Main Cont.

Site Test Report: End Client : National Grid SA


Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 1 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898

1 RELAY INFORMATION:

Model No. P64332NA9M0A10M Function Transformer Differential

Panel Description =6D04+R2 S. No. 36372355/01/16

Frequency 60 Hz Aux. Voltage 125 V DC

2 TRANSFORMER DETAILS:
Transformer Ratio 132/13.8 kV

Vector Group Dyn1

Rating (MVA) 67 MVA

HV ( a ) Side CT Ratio 600/1 A

LV ( b ) Side CT Ratio 3000/1 A

3 MECHANICAL CHECKS:

S.N General checks Status

1. Inspect for no physical damage. OK

2. Verify the wiring connection as per approved drawing. OK

3. Relay case connected to a local earth bar. OK

4. Power up the relay circuit and check relay is healthy. OK

4 I/O CHECK
4.1 WATCHDOG RELAY CHECK:

Contact Status
OUTPUT Remarks
Relay OFF / Software Failure Relay ON / Healthy

J11-J12 Closed Open OK

J13-J14 Open Close OK

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 2 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
4.2 CONTROL INPUT CHECK:
OPTO V DC Applied Terminal No. Function assigned
RESULT
Input No. + Terminal No. - Terminal No. for OPTO input

OPTO-1 D2 D1 MAIN-2 TRIP RELAY OPTD OK


OPTO-2 D4 D3 MAIN-2 LOR RELAY OPTD OK
OPTO-3 D6 D5 BB LOR OPTD OK
OPTO-4 D8 D7 CBF LOR OPTD OK
OPTO-5 D10 D9 TC-2 SUPERVISION OK
OPTO-6 D12 D11 TC-2 SUPERVISION OK
OPTO-7 D14 D13 AC MCB OFF OK
OPTO-8 D16 D15 CB CLOSE & SERVICE OK
OPTO-9 F2 F1 CB OPEN OK
OPTO-10 F4 F3 HV CBF INITIATION OK
OPTO-11 F6 F5 IN/OUT DC FAIL OK
OPTO-12 F8 F7 LV CBF INITIATION OK
OPTO-13 F10 F9 E04-GIS VT MCB TRIP OK
OPTO-14 F12 F11 PROTN IN OK
OPTO-15 F14 F13 LV CB CLOSE & SERVICE OK
OPTO-16 F16 F15 SPARE OK

4.3 CONTROL OUTPUT RELAY CHECK:


Output Relay Output Contact
Function assigned to output relay RESULT
No. No.

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 3 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
RL1 H1-H2 87T & LV REF TO 86T2 L/O Relay OK
RL2 H3-H4 87T & LV REF TO 86T2 L/O Relay OK
RL3

H5-H6 LV CBF TRIP TO 86CBF L/O RELAY OK

RL4 H7-H8 HV CBF TRIP TO 86CBF L/O RELAY OK


RL5
H9-H10 HV CBF TRIP TO 86CBF L/O RELAY OK

RL6 H11-H12 HV OC / EF TO 86T2 L/O Relay OK


H13-H15 (NC) OK
RL7 LV OC / EF & SBEF TO 94T2 TRIP Relay
H14-H15 (NO) OK
H16-H18 (NC) OK
RL8 ABTS INITIATION
H17-H18 (NO) OK
RL9 G1-G2 SPARE OK
RL10 G3-G4 HV OC / EF TO 86T2 L/O Relay OK
RL11 G5-G6 LV OC / EF & SBEF TO 94T2 TRIP Relay OK
RL12 G7-G8 LV OC / EF & SBEF TO 94T2 TRIP Relay OK
RL13 G9-G10 LV OC / EF & SBEF TO 94T2 TRIP Relay OK
RL14 G11-G12 LV CBF TRIP TO 86CBF L/O RELAY OK
G13-G15 (NC) OK
RL15 ABTS BLOCK
G14-G15 (NO) OK
G16-G18 (NC) OK
RL16 LV CBF TRIP SAVE TO 86CBF L/O
G17-G18 (NO) OK

