Professional Documents
Culture Documents
03 Fault Calculations
03 Fault Calculations
03 Fault Calculations
2
Per Unit Calculations
Per Unit Calculations
• A key problem in analyzing power systems is the
large number of transformers.
• It would be very difficult to continually have
to refer impedances to different sides of
transformers
• This problem is avoided by a normalization of all
variables.
• This normalization is known as per unit analysis.
actual quantity
quantity in per unit =
base value of quantity
4
Per Unit Conversion Procedure, 1φ
1. Pick a 1f VA base for the entire system, SB
2. Pick a voltage base for each different voltage
level, VB. Voltage bases are related by
transformer turns ratios. Voltages are line to
neutral.
3. Calculate the impedance base, ZB= (VB)2/SB
4. Calculate the current base, IB = VB/ZB
5. Convert actual values to per unit
Note, per unit conversion affects magnitudes, not the
angles. Also, per unit quantities no longer have units
(i.e., a voltage is 1.0 p.u., not 1 p.u. volts) 5
Per Unit Solution Procedure
Original Circuit 7
Example 1
Using the turns ratio of transformers, the base voltages are
a) 8 kV in generator side, b) 80 kV in line side, c) 16 kV in load side
82 (kV) 2
Z BLeft = = 0.64
100MVA
802 (kV) 2
Z BMiddle = = 64
100MVA
162 (kV) 2
Z BRight = = 2.56
100MVA
Impedances in per unit are:
j1
Z Left = = j1.56 pu
0.64
j 24
Z Middle = = j 0.375 pu
64
10 + j1
Z Right = = 3.91 + j 0.39 pu Same circuit, with values expressed in pu
2.56 8
Example 1
1.00
I = = 0.22 − 30.8 p.u. (not amps)
3.91 + j 2.327
VL = 1.00 − 0.22 − 30.8
= − p.u.
2
VL
SL = = *
VL I L = 0.189 p.u.
Z
SG = 1.00 0.2230.8 = 30.8 p.u.
9
Example 1
To convert back to actual values just multiply
the per unit values by their bases
VLActual
= 0.859 − 30.8 16 kV = 13.7 − 30.8 kV
S LActual = 0.1890 100 MVA = 18.90 MVA
Actual
SG = 0.2230.8 100 MVA = 22.030.8 MVA
100 MVA
Middle
IB = = 1250 Amps
80 kV
Actual
I Middle = 0.22 − 30.8 = 275 − 30.8
10
Three Phase Per Unit
Procedure is very similar to 1f except we use a
3f VA base, and use line to line voltage bases
1. Pick a 3f VA base for the entire system, S B3f
2. Pick a voltage base for each different voltage
level, VB,LL. Voltages are line to line.
3. Calculate the impedance base
2 2 2
VB , LL ( 3 VB , LN ) VB , LN
Z B = 3f = 1f
= 1f
SB 3S B SB
Exactly the same impedance bases as single phase using the
corresponding single phase VA base and voltage base! 11
Three Phase Per Unit
12
Example 2
Solve for the current, load voltage and load
power in the previous circuit, assuming:
• 3φ power base of 300 MVA,
• Line to line voltage bases of 13.8 kV, 138 kV and
27.6 kV (√3 larger than the 1φ example voltages)
• The generator is Y-connected so its line to line
voltage is 13.8 kV.
13
Example 2
Convert to per unit as before.
13.82 (kV) 2
VBLeft = 13.8 (kV) Z BLeft =
300MVA
= 0.64 Z Left =
j1
= j1.56 pu
0.64
VBMiddle = 138 (kV) Z BMiddle =
1382 (kV) 2
= 64 Z Middle =
j 24
= j 0.375 pu
300MVA 64
VBRight = 27.6 (kV) 27.62 (kV) 2 Z Right =
10 + j1
= 3.91 + j 0.39 pu
Z BRight = = 2.56
300MVA 2.56
16
Change of Bases
Change of bases and recalculation of the pu impedances
are done very often. To convert pu impedance on one
base to pu impedance on another base.
