Professional Documents
Culture Documents
MODULE 3 RAC Servicing and Maintenance
MODULE 3 RAC Servicing and Maintenance
LEARNING OUTCOMES:
1. Discuss refrigeration maintenance and servicing;
2. Appreciate the importance of maintenance and servicing refrigeration; and
3. Perform servicing and maintenance of refrigeration units.
RECIPROCATING COMPRESSOR
* Larger pipe than discharge line * Smaller tube than suction line
* Connected from evaporator * Connected to the condenser
* It is on the low-side * It is on the high-side
* Oil will spill-out if turned downwards * Oil will not spill-out if turned downwards
PROCESS TUBE
OIL
Electric motor – is composed of stator and the rotor. Start winding and run winding are
wound in the stator. The rotor has a shafting that is connected to the crankshaft of the piston-
cylinder unit of the compressor.
ACTIVITY NO 1
Activity Title: How to identify the common, running, and starting terminals of a hermetic
Compressor motor?
Materials/Supply/Instrument Needed:
1 set Ohmmeter
1 unit Hermetic compressor
1 pc Yellow pad paper
1 pc Ball pen
1 roll Masking tape
Procedures
1. Get the ohmmeter, and set selector knob to X 1; short circuit
the test probes and adjust the Ohm-zero adjuster.
Example:
Terminals 1 & 2 = 15 Ohms
Terminals 1 & 3 = 3 Ohms
Terminals 2 & 3 = 18 Ohms
4. Get the highest reading among the three; Terminals 2 & 3 got 18 Ohm resistance.
5. Since Terminal 1 is the remaining Terminal where test probe of the ohmmeter is not
connected, mark Terminal 1 as Common Terminal.
6. Compare Terminals 1 & 2 with 15-Ohm resistance and Terminals 1 & 3 with only 3-
Ohm resistance.
7. Mark Terminal 2 as Starting Terminal because it has second highest resistance
8. Mark Terminal 3 as Running Terminal because it has the lowest resistance value.
9. Label the terminals
1. Short Circuit
If two sets of
terminals have the same
resistance value, such as:
1 – 2 = 15 Ohms;
1 – 3 = 15 Ohms;
2 – 3 = 3 Ohms,
you have a short circuit
motor.
3. Grounded
If there is reading
resistance or continuity
between the terminals
and the case metal or
body, you have a
grounded motor
4. High-Ampere – After
taking the resistance between the terminals
and the CSR is good, the piston is
functioning, there is suction and discharging,
but the ammeter reading is too high beyond
the specification of the amperage reading of
the motor, you have a high-ampere motor
trouble.
5. Loose Compression Motor – It means that the motor is running and the piston is
moving but there is no suction or discharge pressure, it is known as the loose
compression trouble. Weak valves can be categorized in this mechanical defect, it means
that there is suction and discharging but it cannot maintain the pressure on the discharge
line or suction.
6. Stuck-up Compressor – When you turn on the compressor and there is no suction
and discharge pressure, but a humming sound of the motor and the amperage reading is
high, the piston is stuck-up in the cylinder, defective bushing or mechanical parts, or
defective electrical motor.
1. Reverse the compression rotation by connecting the extra capacitor into the
electrical circuit of the main winding. Turn-on the power from one to three seconds. This
capacitor cannot be left in the circuit for more than three seconds. It will cause the motor
overheat. If the compressor is successfully reversed, remove the capacitor and try to run
the compressor using the normal electrical connection. If the motor does not start after
three or four attempts, replace the compressor.
1. While the
compressor is in the
system, install the
compound gage on
the low side and
pressure gage on the
high side. Turn on the
compressor and
observe the reading
on the gage. If you have both same gage reading, example: compound gage reads 35 psig
and the pressure gage has 35 psig also, you have loose compression. There is no suction
and discharging of refrigerant.
2. Remove the
compressor from the
system, install
compound gage on
the suction line and
pressure gage on the
discharge line. Turn-
on the compressor
and observe the gages
readings. Let pressure 25” Hg build-up in the compound gage and 130 psig on the
pressure gage.