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 4 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
4.1 USER PROGRAMABLE LED’S FUNCTION TEST:
LED NO’S COLOR FUNCTION DUTY REMARKS
1 Red Pre-configured led’s OK
2 Red Pre-configured led’s OK
3 Red Pre-configured led’s OK
4 Red Pre-configured led’s OK
5 Red Pre-configured led’s OK
6 Red Pre-configured led’s OK
7 Red Pre-configured led’s OK
8 Red Pre-configured led’s OK

4.2 FUNCTION KEY LED’S TEST:


LED NO’S COLOR FUNCTION DUTY REMARKS
1 Red Pre-configured led’s OK
2 Red Pre-configured led’s OK
3 Red Pre-configured led’s OK
4 Red Pre-configured led’s OK
5 Red Pre-configured led’s OK
6 Red Pre-configured led’s OK
7 Red Pre-configured led’s OK
8 Red Pre-configured led’s OK
9 Red Pre-configured led’s OK
10 Red Pre-configured led’s OK

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 5 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
5 MEASUREMENTS:
T1: 600 / 1 A; T2:3000/1A; TN2 (LV-REF): 3000/1A; TN3 (LV): 800/1A

PHASE INJECTED EXPECTED MEASURED


CURRENT (A) CURRENT (A) CURRENT (A)
IA (HV) 1 600 601.6
IB (HV) 1 600 602.3
IC (HV) 1 600 601.4
IA (LV) 1 3000 3001
IB (LV) 1 3000 3003
IC (LV) 1 3000 3005

Function CT Ratio Winding Expected (A) Actual (A)


50G-LV 800 / 1A TN3 800 799.8
LV-REF 3000 / 1A TN2 3000 3008

PHASE INJECTED EXPECTED MEASURED


VOLTAGE (V) VOLTAGE (KV) VOLTAGE (KV)
VA-N 66.4 76.2 76.38
VA-N 66.4 76.2 76.39
VA-N 66.4 76.2 76.38
VA-B 115 132 132.3
VB-C 115 132 132.3
VC-A 115 132 132.3

6 DIFFERENTIAL ELEMENT:
Iref a (Prim)=Sref /√3* Vnom a = (67MVA/1.732*132KV) = 293.049A

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 6 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898

Iref b (Prim)=Sref /√3* Vnom b = (67MVA/1.732*13.8KV) = 2803.077A

Kam,a = CT Ratio a / Iref a = (600/293.049) = 2.047439

Kam,b = CT Ratio b / Iref b = (3000/2803.077) = 1.070252

Where:
Iref a (Prim) 293.049AHV full load current (Primary value)
Iref b (Prim) 2803.077ALV full load current (Primary value)
Sref 67 MVA Transformer capacity
Vnom,a 132 KV Transformer HV Side voltage
Vnom,b 13.8 KV Transformer LV Side voltage
CT Ratio a: 600A Transformer HV Side phase CT raAtio
CT Ratio b: 3000A Transformer LV Side phase CT ratio
Kam,a 2.047439 Winding “a” amplitude matching factor
Kam,b 1.070252 Winding “b” amplitude matching factor

6.1 LOW SET ELEMENT CURRENT SENSITIVITY TEST ( Is1 ):


6.1.1 OBJECTIVE : TO TEST THRESHOLD IS1 :
Test method:
Inject balanced currents in all phases (one by one)
Gradually increase currents till relay operation. Note down the value.
Pass criteria:
The operating current should be within +/- 5% of {Is1 / Kamp}.