𝑜𝑙𝑑 be the pu impedance with bases 𝑆 𝑜𝑙𝑑 and 𝑉 𝑜𝑙𝑑
Let 𝑍𝑝𝑢 𝐵 𝐵
old
Z S
Z old
= old = Z B
pu
ZB (
VBold )
2
Z S Bnew
Z new
= new = Z
pu
ZB (
VBnew 2
)
17
Change of Bases
The relationship between the new and the old per-unit
𝑛𝑒𝑤
𝑍𝑝𝑢
values is 𝑜𝑙𝑑 , which gives
𝑍𝑝𝑢
2
S new
V old
Z new
pu =Z old
pu B
old
B
new
S B V
B
If the voltage bases are the same,
S Bnew
new
Z pu = Z pu
old
old
SB
18
Example 3
The one line-diagram of a three-phase power system is shown in the figure
below. Select a common base of SB = 100 MVA and VB = 11 kV in motor side. The
manufacturer's data for each device is:
G: 100 MVA 22 kV X = 20%
T1: 80 MVA 22/220 kV X = 12%
T2: 50 MVA 220/11 kV X = 8%
T3: 50 MVA 22/110 kV X = 9%
T4: 50 MVA 110/11 kV X = 10%
M: 80 MVA 10.45 kV X = 20%
The three phase load at bus 4 absorbs 50 MVA, 0.8 PF lagging at 10.45 kV.
Line 1 and Line 2 have a reactance of 36.3 and 60.5 respectively.
Draw an impedance diagram with all impedances including the load impedance
marked per-unit. 1
T1 T2
4
2 3
Line 1
G M
T3 T4
5 6
Line 2
Load
19
Example 3
The voltage bases must be determined for all sections of the power network.
220
VB 3 = 11 = 220 kV = VB 2
11
22
VB1 = 220 = 22 kV
220
Line 1: Z B 2 =
(220 )
2
= 484
100
Line 2: Z B 5 =
(110 )
2
= 121
100
36.3
Line 1: X = = 0.075 pu
484
60.5
Line 2: X = = 0.5 pu
121
22
Example 3
The load apparent power at 0.8 PF lagging is:
S L (3f ) = 5036.9 o MVA
VL2− L
ZL = * =
(10.45)
2
= 1.74724 + j1.3104
S L (3f ) 50 − 36.9 o
Z B4 =
(11)
2
= 1.21
100
Therefore, the load impedance in per unit is:
1.74724 + j1.3104
Z L ( pu ) = = 1.444 + j1.083 pu
1.21
23
Example 3
Shown here is the one line diagram of the power system network
in per-unit system based on selected power and voltage base.
Eg G j1.083 M Em
IL
30
Fault Types
• There are two main types of faults
• symmetric faults: system remains balanced; these
faults are relatively rare but easy to analyze.
• unsymmetric faults: system is no longer balanced;
very common, but more difficult to analyze.
• The most common type of fault on a three
phase system by far is the single line-to-ground
(SLG), followed by the line-to-line faults (LL),
double line-to-ground (DLG) faults, and
balanced three phase faults.
31
Fault Types
32
Fault Types
Ia
Ic
Ic
Ia
Ib
Ib
Balanced System Unbalanced System
(Symmetrical faults) (Unsymmetrical faults)
Fault Types
34
Switching Scenario to Clear the Fault
1. Within one to two cycles (16.67 ms) relays at both
ends of line detect high currents, signaling circuit
breakers to open the line
• nearby locations see decreased voltages
2. Circuit breakers open to de-energize line in an
additional one to two cycles
• breaking tens of thousands of amps of fault current is not a
small feat!
