Professional Documents
Culture Documents
Air Conditioning Duct Design
Air Conditioning Duct Design
Thermal Stream
Done By:
Abirham Yazie ATR/7907/09
Biruk Solomon ATR/7460/09
Samson H/Michael ATR/9817/09
Sophonias Dawit ATR?2651/09
In order to calculate the mass flow rate, we need to select the appropriate heat load. So, we need
to Calculate to see whether the heating or cooling loads are larger:
Heating Load, 𝑄 = 1.6 + 1.8 + 1.2 + 1 = 5.6 𝐾𝑊
Cooling Load, 𝑄 = 2.1 + 2.4 + 1.2 + 1.6 = 7.3 𝐾𝑊
𝐻𝑒𝑎𝑡𝑖𝑛𝑔 𝐿𝑜𝑎𝑑 ≤ 𝐶𝑜𝑜𝑙𝑖𝑛𝑔 𝐿𝑜𝑎𝑑
So, we will use the cooling loads to each room to calculate their mass flow rate. And a
temperature difference of 10 K is selected between the ambient and the rooms’ temperature for
effective heat transfer.
Room 1:
𝐾𝐽
2.1 𝐾𝑊 = 𝑚̇ ∗ 1.005 ∗ 10𝐾
𝐾𝑔. 𝐾
𝐾𝑔⁄
𝑚̇ = 0.209 𝑠
Room 2:
𝐾𝐽
2.4 𝐾𝑊 = 𝑚̇ ∗ 1.005 ∗ 10𝐾
𝐾𝑔. 𝐾
𝐾𝑔⁄
𝑚̇ = 0.239 𝑠
Room 3:
𝐾𝐽
1.2 𝐾𝑊 = 𝑚̇ ∗ 1.005 ∗ 10𝐾
𝐾𝑔. 𝐾
𝐾𝑔⁄
𝑚̇ = 0.119 𝑠
Room 4:
𝐾𝐽
1.6 𝐾𝑊 = 𝑚̇ ∗ 1.005 ∗ 10𝐾
𝐾𝑔. 𝐾
𝐾𝑔⁄
𝑚̇ = 0.159 𝑠
𝐾𝑔⁄
We will use density of air at STP, 𝜌 = 1.225 𝑠 to calculate the flow rate,
𝑚̇
𝑄̇ =
𝜌
Room 1:
0.209 3
𝑄̇1 = = 0.171 𝑚 ⁄𝑠
1.225
Room 2:
0.239 3
𝑄̇2 = = 0.195 𝑚 ⁄𝑠
1.225
Room 3:
0.119 3
𝑄̇3 = = 0.097 𝑚 ⁄𝑠
1.225
Room 4:
0.159 3
𝑄̇4 = = 0.130 𝑚 ⁄𝑠
1.225
Then we need to determine the flow rate at different sections of the main pipe.
For the First Section (Section A) of the main duct:
𝑄̇
⃗ =
𝑉
𝐴𝑐
The calculated velocities are tabulated as follows:
Pipe Section Flow Rate (m3/s) Cross-sectional Area Velocity (m/s)
(m2)
Main Duct (Section 0.593 0.196 3.026
A)
Main Duct (Section 0.227 0.126 1.802
B)
Branch Duct (Room 0.171 0.078 2.192
1)
Branch Duct (Room 0.195 0.078 2.5
2)
Branch Duct (Room 0.097 0.049 1.980
3)
Branch Duct (Room 0.130 0.078 1.667
4)
For Room 3:
Parameters SD5-10 Tee
Dc (m) 0.400
Db (m) 0.250
Ds (m) 0.315
Dc-Ds (m) 0.085
Using tables below, we will interpolate to determine the values of 𝐶𝑏1 , 𝐶𝑏2 , 𝑎𝑛𝑑 𝐶𝑠 .