Calculation For Pickup Current Is1 = 0.3 A


Manual P63x/EN M/Aq6 – Operation – Page no. 3-171
Side “a” Pick up Current = Ia = Is1/Kam,a
Side “a” Pick up Current Ia = 0.3/2.047439 = 0.1465A

Side “b” Pick up Current = Ib = Is1*√3/Kam,b


Side “b” Pick up Current Ib=0.3*√3/1.070252 = 0.4855 A

Reference Winding Even VG-numeral Odd VG-numeral


Type of fault
(Upper Voltage) 0,2,4,6,8,10 1,3,5,7,9,11

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 7 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
Three-phase 1 1 1
Two-phase 1 1 0.866
Single-phase with I0 elimination

1.5 1.5 1.73

Single-phase without I0 elimination 1 1 1.73

6.1.2 HV SIDE

Calculated Pick Up Drop Off Measured time


Fault Type Setting (A)
value (m.A) (A) (A) @2XIs (m.S)
A-N 0.3 146 0.147 0.141 29.3
B-N 0.3 146 0.147 0.141 27.9
C-N 0.3 146 0.147 0.141 29.2
A-B-C 0.3 146 0.148 0.141 30.4
Accuracy: ± 0.5%

6.1.3 LV SIDE

Calculated Pick Up Drop Off Measured time


Fault Type Setting (A)
value(m.A) (mA) (mA) @2XIs (m.S)
A-N 0.3 485 484 465 33.4
B-N 0.3 485 478 475 32.0
C-N 0.3 485 475 471 33.0
A-B-C 0.3 280 281 269 30.4

6.1.4 TESTING OF DIFFERENTIAL RELAY (HIGH SET ELEMENT 1&2)

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 8 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898

TESTING OF HIGH SET-2 (IS-HS1):


6.1.5 HV SIDE

Setting Calculated Pick Up Drop Off Measured time


Fault Type
(A) value (A) (A) (A) @2XIs (m.sec)
A-N 3 1.465 1.463 1.453 18.9
B-N 3 1.465 1.458 1.453 18.6
C-N 3 1.465 1.457 1.452 19.7
A-B-C 3 1.465 1.459 1.452 16.8

6.1.6 LV SIDE

Setting Calculated Pick Up Drop Off Measured time


Fault Type
(A) value (A) (A) (A) @2XIs (m.sec)
A-N 3 4.856 4.839 4.827 22.6
B-N 3 4.856 4.838 4.825 24.8
C-N 3 4.856 4.840 4.823 24.6
A-B-C 3 2.803 2.803 2.794 22.8

SLOPE CHECK
6.1.7 M1 SLOPE

Test method:

Inject balanced currents in all phases written as “Injected current side ‘a’ ” & “Injected current
side ‘b’ ” (one by one) as of following procedure (This procedure is applicable only for vector
group Dyn1, for other vector groups, please check manual page # 540):-

S.No HV side (Delta) LV side (Wye)

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 9 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
1 Ia<0° Ia<180°
Ic<180°

Ib<0°

2 Ib<180°
Ia<180°

Ic<0°
3 Ic<180°
Ib<180°

to find pick up point. Note down the value of Differential and Restrained current and find the
slope using formula:-
Id
m=
Ir
Where, Id &Ir are Displayed differential & restrained currents.

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 10 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898

Calculation For Pickup Current for slope M1

So, for the slope K1,


Is1
≤ Is2Ibias ≤Is2
K1

At Is1=0.3, K1=0.3 , Is2= 2.0


1≤Ibias≤4
Choose any Point of Ibisabetween 1&2 (in our case 1.5). Then Calculate I diff using formula
m = Id/Ir
Where, m = K1 = 0.3 , Ir = 1.5,
So, Id = 0.45,

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 11 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
Now calculate I1& I2 using following information

Restraining current Ir = {(Iam,x,a + 1/√3 Iam,x,b) /2}

Ir = {(Ia*Kam,a + 1/√3(Ib*Kam,b)) / 2}

Ir = {(Ia*2.047439+ (1/√3(Ib*1.070252))) / 2}

Ir = {(2.047439Ia + 0.6179Ib) / 2}

Differential current Id = { Iam,x,a - 1/√3 Iam,x,b }

Id = { Ia*Kam,a - 1/√3(Ib*Kam,b) }
Id = { Ia*2.047439- (1/√3(Ib*1.070252))
}
Id = { 2.047439 Ia – 0.617928Ib }

Ia=0.821 A
Ib=2.0 A
Now use Following Table to Inject Currents on both sides,

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 12 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
Since HV side is Delta and LV is Star.