• with line removal, voltages usually return to near normal
3. Circuit breakers may reclose after several seconds,
trying to restore faulted line to service
35
Fault Impedance
The terms bolted fault or solid fault are
sometimes used to describe ideal short circuits
(Zero fault impedance). The assumption of bolted
fault is conservative.
t =0
Vm sin(t + ) I (t )
1.0
Im = Vm / Z,
Current
= L / R, 0.0
= tan-1(ωL/R) -1.0
Max. DC component, - = - / 2
Min. DC component, - = / 2
39
Machine Reactances
3 types of reactances are used to describe the transient
behavior of a faulted machine
40
Generator Modeling During Faults
• During a fault the only devices that can contribute fault
current are those with energy storage (G & M)
• Thus the models of generators (and other rotating
machines) are very important since they contribute the
bulk of the fault current.
• Generators can be approximated as a constant voltage
behind a time-varying reactance.
ra x
E I Vt
41
Generator Short Circuit Currents
42
Network Fault Analysis Simplifications
To simplify fault analysis, these assumptions are considered:
• Transmission lines are represented by series reactances
• Transformers are represented by their leakage reactances
• Synchronous machines are modeled as a constant
voltage behind direct-axis subtransient reactance
• Induction motors are ignored or treated as synchronous
machines
• Other (non spinning) loads are ignored
• Pre-fault voltages are assumed 1.0 pu, otherwise stated.
• Load (pre-fault) currents can be ignored
43
Example 4
For the network shown, assume a fault on the
generator terminal; all data is in pu except the
transmission line reactance, calculate the fault current.
Faulted
network per
unit diagram
k
k
Z th
Vth
k
0
V
+ 0 Z kk If
If = k
Z kk + Z f
− Vk
Zf
49
Fault Level (Short Circuit Capacity)
For a solid fault, Zf = 0 and If = Vth / Zth
Short Circuit Capacity, SCC = Vth If = Vth2 / Zth
If Vth is in pu then, SCC ≈ 1 / Zth in pu MVA
Comments
• SCC is a measure of voltage stiffness.
• An infinite bus has Zth = 0, i.e. SCC = ∞
• SCC can be used to model a utility network supplying an
industrial plant.
k k
Utility
Industrial Industrial
Plant Plant
Z th = 1 SCC 50
Symmetrical Components
Analysis of Unsymmetrical Systems
52
Symmetrical Components
• The key idea of symmetrical component analysis is to
decompose the system into three sequence networks.
• The networks are then coupled only at the point of the
fault
• The three sequence networks are known as the
• positive sequence (1) (this is the one we’ve been using)
• negative sequence (2)
• zero sequence (0)
• Presented in paper by Charles L. Fortescue in 1918
(judged as the most important power paper of 20th century)
Heydt, G. T.; Venkata, S. S.; Balijepalli, N. (October 24, 2000). "High Impact Papers in Power Engineering, 1900-
1999" Proceedings 2000 North American Power Symposium, vol. 1, October 2000. North American Power
53
Symposium (NAPS). Waterloo, Ontario.
Symmetrical Components
Ia
Ic
Ib
I a1
I c1
Ib 2
Ia0
Ib0 Ia2
Ic0 I b1 Ic2
Problem in Analysis in
abc Symmetrical
Components
012
55
Symmetrical Components
59
Sequence Components Representation
Any arbitrary set of three phasors, say Ia , Ib , Ic
can be represented as a sum of the three
sequence components
I a = I a 0 + I a1 + I a 2
I b = I b0 + I b1 + I b 2
I c = I c 0 + I c1 + I c 2
where
I a 0 , I b0 , I c 0 is the zero sequence components
I a1 , I b1 , I c1 is the positive sequence components
I a 2 , I b 2 , I c 2 is the negative sequence components
60
Symmetrical Components
61
Conversion from Sequence to Phase
1+ + = 0 2
62
Conversion from Sequence to Phase
Since
I a = I a 0 + I a1 + I a 2
I b = I b 0 + I b 1 + I b 2 = I a 0 + a 2 I a1 + aI a 2
I c = I c 0 + I c 1 + I c 2 = I a 0 + aI a1 + a 2I a 2
Then
a
I 1 1 1 1 1 1 I a 0
I = I 1 + I 2 + I = 1 2 I
b a 0 a1 a 2 a1
I c 1 2 1 2 I
a 2
63
Conversion from Sequence to Phase
I a 100
Let I = I b = 10 − Find Is
I c 10
66
Example 5
I a 100
Let I = I b = 10 − Then
I c 10
1 1 1 100
1 2
I s = A I = 1 10 − = 100
−1
3
1 2 10 0
100 0
If I = 10 + → Is = 0
10 − 100 67
Example 6
V a 0
Let V = V b =
V c −
Find Vs
68
Example 6
Va 0
Let V = Vb =
Vc −
Then
1 1 1 0 0
1 2
Vs = A V = 1 = −
−1
3
1 2 − 6.12
69
Example 7
I a 0 100
Let I s = I a1 = −10
I a 2
Find Iabc
70
Example 7
I a 0 100
Let I s = I a1 = −10
I a 2
Then
1 1 1 100
I abc = AI s = 1 2
−10 =
1 2 −
71
Symmetrical Components
• How to transform voltages and currents from abc to 012 and vice
versa?
