Professional Documents
Culture Documents
Meliopoulos 94
Meliopoulos 94
net/publication/3272594
A New Method and Instrument for Touch and Step Voltage Measurements
CITATIONS READS
20 4,650
3 authors, including:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by A.P. Sakis Meliopoulos on 10 January 2015.
A New Method and Instrument for Touch and Step Voltage Measurements
A. P. Sakis Meliopoulos Shashi Pate1 G. J. Cokkinides
Fellow Senior Member Member
School of Electrical & Computer Engineering Research Center Dept. of Electrical & Computer Engr
Georgia Institute of Technology Georgia Power Company University of South Carolina
Atlanta, Georgia 30332 Atlanta, Georgia 30302 Columbia, South Carolina 29208
Abstract This paper describes a new method and instrument (2) The step voltage meter function of the Smart Ground
for measuring touch and step voltages near a grounding system, Multimeter measures the actual step voltage at a substation
for example in and around a substation. The hardware, as a function of the fault current. The measurement is
software, and testing procedures are an extension of the smart performed at a user selected point anywhere above or near
ground multimeter, developed under EPRI sponsorship. The a grounding system. The measurement provides the actual
instrument injects a transient electric current between the step voltage per ampere of fault current. It requires as an
ground under testing and an auxiliary ground, and it measures input the fault current available at the location of the
ground potential differences (GPDs) at up to six locations. The grounding system which is used to project the actual step
GPD measurements are processed with software which rejects voltage under fault conditions.
external noise using correlation methods. Subsequently,
statistical estimation methods are used to extract the touch or *. Description Of the MeasurementApproach
step voltages from the thousands of measurement points The method for measuring touch voltages requires that six
normalized with the system short circuit capability. Knowledge probes be placed at six points, designated as 3B, 2B, lB, 3Y, 2Y,
of the short circuit capability of the substation allows the quick and lY, where touch voltages must be measured, as it is
measurement of the touch and step voltages. illustrated in Figure 1. The meter injects a transient electric
current i(t) between the ground grid under test and a
1. Introduction temporarily installed current retum electrode(as is shown in
Several instruments are available for grounding Figure 1) for a short period of time, typically 0.3 seconds.
measurements, for example ground impedance measurements, During this time, measurements of the injected electric current
and soil resistivity measurements. Recently, a PC based and of the transient ground potential differences are taken
instrument has been developed [7]which performs a number of (locations 3B, 2B, lB, 3Y, 2Y, and 1Y shown in Figure 1). The
ground measurement functions. These functions are listed in ground potential differences are measurements of the voltage
Table 1. This paper concentrates on the touch and step voltage difference between the ground under test and points 3B, 2B, lB,
functions of the meter which have been recently developed and 3Y, 2Y, and 1Y shown in Figure 1. For touch voltage
tested. A brief description of these function is stated as follows: measurements, the probes 3B, ZB, lB, 3Y, 2Y, and 1Y can be
placed at any location where the touch voltage is to be
Table 1. Present Functions of the Smart Ground measured. For step voltages, the six probes must be placed in
Multimeter the arrangement shown in Figure 2. The distance d is 3 feet or 1
meter. These measurements are processed by computer
Substation Ground Impedance Meter ' software to extract the touch or step voltages at any frequency of
Touch Voltage Meter interest.
Step Voltage Meter
Smart Ground
Tower Ground Resistance Meter
Soil Resistivity Meter
Multimeter 0
(1) The touch voltage meter function of the Smart Ground
Multimeter measures the actual touch voltage at a PROBE ASSEMBLY
substation as a function of the fault current. The Current YELLOW VOLTAGE
Return
measurement is performed at up to six points anywhere Electrod
above or near a grounding system. The measurement
provides the touch voltage per ampere of fault current. It
requires as an input the fault current available at the
location of the grounding system which is used to project
the actual touch voltage under fault conditions.
0 1994 IEEE
0885-8977/94/$04.00
*
I
Smart Ground
Multimeter
-------
BLUEVOLTAGE
FNBEASSEMBLY
3.1 Extemal Hardware
Acquisition
Personal Computer
These components are illustrated in Figure 3 and described
in the following paragraphs.
Vdtage Pmbe Assemply B Voltage Pmbe Assemply A
Triplex
Shielded
Cables
-
Ill
+ Specifically, the signals from the six voltage probes and the
current transformer first pass through the analog signal
processing unit. This circuit provides the following functions:
Protection of the personal computer electronicsagainst
C u m Return Gmunding System transients via proper MOV surge protectors
Electrode Under Test
Low pass filtering to prevent aliasing upon sampling
Figure 3. Illustration of the 'Smart' Ground Impedance
Meter
1852
0 Appropriate amplification to optimize the use of the 4. Description of Smart Ground Multimeter Software
A/D converter dynamic range, via programmable gain
amplifiers. The smart ground multimeter software is installed in a
personal computer which controls the measurement process,
0 Optional attenuation of 60 Hz signals to reduce processes the data and displays the results. The user interface is
interference from nearby 60 Hz circuits fully graphic (GUI)and can be operated with a mouse or the F
Operations such as gain selection, calibration, and 60 Hz keys. The software consists of the following components:
filter bypassing are controlled automatically by the computer. 1. The user interface
A block diagram of the voltage signal processing circuit is 2. Measurement data collection algorithm
illustrated in Figure 5. The outputs of the signal acquisition and 3. Error correction algorithm
control channels are connected to the input of the A/D 4. Channel Calibration Algorithm
converter board which is installed inside the personal computer. 5. Probe Calibration Algorithm
The data acquisition board also has several digital lines which 6. Data Analysis Software
are used to select the gain, source voltage, etc.
The user interface allows the user to perform the followmg
An important feature of the smart ground multimeter functions:
instrumentation is the ability to (a) measure the transfer
function of the measurement channel and compensate for it Inspect and modify measurement parameters
during processing of the measurements (channel calibration) Initiate Measurements
and (b) to measure the ground resistance of the voltage probes Generate warning messages about improper use of the
and the cable capacitance and compensate for it during Smart Ground Multimeter
measurements (probe calibration). The calibration circuitry is Generate reports of intermediate and final results
illustrated in Figure 5. Specifically, during the channel
calibration, a known noise source is connected to the input of The data analysis software extracts the touch and step
the channel, while the voltage probe is disconnected via the voltages from the measurements. The algorithm employed was
indicated relays, and the output is recorded. From these developed after a careful analytical investigation of all factor
measurements the transfer function of the channel is computed. affecting measurement of touch and step voltages, and
The probe calibration (measurement of the voltage probe subsequent field verification. The analytical investigation was
resistance and cable capaatance) is performed by connecting a performed using the EPRI SGA package and consisted of
known noise source to the voltage probe assemblies while the simulating a substation grounding system together with the
channel is also connected to the voltage probes. The response is probes of the Smart Ground Multimeter. A three dimensional
measured. From this measurement, the admittance of the plot of such a system is illustrated in Figure 6. The Figure
voltage probes and cable capacitance is extracted. The shows a ground mat, four tower grounding systems, the six
admittance is used in the probe error correction algorithm voltage probes of the Smart Ground Multimeter and the three
during measurements. The calibration and associated error current return electrodes of the Smart Ground Multimeter. The
correction algorithms ensure highly accurate and reliable system was modeled as a multiground system. For this system
measurements. electric faults were simulated by injecting an electric current into
the ground mat and assuming that the current retum ground is
In summary, the design of the Smart Ground Multimeter
located very far away from the substation. The tower grounds
hardware ensures:
may or may not be connected to the ground mat. The operation
Measurements with high signal to noise ratio of the Smart Ground Multimeter was simulated the injecting a
A dynamic range of above 90 db current into the ground mat and assuming that the current
Measurement accuracy retums through the three current retum electrodes. Again the
tower grounds may or may not be connected to the ground mat.
Probe
ibration
T
Fmm
-Lil E 7 n
S G S E V5.0 -
30 f m u n d i w 5v.L.n P l o t
TITLE: Smarl Ciound Y u l t l u 1 . r I Touch Va1t.p.
Eledmde
Y...urlmi.
Tower
Grounds
Figure 5. Functional Block Diagram of a Single Channel of Figure 6. Three Dimensional Plot of a Typical Configuration
the Signal Acquisition and Control Module Used in the Analytical Investigation
1853
This investigation revealed that the two most important Table 2. Effects of Current Retum Electrode Proximity on
parameters which affect touch and step voltage measurements Touch Voltage Measurements
are:
1. Proximity of the Current Return Electrode I&
2. Number of tower grounds connected to the ground
mat or specifically total impedance of other grounds 00 900 600 400 300 200
connected to the ground mat.
As an example of typical results of this investigation, Table
1 lists the computed touch voltages under four scenarios. The
first scenario designated as simulation of system fault and
neutrals/shields disconnected corresponds to the usual
definition of touch voltage (see for example IEEE Std 80). The 5. Field Verification
current is injected into the ground mat (and it is assumed to The smart ground multimeter has been extensively tested in
retum from another ground at a remote location) and the effects the laboratory and in the field. In April 21, 1993 a set of
of other nearby grounds are neglected. In the second scenario, comprehensive field tests were performed at Georgia Power
designated as simulation of system fault and neutrals/shields Company's Texas Valley Substation.
connected is similar to the first except that the effect of the
nearby tower grounds are accounted for. Note a slight decrease The Texas Valley Substation is a 115kV/12kV located in
of touch voltage as a percent of ground potential rise. The other North Georgia near Rome. This substation has been used for
two scenarios designated as simulation of smart ground grounding related research by Georgia Power since 1981[2]. All
Multimeter account for the current retum electrode proximity. the neutrals and shield wires in this substation are connected to
The values in Table 1 have been computed assuming the current a common point. A switch is used to connect or disconnect this
retum electrode to be placed 400 feet from the center of the common point to the station ground mat. In this way, the
ground mat. Note in this case about 20% increase of touch static/neutrak can be connected or disconnected from the
voltage due to current retum electrode proximity. On the other ground mat via a switch. In addition, the 115kV line between
hand the effect of nearby grounds is relatively small about 6% Sommerville and Texas Valley can be deenergized. When
for the cases in Table 1. The effect of the current return deenergized, one of the phase conductors is used to inject a
electrode proximity was investigated by simulating many current into the Texas Valley ground mat from the Sommerville
configurations with the current return electrode at different Substation located many miles away. The method has been
distances from the grounding system and computing the touch coined the current injection(C1) method and it is described in
voltage as a percentage of ground potential rise. As an example, [2].The injected current is about 157A.
Table 2 presents a sample of results of this investigation. The In April 21, 1993 measurements were performed of touch
example system consists of a 200'x 200'ground mat with 50'x and step voltages using the Smart Ground Multimeter & the
50'meshes. The current retum electrode is placed at different current injection method. The measurements were performed at
distances from the ground mat center. Note that the value 30 points along a line near the center of the station and at
28.92% is the true value of the touch voltage. Note that if the another 24 points along a line near the northwest corner of the
current retum electrode is placed 400 feet from the ground mat station. The location of these lines with respect to the station are
center, the mesh voltage will increase by 23%. Based on these shown in Figure 7. Measurements were made with the static
results, which were verified in the field, the following has been wires connected and disconnected. A typical report of the
implemented. The smart ground meter, computes the effect of Smart Ground Multimeter is shown in Figure 8. The same
the current retum electrode proximity and subtracts it from the measurements were made (the same day) using the current
actual measurement. In addition, it is recommended that the injection method[2]. A comparison of all results is shown in
current return electrode be placed at least two times the Figure 9,10,11,and 12. The Figures are self explanatory. Note
diagonal length of the ground from the ground center. that both methods give comparative results.
Table 1. Computed Touch Voltages Under Several
The measured touch voltages were also compared to
Scenarios (in percent of ground potential rise)
computed values with EPRI's SGA program (81. First soil
Simulation of System Simulation of Smart resistivity measurements were taken with the wenner method.
Fault Ground Multimeter For this purpose two locations (A and B) were selected near the
Neutrals Neutrals Neutrals Neutrals substation. At each location, 36 measurements were obtained
/shields /shields /Shields /Shields with spacing ranging from 2 feet to 90 feet. These
measurements were processed with the program SOMIP [8]to
29.38 27.44 35.71 37.81 establish the proper soil resistivity model. Using the soil
P*z 30.09 28.13 36.62 38.86 resistivity model, the ground resistance was computed using the
P*3 30.49 28.51 37.06 39.47 program SGSYS. The results are tabulated in Table 3. Note that
the program SOMIP provides expected errors vs. confidence
level. The soil resistivity measurements from location B provide
soil model parameters with very high expected errors. The soil
1854
model obtained with the program SOMIP by combining the For each one of the soil models, the touch voltages, at the same
measurements from locations A and B (A+B) are also given for locations indicated in Figure 7, were computed using the
comparative purposes. As an additional check point the ground program SGSYS and assuming a current injection of 157
resistance was measured (the same day) and found to be 0.565 amperes into the ground grid. The computed maximum and
ohms. Note that the soil resistivity measurements at locatiion A minimum touch voltage were superimposed on those measured
are in conformance with the measured ground resistance. with the smart ground multimeter and the current injection
T.*. Valley S"b.tat1.a" Ten1 SusLem method. Figure 13 illustrates these results for a specific case
56SV5 V5 0 using the soil model obtained at location A and Figure 14
4, 3 - b N
illustrates similar results for the same case using the soil model
obtained from both locations A and B. The results indicate that
the computer models are conservative as compared to measured
values.
I I
-108. -72 -36 0 36 72 108
x-hiis ( f e d )
l o p VI." x-* Pl."s
Locetbn of Measurements
Figure 7. Ground Mat at the Texas Valley Substation
q
2 1.0-
0.0
0
I
5
,
10 15
,
20
, ,
25
,
30
Locationlndex +
Figure 9. Measured Touch Voltages Near the Center of
the Ground Mat at Texas Valley Substation
with the SGM and the Current Injection (Cl)
Method. Neutral Wires Connected.
f 20.0
15.0
r
cc
E
5
0
U
Q 10.0
-
g
a,
ul
e
0
r.
5.0
=
m
P
5
2 0.0
5 10 15 20 25 30
Location Index
Figure IO. Measured Touch Voltages Near the Center of
the Ground Mat at Texas Valley Substation
with the SGM and the Current Injection (CI)
Method. Neutral Wires Disconnected.
1855
32.0.
30.0
4
1 25.0
2
-
s
C
20.0
5
0
3
3 15.0
-
??
Y
-a
sg) 10.0
m
L
>
5
ss
I- 0.0 1
0 5 10 15 20 25 30
Location Index +
Figure 11. Measured Touch Voltages Near the North
West Comer of the Ground Mat at Texas 5 10 15 20 25 30
Valley Substation with the SGM and the Location Index +
"i
Current Injection (Cl) Method. Figure 13. Computed and Measured Touch Voltages
Neutral Wires Connected. Near the Center of the Ground Mat at Texas
Valley Substation. Soil Model A.
A 60.4
Lo 20.
> I
, k 0.0
5 10 15 20 25 30
Location Index + I
5 10 15 20 25 30
Figure 12. Measured Touch Voltages Near the North Locatlonlndex +
West Comer of the Ground Mat at Texas Figure 14. Computed and Measured Touch Voltages
Valley Substation with the SGM and the Near the Center of the Ground Mat at Texas
Current Injection (Cl) Method. Valley Substation. Soil Model A+B.
Neutral Wires Disconnected.
1856
from the National Technical University of Athens, Greece, in
1972;the M.S.E.E. and Ph.D. degrees from the Georgia Institute
of Technology in 1974 and 1976, respectively. In 1971, he
6. Summary worked for Westem Electric in Atlanta, Georgia. In 1976, he
joined the Faculty of Electrical Engineering, Georgia Institute of
A new €unction of the Smart Ground Multimeter has been Technology, where he is presently a professor. He is active in
developed and successfully tested in the field against a well teaching and research in the general areas of modeling, analysis,
established and accepted method. This function provides and control of power systems. He has made significant
measurements of touch and step voltages for a specific fault contributions to power system grounding, harmonics, and
current level. The advantages of the new instrument are (a) ease reliability assessment of power systems. He is the author of the
of performing the measurements, and (b) accuracy of results by books, Power Systems Grounding and Transients, Marcel
means of error correction algorithms and compensation for the Dekker, June 1988, Ligthning and Overvoltage Protection,
effects of the current retum electrode and other grounds which Section 27, Standard Handbook for Electrical Engineers,
may be connected to the ground mat. To our knowledge this is McGraw Hill, 1993, and the monograph, Numerical Solution
the first device of its kind. The instrument can be used to Methods of Algebraic Equations, EPRI monograph series. Dr.
investigate and measure the maximum touch or step voltage in Meliopoulos is a member of the Hellenic Society of Professional
a substation. Engineering and the Sigma Xi.
Acknowledgments Shashi Patel (M '70,SM '84) was bom in Fiji Islands in 1943. He
received the B.S.E.E. degree from M.S. University of Baroda,
The authors are grateful for the financial support from EPRI India in 1965 and M.S.E.E. degree from Georgia Institute of
and in developing the touch and step voltage function of the Technology, Atlanta, Georgia in 1976. From 1965 to 1967 he was
smart ground multimeter. with Gujarat Electricity Board, India, in charge of a district
office. He worked as a Power System Engineer at BPA,
References Portland, Oregon during the summer of 1969. Since 1970, he
has been employed by Georgia Power Company. He is
1. "A Manual on Ground Resistance Testing," James G. Biddle presently a Staff Services Engineer in Georgia Power Research
Company, Publication No. 25-J,
1952. Center, Forest Park, Georgia. He has been actively involved in
IEEE/PES Substation Committee since 1978. His other areas of
2. S.G.Patel, "Field Measurements at Texas Valley Substation," interest include HV testing, switchgears, induced voltages,
December 1981.
Final Report on EPRI, RP-1494-2, grounding and corrosion. He is registered Professional
3. I.D. Lu and R.M. Shier, "Application of a Digital Signal Engineer in the state of Georgia.
Analyzer to the Measurement of Power System Ground George Cokkinides (M '85)was bom in Athens, Greece, in
Impedances," IEEE Transactions on Power Apparatus and 1955. He obtained the B.S., M.S., and Ph.D. degrees at the
Systems, vol. PAS-100, no. 4,pp. 1918-1922,April 1981. Georgia Institute of Technology in 1978, 1980, and 1985,
4. IEEE Std. 81, "IEEE Recommended Guide for Measuring respectively. From 1983 to 1985,he was a research engineering
Ground Resistance and Potential Gradients in the Earth," at the Georgia Tech Research Institute. Since 1985,he has been
1962. with the University of South Carolina where he is presently an
Associate Professor of Electrical Engineering. His research
5. ANSI/IEEE Std. 80,"IEEE Guide for Safety in AC Substation interests include power system modeling and simulation, power
Grounding" 1986. electronics applications, power system harmonics, and
6. P.H. Reynolds, D.S. Ironside, A.H. Silcocks, and J.B. measurement instrumentation. Dr. Cokkinides is a member of
Williams, "A New Instrument for Measuring Ground the IEEE/PES and the Sigma Xi.
Impedances," presented at the IEEE PES Winter Meeting,
New York, New York, Paper A 79 080-3,February 1979.
7. A.P. Meliopoulos, G. Cokkinides, H. Abdallah, S. Duong,
and S. Patel, "A PC Based Ground Impedance Measurement
Instrument," IEEE Transactions on Power Delivery, Vol 8,
No. 3,July 1993.
8. AP. Meliopoulos, "SGA Users Manual, Vol. 3, Computer
Model SGSYS Version 5.0," and "SGA Users Manual, Vol. 1,
Computer Model SOMIP Version 2.0,"EPRI Report, 1992.
Biographies
A. P. Sakis Meliopoulos (M '76,SM '83,F '93) was bom in
Katerini, Greece, in 1949.He received the M.E. and E.E. diploma
1857
Discussion impedance. A comparison of results with figures 9 to 14 of
the present paper and with figure 7 of the author’s refer-
ence [7] would be self speaking. Again real correction
Jacques Fortin (Hydro-Quebec, Montreal, Quebec,
factors should be given.
Canada): The authors have published a welcome paper
More results and comparisons are needed to attain
for engineers having to certify the security of persons in confidence in the proposed method based on GPD.
the vicinity of power installations. Specifically the real correctionfactor should be determined
In one of our measurement techniques, based on the
on the field test site for a wide variety of distances to
Fall-of-Potential method, test current may be varied in current probe (100 m to 10 km and more) and for a wide
the range of 0.1 to 20A, depending on the circuit used to -
variety of soil resistivities (100 0 m to 10 000 Cl m).
perform the grounding test and of course on the purpose.
Current distribution is also affected by the position of
A single frequency (50-55 to 65-70 Hz) is applied be-
the current electrode when in proximity, which in turn
cause of practical advantages. Depending on the case, the
affects touch voltage near substation and elsewhere.
test current is circulated through a communication cable
We have developed new methods to measure the ground
pair, a drop wire lying on the soil or a de-energized power impedance of a line and the ground resistance of a single
line.
tower in presence of overhead ground wires and counter-
poises. No corrections are needed. It could be interesting
Depending on the case, the folliwng measurements are per-
to compare all those methods at the same site.
formed.
The authors have presented a new method which needs
1. ground current distribution on: more field testing to allow comparison with long current
-overhead wires and counterpoises connected to injection circuit for a large variety of external conditions.
power lines; If the author’s method were to be validated, it would
-neutral conductors connected to distribution lines; represent a new method overcoming some practical prob-
-communication cables shields; lems of the Fall-of-Potential method. If not, it should be
-ground connections to neutral point of Y connected possible to use the SGM to apply the Fall-of-Potential
transformers; method.
-other ground conductors or metallic structures;
Manuscript received February 15, 1994.
2. touch and step voltages inside and outside the substa-
tion up to 1 km away (aerial pothead, tower, fence,
private installation, etc.);
3. potential profile up to a certain point (k 1 km). The
extrapolation ( s 15%) of the curve gives the impedance
to remote earth.
F. P. DAWALIBI, Safe Engineering Services &
All measurements are referred to the test curtent by a technologies Itd., Montreal, Quebec, Canada, H3M
standard two channel F I T instrument. Calibration factors 164. The authors have deployed considerable hardware
for amplitude and phase are verified and entered in the
and software resources to design their Smart Ground
instrument. A simple computer program interpolates
measurements at 60 Hz. Analysis of results can then be Multimeter. It is however regrettable to note that they have
performed. not carried out a similar effort with respect to the
Our field experience shows that current electrode dis- fundamental grounding principles on which the meter
tance to the multi grounded system under test affects should have been based. This meter has been designed with
particularly touch voltage measurements by a factor of 1 implicit assumptions, the most noticeable of which are:
to 4 inside or close to the substation. This factor is
dependent on the distance to the current electrode and Homogeneous and isotropic uniform soils or two-
on the soil resistivity between current electrodes (100 - layer horizontal soils.
10OOO Cl * m). A factor of 1.2 or greater, to us is unaccept- 0 No significant localized soil heterogeneities or
able. The correction in such a case would appear closer to perturbations are to be expected.
a mathematical algorithm than a field test measurement. No extensive metallic structure (such as water lines,
Could the authors give the following factors concerning pipelines, buried tanks, etc.) are present in the soil.
results shown in figures 9 to 14 for eachprobe: 0 The grounding, network has a reasonable regular
157 Vti/I (from Fm at 60Hz) shape easily identifiable by the operator who must
real correction factor = define its skeleton a n w r center.
Vti (from CI method)
What are the corresponding factors applied by the As stated by the authors, this multimeter is an extension of
SGM? their original Smart Ground Multimeter. Consequently, it
Did authors use the de-energized line to circulate the is still plagued by all the deficiencies which I identified and
SGM test current to remote earth? If that is possible, discussed more than a year ago (see discussion and closure
assuming adequate protection, the Fall-of-Potential of Reference 7 of the authors’ paper). The authors eluded
method could be performed to measure touch voltage and most of the points I raised by concentrating their closure on
1858
details which did not address the questions and criticisms customers in order to prevent widespread use of the
raised. This time, I am including a discussion of a few multimeter at sites which are clearly outside the range
basic points for the benefit of the readers who should of the multimeter. This is important, particularly if the
clearly undestand my reservations conceming the shape of the grounding network is complicated and does
multimeter before deciding to use it: not present a clearly identifiable center.
Company), and G. J. COKKINIDES (University of South neutral fashion, i.e. without any corrections, "bad data rejection",
Carolina): The authors would like to thank the discussors for and similar interventions ...I. This statement ignores the
giving us the opportunity to comment on this new method fundamental behaviour of grounding systems, which our
and emphasize some key points. paper brought into focus and Mr. Fortin's discussion has
We are grateful that Mr Jacques Fortin has shared his amplified: 'current electrode distance affects particularly touch
experience and provided independent verification that the voltage measurements by a factor of 1 to 4'. Experienced
current retum electrocde distance affects particularly the engineers with this type of measurements would agree with
touch voltage measurements inside or close to the Mr. Fortin and ourselves that these errors must be corrected.
substation. He reports that he has observed errors as high as Our paper offers a practical method and instrument for this
300%(factors of 1to 4). He suggests that an error of 20% or purpose. For the benefit of our readers, we emphasize that
higher (factor of 1.20) is unacceptable and should be touch voltage measurements with practical lengths of
corrected with mathematical algorithm. We totally agree. current retum electrodes are subject to large errors. These
The Smart Ground Multimeter does exaclty that. It is an errors are independent of the quality of the hardware. It is
integrated system of hardware and software which correct our belief that the only practical way to correct for these
the measurement error by a mathematical algorithm which errors is by software. Mr. Fortin's discussion also suggets
requires as inputs the approximate size of the grounding correction with a mathematical algorithm.
system and the distance of the current electrode. More
sophisticated algorithms can be applied if necessary. Mr Dawalibi states that measurements of step voltages are
unnecessary if touch voltages are measured. This statement
Information requested by Mr Fortin is provided below. The is regretably false: it is possible, for specific ground grids,
correction factors applied by the SGM for the measurements step voltages may exceed allowable levels while touch
at the Texas Valley substation ranged from 1.08 to 1.92. The voltages are within limits. For the benefit of our readers, we
real correction factor, as defined by Mr Fortin, can be read present a simple case where step voltages exceed limits
from Figures 9, 10,11, and 12 as the ratio of the solid line while touch voltages are within limits:
(SGM data) to the dotted line (CI method). We did not use Consider an 8x8 mesh ground grid, 10 feet spacing between
the de-energized line as the current retum system for the parallel ground conductors, buried 1.5 feet in a two layer
SGM measurements. We agree with Mr. Fortin, it would soil (upper soil resistivity = 200 ohm.meters, lower soil
have been a valuable test to use the de-energized line as the resistivity = 1000 ohm.meters, and upper soil thickness of 6
current retum system for the SGM. Mr. Fortin suggests a feet). The maximum earth current is 415 Amperes (current
comparison of the results with Figure 7 of reference [A. flowing into soil from grid, under worst fault conditions).
Specifically, Figure 7 of reference [7] shows measurements Consider the usual case where a 4 inch layer of 3000
of the ground grid impedance with the static/neutrals ohm.meter crushed rock covers the substation and extends 3
connected/disconnected. The grid resistance is 0.56 when feet outside the fence. The fence is located 3 feet inside the
the static/neutrals are disconnected. This measurement is in perimeter of the ground grid and it is bonded to the ground
close agreement with the computed value of 0.584 ohms, grid. For a 0.5 second fault duration, the permissible touch
using the soil model A (see Table 3). Note also that in and step voltages are:
Figure 13, the touch voltage measurements with the SGM
are in agreement with the computed touch voltages using Inside the Substation and up to 3 Feet from Fence (crushed
the soil model A (see curve MIN in Figure 13). This rock):
agreement suggests that the soil model of the Texas Valley
Substation is the one provided by the soil resistivity
measurements at location A (model A).
Maximum Step Voltage = 392 volts. It occurs about 6.5 feet for the range of current probe locations (325to 1660 feet), the
from the corner of the station fence. Applicable permissible Smart Ground Multimeter provides measurements which
step voltage is 368 volts. are practically constant (20% excursion), while the
Note that the step voltage is over the limit, while the touch measurements with the Ground tester show an excursion of
voltage is below the limit. Above computations were 85 percent. The figure illustrate the superiority of the SGM
performed with our analysis program (El" program) and as compared to other meters or measurements without
we expect that they can be verified with a number of other correction. The small variability of the SGM measurements
programs. In above case, and many other similar cases, is attributed to the presence of distribution poles near the
measurement of step voltages is necessary. location of the current retum electrode. The advantage of
the SGM approach is that corrections for the proximity of the
Another minor point that we would like to make is that Mr. distribution pole ground or other grounds can be integrated
Dawalibi's belief that the use of six potential probes and
I... into the SGM system.
associated leads simultaneously can be an extreme nuisance to a
team of three people or less and quite exhausting
...Iis amusing.
One person is enough to operate the smart ground . . - .- Ground Tester
multimeter and it takes less than 5 minutes to move six 2.0 SGM
probes from one location to another. The meter performs
touch voltage measurements simultaneously at six locations,
thus minimizing the overall testing time. The users of the
Smart Ground Multimeter will totally disagree with Mr
Dawalibi's statement.
F I
In summary, touch and step voltage measurements with
conventional methods may have unacceptably large errors.
This fact has been brought into focus by our paper and
amplified by Mr. Fortin's discussion. These large errors
must be corrected with software or other means. The new
method and istrument does just that: it combines hardware 0 500 1000 1500 2000
and software for the direct measurement of touch and step
voltages and uses error correction methods via software. Distance of Current Return Electrode from
The central requirement of a touch and step voltage meter is Grid Center (feet) >
-
to provide the same measurement independent of the
position of the current probe. To illustrate this point, we Figure 1. Touch Voltage Measurements vs Current
have performed touch voltage measurements at a specific Probe Location
substation using the Smart Ground Multimeter and the
Ground tester, while the current probe location was Manuscript received May 9.1994.
variable. The results are illustrated in Figure 1. Note that