LEGEND:

SYMBOLS DESCRIPTION

GROUND FLOOR LAY-OUT FOR LIGHTING LOADS


PANEL BOARD MDP-DPA: Scale 1:100 MTS.
1-Phase, 240V,2-W+G, NEMA 1
(DP,WALL MOUNTED FLUSH TYPE),HINGED 5000mm.
DPA
TYPE COVER , KEYED LOCKED
1- 100AF,2POLE,100AT,22 to 50 kaic @
240Vac,MCCB(Molded Case Circuit Breaker) d
EF EF b EF b
c
SPECIFICATIONS OF 2 – 18 WATTS T8 LED 2 2
a
a
FLUORESCENT TUBE WITHOUT BALLAST & 2cd
a b c a b c a b c 2ab
STARTER
2 1
DPA

Up
a,b,& c a b c a b c a b c 1
4000mm
3810mm. DPA 1

Double(2)-T8 LED Fluorecent Tubes, 18Watts each 2


M Service Entrance
(Replacement of 36Watts Tube), Daylight, 220/240Volts, 50/ 2ab c 2ab c 2ab c
2 1 3-way X
60Hz, 1800 to 2000 Lumens per tube, Average Life per tube: 2 3Way 2

Up

Up
Down
3way
ab
20,000 hrs, using Industrial Type double-tube luminaire, a b a b a b ab a 1
(Size:1180x125x65mm) with-out ballast & starter DPA
C O R R I D O R
Wall Mounted Exhaust Fan,12 inches, 230V,
60hz, 50watts,Air Flow=18.0m3/min, 56dB, Case
EF
Size=40.5cmx14cmx40.5cm,Installation
Dimension=33.5cmx33.5cm

6Watts,E-27, Daylight LED Bulb, 200 to 250 lumens,


220/240V, 50/60hz, Average Life: 20,000 hrs(Toilet)

9Watts,E-27, Daylight LED Bulb, 700 to 800 lumens,


220/240V, 50/60hz, Average Life: 20,000
hrs(Hallway)

Circuit Homerun Conductor GROUND FLOOR LAY-OUT FOR POWER LOADS


C Sizes of homerun conductor shall be referred to Scale 1:100 MTS.
Schedule of loads & Computations 4500mm.

Weatherproof 2- Gang Conv. Outlet, 3-prongs (For grounding),


WP wide series, universal & Flush Type,16A, 250V
2CD 2CD 2CD
240v
C C C
2- Gang Conv. Outlet, 3-prongs (For grounding), wide series, universal D D D
F F F F F F
240v
& Flush Type,16A, 250V
240v 240v 240v 5
DPA
240v 240v 240v

Up
PB Push Button Switch, Bell Push 10A, 250V, Flush Type
3
F F F F F F
Vibrating Ringing Bell, 220V,200mm(8inches) 3810mm. A B A B A B DPA
B
diameter (Color-Green) 4
DPA
MDP/DPA Overhead
2AB 2AB 2AB M
1- Gang Switch, 10A, 250V Flush Type Service Entrance
1
Up

Up
Down

WP PB
240v

B 10
2- Gang Switch,10A, 250V, Flush Type C O R R I D O R DPA
2

3-way Switch, 10A, 250V Flush Type


3-WAY

Ceiling Fan,16" inches/40.64 cm, Plastic Fan Blade, Motor


F with built-in thermal fuse, 4-speed settings, Power
input=60watts, gray in color and 3D aeromatic brand or its
equivalent WITH CONTROL SWITCH

2- Gang Switch,10A, 250V, Flush Type


2AB/CD

SHEET Designed & Sealed by a Professional


Electrical Engineer (PEE)
Name of Project : Prepared by: Submitted by: Recommending Approval : APPROVED: SET NO.: SHEET NO.:
Republic of the Philippines CONTENTS:
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS Construction of Multi-Purpose Building(Community
Lay-out for 32
Misamis Oriental First District Engineering Office College Building) E
OFFICE OF THE DISTRICT ENGINEER
Lighting & Power ERIEL F. SISON HAROLD C. CAERMARE MARCELINO O. CABEGUIN,JR.,A.E.R. MARIVEL FRANCES L. ONG, A.E.R.
1 of 7 38
Loads at Ground
Purok 5, Brgy. 26, Gingoog City PTR #.: PRC Reg. #: Electrical Engineer II Chief of Planning & Design Section OIC Assistant District Engineer District Engineer
Floor Date Issued: Valid Until:
Place Issued: TIN:
LOCATION: Brgy. Poblacion, Sugbongcogon, Misamis Oriental DATE : DATE : DATE : DATE :
LEGEND:
SECOND FLOOR LIGHTING LAY-OUT
Scale 1:100 MTS.
SYMBOLS DESCRIPTION
5000mm.