Shut-off the compressor and observe the gage reading. If the compound gage reading of
25” Hg goes down to 15” to 0” Hg, while the pressure gage reading of 130 psig goes
down to 50 to 0 psig within 15 minutes, your valves are weak
If the pressure on both sides maintain readings within 15 min., the valves are good. The
pressure will really go down slowly but not within a limit of 15 min.
2. Place your test prods one on the R connection and the other to the screw on the side
of the relay. Find out if there is continuity. If none, the relay is defective; if there is,
continue the test.
3. Then place the other test prod from the screw to the S.
1. Get Ohmmeter and adjust the selector range knob to X1 ohm. Zero-in the pointer by
adjusting the Zero-ohm adjuster knob.
A. Bulb
1. Get the ohmmeter and turn the selector range knob to X10 ohm; zero-in the pointer.
2. Place the test prods to the bulb as shown in the figure. The pointer must deflect to
resistance reading showing that the bulb is good; if no deflection occurs, the bulb is
defective.
B. Switch
GAGE MANIFOLD
Gage manifold is
composed of compound gage,
pressure gage, manifold, hook,
and two valves. The compound
gage measures the positive
pressure as well as the negative
pressure. The positive pressure
is measured up to 250 psig and
the negative pressure is
measured in 30” Hg. Vacuum.
The pressure gage measures pressure up to 500 psig. It is connected to the high-
side-pressure while the compound gage is connected to the low-side-pressure.
3. Wait for the vacuum reading of 29.9” Hg. Evacuation could be done within 15
minutes or more, depending on the design of the system.
4. If 29.9” Hg vacuum is reached, close valves A and B and turn-off the vacuum pump.
We are now on the process of leak testing by observing the compound gage. If within
15 minutes the needle of the compound gage deflected from 29.9” Hg to zero slowly,
the system has a leak. If the needle stays at 29.9” Hg within that time limit, proceed to
the next step.
5. While the valves are close, remove the vacuum pump and replace it with the freon
tank (B). Open the valve of the freon tank and loosen the connection of the hose to the
gage manifold, to purge air in the hose by refrigerant vapor for three seconds and then
tighten up the connection.
(A) (B)
6. Open valve A and charge the system with refrigerant in a vapor form up to 10 psig
just pressurized the system for leak-testing, then close Valve A. Conduct testing by
soap-bubbles to every connection of tubes as well as in the gage manifold.
7. If no leak is found, open once more valve A and add refrigerant up to 30 psig. Close
valve A and continue the leak- testing procedure.
8. If no leak is found, run the compressor. Observe from 30 psig of compound gage, it
will go down and settle slowly. Maintain a compound gage reading of 6-8 psig, while
the pressure gage will go up from 30 psig to 150 – 175 psig.
CAUTION:
When charging, observe ammeter reading. Amperage will be based on the
specification of the motor. Charging pressure must conform with the amperage of
the motor.
9. Observe the evaporator or freezer; a hizzing sound can be heard from the sudden
expansion (Sprayed) of the refrigerant from the capillary tube. A frost will develop
within a minute and ice can be produced within
one hour.
CAUTION:
If leak is found, repair the leak from procedure no.1 of charging the system.
remove the refrigerant in the system when soldering.
- When charging is being done in a room, open the windows for ventilation.
- Do not let children below 12 years old stay inside the same room, their body
resistance may not handle the smell of the refrigerant
13. After the pinch-off, place the plug nut and accomplish the leak-testing procedure.
Within one hour, the compound reading must maintain its reading of 8 psig; if it goes
down, it means that the system has leak. Repair the leak if any and go back to
procedure no. 1.
SELF-EVACUATION METHOD
6. Run the compressor once more, put flow on the capillary tube then close it again by
your thumb to minimize the entry of the air in the system. Wait for 50seconds, then
put-off the compressor. The flow must not reach the compressor; it may damage the
compressor windings.
CAUTION:
When charging, observe the ammeter reading. Amperage will be based on the
specification of the motor. Charging pressure must conform with the amperage of
the compressor.