72
Symmetrical Components
73
Sequence Impedances of Y-Connected Loads
Then
1
AV012 = ZY AI 012
+ 3Z n I a 0 1
1
1
−1 −1
V012 = ZY A AI 012 + 3Z n I a 0 A 1
1
75
Sequence Impedances of Y-Connected Loads
Then
Note: Z1 = Z2 = ZY and Z0 = ZY + 3 Zn 76
Sequence Impedances of Y-Connected Loads
+ + +
I a1 Ia2 I a0
ZY Va 0
Z Y Va1 Va 2 _ ZY
_
n n n
3Z n
_
Va1 = Z y I a1 , Va 2 = Z y I a 2 , Va 0 = ( Z y + 3Z n ) I a 0
77
Sequence Impedances of Y-Connected Loads
+ +
+ I a0
I a1 Ia2
Z Y Va1
ZY Z Y Va 0 ZY
Va 2 _ n ZY
n
_
n n ZY
Va1 = Z y I a1 , Va 2 = Z y I a 2 , Va 0 = 0
78
Sequence Impedances of -Connected Loads
• Obviously, a Δ-connection can not provide a path
through neutral. Therefore, the line currents flowing into
Δ-connection cannot contain any zero sequence
components.
• Sometimes single-phase circulating
currents can be produced in the Δ-
connected transformers and Z Z
generators by either induction or
zero sequence generated voltages.
Z
Transforming Δ-Y, ZY = ZΔ / 3
79
Sequence Impedances of -Connected Loads
+ + +
I Ia2 I a0
Z a1 Z Z Va 0
3 Va1 Va 2
3
_
n
_
n n_
Z Z
Z Z
Va1 = I a1 , Va 2 = I a 2 , Va 0 = 0 Z
3 3
80
Sequence Impedances of Transmission Lines
Note:
Ia
• Z0 is much larger than Z1 a
and Z2 Ib
b
• Z1 = Z2 = per phase c
Ic
reactance of line In
n
• Z0 is determined
empirically
Z1 Z2 Z0
81
Sequence Diagrams for Generators
+
Zs Ia
Ea Va
Eb
Zs Ib
Zn Z s Ec +
Ic Vb
+
V_c _ _
In
• Key point: generators are balanced and only produce
positive sequence voltages; therefore only the
positive sequence has a voltage source
• During a fault Z+ Z− Xd”. The zero sequence impedance is
usually substantially smaller. The value of Zn depends on
whether the generator is grounded 82
Sequence Diagrams for Generators
+ + +
Z1 I a1 Z2
Ia2 I a0
Va1 Z0 Va 0
Ea Va 2 _
_
n n n
3Z n
Va0 = – Z0 Ia0
_
Va1 = Ea – Z1 Ia1
Va2 = – Z2 Ia2
83
Sequence Diagrams for Transformers
• The positive and negative sequence diagrams for
transformers are equal and similar to transmission lines.
