Professional Documents
Culture Documents
K3G400PW0301 KM220251 Data Sheet
K3G400PW0301 KM220251 Data Sheet
K3G400PW0301 KM220251 Data Sheet
backward-curved, single-intake
with support bracket
Nominal data
Type K3G400-PW03-01
Motor M3G112-IA
Phase 3~
Nominal voltage VAC 400
Nominal voltage range VAC 380 .. 480
Frequency Hz 50/60
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3G400-PW03-01 EC centrifugal module - RadiPac
backward-curved, single-intake
with support bracket
Technical description
Weight 25.1 kg
Size 400 mm
Motor size 112
Rotor surface Painted black
Electronics housing material Die-cast aluminum
Impeller material Sheet aluminum
Support plate material Sheet steel, galvanized
Support bracket material Steel, painted black
Inlet nozzle material Sheet steel, galvanized
Number of blades 5
Direction of rotation Clockwise, viewed toward rotor
Degree of protection IP55
Insulation class "F"
Moisture (F) / Environmental (H) H1
protection class
Ambient temperature note Occasional start-up at temperatures between -40°C and -25°C is permitted. For
continuous operation at ambient temperatures below -25°C (such as refrigeration
applications), use must be made of a fan design with special low-temperature bearings.
Max. permitted ambient temp. +80 °C
for motor (transport/storage)
Min. permitted ambient temp. for -40 °C
motor (transport/storage)
Installation position See legend on product drawing
Condensation drainage holes On rotor side
Mode S1
Motor bearing Ball bearing
Technical features - Operation and alarm display with LED
- External 15-50 VDC input (parameterization)
- Alarm relay
- Integrated PI controller
- Configurable inputs/outputs (I/O)
- MODBUS V6.3
- Motor current limitation
- RS-485 MODBUS-RTU
- Soft start
- Voltage output 3.3-24 VDC, Pmax = 800 mW
- Control interface with SELV potential safely disconnected from the mains
- Thermal overload protection for electronics/motor
- Line undervoltage / phase failure detection
EMC immunity to interference According to EN 61000-6-2 (industrial environment)
EMC interference emission According to EN 61000-6-3 (household environment), except EN 61000-3-2 for
professionally used equipment with a total rated power greater than 1 kW
Touch current according to IEC <= 3.5 mA
60990 (measuring circuit Fig. 4,
TN system)
Electrical hookup Terminal box
Motor protection Electronic motor protection
Protection class I (additional protective earth terminal on motor housing (bearing shield) required)
Conformity with standards EN 61800-5-1; CE
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3G400-PW03-01 EC centrifugal module - RadiPac
backward-curved, single-intake
with support bracket
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3G400-PW03-01 EC centrifugal module - RadiPac
backward-curved, single-intake
with support bracket
Product drawing
1 Installed position: shaft horizontal (install support struts only vertically as illustrated) or rotor on bottom; rotor on top on request
2 Cable diameter min. 4 mm, max. 10 mm, tightening torque 4 ± 0.6 Nm
(The tightening torque is designed for PVC cables. If the cable materials are different, the tightening torque may have to be
adjusted)
3 Tightening torque 1.5 ± 0.2 Nm
4 Inlet ring with pressure tap (k-factor: 188)
5 Attachment holes for FlowGrid 35505-2-2957 (not included in scope of delivery)
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3G400-PW03-01 EC centrifugal module - RadiPac
backward-curved, single-intake
with support bracket
Connection diagram
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
○ configurable option
For further information and additional functions see EC Control Software, Fan-Set-App,
D101 [...]
D147 [...]
D104 [...]
D12E [...]
D148 [...]
D16C [...]
D16A [...]