SET SET R Y B
SLOPE IS1> DESCRIPTION
M1 (A) Calculated Actual Calculated Actual Calculated Actual

Injected Current side ‘a’(A) 0.821 0.821 0.821 0.821 0.821 0.821

Injected Current side’b’(A) 2.0 2.0 2.0 2.0 2.0 2.0

Restrain Calculated 1.5 1.5 1.5


30% 0.3 Current
(A) Displayed 1.461 1.462 1.463

Differential Calculated 0.450 0.450 0.450


Current
(A) Displayed 0.446 0.441 0.447

Calculated Slope % M1 30.5 30.1 30.5

calculated M= ID/IR So, M=0.45/1.5, M=0.30, M=30.0%

6.1.8 M2 SLOPE

So, for the slope K2,


Ibias ≥ Is2
At Is2 = 2.0, K1 = 0.3, K2 = 0.8
Choose Ibias> 2 (3.0 A) and then calculate Idiff using equation
Idiff = K1*Is2 + K2(Ibias – Is2) =(0.3*2.0)+0.8(3.0-2.0)
Idiff = 1.4 A

Ia=1.807 A
Ib=3.722 A

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 13 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898

Choose Ibias> 2 (3.5 A) and then calculate Idiff using equation


Idiff = K1*Is2 + K2(Ibias – Is2) Idiff = 1.8 A
From above equation Ia=2.149 A Ib=4.208 A

Following above table no 17 for all Phases, check pickup value by changing HV side current.
Then note down Differential and restrain currents from the relay, then verify slope using
formula m = ∆Id/∆Ir;
Follow the same process for 2nd Point of Ibias

SET SET R Y B
SLOPE IS2> DESCRIPTION
M2 (A) Calculated Actual Calculated Actual Calculated Actual

Injected Current side ‘a’(A) 1.807 1.811 1.807 1.812 1.807 1.812

Injected Current side’b’(A) 3.722 3.725 3.722 3.733 3.722 3.730

Restrain Calculated 3.0 3.0 3.0


Current
(A) Displayed 3.005 3.008 3.009

Differentia Calculated 1.4 1.4 1.4


l
Current
Displayed 1.409 1.403 1.405
(A)
0.8 2.0
Injected Current side ‘a’(A) 2.149 2.149 2.149 2.155 2.149 2.155

Injected Current side’b’(A) 4.208 4.210 4.208 4.219 4.208 4.217

Restrain Calculated 3.5 3.5 3.5


Current
(A) Displayed 3.511 3.511 3.510

Differential Calculated 1.8 1.8 1.8


Current
(A) Displayed 1.811 1.805 1.807

Calculated Slope % M1 79.4 79.9 81.2

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 14 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
6.2 DIFFERENTIAL ELEMENT 2ND HARMONIC RESTRAIN TEST

Injected Relay Expected Actual Relay


Applied Phase Setting
Current ( A ) Condition ( m.A ) (A) Condition
R Side a 1.0 Blocked 15% 150 0.147 Unblocked
Phase Side b 1.0 Blocked 15% 150 0.146 Unblocked
Y Side a 1.0 Blocked 15% 150 0.148 Unblocked
Phase Side b 1.0 Blocked 15% 150 0.147 Unblocked
B Side a 1.0 Blocked 15% 150 0.147 Unblocked
Phase Side b 1.0 Blocked 15% 150 0.148 Unblocked

Deviation: +/-10%

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 15 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898

6.3 DIFFERENTIAL ELEMENT 5TH HARMONIC RESTRAIN TEST


Injected Relay Expected Actual Relay
Applied Phase Setting
Current ( A ) Condition (m. A ) ( m.A ) Condition
R Side a 1.0 Blocked 30 % 300 300 Unblocked
Phase Side b 1.0 Blocked 30 % 300 302 Unblocked
Y Side a 1.0 Blocked 30 % 300 300 Unblocked
Phase Side b 1.0 Blocked 30 % 300 302 Unblocked
B Side a 1.0 Blocked 30 % 300 301 Unblocked
Phase Side b 1.0 Blocked 30 % 300 299 Unblocked