PANEL BOARD DPB:


DPB 1-Phase, 240V,2-W+G, NEMA 1 EF
d
EF
d EF b 1000mm
(DP,WALL MOUNTED FLUSH TYPE),
c
HINGED TYPE COVER , KEYED LOCKED 2 2 2
a
a
1- 60AF,2POLE,40AT,10kaic @ 240Vac 2000mm
Bolt-on Circuit Breaker/MINI-TYPE CIRCUIT BREAKER) a b c a b c a b c
2cd 2ab
2 x
1
DPB

To
SPECIFICATIONS OF 2 – 18 WATTS T8 LED

S 3wa
FLUORESCENT TUBE WITHOUT BALLAST & a b c a b c a b c 1
4000mm

yX
3810mm.
STARTER
1
DPB
2ab c 2ab c c 1
2ab
a,b,& c 3Way2 2 3Way 3Way x

Up

Down
ab ab
a b a b a b a
Double(2)-T8 LED Fluorecent Tubes, 18Watts each
(Replacement of 36Watts Tube), Daylight, 220/240Volts, 50/ C O R R I D O R

60Hz, 1800 to 2000 Lumens per tube, Average Life per tube:
20,000 hrs, using Industrial Type double-tube luminaire,
(Size:1180x125x65mm) with-out ballast & starter

Wall Mounted Exhaust Fan,12 inches, 230V,


60hz, 50watts,Air Flow=18.0m3/min, 56dB, Case
EF
Size=40.5cmx14cmx40.5cm,Installation
Dimension=33.5cmx33.5cm
SECOND FLOOR POWER LAY-OUT
Scale 1:100 MTS.
6Watts,E-27, Daylight LED Bulb, 200 to 250 lumens,
220/240V, 50/60hz, Average Life: 20,000 hrs(Toilet)
4500mm.
4500mm.
9Watts,E-27, Daylight LED Bulb, 700 to 800 lumens,
220/240V, 50/60hz, Average Life: 20,000
hrs(Hallway) 2CD 2CD 2CD 1000mm

Circuit Homerun Conductor C C C


D D D
C Sizes of homerun conductor shall be referred to F F F F F F
5 2000mm
Schedule of loads & Computations DPB
240v 240v 240v

240v 240v 240v


WP Weatherproof 2- Gang Conv. Outlet, 3-prongs (For grounding), 3
wide series, universal & Flush Type,16A, 250V DPB
F F F F F F
A B A B A B 4000mm
240v 3810mm.
4
2- Gang Conv. Outlet, 3-prongs (For grounding), wide series, universal DPB DPB
240v
& Flush Type,16A, 250V 2AB 2AB 2AB
Up

Down

WP PB

240v
B 10
PB Push Button Switch, Bell Push 10A, 250V, Flush Type DPA
C O R R I D O R

Vibrating Ringing Bell, 220V,200mm(8inches)


B
diameter (Color-Green)

1- Gang Switch, 10A, 250V Flush Type


1

2- Gang Switch,10A, 250V, Flush Type


2

3-way Switch, 10A, 250V Flush Type


3-WAY

Ceiling Fan,16" inches/40.64 cm, Plastic Fan Blade, Motor


F with built-in thermal fuse, 4-speed settings, Power
input=60watts, gray in color and 3D aeromatic brand or its
equivalent WITH CONTROL SWITCH

2- Gang Switch,10A, 250V, Flush Type


2AB/CD

SHEET Designed & Sealed by a Professional


Electrical Engineer (PEE)
Name of Project : Prepared by: Submitted by: Recommending Approval : APPROVED: SET NO.: SHEET NO.:
Republic of the Philippines CONTENTS:
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS Construction of Multi-Purpose Building(Community
Lay-out for 33
Misamis Oriental First District Engineering Office College Building) E
OFFICE OF THE DISTRICT ENGINEER
Lighting & Power ERIEL F. SISON HAROLD C. CAERMARE MARCELINO O. CABEGUIN,JR.,A.E.R. MARIVEL FRANCES L. ONG, A.E.R.
2 of 7 38
Loads at Second
Purok 5, Brgy. 26, Gingoog City PTR #.: PRC Reg. #: Electrical Engineer II Chief of Planning & Design Section OIC Assistant District Engineer District Engineer
Floor Date Issued: Valid Until:
Place Issued: TIN:
LOCATION: Brgy. Poblacion, Sugbongcogon, Misamis Oriental DATE : DATE : DATE : DATE :
SCHEDULE OF LOADS & COMPUTATION POWER RISER DIAGRAM B B

MAIN: 100AF, 100AT, 2-Pole, 240 Volts,22 to 50 KAIC @220V/240V, MOLDED CASE CIRCUIT
BREAKER(MCCB)
CKT. PROTECTION
CKT. LOAD Circuit Breaker, Bolt-on Type or MCB
P No.
DESCRIPTION OF LOADS
(V-A)
(V) (A) SIZE OF CKT. HOMERUN CONDUCTOR
AF P AT KAIC DPB
F F
LIGHTING 2
1 19 0 3 2,140 230 9.30 100 2 15 10 2-#3.5mm , THHN/THWN Stranded Wire in 15mm dia. PVC Pipe
OUTLETS
Provide Secondary Rack,
LIGHTING Two Spools
2
OUTLETS
12 0 0 1,200 230 5.22 100 2 15 10 2-#3.5mm 2, THHN/THWN Stranded Wire in 15mm dia. PVC Pipe PROVIDE 6X6
METAL PULL BOX WITH COVER
CEILING FAN 2-#3.5mm 2, THHN/THWN Stranded Wire and 1-#2.0mm 2, TW
3 0 0 8 800 230 3.48 100 2 15 10
OUTLET Stranded wire(GROUND) in 15mm dia. PVC Pipe