Z1 = Z2 = transformer leakage impedance
• The zero sequence network depends on
✓ Winding type (Δ or Y)
✓ Neutral grounding
✓ What terminal we look into
Z0
ZN Zn
1 Pri Sec
Z 0 = Z l + 3Z N + 3Z n
2 Pri Sec
ZN
Z0
3 Pri
Z 0 = Z l + 3Z N
Sec
4 Pri Sec
Z0
5 Pri Sec
90
Example 8
• Draw the sequence networks of the system shown
• Find the Thevenin sequence impedances as seen at bus 1
• Calculate the fault current in per unit for a bolted three-
phase fault at bus 1
Element X1 X2 X0
G1 0.10 0.10 0.05
G2 0.10 0.10 0.05
T1 0.25 0.25 0.25
T2 0.25 0.25 0.25
Line 1-2 0.30 0.30 0.50
91
Example 8
Positive sequence network
Z2 = Z 1 92
Example 8
Zero sequence network
93
Example 8
For a bolted three-phase fault at bus 1, the fault
current is
1
𝐼𝑓 = 1
𝑧
R T
AC M N
AC
Q S
Zn
95
Example 9
R
T
N
M
Q S
3Zn
Reference
97
Example 10
99
Example 11
• How to transform voltages and currents from abc to 012 and vice
versa?
• How to represent power system elements in 012?
103
Unbalanced Fault Analysis: General Steps
The procedure to handle the unsymmetrical
faults is as follows: -
1. Check the per unit quantities
2. Represent the system by the 3 sequence
networks
3. Reduce the sequence networks to their
Thevenin equivalents at the point of fault
+ + +
Z1 I a1 Ia2 I a0
Va1 Z2 V Z 0 Va 0
a2
V f0 _ _ _
104
Unbalanced Fault Analysis: General Steps
4. Connect sequence networks according to the
fault type
SLG : Connect the equivalents in series
LL : Connect +ve and –ve in parallel
LLG : Connect the equivalents in parallel
5. Solve for the sequence components of fault
currents and voltages at the faulted bus
6. Transform sequence components of fault
currents and voltages to phase values
( 012 abc )
105
Single Line-To-Ground Fault
Fault Conditions Ia
a
• Va = Zf If
Zf If
• Ib = Ic= 0 b
• If = Ia
c
Ia0 1 1 1 Ia 1 1 1 I f
1
I s = I a1 = 1 a 2 1
a I b = 1 a 2
a 0
3 3
I a 2 1 a 2
a Ic
1 a
2
a 0
106
Single Line-To-Ground Fault
Ia0 = Ia1 = Ia2 = If / 3
Va0 = – Z0 Ia0
Va1 = Vf0 – Z1 Ia1
Va2 = – Z2 Ia2
Where Z0, Z1, and Z2 are Thevenin
impedances of the sequence circuits at the
fault location
Va = Va0 + Va1 + Va2 = Vf0 – (Z0+Z1+Z2) Ia0
Va = Zf If = 3 Zf Ia0 = Vf0 – (Z0+Z1+Z2) Ia0
107
Single Line-To-Ground Fault
Hence, 0
V
I a 0 = I a1 = I a 2 =
f
Z 1 + Z 2 + Z 0 + 3Z f
Therefore, sequence networks are connected as shown,
+ + +
Z1 I a1 Ia2 I a0
Va1 Z2 V Z 0 Va 0
a2
V f0 _ _ _
3Z f
108
Line-To-Line Fault
Fault Conditions a
• Vb – Vc = Zf If Ib
b If
• Ib = – Ic= If f
Z
• Ia = 0 c
Hence, Ic
Ia0 1 1 1 Ia 1 1 1 0
1 2 1 2