13. Observe the evaporator or freezer; a hizzing sound can be heard from the sudden
expansion (sprayed) of the refrigerant from the capillary tube. A frost will develop
within a minute and ice can be produced within one hour.
OVERCHARGED REFRIGERANT
If the suction line is sweating or frosting, it means that the system is overcharged
with refrigerant. This can cause high-head pressure and high amperage to the
compressor which further results to compressor damage.
LEAK TESTING
There are five methods in detecting leaks in the system. One is by means of oil
spots on the refrigeration system. There is 2 to 4 percent oil mixed with the refrigerant
throughout the entire system and for some reason it will always come out and show
where the leak is. Another is by means of soap-bubbles. Pressurized the system with at
least 30psig. Apply soap-bubbles to every flare, hose, clamp, silver solder joints and to
all joints in the system. Leak will show-up through the soap-bubbles. Check for
corrosive tubes and copper oxide, for it will damage the copper. Greenish color will
appear on the tube if it is
attacked by copper oxide.
The third method is by means of halide torch. When using halide torch, make
sure that the room is free from refrigerant vapors. When you open the halide torch,
observe the color of the flame. When its sensor hose is over the leak, the color of the
flame will become green in color. A fraint green color indicates a small leak. If the leak
is large, the flame will be unmistakably green to purple.
The fourth method is by means of electronic leak detector. In operation, the gun
detector is turned on and adjusted in a normal atmosphere. The leak detecting probe is
then passed over the surface of all joints or connections in the system. If there is a leak,
no matter how tiny, the halogenated refrigerant is drawn into the probe. The leak gun
detector will make a piercing sound, or a light will flash, or both, denoting that there is
indeed a leak.
The fifth method is by using the compound gage of the gage manifold. It will tell
you if the system has leak. After you have done the evacuation of the system, close the
valves on both on both sides and wait for 15 minutes. If the gage stays at same vacuum
pressure, there is an excellent chance that there is no leak. If it changes, when the
pressure reading goes up within the period of time, your system has leak.
Remember that refrigerant does not wear out; it just leaks away. Every leak in the
system must be repaired before evacuating the system and making the final charge. All
flare nuts, bolts and clamps if there are any, must be tightened up.
Thermostat will trip for a Thermostat set to lower Reset the thermostat
Short period setting
LOW COOLING
SYMPTOMS POSSIBLE CAUSE REMEDY
Low pressure Lack of refrigerant Repair leak and add
Sweating evaporator refrigerant
Compressor runs for a short Low setting of thermostat Reset the thermostat
time
Door will not close tightly Loose door gasket Replace door gasket
Door is not close tightly Loose door gasket Replace door gasket
COPRESSOR TRIPPING
SYMPTOMS POSSIBLE CAUSE REMEDY
Overheat compressor High head pressure Replace compressor
High ampere
Reference: Refrigeration and Air Conditioning: repair and Troubleshooting Guide, reprinted
2010, by Joy Job A. Cabangon
Self-check
I Multiple Choice
Direction: Write the letter of the correct answer on the space provided.
__1. Short circuit in the hermetic compressor can be identified easily because of the following,
except…a) Common-Run and Common Start terminals have the same resistance value b)
Start-Run terminals have below normal resistance value c) The compressor dome and any
three terminals have resistance d) all of these
__2. If Common-Start terminals have resistance, while Common-Run and Start-Run have no
resistance, the hermetic compressor is…a) burn out or open b) shorted c) grounded d) all
of these
__3. If there is reading resistance or continuity between the terminals and the case metal or
body, the hermetic compressor has a…a) shorted motor b) grounded motor c) open or burn
out motor. d) all of these.