4
CEILING FAN
0 0 4 400 230 1.74 100 2 15 10
2-#3.5mm 2, THHN/THWN Stranded Wire and 1-#2.0mm 2, TW 2ND FLOOR
OUTLET Stranded wire(GROUND) in 15mm dia. PVC Pipe
CONVENIENCE 2-#3.5mm 2, THHN/THWN Stranded Wire and 1-#2.0mm 2, TW
5 0 7 1 1,450 230 6.30 100 2 15 10
OUTLETS Stranded wire(GROUND) in 15mm dia. PVC Pipe SERVICE ENTRANCE: Building Wall
SECOND FLOOR 2-#30mm2, THW Stranded Wire in
2-#8.0mm2, THHN/THWN Stranded Wire and 1-#5.5mm2, TW 2#8.0mm2, THW, Stranded Copper Wire, ISO
DPB ELECTRICAL 0 0 1 6,490 230 29.16 100 2 40 10 40mm(1-1/2") dia. EMT Pipe
Stranded wire(GROUND) in 3/4" dia. PVC Pipe Certified and 1-#5.5mm2, TW Stranded B B
LOADS
2.0 HP,1-Φ,230V 2-#5.5mm2, THW Stranded Wire and 1-#3.5mm2, TW Stranded
wire(GROUND) in 25mm PVC Pipe
PPH-1 0 0 1 1,492 230 8.11 100 2 30 10 CL-100, Industrial Type
WATER PUMP MOTOR wire(GROUND) in 3/4" dia. PVC Pipe
DPA Kilowatt-Hour Meter Base
2.0 HP,1-Φ,230V 2-#5.5mm2, THW Stranded Wire and 1-#3.5mm2, TW Stranded with Metal Enclosure
PPH-2 WATER PUMP MOTOR 0 0 1 1,492 230 6.49 100 2 30 10
wire(GROUND) in 3/4" dia. PVC Pipe

SPARE 0 0 1 1,000
FEEDER CONDUCTOR: M 2-#5.5mm2, THW Stranded Wire and
9 230 4.35 100 2 15 10
2-#30mm2, THW Stranded Wire 1-#3.5mm2, TW Stranded
MDP/
2-#3.5mm 2, THHN/THWN Stranded Wire and 1-#2.0mm 2, TW in 50mm(2") dia. PVC Pipe
DPA wire(GROUND) in 20mm dia. PVC
10 FACP 0 0 1 500 230 2.17 100 2 15 10 F F
Stranded wire(GROUND) in 15mm dia. PVC Pipe Pipe
11 SPARE 0 0 1 500 230 2.17 100 2 20 10
PROVIDE 8X8
12 SPARE 0 0 1 500 230 2.17 100 2 20 10 METAL PULL BOX
WITH COVER TO FACP
Total Power in Volt-Ampere & Load P1 P2
2-#3.5mm2, THHN/THWN Stranded
Current/Size of Service Entrance 17,964 230 74.16 100 2 100 22-50 2-#30 mm2, THW, Stranded Wire in 1-1/2" diameter EMT Pipe
Conductor with Demand Factor 1-#8.0mm2, TW, Stranded Copper ELECTRICAL Wire and 1-#2.0mm2, TW Stranded
Wire, in ½” diamter PVC pipe ISO wire(GROUND) in 15mm dia. PVC Pipe
LIGHTING
1
OUTLETS
18 0 3 2,040 230 8.87 60 2 15 10 2-#3.5mm 2, THHN/THWN Stranded Wire in 15mm dia. PVC Pipe Certified,(Color Green for MAIN
Grounding)
LIGHTING
2 12 0 0 1,200 230 5.22 60 2 15 10 2-#3.5mm 2, THHN/THWN Stranded Wire in 15mm dia. PVC Pipe M M
OUTLETS
PROVIDE 8X8
CEILING FAN 2 2
2-#3.5mm , THHN/THWN Stranded Wire and 1-#2.0mm , TW METAL PULL BOX WITH COVER WATER PUMP, WATER PUMP,
3 0 0 8 800 230 3.48 60 2 15 10
OUTLET Stranded wire(GROUND) in 15mm dia. PVC Pipe 2-HP,230V, 1Φ 2-HP,230V, 1Φ
CEILING FAN 2-#3.5mm 2, THHN/THWN Stranded Wire and 1-#2.0mm 2, TW
4 0 0 4 400 230 1.74 60 2 15 10 16mm dia. x 2400mm length
OUTLET Stranded wire(GROUND) in 15mm dia. PVC Pipe 2-#30mm2, THW Stranded Wire and 1-
Grounding Rod Copperweld
CONVENIENCE 2-#3.5mm 2, THHN/THWN Stranded Wire and 1-#2.0mm 2, TW #8.0mm2, TW Stranded wire(GROUND)
DPB 5 0 7 1 1,450 230 6.30 60 2 15 10
OUTLETS Stranded wire(GROUND) in 15mm dia. PVC Pipe in 50mm(2") PVC Pipe
6 SPARE 0 0 1 1,000 230 4.35 60 2 15 10
2#8.0mm2, THW, Stranded Copper 100AF, 100AT, 2-Pole,
7 SPARE 0 0 1 500 230 2.17 60 2 20 10 Wire, ISO Certified & DPB)and 1- 240 Volts, 22 TO 50KAIC,
MOLDED CASE CIRCUIT BREAKER
#5.5mm2, TW Stranded MCCB
8 SPARE 0 0 1 500 230 2.17 60 2 20 10
wire(GROUND) in 25mm PVC Pipe
(NOTE: TAPPED TO DP”A” BRANCH #6) Lighting Lighting
Total Power in Volt-Ampere & Load 2-#8.0mm2, THW Stranded Wire and 1-#5.5mm2, TW Stranded 1- 60AF,2POLE,40AT Outlets 1 2 Outlets
6,490 230 29.16 60 2 40 10 15AT 15AT
Current wire(GROUND) in 3/4" dia. PVC Pipe 10kaic @ 240Vac,
Bolt-on Circuit Breaker Ceiling Ceiling
(IL)Total Load 3 4
SERVICE ENTRANCE: 2-#30 mm2, THW, Stranded Wire in 1-1/2" diameter EMT Pipe OR MCB Fan Outlets 15AT 15AT Fan Outlets
Current with
Demand
74.16 AMPERES Lighting Lighting
PANEL BOARD MDP-DPA:
100AF, 100AT, 2-Pole, 240 Volts,22 to 50 KAIC @220V/240V 1 2 Convenience
Factor
MAIN PROTECTION:
MOLDED CASE CIRCUIT BREAKER(MCCB) PANEL BOARD DPB: Outlets 15AT 15AT Outlets 1-Phase, 240V,2-W+G, NEMA 1 Outlets 5 6 DPB
15AT 40AT
1-Phase, 240V,2-W+G, NEMA 1 (DP,WALL MOUNTED FLUSH TYPE),HINGED
Ceiling Ceiling TYPE COVER , KEYED LOCKED
(DP,WALL MOUNTED FLUSH TYPE), 3 4
TOTAL LOAD IN KVA Fan Outlets 15AT 15AT Fan Outlets PPH-1 7 8 PPH-2
TOTAL APPARENT USE 1-25-KVA TRANSFORMER, 13.2/7.62KV Primary Voltage and HINGED TYPE COVER , KEYED LOCKED 1- 100AF,2POLE,100AT,22 to 50 kaic @ 30AT 30AT
TRANSFORMER REQUIREMENTS 1- 60AF,2POLE,40AT,10kaic @ 240Vac
POWER(PKVA) 230Volts Secondary Voltage Convenience 240Vac,MCCB(Molded Case Circuit Breaker)
17.96 KVA Bolt-on Circuit Breaker/MINI-TYPE 5 6 SPARE
Outlets
CIRCUIT BREAKER)
15AT 15AT SPARE 9 10 FACP
15AT 15AT
SPARE 7 8 SPARE
20AT 20AT SPARE 11 12 SPARE
20AT 20AT