I s = I a1 = 1 a a I b = 1 a a If
3 3
I a 2 1 a 2 a I c 1 a 2 a − I f
109
Line-To-Line Fault
Ia0 = 0, Ia1 = (a – a2)If / 3, Ia2 = (a2 – a)If / 3
i.e., Ia1 = – Ia2
Vb – Vc = (a2 – a)(Va1 – Va2) = Zf If
Va1 = Vf0 – Z1 Ia1
Va2 = – Z2 Ia2
Substitute Va1, Va2, Ia1 = – Ia2
3Zf Ia1/(a – a2) = (a2 – a)[Vf0 – (Z1+Z2) Ia1]
110
Line-To-Line Fault
Solving for Ia1 results in 0
V
I a1 = − I a 2 = f
Z1 + Z 2 + Z f
Therefore, sequence networks are connected as shown
+ +
Z1 I a1 Ia2
Va1 Z2 V
a2
V f0 _ _
Zf 111
Line-To-Line-To-Ground Fault
Fault Conditions a
• Vb = Vc = Zf If Ib
• I b + I c= I f b
If
• Ia = 0
c
Since Ia + Ib + Ic= 3 Ia0 , Ic Zf
Then If = 3 Ia0
i.e., Vb = Vc = 3 Zf Ia0
+ + +
Z1 I a1 Ia2 I a0
Va1 Z2 V Z 0 Va 0
0 a2
V f
_ _ _
3Z f
114
Line-To-Line-To-Ground Fault
From the connection, the sequence currents
can be written as
V f0 Z 0 + 3Z f
I a1 = Ia2 = − I a1
Z 2 ( Z 0 + 3Z f ) Z + Z + 3Z
Z1 + 2 0 f
Z + Z + 3Z
2 0 f
Z2
I a 0 = − I a1
Z + Z + 3Z
2 0 f
115
Unbalanced Fault Summary
• SLG: Sequence networks are connected in series,
parallel to three times the fault impedance
• LL: Positive and negative sequence networks are
connected in parallel; zero sequence network is
not included since there is no path to ground
• DLG: Positive, negative and zero sequence
networks are connected in parallel, with the zero
sequence network including three times the
fault impedance
116
Example 12
Calculate the fault current in per
unit for
a) A bolted 3-phase fault at bus 1.
b) A bolted SLD fault at bus 1. Element X1 X2 X0
G1 0.10 0.10 0.05
c) A bolted LL fault at bus 1.
G2 0.10 0.10 0.05
d) A bolted DLG fault at bus 1. T 0.25 0.25 0.25
1
T2 0.25 0.25 0.25
Line 1-2 0.30 0.30 0.50
117
Example 12
Positive sequence network
Z2 = Z 1 118
Example 12
Zero sequence network
119
Example 12
(a) For a bolted three-phase fault at bus 1, the
fault current is
1
𝐼𝑓 = 1
𝑧
120
Example 12
(b) For a bolted SLG fault at bus 1, the fault current is
V f0
I a 0 = I a1 = I a 2 =
Z 1 + Z 2 + Z 0 + 3Z f
+ + +
Z1 I a1 Ia2 I a0
Va1 Z2 V Z 0 Va 0
a2
V f0 _ _ _
3Z f
121
Example 12
(c) For a bolted LL fault at bus 1, the fault current is
0
V
I a1 = − I a 2 = f
Z1 + Z 2 + Z f
+ +
Z1 I a1 Ia2
Va1 Z2 V
0 a2
Vf _ _
Zf
122
Example 12
(d) For a bolted LLG fault at bus 1, the fault current is
V f0
I a1 = = − j 3.02767 pu
Z 2 ( Z 0 + 3Z f )
Z1 +
Z + Z + 3Z
2 0 f +
Z1 I a1 Ia2
+
I a0
+
Z 0 + 3Z f Va1 Z2 V
a2
Z 0 Va 0
= − I a1 = j1.36792 pu
0
Ia2 Vf _ _ _
Z + Z + 3Z
2 0 f 3Z f
Z2
Ia0 = − I a1 = j1.65975 pu
Z + Z + 3Z
2 0 f
I f = 3I a 0 = j 4.97925 pu
123
124