6.6 CROSS BLOCK TEST

Winding IR IY IB Cross Block on


I > pickup I > pickup
I > pickup with
without 2nd without 2nd OK
2nd harmonic
harmonic harmonic
I > pickup I > pickup
I > pickup with
HV without 2nd without 2nd OK
2nd harmonic
harmonic harmonic
I > pickup I > pickup
I > pickup with
without 2nd without 2nd OK
2nd harmonic
harmonic harmonic
I > pickup I > pickup
I > pickup with
without 2nd without 2nd
2nd harmonic OK
harmonic harmonic
I > pickup I > pickup
I > pickup with
l.V without 2nd without 2nd
2nd harmonic OK
harmonic harmonic
I > pickup I > pickup
I > pickup with
without 2nd without 2nd
2nd harmonic OK
harmonic harmonic

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 16 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
6.4 HV SIDE OVER CURRENTPROTECTION TEST
6.4.1 I>1, 1ST STAGE

Phase Setting Pickup (mA) Drop Off (mA)


R 500 mA 499 477
Y 500 mA 499 477
B 500 mA 499 476

6.4.2 I>1, 1ST STAGE INVERSE TIME OVER CURRENT CURVES (IEC INVERSE):
TIME MULTIPLIER SETTING (T = 0.1)
Set Current (In) Injected Calculated Time Actual
Curve Type
(m.A) Current (sec) Time (sec)
Standard 500 mA 2 x In 1.003 1.03
Inverse 500 mA 5 x In 0.428 0.453
500 mA 2 x In 1.350 1.37
Very Inverse
500 mA 5 x In 0.338 0.357
500 mA 2 x In 2.667 2.65
Extreme inverse
500 mA 5 x In 0.333 0.350
Def. Time 500 mA 2 x In 0.200 0.128

6.5 LV SIDE OVER CURRENTPROTECTION TEST


6.5.1 I>1, 1ST STAGE

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 17 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
Phase Setting Pickup (mA) Drop Off (mA)
R 500 mA 500 477
Y

500 mA 499 476

B 500 mA 499 477

6.5.2 I>1, 1ST STAGE INVERSE TIME OVER CURRENT CURVES (IEC INVERSE):
TIME MULTIPLIER SETTING (T = 0.1)
Set Current (In) Injected Calculated Time Actual
Curve Type
(m.A) Current (sec) Time (sec)
Standard 500 mA 2 x In 1.003 1.04
Inverse 500 mA 5 x In 0.428 0.455
500 mA 2 x In 1.350 1.38
Very Inverse
500 mA 5 x In 0.338 0.355
500 mA 2 x In 2.667 2.64
Extreme inverse
500 mA 5 x In 0.333 0.344
Def. Time 500 mA 2 x In 0.200 0.123

6.6 Earth Fault HIGHT VOLTAGE SIDE:

6.6.1 1ST STAGE EARTH FAULT-1 (DERIVED-T1)

SETTING PICK- UP DROP-UP


SIDE
(m.A) (m.A) (m.A)
T1 500 499 451

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 18 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
6.6.2 IN>1, INVERSE TIME EARTH FAULT CURVES (IEC INVERSE):
TIME MULTIPLIER SETTING (T = 0.1)
Set Current (In) Injected Calculated Time Actual
Curve Type
(m.A) Current (sec) Time (sec)
Standard 500 mA 2 x In 1.003 1.03
Inverse 500 mA 5 x In 0.428 0.448
500 mA 2 x In 1.350 1.37
Very Inverse
500 mA 5 x In 0.338 0.356
500 mA 2 x In 2.667 2.68
Extreme inverse
500 mA 5 x In 0.333 0.344
Def. Time 500 mA 2 x In 0.200 0.122