1-#5.5mm2, TW, Stranded Copper Wire, in ½” diamter 1-#8.0mm2, TW, Stranded Copper Wire, in ½” diamter PVC
PVC pipe ISO Certified,(Color Green for Grounding) pipe ISO Certified,(Color Green for MAIN Grounding)

Designed & Sealed by a Professional


SHEET CONTENTS: Electrical Engineer (PEE) Name of Project : Prepared by: Submitted by: Recommending Approval : APPROVED: SET NO.: SHEET NO.:
Republic of the Philippines
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS Schedule of Loads Construction of Multi-Purpose Building(Community
Misamis Oriental First District Engineering Office & Power Riser
College Building) E 34
OFFICE OF THE DISTRICT ENGINEER Diagram ERIEL F. SISON HAROLD C. CAERMARE MARCELINO O. CABEGUIN,JR.,A.E.R. MARIVEL FRANCES L. ONG, A.E.R.
3 of 7 38
Purok 5, Brgy. 26, Gingoog City Details of Panel PTR #.: PRC Reg. #: Electrical Engineer II Chief of Planning & Design Section OIC Assistant District Engineer District Engineer
Date Issued: Valid Until:
Board
Place Issued: TIN:
LOCATION: Brgy. Poblacion, Sugbongcogon, Misamis Oriental DATE : DATE : DATE : DATE :
GENERAL NOTES & SPECIFICATIONS ILLUMINATION REQUIREMENTS
No of Fixtures required/LUX for the INDIVIDUAL CLASSROOM

1. All electrical works and materials to be used shall be in accordance with the latest edition Required Lux: (E) 300
of the Philippine Electrical Code (PEC) , R.A. 7920, P.D. 1096, LGU local ordinances and Type of Activity Multi-Purpose Building
utility company of MORESCO II. Room Index
Length:(L) 7 Meter
Width: (w) 9 Meter
2. The eletrical wiring conductors and materials to be used shall be new and of approved Height: (h) 2.8 Meter
type for both location and purpose. Square
Area (Sq. Meter) 63
Meters

3. There shall be one(1) service drop to the building. Service shall be 230-volts A.C., single Working Level: 2 Meter
Fixture hanging Level : 2 Meter
phase 2-wires and 60Hz of frequency.
Actual Height: (Hm) 2.7 Meter

Type of Luminaire / Fixtures:


4. The contractor shall verify and be oriented of the actual location of the service entrance
Surface Mounted
for ready connection of the power utility service. Type of Fixture:
Fluorescent Lamp
Double(2)-T8 LED
5. The type of wiring installation shall be concealed using schedule #40 PVC pipes as Type of Lamp: Fluorecent Tubes,
raceway of branch circuits and EMT electric metallic tubing for the service entrance. The 18Watts each
No of Lamps per Fixture: (n) 2 Nos
minimum size of branch circuit homerun conductors shall be 2-#3.5mm2 THHN/THWN
Lamp Watt: 18 Watt
stranded copper & ISO certified.The minimum size of pipes to be used shall be ½-inch Lamp Flux: 3600 Lumen
diameter. Room Index: (K) 1
Utilization Factor: (Uf) 1
6. As indicated in the approved electrical plan, specifications of lamps, switches and other Maintenance Factor: (Mf) 1
:Results:
electrical devices should be followed during installation.
Required No of Fixtures: 5 Nos

