND RULES AND REGULATIONS OF THE LOCAL
1

CIRCUIT HOMERUN ENFORCING AUTHORITY.


2 - 30mm THHN WIRE
GROUND LINE 8.0mm THW 2. THE TYPE OF POWER SERVICE TO BE SUPPLIED SHALL
PB
PANEL BOARD
32mmØ PVC PIPE BE 220V- WYE SECONDARY; 3Ø, 3W, 60Hz
MDP
MAIN DISTRIBUTION PANEL 3. THE CONTRACTOR SHALL VERIFY AND ORIENT THE
M ELECTRIC METER ACTUAL LOCATION OF THE SERVICE ENTRANCE CONNEC
TION TO. UTILITY POWER SUPPLY.
4. THE MAIN PANEL BOARD SHALL BE CONNECTED TO THE
NEAREST DISTRIBUTION SUBSTATION.
5. UNLESS OTHERWISE SPECIFIED, THE MINIMUM SIZE OF
WIRE AND CONDUIT SHALL BE NO. 3.5mm (#12) AND
NORMAL DIAMETER RESPECTIVELY.
15AT 1P 15AT 1P
LIGHTING LIGHTING
6. SERVICE ENTRANCE HEREIN SHALL BE IN INTERMEDIATE
OUTLET 1 1 OUTLET METALLIC CONDUIT (IMC) PIPE.
15AT 1P 20AT 1P 7. BRANCH CIRCUIT INSTALLATION FOR LIGHTING AND POWER
LIGHTING LIGHTING SYSTEM SHALL BE PROPERLY IDENTIFIED BY USING
OUTLET
1 1 OUTLET
15AT 1P 20AT 1P
METALLIC CONDUIT PIPE SCHEDULE 40"
CONVINIENCE
1 1
CONVINIENCE 8. ALL ELECTRICAL EQUIPMENT SHALL BE EQUIPPED WITH
OUTLET OUTLET
20AT 1P 30AT 1P
PROPER GROUNDING, GROUND WIRES SHALL GREEN
CONVINIENCE
INSULATION.
1 1 ACU
OUTLET 9. ALL MATERIALS SHALL BE NEW , OF LATEST MANUFACTURE
20AT 1P 30AT 1P
AND OF THE AND OF THE APPROVED TYPE.
ACU 1 1 ACU
10. STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES,
30AT 1P 20AT 1P TERMINATION AND OTHER APPURTENANCES FOR THE ENT-
ACU 1 1 REF IRE ELECTRICAL INSTALLATION SHALL BE USED.
30AT 1P 15AT 1P 11. ALL NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL .
(GROUND FLOOR) (2nd FLOOR) RANGE 1 1 SPARE
EQUIPMENT . AND LIGHTING FIXTURE SHALL BE EFFEC-
TIVELY GROUNDED.
NEUTRAL BUSBAR
1 LIGHTING LAYOUT PLAN 2 LIGHTING LAYOUT PLAN GROUND BUSBAR
13. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER
THE DIRECT SUPERVISION OR A DULY LICENSED ELECTRICAL
E-1 SCALE 1:75M E-1 SCALE 1:75M ENGINEER. ENGINEER.
14. FIXTURE MOUNTING HEIGHT SHALL BE AS FOLLOWS:
a. LIGHTING SWITCH - 1.40m ABOVE THE FINISH FLOOR LINE
5 RISER DIAGRAM AND 0.10m AWAY FROM DOOR JAMB
b. CONVENIENCE OUTLETS - 0.40m ABOVE THE FINISH
E-1 FINISH FLOOR LINE AND 0.15m ABOVE THE FINISH
LEGEND: WORKING COUNTER FROM JAMB.
c. PANEL BOARD - 1.80m ABOVE THE FINISH FLOOR LINE.
PANEL BOARD

CIRCUIT NO.
SCHEDULE OF LOADS
220V OUTLET OUTLET BRANCH CIRCUIT
CKT NO. LOAD SERVED VA VOLTS AMP L.O C.O PROTECTION
SIZE OF WIRES SIZE OF CONDUITS

220V OUTLET 1 L - OUTLET 1100 230 4.78 11


2 L - OUTLET 800 230 3.47 8 15 AT, 2P CB USE: 2-2.0 sq. mm. 20 mm Ø PVC
THHN STR. WIRE CONDUIT
L-SWITCH 3 L - OUTLET 1100 230 4.78 11
FLOURESCENT 4 L - OUTLET 1000 230 4.34 10
5 C - OUTLET 2250 230 9.78 9
USE 2-3.5 sq. mm. 20 mm Ø PVC
COVE LIGHT 6 C - OUTLET 2000 230 8.69 8 20 AT, 2P CB
THHN STR. WIRE CONDUIT

REF
REF 7 C - OUTLET 2250 230 9.89 9
R 8 ACU OUTLET 2760 230 12.00 1
RANGE 9 ACU OUTLET 2760 230 12.00 1 USE 2-5.5 sq. mm. 20 mm Ø PVC
30 AT, 2P CB THHN STR. WIRE CONDUIT
S2 2- GANG SWITCH 10 ACU OUTLET 2760 230 12.00 1
S3 3- GANG SWITCH 11 ACU OUTLET 2760 230 12.00 1
12 REFRIGERATOR 750 230 3.26 1 30 AT, 2P CB
DOWN LIGHT
13 RANGE 4000 230 17.39 1 30 AT, 2P CB USE 2-3.5 sq. mm. 20 mm Ø PVC
PIN LIGHT 14 SPARE OUTLET 1200 230 5.22 1 20 AT, 2P CB THHN STR. WIRE CONDUIT

(2nd FLOOR) WALL LIGHT TOTAL LOAD 27,107.54 119.60

4 POWER LAYOUT PLAN FOR FEEDER LINE: SERVICE FEEDER: ENCLOSURE: NEMA I
(GROUND FLOOR) USE 2-30.0 sq.mm THHN MOUNTING: SURFACE
E-1 SCALE 1:80M I TOTAL = 119.60 x 80% D.F. 1-8.0 sq.mm THW /32mm Ø PVC MAIN: 100 AT, 2P, 230V
3 POWER LAYOUT PLAN I TOTAL = 95.68 AMP CIRCUIT BREAKER
E-1 SCALE 1:80M 6 COMPUTATION OF LOADS
E-1
ARCHITECT ENGINEER PROJECT TITLE OWNER: DRAWN BY: REVISIONS: SHEET CONTENTS: SHEET N0.:

AR. RHOEL D. SAMSON PROPOSED TWO STOREY RESIDENCE MR. JOSE G. MANARIN GENERAL NOTES
1
E
LIGHTING LAYOUT
DATE:
POWER LAYOUT
PRC Reg No. 16407 PLACE: MANILA CITY PRC Reg No. PLACE: ADDRESS: CHECKED BY:
NOTE: THIS DRAWING AS INSTRUMENTS OF SERVICE ARE INTELLECTUAL RISER DIAGRAM
PROPERTY OF THE ARCHITECT.IT SHALL BE UNLAWFUL FOR A PERSON TO COMPUTATION OF
PTR No. 8436749 IAPOA - 15765280641121219 TIN No. Date: COPY OR DUPLICATE SUCH DRAWINGS WITHOUT THE CONSENT OF THE LOT 17 BLOCK 17 QUEEN OF PEACE ST. OUR LADY OF LOURDES SUBD. RD SAMSON
CUPANG , ANTIPOLO CITY LOADS
ARCHITECT/AUTHOR OF THE SAID DOCUMENTS- RA 9266.
TIN No. 186099524 Date: DEC 12, 2019 PTR No. DATE: ELECTRICAL