𝐴𝑠 𝐴𝑏1 𝐴𝑏2 𝐶𝑏1 𝑎𝑛𝑑 𝐶𝑏2
𝑎𝑛𝑑
𝐴𝑐 𝐴𝑐 𝐴𝑐 0.2 0.288 0.3 0.329 0.4
0.55 0.30 1.56 0.65 0.39
0.38 2.696 1.090 0.598
0.40 2.98 1.20 0.65
0.643 0.38 2.696 1.283 1.090 0.947 0.598
0.80 0.30 1.56 0.65 0.39
0.38 2.696 1.090 0.598
0.40 2.98 1.20 0.65
𝐶𝑏1 = 1.283
𝐶𝑏2 = 0.947
𝐴𝑠 𝑄𝑠
𝐴𝑐 𝑄𝑐
0.3 0.383 0.4
0.6 0.20 0.14
0.643 0.2559 0.174 0.157
0.7 0.33 0.18
𝐶𝑠 = 0.174
At the SD5-10 Tee:
Parameters Values
𝑄𝑐 - Section B of the Main Duct (m3/s) 0.227
𝑄𝑏 - Branch Duct to Room 3 (m3/s) 0.097
𝑄𝑠 - Branch Duct to Room 4 (m3/s) 0.130
𝐴𝑐 (m2) 0.126
𝐴𝑏 (m2) 0.049
𝐴𝑠 (m2) 0.078
𝐴𝑠 /𝐴𝑐 0.619
𝐴𝑏 /𝐴𝑐 0.389
𝑄𝑏 /𝑄𝑐 0.427
𝑄𝑠 /𝑄𝑐 0.573
𝐶𝑏
𝐴𝑏 𝑄𝑏
𝐴𝑐 𝑄𝑐
0.4 0.427 0.5
0.3 0.39 0.29
0.389 0.621 0.565 0.415
0.4 0.65 0.43
𝐶𝑏 = 0.565
𝐶𝑠
𝐴𝑠 𝑄𝑠
𝐴𝑐 𝑄𝑐
0.4 0.427 0.5
0.6 0.14 0.13
0.619 0.144 0.135 0.132
0.7 0.16 0.14
𝐶𝑠 = 0.135
At the CD3-5 Elbow:
D (m) 0.3 0.315 0.35
𝐶𝑜 0.26 0.257 0.25
𝐶𝑜 = 0.257
Accessory Pressure Loss
I. Diffuser Loss
Next we will select diffusers for each room with diameters close to the duct sizes.
We will be selecting diffusers from catalogue by Price Industry.
The RCDE series round cone diffusers have nominal duct size diameters close to duct diameters.
∆𝑷𝒅𝟑 = 𝟏. 𝟔𝟖𝟐 𝑷𝒂
Step 9: Determine the total pressure loss in each run.
Sec Len Flow Pressure Duct Velocity Velocity Fittings Pressure Loss Section
𝑚
tion gth Rate Drop per Size (𝑠) Pressure Pressure Total
(m) (m3/ Meter (m) (Pa) Loss Pressure
Fittin Straight
s) (Pa/m) Factor Loss
gs (Pa)
(C) (Pa)
(Pa)
Sec 2.7 0.59 0.4 0.5 3.026 5.609 1.117 1.117
tion 925 3
A
Cro 3.026 5.609 𝐶𝑏1 7.196 7.196
ss = 1.283
𝐶𝑏2 5.312 5.312
= 0.947
𝐶𝑠 0.976 0.976
= 0.174
Sec 4.5 0.22 0.4 0.4 1.802 1.989 1.807 1.807
tion 175 7
B
Roo 1.9 0.17 0.4 0.31 2.192 2.943 2.488 0.76 3.248
m1 1 5
Roo 1.9 0.19 0.4 0.31 2.5 3.828 2.488 0.76 3.248
m2 5 5
Tee 1.802 1.989 𝐶𝑏 1.124 1.124
= 0.565
𝐶𝑠 0.269 0.269
= 0.135
Roo 1.9 0.09 0.4 0.25 1.980 2.401 2.488 0.78 3.268
m3 5 7
Elb 1.667 1.702 𝐶𝑜 0.437 0.437
ow = 0.257
Roo 2.0 0.13 0.4 0.31 1.667 1.702 2.488 0.818 3.306
m4 45 0 5
Total Pressure Drop = Frictional Pressure Drop + Dynamic Pressure Loss
Run Frictional Dynamic Pressure Loss (Pa) Total Pressure Drop
Pressure Drop (Pa)
(Pa)
𝒇𝟏 = 𝟎. 𝟑𝟕𝟐
For Room 1:
𝜌𝑉𝐷 1.225 ∗ 2.192 ∗ 0.315
𝑅𝑒 = = = 46,731.38
𝜇 1.81 × 10−5
𝜀 0.15
= = 0.0005
𝐷 315
𝒇𝟐 = 𝟎. 𝟑𝟖𝟕
Now equating the pressures to find the equivalent length of the duct section leading to room 1.