__4. Causes of high amperage reading of motor having good resistances in the common, start,
and run windings are…a) the current flows more the required one b) the defective
mechanical or defective motor winding c) the compressor with very hot case that it cannot
be touched for 5 seconds. d) all of these
__5. This compressor trouble is characterized with no suction or discharge pressure even if the
hermetic compressor’s piston is moving or there is suction and discharging but it cannot
maintain pressure on the discharge line or suction. a) loose compression b) stuck-up
compressor c) grounded or shorted compressor d) all of these
__6. The following are the distinguishing feature of a discharge line, except…a) Smaller tube
than suction line b) Connected to the evaporator c) Oil will not spill-out if turned
downwards d) It is on the high-side
__7. The following are the identification feature of the process tube, except…a) It is on the
high-pressure side b) It can be used as a suction line c) It is used for charging line d) It is
used for evacuation
__8. The following are three pin-terminals found in the hermetic compressor, except…a)
Common b) Start c) L1 and L2 d) Run
__9. The following are the stator winding of an electric motor, except…a) run winding b) start
winding c) rotor winding d) all of these
__10. Reciprocating compressor is a compressor where piston inside the cylinder is moving…a)
up-side-down b) up and down c) side by side d) sideward
__11. If the pointer of the ohmmeter is deflected, after inverting the relay up-side-down without
removing the test prod on the S and R connection, the relay is…a) defective b) weak c)
good. d) all of these
__12. The Overload Protector (O.L.P.) is________if there is no continuity after placing the test
prods to its terminals. a) defective b) weak c) good. d) all of these
__13. The purpose of placing the sensing bulb’s thermostat to a container filled with ice, check
the continuity, and 20 to minutes’ time observation is to check if the thermostat…a)
responds to the change of temperature. b) senses the presence of ice. c) detects
temperature change. d) all of these
__14. After 20 to 30 minutes of removing the sensing bulb of the thermostat at number 1 setting
in a container filled with ice without zero-ohm continuity deflection, it means, the
thermostat is…a) defective b) good c) weak d) all of these
__15. Within 20 to 30 minutes of placing the sensing bulb of the thermostat at number 1 setting
in a container filled with ice without zero-ohm continuity deflection, it means, the
thermostat is…a) defective b) good c) weak d) all of these
__16. If the suction line is sweating or frosting, it means that the system is…a) undercharged
with refrigerant b) overcharged with refrigerant c) lack of refrigerant d) none of these
__17. Overcharged refrigeration system manifested the following symptoms, except…a) high-
head pressure b) high amperage than normal c) frosting evaporator. d) suction line
sweating/frosting
__18. The following are leak testing methods, except…a) oil spots on the refrigeration system b)
soap-bubble method c) refrigerant inhalation d) halide torch
__19. The following are symptoms of refrigeration system if the compressor will not start,
except…a) No voltage on the outlet/socket b) No resistance reading in overload relay c)
No resistance reading in the compressor d) There is resistance reading in the starting
relay.
__20. If the refrigeration system cannot produce ice even the compressor is running, its possible
defect might be…a) no refrigerant b) loose compression c) clog drier or strainer d) all of
these.
__21. The following tools are used to evacuate and charge the system with refrigerant, except…
a) blow torch b) Freon tank and charging line c) adjustable wrench d) Gage manifold and
hoses
__22. Which of the following does not belong to the group? a) compound gage b) pressure gage
c) manifold hook, d) two hand bulbs.
__23. The positive pressure is up to 250 psig and negative pressure is up to…a) 30” Hg. b) 30’
Hg. c) 30, Hg. d) all of these
__24. The pressure gage measures pressure up to…a) 500 psi. b) 500 psig. c) 500 pcs. d) all of
these
__25. Pressure gage is connected to the high-side-pressure, compound gage in connected to
the…a) low-pressure b) low-side-pressure c) pressure-side d) all of these
__26. This appliance has temperature ranging from 350 F to 400F necessary in the preservation of
food. a) refrigerant b) refrigeration c) refrigerator d) all of these.
