3.2.7 To assign connection panel I/O and operator’s panel I/O modules to the
Distribution I/O I/O Link, set the group number with an I/O Link serial number (use a
smaller number toward the I/O Link master CNC, like 0, 1, and 2). Also,
Connection I/O Module set the base number and slot number to 0 and 1, respectively. If a
and Distribution I/O combination of the basic module and expansion modules is used as the
Operator’s Panel I/O connection panel I/O module, assign all the modules in one I/O Link
Module Assignment group as one unit. Unlike the I/O Unit MODEL–A, it is unnecessary to
Methods specify a slot number. An assignment example is shown below.
Assignment example
Example
CNC
JD1A
96 input points and 64 output points (X20 and higher, Y10 and higher)
Connection Expansion Expansion Expansion
panel I/O module 1 module 2 module 3
basic module
JD1B
JD1A
24 input points and 16 output points (X100 and higher, Y100 and higher)
Connection
panel I/O
basic module
JD1B
JD1A
X004 0 0 1 CM14I
X020 1 0 1 CM12I
X100 2 0 1 CM03I
Y000 0 0 1 CM08O
Y010 1 0 1 CM08O
Y100 2 0 1 CM02O
71