Passive Fire Protection Design Report For Fire Walls H-60 at BM-6 On CPP-2

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

RESEARCH AND ENGINEERING

INSTITUTE FOR OFFSHORE OIL AND GAS

PROJECT NAME : METAL STRUCTURES REPAIR WORKS CPP-2

DOCUMENT TITLE : PASSIVE FIRE PROTECTION DESIGN REPORT


FOR FIRE WALLS CLASS H-60 AT BM-6 ON
CPP-2
DOCUMENT NO. : CPP2-265-TS-AC7-RPT-002

DC ENG.MGR PRO. MGR

0 IFA 19.10.2023

REV. DES. DATE PREPARED CHECKED DEPT.MGR


METAL STRUCTURES REPAIR WORKS CPP-2 CPP2-265-TS-AC7-RPT-002
PASSIVE FIRE PROTECTION DESIGN
REPORT FOR FIRE WALLS CLASS H-60 AT Rev. 0 Page 2 of 5
BM-6 ON CPP-2

TRACK CHANGES

No Rev. Content of Change Note

1 0 Issued for Approval


METAL STRUCTURES REPAIR WORKS CPP-2 CPP2-265-TS-AC7-RPT-002
PASSIVE FIRE PROTECTION DESIGN
REPORT FOR FIRE WALLS CLASS H-60 AT Rev. 0 Page 3 of 5
BM-6 ON CPP-2

TABLE OF CONTENTS

1 GENERAL TECHNICAL REQUIREMENT 4


2 VOLUME OF ANTICORROSION COATING WORKS 4
3 PROTECTION COATING SYSTEMS 5
4 TECHOLOGICAL PROCEDURE 5

___________________________________________________________________________________
METAL STRUCTURES REPAIR WORKS CPP-2 CPP2-265-TS-AC7-RPT-002
PASSIVE FIRE PROTECTION DESIGN REPORT FOR FIRE WALLS CLASS H-60 AT BM-6
ON CPP-2 Rev. 0 Page 4 of 5

1 GENERAL TECHNICAL REQUIREMENT


The passive fire protection (PFP) materials, surface preparation, and PFP application for Fire Walls (H-60) shall be carried out in accordance with
the technical requirements of the document CPP2-265-GE-AC7-SP-001 “Specification for Passive Fire Protection for Fire Walls Class H-60”.
This document also proposes the PFP system to be used to construct Fire Walls class H-60 at BM-6 on CPP-2, however, the Contractor/Vendor
can propose (PFP) materials but must meet the technical requirements in the document CPP2-265-GE-AC7-SP-001 “Specification for Passive Fire
Protection for Fire Walls Class H-60”.
2 VOLUME OF WORKS
Table No.1

Cleaning &
Dry film
Description of painting area for
No. thickness Topcoat’s colour Type of Class Surface preparation
item main surface
(µm)
(m²)

1 2 3 4 5 6 7
No. 17 (Fire
resistant paint class
H-60/Sơn chống Blast cleaning to Sa 2.5/ISO
1. cháy class H-60) in 200 9580 (4 layers) Yellow RAL 1003 H-60 8501-1. Surface profile:
the document No. 50÷85 µm.
CPP2-265-TS-
ST6-RL-001
TOTAL: 200
Notes:
- The volume of works has been calculated according to the following documents and drawings:
• CPP2-265-TS-ST6-RL-001_0_REPARATION LIST.

___________________________________________________________________________________
METAL STRUCTURES REPAIR WORKS CPP-2 CPP2-265-TS-AC7-RPT-002
PASSIVE FIRE PROTECTION DESIGN
REPORT FOR FIRE WALLS CLASS H-60 AT Rev. 0 Page 5 of 5
BM-6 ON CPP-2

3 PFP SYSTEMS
3.1 Option 1: “INTERNATIONAL PAINT”

№ Coating film thickness (microns)


of PFP SYSTEM
coat DFT WFT

1 2 3 4

1st Interzinc 52E, Grey 65 100

2nd Intergard 269, Red 35 74

3rd Chartek 7E, Grey 9430 9430

4th Interthane 990, Yellow RAL 1003 50 88

Total: 9580

3.2 Option 2: “JOTUN”

№ Coating film thickness (microns)


of PFP SYSTEM
coat DFT WFT

1 2 3 4

1st Barrier, Grey 65 123

2nd Penguard Tie-coat 100, Red 35 83

3rd Jotachar JF750, Grey 12900 12900

4th Hardtop AX, Yellow RAL 1003 50 79

Total: 13050

Note: Coating thickness can be reconfirmed by the PFP SUPPLIER.


4 TECHOLOGICAL PROCEDURE
Notes:
- The document CPP2-265-GE-AC7-SP-001 “Specification for Passive Fire Protection for Fire
Walls Class H-60” is used to consult coating technological procedures.

___________________________________________________________________________________