(selected directly
(selected directly
via IO mode)
D130 [0]
D130 [1]
D130 [2]
D130 [5]
D00C [1]
D130 [4]
via IO mode)
or MODBUS Parameter Specification V6.3
INPUT OUTPUT
inverse
K3G400-PW03-01
configurable IO
functions: normal /
Terminal/plug assignment
MODBUS
Register for IO
mode
cooling (neg.)
signal: actual speed
signal: system modulation level %
signal: remote control output 0-10V
pulse input for auto-adressing
pulse output for auto-adressing
○ Din3 (active low): digital input active: applied voltage < 1,5VDC, SELV D15A [1]
not active: pin open or applied voltage 3,5-50VDC
○ PWMin3: digital input, idle level high PWM = 40Hz - 10kHz, characteristics parameterizable D15A [7]
active: pin open or applied voltage 3,5-50VDC ○
IO3 not active: applied voltage < 1,5VDC, SELV
backward-curved, single-intake
○ PWMin3: digital input, idle level low 40Hz - 10kHz, characteristics parameterizable D15A [8]
active: applied voltage 3,5-50VDC ○
not active: pin open or applied voltage < 1,5VDC, SELV
Aout3 0-10V: analog output function parameterizable, max. 5mA, max output frequency 300Hz, SELV D15A [4] ○ ○ ○ ○ ○
○ Tacho out (pulses), analog output 0-10V max. 5mA, max output frequency 300Hz, SELV D15A [5] ○
○ Diagnostics out (pulses) 0-10V max. 5mA, max output frequency 300Hz, SELV D15A [6] ○
RSA RS485 bus connection, MODBUS RTU, specification V6.3, SELV
○ ○ ○ ○ ○ ○
RSB
voltage output voltage parameterizable 3,3...24VDC +/- 5%, Pmax=800mW, short-circuit-proof, D16E [...]
supply for external devices, SELV
Vout
alternatively: Input auxillary power supply for 15...50VDC
EC centrifugal module - RadiPac
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3G400-PW03-01 EC centrifugal module - RadiPac
backward-curved, single-intake
with support bracket
1600
4
6
1400
ρ = 1.15 kg/m³ ± 2 %
Measurement: LU-197635-1
600 2
11
2
16 6
400
15
10
200
14
13 9 5 1
pfs
Measured values
Wired U f n Ped I LpAin LwAin LwAout qV pfs qV pfs
V Hz min-1 W A dB(A) dB(A) dB(A) m3/h Pa cfm in. wg
1 3~ 400 50 2700 2174 3.38 91 98 99 10880 0 6405 0.00
2 3~ 400 50 2700 2979 4.57 83 90 94 9040 600 5320 2.41
3 3~ 400 50 2700 3400 5.20 77 85 90 7040 1100 4145 4.42
4 3~ 400 50 2700 3139 4.81 80 87 92 4290 1500 2525 6.02
5 3~ 400 50 2300 1307 2.03 87 94 95 9185 0 5405 0.00
6 3~ 400 50 2300 1810 2.78 79 86 89 7655 432 4505 1.73
7 3~ 400 50 2300 2055 3.14 73 81 85 5940 786 3495 3.16
8 3~ 400 50 2300 1902 2.91 76 83 88 3630 1075 2135 4.32
9 3~ 400 50 1900 737 1.14 82 89 90 7585 0 4465 0.00
10 3~ 400 50 1900 1020 1.56 74 81 85 6325 295 3720 1.18
11 3~ 400 50 1900 1158 1.77 68 76 80 4910 536 2890 2.15
12 3~ 400 50 1900 1072 1.64 71 78 83 3000 734 1765 2.95
13 3~ 400 50 1500 363 0.56 76 83 84 5990 0 3525 0.00
14 3~ 400 50 1500 502 0.77 68 75 79 4990 184 2940 0.74
15 3~ 400 50 1500 570 0.87 62 70 75 3875 334 2280 1.34
16 3~ 400 50 1500 528 0.81 65 72 77 2370 457 1395 1.83
Wired = Wiring · U = Voltage · f = Frequency · n = Speed (rpm) · Ped = Power consumption · I = Current draw · LpAin = Sound pressure level intake side · LwAin = Sound power level intake side
LwAout = Sound power level outlet side · qV = Air flow · pfs = Pressure increase
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com