7. All branch circuit protection shall use Bolt-on Circuit Breakers of Miniature Circuit Actual No of Fixtures along
3 Nos
Length:
Breakers(MCB) with minimum KAIC rating of 10 at 240Volts AC. Main over-current
Actual No of Fixtures across
protection OCP shall use Molded Case type of circuit breakers (MCCB) with minimum KAIC Length:
3 Nos

ratings from 22 to 50 at 240V-AC. Actual No of Fixtures: 6 Nos


Actual Lux: 343

8. Electrical devices shall be installed as follows:


a. Panel board………………………………..1.50 meters above finished floor line
DETAILED COMPUTATION: 0

b. Switches………………………………….. 1.30 meters above finished floor line


c. Duplex Convenience Outlet.……………..0.60 meters above finished floor line DETAILED COMPUTATION BASED ON THE SCHEDULE OF LOADS: *The minimum ampacity and size of branch circuit conductors shall be based on Article
d. Table top Duplex Convenience Outlet….0.30 meters above finished working table
ASSUMED DATAS OF LOADS: 2.10.2.1 page # 39 of the Philippine Electrical Code
100 VOLT-AMPERE PER LIGHTING OUTLET
9. All electrical works shall be tested on insulation resistance using calibrated insulation
tester and shall be witnessed by a licensed Registered Electrical Engineer/Master 200 VOLT-AMPERE PER CONVENIENCE OUTLET
*AMPERE TRIP RATING OF THE OVER-CURRENT PROTECTION SHALL BE BASED ON:
Electrician of both parties. The minimum required insulation resistance per branch circuit
shall be 10 mega-ohms. USING FORMULA OF APPARENT POWER(P) IN VOLT-AMPERE: PEC 2.10.2.2 Overcurrent Protection. Branch-circuit conductors and equipment shall be
protected by overcurrent protective devices that have a rating or setting that complies
10. All types of metal enclosures shall be referred to the single line diagram of individual
P = (I) x (V) with 2.10.2.2(a) through (d).
panel boards for proper reference and correct specifications.
WHERE:
*KAIC RATING OF CIRCUIT BREAKERS SHALL BE BASED ON THE RESULT OF THE
11. All non-current carrying metal parts of an electrical equipment shall be properly
grounded in accordance with the provision of the latest Philippine Electrical Code. P= Apparent Power in Volt-Ampere SHORT CIRCUIT ANALYSIS/COMPUTATION AS REQUIRED PER 1.3.2f, Page #16 of PEC
V= AC Source voltage in Volts COMPUTATION OF TOTAL LOAD CURRENT:
12. All electrical works shall be done under the direct supervision of a duly licensed I= Load Current in Amperes
Registered Electrical Engineer and or Master Electrician.
COMPUTATION OF INDIVIDUAL BRANCH CIRCUIT LOAD CURRENT IN AMPERES: IT= (PT) / (V) =17,964 volt-ampere / 230volts X 0.85 DEMAND FACTOR= 74.16Amperes

I = (P) / (V) = _____ Amperes Refer to Table #3.10.1.16 & 2.10.2.2 the size of service entrance and main over-current protection shall
be as follows:
CORRECT SIZING OF INDIVIDUAL BRANCH CIRCUIT CONDUCTOR SHALL BE BASED ON Table # 3.10.1.16 SERVICE ENTRANCE: 2-#30mm2, THW Stranded Wire and 1-#8.0 mm2, TW Stranded
Allowable Ampacities of Insulated Conductors Rated 0 Through 2000 Volts, 60°C Through 90°C (140°F wire(GROUND) in 1-1/2" dia. EMT Pipe
Through 194°F), Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly
MAIN PROTECTION: 100AF, 100AT, 2-Pole, 22-50 KAIC @ 240 Volts, MOULDED CASE TYPE OF
Buried), Based on Ambient Temperature of 30°C (86°F) , PAGE # 177 OF THE PHILIPPINE ELECTRICAL
CODE PER RESULT OF THE INDIVIDUAL CURRENT FORMULA AS STATED. CIRCUIT BREAKER( MCCB)

SHEET Designed & Sealed by a Professional


Electrical Engineer (PEE)
Name of Project : Prepared by: Submitted by: Recommending Approval : APPROVED: SET NO.: SHEET NO.:
Republic of the Philippines CONTENTS:
General Notes &
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS Construction of Multi-Purpose Building(Community
Specifications 35
Misamis Oriental First District Engineering Office College Building) E
OFFICE OF THE DISTRICT ENGINEER
Illumination ERIEL F. SISON HAROLD C. CAERMARE MARCELINO O. CABEGUIN,JR.,A.E.R. MARIVEL FRANCES L. ONG, A.E.R.
4 of 7 38
Requirements
Purok 5, Brgy. 26, Gingoog City PTR #.: PRC Reg. #: Electrical Engineer II Chief of Planning & Design Section OIC Assistant District Engineer District Engineer
Detailed Date Issued: Valid Until:
Computation Place Issued: TIN:
LOCATION: Brgy. Poblacion, Sugbongcogon, Misamis Oriental DATE : DATE : DATE : DATE :
SHORT CIRCUIT CALCULATION(Single Phase Short Circuits) One Line Diagram Voltage Drop Computation
CONDU
UNITY POWER FACTOR 85% POWER FACTOR
Fault X1 Line-to-Line (L-L) Fault LOAD REMARKS ( 5 % )
CTOR DISTANCE LOAD
COMPUTATION OF AREA IN TYPE OF NO. OF Allowable VD from
VOLTAGE SIZE ONE(1) WAY CURRENT
POLE MOUNTED TRANSFORMER 25-KVA USING COPPER WINDING VOLTAGE DROP USED
(CM) CONDUCTOR SETS
(Feet) (AMPERES) Voltage Voltage Voltage Voltage
FEEDER/SE to Farthest
(V) % VD % VD
USE PERCENT IMPEDANCE %Z=1.30% Available Utility (AWG) Drop @ Load Drop Load
Branch Circuit

