METAL STRUCTURES REPAIR WORKS CPP-2 CPP2-265-TS-AC7-RPT-002
PASSIVE FIRE PROTECTION DESIGN REPORT FOR FIRE WALLS CLASS H-60 AT BM-6
ON CPP-2 Rev. 0 Page 4 of 5
Cleaning &
Dry film
Description of painting area for
No. thickness Topcoat’s colour Type of Class Surface preparation
item main surface
(µm)
(m²)
1 2 3 4 5 6 7
No. 17 (Fire
resistant paint class
H-60/Sơn chống Blast cleaning to Sa 2.5/ISO
1. cháy class H-60) in 200 9580 (4 layers) Yellow RAL 1003 H-60 8501-1. Surface profile:
the document No. 50÷85 µm.
CPP2-265-TS-
ST6-RL-001
TOTAL: 200
Notes:
- The volume of works has been calculated according to the following documents and drawings:
• CPP2-265-TS-ST6-RL-001_0_REPARATION LIST.
___________________________________________________________________________________
METAL STRUCTURES REPAIR WORKS CPP-2 CPP2-265-TS-AC7-RPT-002
PASSIVE FIRE PROTECTION DESIGN
REPORT FOR FIRE WALLS CLASS H-60 AT Rev. 0 Page 5 of 5
BM-6 ON CPP-2
3 PFP SYSTEMS
3.1 Option 1: “INTERNATIONAL PAINT”
1 2 3 4
Total: 9580
1 2 3 4
Total: 13050