__27. Which of the following is not included in the group? a) three-door refrigerator b) floor
mounted evaporator c) two-door refrigerator d) single-door refrigerator
__28. The following are parts of the reciprocating pump, except…a) electric motor b)
connecting rod and crankshaft c) cylinder head and valves d) piston and cylinder
__29. Inside the hermetic or sealed-in unit compressor is the… a) reciprocating pump and
electric motor b) electric motor and fan blade c) reciprocating pump and metal case d) all
of these
__30. Suction line is usually connected on the low side and is identified thru the following,
except…a) larger tube than discharge b) connected from evaporator c) oil will not spill-out
it turned downwards
__31. The sensing bulb is filled with volatile fluid so that the temperature increase, it will boil
inside causes the pressure to push the switching mechanism to…a) open the contact b)
close the contact c) neutralize the contact d) none of these
__32. The pointer deflects to resistance after placing the test prods to the bulb if it is…a)
defective b) good c) weak d) all of these
__33. Refrigerant charging is the process of________to the refrigeration system. a) adding
refrigerant b) loading refrigerant c) all of these d) none of these
__34. Before charging refrigerant to the system, the refrigeration unit must be…a) free from tiny
particles inside the system b) evacuated c) free from moisture d) all of these
__35. Evacuation is the process of removing_________inside the system. a) tiny particles b)
moisture c) dirt d) all of these
__36. In removing the vacuum pump to replace Freon tank, open the valve of the Freon tank and
loosen the connection of the hose to the gage manifold, to…a) purge air in the hose by
refrigerant b) Clean the hose free of air c) flush the hose to remove dirt d) all of these
__37. If no leak is found, run the compressor. While charging refrigerant, observe from 30 psig
of compound gage, it will go down and settle slowly. Maintain a compound gage reading
in the low-pressure-side at…a) 6psig b) 7psig c) 8psig d) all of these
__38. If no leak is found, run the compressor. While charging refrigerant, observe the pressure
gage in the high-pressure side to go up from 30 psig to…a) 150psig b) 165psig c)
175psig d) all of these
__39. Observe the evaporator or freezer; a hizzing sound can be heard from the
sudden_______ of the refrigerant from the capillary tube. a) expansion b) Sprayed c)
vaporization d) all of these
__40. During refrigerant charging, observe the condenser, it will ______ simultaneously with
the reaction of the evaporator. a) reduce the temperature b) raise the temperature. c)
remain the temperature
__41. When evacuating the system, the compound gage is connected to low-pressure-side and
for the high-pressure-side is connected to …a) pressure gage b) hand valves c) manifold
gage d) all of the
__42. Switching on the vacuum pump with open hand valves A and B until reaching negative
pressure of 29.9” Hg, within 15 minutes or more is an indication that the refrigeration
system is…a) perfectly evacuated b) dirt and air free c) tiny particles and moisture free
d) all of these.
__43. If within 15 minutes the needle of the compound gage deflected from 29.9” Hg to zero
slowly, the…a) system is leak free b) the system is perfectly sealed c) system has a leak.
d) all of these.
__44. If the needle stays at 29.9” Hg within that time limit, the…a) system is leak free b) the
system is slightly sealed c) system has a leak. d) all of these.
__45. After evacuating the system, and before connecting Freon tank or refrigerant cylinder,
both hand valves of the manifold gage should be closed to…a) prevent air and moisture
from entering the system b) allow air to enter the system. c) make system filled with
oxygen d) all of these
__46. Stuck-up compressor has no suction and discharge pressure, but a humming sound of the
motor accompanied with high amperage reading. This is primarily caused by the
following, except…a) the piston is stuck-up in the cylinder b) defective bushing or
mechanical parts c) defective electrical motor. d) none of these
__47. The following are remedy for compressor with clogged piston/cylinder unit, except… a)
Reverse the compression rotation b) connect the compressor to a higher voltage source c)
increase the speed of the electric motor d) to increase the torque of the electric motor
__48. If the compound gage reading of 25” Hg goes down to 15” to 0” Hg, while the pressure
gage reading of 130 psig goes down to 50 to 0 psig within 15 minutes, your valves are…a)
weak b) good c) free from defects d) all of these.
__49. If the pressure on both sides maintain readings within 15 min., the valves are… a) weak b)
good c) defective d) all of these.
__50. If there is continuity after connecting test prod on the R connection and the other to the
screw on the side of the current or push-on relay, then it is...a) good b) defective c) weak
d) all of these