TRANSFORMER IMPEDANCE: Infinite Assumption


SERVICE ENTRANCE TO Copper,
TRANSFORMER FULL LOAD AMPERES (F.L.A.) 1 MDP
230 #2 66,630
Stranded
1.0 49.20 74.16 1.41 0.61 228.6 1.20 0.5 228.8
Step 1
IFLA = KVA x 1000 / ELL = Transformer Full Load amperes Copper,
2 MDP TO DPB 230 #8 16,510 1.0 14.76 29.16 0.67 0.29 229.3 0.57 0.2 229.4
IFLA = 25000 / 230 = 108.70 Amps Stranded
Step 2
DPB TO FARTHEST
MULTIPLIER (M)= 100 / (PERCENT IMPEDANCE %Z of the Transformer) x (Impedance Tolerance) 3 CONVENIENCE OUTLET 230 #12 6,530
Copper,
1.0 118.24 6.30 2.94 1.28 227.1 2.50 1.1 227.5
Stranded
M = 100 / 1.170 = 85.47 25KVA, 1-Phase @ CIRCUIT # 5
Transformer
Step 3 1.30% Z TOTAL 5.03 2.19 224.97 4.27 1.86 225.7 PASSED
TRANSFORMER SHORT CIRCUIT CURRENT: 230V
ISC(XFORMER) = Transformer FLA x Multiplier
ISC(XFORMER) = 108.70 x 85.47 9,290.23 Amperes
X1 ISC = 9,290.23 Amperes Voltage Drop Single Line Diagram
Fault X2 SERVICE ENTRANCE TO MDP/DPA 15.00 METERS,
SIZE OF CONDUCTOR: # 30mm2 Cu
Magnetic Conduit
VDTOTAL= 5.03 volts, 2.19% LESS THAN 5%
2-#30 mm2 THW STRANDED COPPER SYMMETRICAL SHORT 5%
LENGTH OF CABLE: = 15 meters
X2 ISC MDP= 6,512.16 AMPS CIRCUIT CURRENT
2%
L = 15 m x 3.28 = 49.20 feet
3%
Calculation of the " f" factor: VDDPB= 0.67 volts,
Step 4 100AF, 100AT, 2-POLE, VD SE= 1.41 volts, 0.61% MDP/ 0.29% VDCO= 2.94 volts, 1.28%
CO
f = 2 x L x ILL / C x n x ELL = Line to Line (L-L) Faults MOULDED CASE DPB OUTLET
f = 914,158.31 / 2,142,910.00 = 0.43 MDP/DPA CIRCUIT BREAKER,
SERVICE ENTRANCE
2-#30mm2, THW Copper Conductor
DPA FARTHEST OUTLET FROM THE SOURCE
2-#3.5mm2, THHN/THWN Copper Conductor
50KAIC, 240v
Step 5
4.50 METERS,
M = 1 / 1+f # 8.0mm2 Cu
2-#8.0mm2, THW Copper
M = 1 / 1.43 = 0.70 Non-Magnetic SYMMETRICAL SHORT
Step 6 Conduit X3 ISC DPB= 4,239 AMPS CIRCUIT CURRENT
Conductor

SYMMETRICAL SHORT
ISC(MDP) = 9,290.23 x 0.70 = 6,512.16 AMPS
CIRCUIT CURRENT DETAILED COMPUTATION OF VOLTAGE DROP: PERCENT of VOLTAGE DROP:
Fault X3 PANEL BOARD MDP TO DPB 60AF, 40AT, 2-Pole,
SIZE OF CONDUCTOR:
DPB 240 Volts, 10KAIC, SINGLE PHASE:
2 MCB
2-#8.0mm , THW STRANDED COPPER
LENGTH OF CABLE: VD= (2) x (K) x (I) x (L) / CM %VD= (VD ) / (V) x 100
60AF, 15AT, 2-Pole,
LT = 4.50 m x 3.28 = 14.76 feet BRANCH CKT. #5
240 Volts, 10KAIC,
PROTECTION
Step 7 MCB WHERE: WHERE:
f = 192,238.98 / 358,570.00 = 0.54 4.84 METERS, # 3.5mm2 Cu VD= Voltage Drop V= Source Voltage VD= Voltage Drop
Step 8 Non-Magnetic Conduit K= Constant value of Copper, 12.90
M = 1 / 1.54 = 0.65 Constant value of Aluminum, 21.20 NOTES:
Step 9
SYMMETRICAL SHORT Load current in Amperes
SYMMETRICAL SHORT X4 ISC C.O.= 2,176 AMPS CIRCUIT CURRENT
I= FPN No. 4: Conductors for branch circuits as defined in Article 1.0, sized to prevent a
ISC(LPB) = 6,512.16 x 0.65 = 4,239 AMPS CIRCUIT CURRENT L= Distance from the source to the load in feet voltage drop exceeding 3 percent at the farthest outlet of power, heating, and lighting
loads, or combinations of such loads, and where the maximum total voltage drop on
Fault X4 PANEL BOARD DPB TO NEAREST CONV. OUTLET CM=
AREA IN Circular Mils of Wire use (datas shall be
both feeders and branch circuits to the farthest outlet does not exceed 5 percent,
referred to Table # 8 of NEC)
SIZE OF CONDUCTOR: NEAREST
CONVENIENCE
provide reasonable efficiency of operation. See FPN No. 2 of 2.15.1.2(a)(3) for
2-#3.5mm2, THHN/THWN STRANDED COPPER OUTLET voltage drop on feeder conductors OF PEC.
LENGTH OF CABLE:
LT = 4.84 m x 3.28 = 15.88 feet
Step 10
f = 134,600.68 / 141,910.00 = 0.95 NOTE: THE ELECTRICAL DESIGN ANALYSIS PER PHILIPPINE ELECTRICAL CODE REQUIREMENT ON ARTICLE 1.3.2.1f Page # 15 shall
Step 11 be included on the drawings or shall be submitted on separate sheets of standard size.
M = 1 / 1.95 = 0.51
Step 12
SYMMETRICAL SHORT
ISC(CO) = 4,239.34 x 0.51 = 2,176 AMPS CIRCUIT CURRENT