6.7 Earth Fault LOW VOLTAGE SIDE:

6.7.1 1ST STAGE EARTH FAULT-1 (DERIVED-T2)

SETTING PICK- UP DROP-UP


SIDE
(m.A) (m.A) (m.A)
T2 500 499 449

6.7.2 IN>1, INVERSE TIME EARTH FAULT CURVES (IEC INVERSE):


TIME MULTIPLIER SETTING (T = 0.1)
Set Current Injected Calculated Time Actual
Curve Type
In(m.A) Current (sec) Time (sec)
Standard 500 mA 2 x In 1.003 1.03
Inverse 500 mA 5 x In 0.428 0.445
500 mA 2 x In 1.350 1.38
Very Inverse
500 mA 5 x In 0.338 0.356
500 mA 2 x In 2.667 2.74
Extreme inverse
500 mA 5 x In 0.333 0.352
Def. Time 500 mA 2 x In 0.200 0.116

6.8 Earth Fault HIGHT VOLTAGE SIDE: (Measured-TN1)

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 19 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
6.8.1 1ST STAGE EARTH FAULT-1

SETTING PICK- UP DROP-UP


SIDE
(m.A) (m.A) (m.A)
T1 500 499 451

6.8.2 IN>1, INVERSE TIME EARTH FAULT CURVES (IEC INVERSE):


TIME MULTIPLIER SETTING (T = 0.1)
Set Current (In) Injected Calculated Time Actual
Curve Type
(m.A) Current (sec) Time (sec)
Standard 500 mA 2 x In 1.003 1.03
Inverse 500 mA 5 x In 0.428 0.445
500 mA 2 x In 1.350 1.37
Very Inverse
500 mA 5 x In 0.338 0.358
500 mA 2 x In 2.667 2.68
Extreme inverse
500 mA 5 x In 0.333 0.349
Def. Time 500 mA 2 x In 0.200 0.121

6.9 Earth Fault LOW VOLTAGE SIDE:

6.9.1 1ST STAGE EARTH FAULT-1 (MEASURED-TN2)

SETTING PICK- UP DROP-UP


SIDE
(m.A) (m.A) (m.A)
T2 500 499 449

6.9.2 IN>1, INVERSE TIME EARTH FAULT CURVES (IEC INVERSE):


TIME MULTIPLIER SETTING (T = 0.1)
Set Current Injected Calculated Time Actual
Curve Type
In(m.A) Current (sec) Time (sec)

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 20 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
Standard 500 mA 2 x In 1.003 1.03
Inverse 500 mA

5 x In 0.428 0.448

500 mA

2 x In 1.350 1.38

Very Inverse
500 mA

5 x In 0.338 0.355

500 mA
2 x In 2.667 2.71
Extreme inverse
500 mA
5 x In 0.333 0.355
Def. Time 500 mA 2 x In 0.200 0.118

6.10 Earth Fault (51G-LV): Measured -IN3


6.10.1 1ST STAGE EARTH FAULT-1

SETTING PICK- UP DROP-UP


COIL
(m.A) (m.A) (m.A)
TN3 500 497 477

6.10.2 IN>1, INVERSE TIME EARTH FAULT CURVES (IEC INVERSE):


TIME MULTIPLIER SETTING (T = 0.1)
Set Current Injected Calculated Time Actual
Curve Type
In(m.A) Current (sec) Time (sec)
Standard 500 mA 2 x In 1.003 1.02
Inverse 500 mA 5 x In 0.428 0.452

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 21 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
Very Inverse 500 mA 2 x In 1.350 1.38
500 mA

5 x In 0.338 0.355

500 mA

2 x In 2.667 2.69

Extreme inverse
500 mA

5 x In 0.333 0.355

Def. Time 500 mA 2 x In 0.200 0.129

6.11 REF LV (LowZ REF)

a) At L.V :Sensitivity Test

Set Current PU DO MEAS TIME AT 2In


PHASE
(m.A) (m.A) (m.A) (m.Sec)
IG 150 150 140 35.6

IR 150 150 141 36.2

IY 150 150 139 36.1

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 22 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
IB 150 150 140 33.0

b) At L.V :Stability Test;