𝑃1 1.117
=
𝑃2 0.76
𝑃1 = 1.470𝑃2
𝑓1 𝐿1 𝑄1 2 𝑓2 𝐿2 𝑄2 2
= 1.47
𝐷1 5 𝐷2 5
0.372 ∗ 2.7925 ∗ 0.5932 0.387 ∗ 𝐿𝑒𝑞 ∗ 0.1712
= 1.47
0.55 0.3155
𝐿𝑒𝑞 = 2.1794 𝑚
Now we will calculate the equivalent length for the fitting, as we have adjusted the smaller
diameter pipe leading to room 1 to have the same diameter and flow rate as the base duct
(Section A of the main duct).
8𝑓𝐿
ℎ𝑙 = 𝑄2
𝜋 2 𝑔𝐷5
𝑃 8𝑓𝐿
= 2 5 𝑄2
𝜌𝑔 𝜋 𝑔𝐷
Pressure lost due to the cross fitting leading to room 1 is 7.196 Pa.
7.196 8 ∗ 0.372 ∗ 𝐿𝑒𝑞
= 0.5932
1.225 𝜋 2 0.55
𝐿𝑒𝑞 = 1.7313𝑚
3
The equivalent length due to filter will also be taken into account. The filter having 0.593𝑚 ⁄𝑠
flow rate and 0.5m diameter, will have 3.026m/s velocity.
𝜌𝑉𝐷 1.225 ∗ 3.026 ∗ 0.5
𝑅𝑒 = = = 102,399.17
𝜇 1.81 × 10−5
𝒇𝟏 = 𝟎. 𝟑𝟕𝟐
The pressure drop across the filter is 49 Pa, so the equivalent length will be:
𝑃 8𝑓𝐿
= 2 5 𝑄2
𝜌𝑔 𝜋 𝑔𝐷
49 8 ∗ 0.372 ∗ 𝐿𝑒𝑞
= 0.5932
1.225 𝜋 2 0.55
𝐿𝑒𝑞 = 11.789 𝑚
Now, we can determine the equation for the system curve using the equation we previously used,
as follows:
𝑃 8𝑓𝐿
= 2 5 𝑄2
𝜌 𝜋 𝐷
𝜌8𝑓𝐿 2
𝑃= 𝑄
𝜋 2 𝐷5
1.225 ∗ 8 ∗ 0.372 ∗ 18.491 2
𝑃= 𝑄
𝜋 2 0.55
𝑷 = 𝟐𝟏𝟖. 𝟓𝟔𝟒 𝑸𝟐
Now we will select fan series that can operate under the pressure and flow rate of the designed
duct system.
Selecting AXCPV 400-6-2 fan from the AXCPV series provided by Systemair. The motors of
the selected fans are equipped with PTC thermistors for optimum motor protection. The motor is
speed controllable by frequency converter.
From the charts above, we can see that the fan will operate at 10 RPM and around 0.55KW.
The dimensions of the selected fan are shown below.