SHEET Designed & Sealed by a Professional


Electrical Engineer (PEE)
Name of Project : Prepared by: Submitted by: Recommending Approval : APPROVED: SET NO.: SHEET NO.:
Republic of the Philippines CONTENTS:
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS Voltage Drop Construction of Multi-Purpose Building(Community
Misamis Oriental First District Engineering Office E 36
Computation College Building) ERIEL F. SISON HAROLD C. CAERMARE MARIVEL FRANCES L. ONG, A.E.R.
OFFICE OF THE DISTRICT ENGINEER MARCELINO O. CABEGUIN,JR.,A.E.R. 5 of 7 38
Purok 5, Brgy. 26, Gingoog City
Short Circuit PTR #.: PRC Reg. #: Electrical Engineer II Chief of Planning & Design Section OIC Assistant District Engineer District Engineer
Calculation Date Issued: Valid Until:
LOCATION: Brgy. Poblacion, Sugbongcogon, Misamis Oriental DATE : DATE : DATE : DATE :
Place Issued: TIN:
GROUND FLOOR PIPE LAY-OUT FOR LIGHTING LOADS Details of Pipe & Boxes :
Scale 1:100 MTS.

½” diameter X 3m PVC Pipe embedded in


2 x 4 Metal Box deep type ,galvanized,
concrete slab ceiling with proper support & gauge #16(Embedded in all concrete
1/2” inch diameter X 3m PVC Pipe embedded in fittings….Note: Circuit homerun conductor hollow blocks walling)
concrete slab ceiling with proper support & for lighting outlets should be 2-#3.5 mm2,
fittings….Note: Circuit homerun conductor for THHN/THWN Stranded Wire
lighting outlets should be 2-#3.5 mm2, THHN/THWN 5000mm.
Stranded Wire ½ inch & ¾ inch diameter x 3 meters
PVC Pipe (Orange in color) lay-out
inside the ceiling & concrete slab
d
EF EF b EF b flooring (Note: Do not use flexible PVC
c pipe)
2 2
a a
2cd
a b c a b c a b c 2ab ------- “ inch diameter x 3 meters EMT Pipe
2 1
DPA

Up
4 x 4 METAL Junction Box with cover,
a b c a b c a b c galvanized, gauge #16 ( For used in
4000mm
3810mm.
1 wooden ceiling/metal parring ceiling and
concrete slab flooring)
2
M Service Entrance
2ab c 2ab c 2ab c
2 1 3-way X
3Way 2 2

Up

Up
Down
ab 3way
a b a b a b ab a 1
DPA
C O R R I D O R

Provide 4 x 4 Metal Junction Provide 1-gang, 3-prongs outlet to Wall fans mounted to
Box installed in concrete slab 1/2” inch diameter X 3m PVC Pipe embedded in 2 x 4 Metal Junction Box installed in concrete HB
concrete slab ceiling with proper support & fittings
ceiling for the lighting outlets walling

Ceiling Fan,16" inches/40.64 cm, Plastic Fan Blade, Motor


with built-in thermal fuse, 4-speed settings, Power
input=60watts, gray in color and 3D aeromatic brand or its
equivalent WITH CONTROL SWITCH (Note: All ceiling GROUND FLOOR PIPE LAY-OUT FOR POWER LOADS ½” diameter X 3m PVC Pipe embedded in concrete slab
fan control rotary switch were individually Scale 1:100 MTS. flooring of the ground floor…..Note: Circuit homerun
controlled by a 1-single switch installed in two- conductor for convenience outlets should be 2-#3.5
4500mm.
gang flush type switch) mm2, THHN/THWN Stranded Wire & 1-2.0mm2, TTW
Stranded Wire for grounding

2 2 2
3
DPA
C C C
D D D
F F F F F F

240v 240v 240v 5


DPA
240v 240v 240v

Up
F F F F F F
A B A B A B
3810mm.

4
DPA DPA Overhead
M
2 2 2 Service Entrance
Up

Up
Down

WP
240v

B
C O R R I D O R

Weatherproof Flush Type Duplex Conv. 2" diameter X 3m PVC Pipe in concrete
Flush Type Duplex Conv. Outlet, Grounding type, Outlet, Grounding type, 16 Amperes, 250 Volt slab…..Note: Service Entrance conductor
16 Amperes, 250 Volt with plate cover (3-prongs) with plate cover (3-prongs) mounted to 2x4 should be 2-#30 mm2, THW Stranded Wire & 1-
mounted to 2x4 Metal Box, Deep Type Metal Box, Deep Type (Galvanized), & to be 8.0mm2, TW Stranded Wire for
(Galvanized), & to be installed 0.30 m aboved installed 0.30 m aboved finished floor line grounding(Green)
finished floor line

