Qatar Factory

For Fire Fighting Equipment & Safety Systems NAFFCO


‫ألجهزة إطفاء الحريق وأنظمة السالمه نافكو‬
AMC: 24462 NAF/2021/FSR: 793
FIELD SERVICE REPORT

DATE 14/10/2023
NAME OF THE CLIENT Mushereib - Elegancia
LOCATION Phase 4- X03
Work Scope Pre – QCD

WORK DONE • Integration Testing of Fire alarm system as per Cause &
Effect.
• Functional testing of Firefighting system is Zone control
valve, Fire hose reel, Landing valve
• Visual inspection of Fire extinguisher, Blanket
• Fire alarm system Telephone Sounder system working
properly
• Third Party system like AHU, DOOR, LIFT, GAS working
properly
FINDINGS
• Hose reel nozzle damage at ground floor.
• Breeching inlet sticker to be provided.
• ZCV stickers to be provided.
• Need access panel at level 9 for ZCV access.
• Lock shield is damage at Level 6 & 9.
• Material to be provided related to trouble.
• Faulty LED to be replaced in override panel.
• Faulty speaker to be replace at level-4.

RECOMMENDATIONS Need to replace defective devices.

SIN
LOCATION DESCRIPTION BRAND MODEL QTY UOM IMAGE
O

SD-116 Smoke
1 SIEMENS FDO-421 02 No’s
SD-38 detector

Quality Reliability Services

P.O. Box 55644, Doha, Qatar, Tel.: (00-974) 44025888, Fax (00-974) 44114630, Web: www.qatarfactory.qa
For Queries, email to– info@qatarfactory.qa
Qatar Factory
For Fire Fighting Equipment & Safety Systems NAFFCO
‫ألجهزة إطفاء الحريق وأنظمة السالمه نافكو‬

AIO-038 Control
2 SIEMENS HTRI-R 2 No’s
AIO-078 module

Monitor
3 AIU-162 SIEMENS HTRI-S 1 No’s
Module

25NFH-02A
Hose reel
4 Ground floor NAFFCO 6MM 1 No’s
nozzle
DIAMETER

Lock shield SHIELD SLSV-25 03 No’s


5 Level-6 & 2
valve 1”

LED red color


6 Ground floor FCC Any 1.8MM 20 No’s
2.5volt

Ceiling SHTP84719-
7 LEVEL-4 SIEMENS 01 No’s
Speaker 001

40*5 CM Acrylics Tag with Red back ground and white Letter:
8 1 No’s
X03 4 - WAY BREECHING INLET TO DRY RISER SYSTEM

Quality Reliability Services

P.O. Box 55644, Doha, Qatar, Tel.: (00-974) 44025888, Fax (00-974) 44114630, Web: www.qatarfactory.qa
For Queries, email to– info@qatarfactory.qa
Qatar Factory
For Fire Fighting Equipment & Safety Systems NAFFCO
‫ألجهزة إطفاء الحريق وأنظمة السالمه نافكو‬

25*6 CM Tag with Red back ground and white Letter


9 100 No’s
ZONE CONTROL VALVE

TESTING ENGINEER WITNESS BY CLIENT