Level 1 Level 2 Level 3

The Active power


Active Utilization Diversity Active Diversity Active Diversity Active
number
power factor demand max factor power factor power factor power
of (W)
(W) max (W) (W) (W)
equipment

LIGHTING-1
(Garden) 2 20 1 20 1 20

LIGHTING-2
19 35 1 35 1 35
(Living & Dining room)

LIGHTING-3a
(Kitchen, Laundry)
18 55 1 55 1 55
LIGHTING-3b
(Toilet, Hallway)

SOCKET-4
5 3520 1 3520 0.15 528
(Living & Dining room)

SOCKET-5A
(Kitchen) 5266.1

8 3520 1 3520 0.15 528


SOCKET-5B
(Laundry, Hallway)

AC-6 / 1,5hp
(Living room) 1 1119 1 1119 1 1119

AC-7 / 2hp
(Dining room) 1 1492 1 1492 1 1492

AC-8 / 1hp
(Kitchen) 1 746 1 746 1 746

DISTRIBUTION BOARD OF THE FIRST FLOOR (0.7)


WATER
HEATER-09 1 3000 1 3000 1 3000
LV / MV
7119

LIGHTING-10
(Master, M-Bath room) 12 55 1 55 1 55

LIGHTING-11a
(Bedroom 2)

LIGHTING-11b 20 55 1 55 1 55
(Bedroom 3)
MAIN GENERAL DISTRIBUTION BOARD (0.9)

LIGHTING-11c
(Toilet, Hallway)

AC-12 / 1,5hp
1 1119 1 1119 1 1119
(Master room)

AC-13 / 1hp
(Bedroom 2) 1 746 1 746 1 746 2643.9

AC-14 / 1hp
(Bedroom 3) 1 746 1 746 1 746

SOCKET-15
(Master, M-Bath room) 5 3520 1 3520 0.15 528

SOCKET-16a
(Bedroom 2)

SOCKET-16b
(Bedroom 3) 9 3520 1 3520 0.15 528
DISTRIBUTION BOARD OF THE SECOND FLOOR (0.7)

SOCKET-16c
(Toilet, Hallway