SHEET Designed & Sealed by a Professional


Electrical Engineer (PEE)
Name of Project : Prepared by: Submitted by: Recommending Approval : APPROVED: SET NO.: SHEET NO.:
Republic of the Philippines CONTENTS:
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS Pipe lay-out for
Construction of Multi-Purpose Building(Community
Lighting & Power 37
Misamis Oriental First District Engineering Office College Building) E
OFFICE OF THE DISTRICT ENGINEER
Loads at Ground
ERIEL F. SISON HAROLD C. CAERMARE MARCELINO O. CABEGUIN,JR.,A.E.R. MARIVEL FRANCES L. ONG, A.E.R.
6 of 7 38
Floor
Purok 5, Brgy. 26, Gingoog City PTR #.: PRC Reg. #: Electrical Engineer II Chief of Planning & Design Section OIC Assistant District Engineer District Engineer
Details of Pipe & Date Issued: Valid Until:
Boxes Place Issued: TIN:
LOCATION: Brgy. Poblacion, Sugbongcogon, Misamis Oriental DATE : DATE : DATE : DATE :
½” diameter X 3m PVC Pipe installed and lay-

SECOND FLOOR LIGHTING LAY-OUT


outed inside the ceiling with proper support &
fittings….Note: Circuit homerun conductor for
Details of Pipe & Boxes :
Scale 1:100 MTS. lighting outlets should be 2-#3.5 mm2, THHN/
THWN Stranded Wire
5000mm. 2 x 4 Metal Box deep type ,galvanized,
gauge #16(Embedded in all concrete
3/4” inch diameter X 3m PVC Pipe installed and hollow blocks walling)
lay-outed inside the ceiling with proper support & EF EF
d EF b 1000mm
d
fittings….Note: Circuit homerun conductor for
c ½ inch & ¾ inch diameter x 3 meters
lighting outlets should be 2-#3.5 mm2, THHN/ a
2 2 2
a
THWN Stranded Wire 2000mm PVC Pipe (Orange in color) lay-out
a b c a b c a b c
2cd 2ab inside the ceiling & concrete slab
2 x
flooring (Note: Do not use flexible PVC
1 pipe)
DPB

To
S 3wa
a b c a b c a b c 1
4000mm

yX
3810mm.
Provide 4 x 4 Metal 1 ------- “ inch diameter x 3 meters EMT Pipe
Junction Box installed in DPB
concrete slab ceiling for 2ab c 2ab c c 1
2ab
3Way2 2 3Way x
4 x 4 METAL Junction Box with cover,
the lighting outlets 3Way

Up

Down
ab ab galvanized, gauge #16 ( For used in
a b a b a b a
wooden ceiling/metal parring ceiling and
C O R R I D O R concrete slab flooring)

½” diameter X 3m PVC Pipe embedded in


concrete slab flooring of the 2nd floor…..Note:
Circuit homerun conductor for convenience
outlets should be 2-#3.5 mm2, THHN/THWN
Flush Type Duplex Conv. Outlet, SECOND FLOOR POWER LAY-OUT Stranded Wire & 1-2.0mm2, TW Stranded Wire
Grounding type, 16 Amperes, 250 Volt Scale 1:100 MTS. for grounding
with plate cover (3-prongs) mounted to
2x4 Metal Box, Deep Type (Galvanized), 4500mm.

& to be installed 0.30 m aboved finished 4500mm.


floor line
2 2 2
1000mm
Ceiling Fan,16" inches/40.64 cm, Plastic Fan Blade, Motor
with built-in thermal fuse, 4-speed settings, Power C
D
C
D
C
D
input=60watts, gray in color and 3D aeromatic brand or its F F F F F F 5
equivalent WITH CONTROL SWITCH (Note: All ceiling DPB
240v 240v 240v
fan control rotary switch were individually 2000mm

controlled by a 1-single switch installed in two- 240v 240v 240v


3
gang flush type switch) DPB
F F F F F F
A B A B A B 4000mm
3810mm.
4
DPB
DPB
2 2 2
Up

Down

WP

240v
B
C O R R I D O R

Weatherproof Flush Type Duplex


Conv. Outlet, Grounding type, 16 ½” diameter X 3m PVC Pipe installed & lay-out
Amperes, 250 Volt with plate cover inside the ceiling…..Note: Circuit homerun
(3-prongs) mounted to 2x4 Metal conductor for fire alarm should be 2-#3.5 mm2,
Box, Deep Type (Galvanized), & to THHN/THWN Stranded Wire & 1-2.0mm2, TW
be installed 0.30 m aboved finished Stranded Wire for grounding
floor line

SHEET Designed & Sealed by a Professional


Electrical Engineer (PEE)
Name of Project : Prepared by: Submitted by: Recommending Approval : APPROVED: SET NO.: SHEET NO.:
Republic of the Philippines CONTENTS:
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS Pipe lay-out for
Construction of Multi-Purpose Building(Community
Lighting & Power 38
Misamis Oriental First District Engineering Office College Building) E
OFFICE OF THE DISTRICT ENGINEER
Loads at Second ERIEL F. SISON HAROLD C. CAERMARE MARCELINO O. CABEGUIN,JR.,A.E.R. MARIVEL FRANCES L. ONG, A.E.R.
7 of 7 38
Floor
Purok 5, Brgy. 26, Gingoog City PTR #.: PRC Reg. #: Electrical Engineer II Chief of Planning & Design Section OIC Assistant District Engineer District Engineer
Details of Pipe & Date Issued: Valid Until:
Boxes Place Issued: TIN:
LOCATION: Brgy. Poblacion, Sugbongcogon, Misamis Oriental DATE : DATE : DATE : DATE :