Injected Current (A) Displayed Current in primary(A)


PHASE
Phase CT Ref CT (IN) ID IR

IR 0.300 <0 0.300 <180 0.0 299.4

IY 0.300 <0 0.300 <180 0.0 300.5

IB 0.300 <0 0.300 <180 0.0 299.3

c) At L.V :Slope-2 Test;

So, for the slope K2,


Ibias ≥ Is2

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 23 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
At Is2 = 1.1, K1 = 0.0, K2 = 1.5
Choose Ibias> 1.1 (1.3 A) and then calculate Idiff using equation
Idiff = K1*Is2 + K2(Ibias – Is2) =(0.0*2.0)+1.5(1.3-1.1)
Idiff =0.3 A

Ir =1/2(IPH CT +IN CT) = 0.5(Ia+Ib)


Id = (IPH CT +IN CT)= (Ia+Ib)
So, Ia = 1.45A Ib =1.15A

Choose other Ibias> 1.1 (1.5 A) and then calculate Idiff using equation
Idiff = K1*Is2 + K2(Ibias – Is2) =(0.0*2.0)+1.5(1.5-1.1)
Idiff =0.6 A

Ir =1/2(IPH CT +IN CT) = 0.5(Ia+Ib)


Id = (IPH CT +IN CT)= (Ia+Ib)

So, Ia = 1.8 A Ib =1.2 A

Inject the above calculated current. Then note down Differential and restrain currents from
the relay, then verify slope using formula m = ∆Id/∆Ir;
Follow the same process for 2nd Point of Ibias

SET SET IS2>


DESCRIPTION
SLOPE M2 (A)
Calculated Actual
150 % 1.1
Injected Current side ‘a’(A) 1.45 1.45

Injected Current side’b’(A) 1.15 1.150

Restrain Calculated 1.3


Current
(A) Displayed 1.303

Differential Calculated 0.30


Current
(A) Displayed 0.303

Injected Current side ‘a’(A) 1.8 1.801

Injected Current side’b’(A) 1.2 1.200

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 24 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
Differential Displayed 0.600
Calculated Slope % M1 150.0

6.12 HV BREAKER FAILURE PROTECTION (50BF)

FUNCTION NAME: - BREAKER FAILURE LOGIC CB1(HV)


Pickup Current: 10% time delay : 0.25 Sec
CBF Reset Mode: CB Open & I<

PHASE SETING (A) PICKUP (A) DROP OFF (A) TRIP TIME (ms)

R 0.110 0.102 267.5


Y 0.1 0.110 0.102 267.5
B 0.110 0.102 267.5

6.13 LV BREAKER FAILURE PROTECTION (50BF)

FUNCTION NAME: - BREAKER FAILURE LOGIC CB2 (LV)


Pickup Current: 10% time delay: 0.25 Sec
CBF Rest Mode: CB open & I<

PHASE SETING (A) PICKUP (A) DROP OFF (A) TRIP TIME (ms)

R 0.111 0.102 265.4


Y 0.1 0.111 0.102 265.4
B 0.111 0.102 265.4

CALIBRATION DETAILS:

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature:
Main Cont. Site Test Report: End Client : National Grid SA
Control Room ǁ Acceptance Test Report For
P643 Relay
Sub Cont: Panel Description:
E04 SET-2 TRANSFORMER-2
PROTECTON PANEL (=6D04+R2) Page 25 of 25

MANUF: Site: CONTRACT no.:


SCHNEIDER GREGAR 132/13.8 KV S/S 4400005898
Test equipment used SL.NO. of Test equipment Calibration valid up to
FREJA 300 8501840 1.08.2018

GeSCo
DATE
Engr: SIVARAMAN ID: GES023
30.4.2018 Signature: